CO2METER RAD-0502 CO2 Controller for Grow Rooms Instruction Manual
- June 17, 2024
- CO2METER
Table of Contents
- CO2METER RAD-0502 CO2 Controller for Grow Rooms
- Product Information
- Product Usage Instructions
- Product Overview
- Package Content and Unit Layout
- Connection Diagram
- Operating the RAD-0502
- Safety Precautions And Product Care
- Installation Instructions
- Product Help
- Settings
- Temperature Unit and Setting
- Relay Selection for Temperature, Humidity, and Light
- Light Setting
- Time Setting And Cycle Display
- Buzzer Setting
- Recovery Setting
- Technical Specifications
- Dimensions
- Fault Codes and Troubleshooting
- Support and Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
CO2METER RAD-0502 CO2 Controller for Grow Rooms
Product Information
Specifications
- Product Name: RAD-0502 Indoor CO2 Grow Controller
- Application: Indoor greenhouse CO2 control and ventilation
- Display: LCD Display
- CO2 Sensor Range: 0-5000 ppm
- Temperature Range: -10°C to 50°C
- Humidity Range: 0% to 100%
- Power Input: 110-240V AC, 50/60Hz
Frequently Asked Questions
- Q: What is the range of CO2 concentrations that can be measured by the sensor?
- A: The CO2 sensor unit can measure concentrations ranging from 0 to 5000 ppm.
- Q: How can I change the displayed parameters on the LCD screen?
- A: Use the MODE button to switch between CO2 levels, humidity, temperature, and light readings on the display.
Product Usage Instructions
Package Content and Unit Layout
- Indoor CO2 Grow Controller Main Unit:
- A. LCD Display
- B. Green LED (lights when relay activates)
- Indoor CO2 Grow Controller CO2 Sensor Unit:
- A. CO2 Entry
- B. LCD Display
Operating the RAD-0502
- Ensure power is supplied to the grow controller.
- The LEDs indicate various states such as power supply, CO2 concentrations, and sensor activities.
Safety Precautions
- Follow all safety guidelines provided in the manual to ensure correct and safe use of the product.
Product Overview
Model: RAD-0502 CO2 Controller for Grow Rooms
Thank you for selecting the RAD-0502 CO2 Controller for Grow Rooms, which is designed to regulate CO2 levels and allows growers to set high/low targets to maximize plant yields and profitability. The CO2 Controller for Grow Rooms uses a dual beam NDIR technology to accurately measure CO2 concentrations up to 3,000ppm. With a built-in temperature measurement and photo sensor, the controller can turn off relays during dark periods to save Carbon Dioxide (during green house mode). Furthermore, the CO2 grow controller is an ideal solution for many growers who utilize the device across indoor greenhouses, cultivation centers, hydroponic rooms, or anywhere regulated CO2 levels are important for plant growth.
- Accurate CO2 control for small to large sized indoor grow facilities
- Control 2 zones with 2 sensors
- Customizable CO2 set points for high and low target levels
- Dual beam NDIR technology accurately measures CO2 concentrations 0-3,000ppm
- Built-in temperature, humidity, and light
- Relay output can automatically control CO2 generator or compressed CO2 tanks
- Versatile modes for greenhouse or HVAC
Package Content and Unit Layout
The RAD-0502 package comprises the following parts:
- (1) Indoor CO2 Controller
- (2) Remote CO2 Sensors
- (2) Relay Cables
- (2) CAT5e Cables – 25′ ft.
- (1) Wall Plug Safety Strap
- (1) Mounting Bracket
- (6 pieces) Screws
- (1) Power Supply
- (3 pieces) International Power Adapters
Indoor CO2 Grow Controller Main Unit
- A. LCD Display
- B. Green LED (lights when relay activate)
- C. Green LED (power on indicator)
- D. Green LED (lights when CO2 concentration is above set point)
- E. Green LED (lights when daytime)
- F. UP button
- G. MODE Button
- H. DOWN Button
- I. ENTER Button
- J. RESET Button
- K. Communication Cable to sensor unit
- L. Relay Cable (configurable)
- M. Relay Cable (configurable)
- N. Power Plug
Indoor CO2 Grow Controller CO2 Sensor Unit
- A. CO2 Entry
- B. LCD Display
- C. Panel Holders
- D. Green LED (lights when relays activate)
- E. Green LED (lights when daytime)
- F. TEMP/HR Sensor
- G. Photo Sensor (monitors light or darkness)
- H. Communication Cable to Main Unit
Connection Diagram
Please Note: The CO2 Controller is designed for indoor greenhouse application, or for ventilation
LCD Display Symbols
Symbol | Meaning | Description |
---|
1300 CO2
ppm| CO2 levels| CO2 concentrations shown in ppm (parts per million)
50 RH%| Humidity| Display shows current humidity. Can be changed by
pressing “MODE” key
24 TEMP °C| Temperature| Displays current temperature. The unit can be
switched by pressing “MODE” key.
0.2 LIGHT IX| Light| Displays current light. The unit can be switched by
pressing “MODE” key
MAX| Maximum| Displays the maximum value in the selected time
MIN| Minimum| Displays the minimum value in the selected time
AVG| Average| Displays the average value in the selected time
Operating the RAD-0502
- The first power LED will appear green when the power is supplied to the grow controller The second power LED will appear green when the CO2 concentrations are lower than the set point 1 (configurable)
- The third power LED will appear green and turn on when the CO2 concentrations reach above set point 2
- The fourth power LED will appear lit when the photo sensor is active, and the photo sensor is used to detect the presence or absence of light
Safety Precautions And Product Care
Safety Precautions
At CO2Meter, your safety is very important to us. To ensure correct and safe use of the RAD-0502 controller for grow rooms, please read this entire user manual before operation. Otherwise, the protection provided by the equipment manufacturer may be impaired. Please adhere to the warnings below that highlight important safety information and should be observed at all times.
- Please handle the device carefully, do NOT subject the unit to impact or shock, otherwise this may decrease the sensor’s overall accuracy and precision.
- Do NOT place the unit or the power plug near a heat source, as heat can distort the unit and may result in fire or injury.
- Do NOT open the CO2 Grow Controller or touch any of the exposed electronic circuitry, under any circumstances. Should you touch any exposed wiring, this can result in electric shock.
- Only connect devices to the RAD-0502 CO2 Grow Controller that use grounded plugs.
- Our replacement sensor can NOT be used to monitor additional grow spaces, this device can ONLY monitor CO2 concentrations in up to (2) grow zones.
- Please Note: the RAD-0502 may NOT be used for CO2 safety per OSHA guidelines as it does not meet the need to measure and operate at OSHA’s Short Term Exposure Limit of 30,000 ppm.
Product Care
Co2Meter wants you to get the most out of your product or sensor technology. In order to do so, please observe the following care instructions.
- Repair – Do NOT attempt to repair the product or modify the circuitry by yourself.
- Cleaning – Please disconnect the power before cleaning. Use a damp cloth and do NOT use liquid cleaning agents such as Benzene, Thinner, or Aerosols. Using these agents will critically damage the device.
Installation Instructions
- Choose a suitable location at plant level to install the CO2 Sensor unit.
- Choose a suitable location at eye level to mount the CO2 Grow Controller unit.
- Next, connect a CO2 generator or bottled CO2 control regulator to the desired relays (please note the CO2 Grow Controller has 2 relay outputs. The relays can control a CO2 generator or a bottled CO2 regulator to produce CO2)
- The first relay will then be triggered, and the power will be supplied when the CO2 concentration is out of the desired set point range.
- The second relay will then be triggered allowing temperature, humidity, and light capabilities dependent upon the user preference.
Main Display Content Switching
- Press the “MODE” key to switch the main display contents across CO2, RH, TEMP, and LIGHT
Display Switching Content Attached
- Press enter to attach the display and then it will switch between temperature and humidity, or Carbon Dioxide and light.
Change Table Time Range
- On the main CO2 Grow Controller, press the enter key for 5 seconds to switch the time range from CO2 TEMP and RH tables. The time range of each column in the table can be respectively 5 minutes without CO2. 2 hours, 14 hours, 56 hours, and 14 days. (Co2 has a 5- minute trend)
- Press enter for 3 seconds to switch table time range to the main display mode
- Press enter to enter calibration mode
- Press enter to enter into the CO2 calibration mode or press mode to return back to the settings screen.
- Press the up or down keys to set the value to be corrected or press the mode key to exit the setting screen.
- Press and hold the enter key to start the calibration or press the mode key to exit the settings screen
- Wait for 3 minutes for the calibration to finalize and press the mode key to exit the calibration
- After calibration, if the correction is successful press up or down to save or not save
- If the calibration has failed, press the up or down key to set the value to be corrected and then press enter to start the calibration again or press mode to exit the setting
Historical Query
Press the up or down key to query the history record in the table and then the time of the record will be displayed in the upper left-hand corner. (This function is not available in the CO2 5-minute trend table)
- Press the up or down button to query the history in the current table
- Press the mode key to return to the current value display when querying the history
Product Help
The CO2 Grow Controller can further explain the icons and acronyms in the help options menu
- Press and hold the mode key for 3 seconds in order to enter the setting screen
- Press the enter key to access the settings screen or hold/press mode key to return to menu
- Press the up or down key to find the correct setting for information that is needed
Settings
CO2 Settings
- Press and hold the mode key for 3 seconds to enter into the settings screen
- Press the up or down key to select CO2 or press/hold the mode key for 3 secs to return to main screen
- Press enter to enter the CO2 setting or press and hold the mode key to return the main menu
- Press mode key to return to settings screen or press/hold the mode key for 3 secs to return to main menu
CO2 Mode Settings
There are 2 modes for CO2: GH and HVAC
The following operation is based on the configuration in section 15
- Press enter to enter into the CO2 Mode setting screen
- Press the up or down keys to select the CO2 mode or press the mode key to exit the selection
- Press enter to confirm the selection or mode in order to cancel the setting
CO2 Concentration and Control Range Setting
The values of CO2 1 and CO2 2 can be set in both GH and HVAC mode to control
the CO2 concentrations.
The following operation is an example below of CO2 and GH mode.
The following operation below is also based on the display table after
“section 15”
- Press the up or down keys to select CO2 1
- Press enter to enter into the CO2 1 settings screen
- Press the up or down keys to set the desired value or press the mode key to exit the settings screen
- Press enter to confirm the setting or press mode to cancel the setting
CO2 Calibration
- Press and hold the mode key for 3 seconds to enter into the settings screen
- Press the up or down key to select calibration or press and hold the mode key for 3 seconds to return to the main display menu
- Press enter to enter into the calibration mode
- Press enter to enter the CO2 calibration mode or press mode to return to the settings screen
- Press the up or down key to set the value you wish to be corrected or press the mode key to exit the setting
- Press and hold the enter key to start the calibration or press the mode key to exit the setting
- Wait for 3 minutes for the calibration process to finish or press the mode key to exit
- After correction, if the calibration is successful, press the up or down keys to save or not save the data
- If the calibration has failed, press the up or down keys to set the value to the correct placement and press enter to start the calibration again. Press mode to exit the setting.
Sensors must be calibrated individually, using sensor port 1
Temperature Unit and Setting
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down key to select TEMP or press and hold the mode key for 3 seconds to return to the main display mode
- Press enter to enter into the setting screen of TEMP
- Press the up or down keys to select the temperature unit setting
- Press enter to enter the temperature unit setting screen or press mode to return
- Press the up or down keys to select the temperature unit or press mode to return
- Press enter to confirm your setting or press the mode key to cancel the setting
The Range Setting of Temperature and Humidity
This RAD-0502 CO2 Grow Controller can determine a required temperature and humidity range by setting the upper and lower limits of temperature and humidity. This device can also record the effective light time by setting the value point of light intensity and avoiding frequent turnoff of the relays by setting a buffer of light intensity. The following display example above shows the lower limit in TEMP.
- Press and hold the mode key for 3 seconds to enter into the setting screen
- Press the up or down keys to select TEMP or press and hold the mode key for 3 seconds to return to the main display mode
- Press enter to enter into the settings screen for TEMP
- Press the up or down keys to select TEMP 1 or press the mode key to return back to the menu
- Press the enter key to enter into the TEMP 1 setting
- Press the up or down key to set the desired value or press the mode key to return
- Press enter to confirm this setting or press the mode key to cancel the setting
Temperature and Humidity Calibration
The RAD-0502 CO2 Grow Controller can also calibrate the temperature and humidity for the device. The following display example below illustrates temperature calibration.
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down key to select calibration or press and hold the mode key for 3 seconds to return to the main display mode
- Press enter in order to enter into the calibration mode
- Press the up or down keys to select TEMP or press the mode key to return
- Press enter to enter into the temperature calibration mode
- Press the up or down key to set the value or press the mode key to exit the setting
- Press and hold the enter key for 1 second to start the calibration or press the mode key to exit the setting
- After calibration, if the calibration is successful, the upper left corner will display a green “pass” sign.
- If the calibration fails, the upper left corner will display a red “fail” sign.
- Press enter to confirm the calibration and return to the main screen or press mode to cancel the calibration.
Relay Selection for Temperature, Humidity, and Light
The RAD-0502 CO2 Grow Controller can be selected to turn on one of the relays for temperature, humidity, and light. The following display below is an illustration of how to turn on the temperature relays.
- Press and hold the mode key for 3 seconds to enter into the settings screen
- Press the up or down key to select TEMP or press and hold the mode key for 3 seconds to return back to the main display screen
- Press enter to enter into the settings screen for TEMP
- Press enter to enter the relay output setting or press mode to return
- Press the up or down key to select whether to turn on the relays or press the mode key to return
- Press the enter key to confirm your selection or press the mode key to cancel
Relay Control of Temperature and Humidity
When the temperature or humidity relay is on, the product can choose whether
the relay is closed or when the value is too low or too high. Take the
temperature as an example. When “> TEMP 2, ON” is selected for relay control,
it means that the temperature is too high, and the relay will close and the
equipment used to reduce the temperature will be opened in order to reduce the
temperature.
The following illustration below is an example of how to choose the TEMP relay
control type.
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down key to select TEMP or press and hold the mode key for 3 seconds to return to the main display screen
- Press enter to enter into the setting screen for TEMP
- Press the up or down keys to select temp relay control, or press the mode key to return
- Press enter to enter the setting screen for temp relay control, or press the mode key to return
- Press the up or down key to select the temp relay control type, or press the mode key to return
- Press enter to confirm or press the mode key to cancel
Light Setting
- Press and hold the mode key for 3 seconds to enter into the setting screen
- Press the up or down keys to select LIGHT or press and hold the mode key for 3 seconds to return to the main display screen
- Press enter to enter into the light setting, or press and hold the mode key to return to the main menu
- Press the mode key to return to the setting screen or press and hold the mode key for 3 seconds to return to the main menu
Light Set Point Setting
The light set point is used to distinguish whether the current light intensity meets the limit of crop photosynthesis. The following illustration below shows the operation after section 23, “Light Set Point Setting”.
- Press the up or down key to select light set point setting
- Press enter to enter into the light set point setting
- Press the up or down keys to set the desired value or press mode to return
- Press enter to confirm or press the mode key to cancel
Light Hysteresis Setting
In greenhouse mode when the light intensity decreases, it is lower than the light set point minus the light hysteresis. This means the CO2 relay will always be turned off. When the light intensity increases higher than the light set point, the CO2 relay will determine whether to open or close according to the current CO2 concentration.
- Press the up or down key to select the light hysteresis setting
- Press the enter button to enter into the light set point setting
- Press the up or down keys to set the desired value or press the mode key to return
- Press the enter key to confirm or press the mode key to cancel
Light Relay Control Type Setting
There are 2 modes for the lighting relay control: Manual Mode & Automatic Mode. When the device is in manual mode, the relay is always closed in the set time area, and it is always open during the rest time. When in the automatic mode, the relay will determine whether to close or open according to light intensity in the set time area, and it will always be open at other time sets. The following illustration below showcases the operation after “section 23 Light Setting”.
- Press the up or down keys to select light hysteresis setting
- Press the enter key to enter light relay control type settings
- Press the up or down keys to select automatic or manual mode, or press mode to return
- Press enter to confirm or press the mode key to cancel
Light Expose Time Setting
The RAD-0502 CO2 Grow Controller can set the automatic or manual time interval of the relay control. The following illustration below is an example of setting a time interval in automatic mode.
- Press the up or down keys to select the light hysteresis setting
- Press the enter key to enter into light expose start time setting
- Press the up or down keys to set the start time or press the mode key to return back to the setting menu
- Press enter to confirm the start time and enter light expose and time setting
- Press the up or down key to set the end time or press the mode key to return
- Press enter to confirm the end time or press the mode key to cancel
Light Set Point MAX Setting
In the automatic mode, the relay can be switched off by setting the light set point MAX. When the light intensity is lower than the light set point, the relay is closed as well as when the light intensity is higher than the light set point MAX. The illustration below is based on an operation after “23. Light Setting”
- Press the up or down keys to select the light set point MAX setting
- Press the enter key to enter into the light set point MAX setting
- Press the up or down key to set the desired value or press the mode key to return
- Press the enter key to confirm or press the mode key to cancel
Time Setting And Cycle Display
Time Setting
The RAD-0502 CO2 Grow Controller can set the year, month, day, hour, and minute of the current time. The following illustration below is an example of the year setting.
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down key to select the time or press and hold the mode key for 3 seconds to return to the main display mode
- Press enter to enter into the setting screen for time
- Press enter to enter the year setting or press the mode key to return
- Press the up or down keys to set the desired value or press the mode key to return
- Press the enter key to confirm this setting or press the mode key to cancel the setting.
Cycle Display and Back-light Sleep Settings
The RAD-0502 CO2 Grow Controller can choose to turn on or off the cyclic display and back- light sleep. You can select “ON” when the cyclic display needs to be turned on and select “OFF” when the cyclic display needs to be turned off. You can select “AUTO” when the back- light needs to be turned on and select “ON” when the backlight does not need to be turned on.
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down keys to select display or press and hold the mode key for 3 seconds to return to the main display screen
- Press the enter key to enter into the setting screen of the display
- Press the enter key to show all or press the mode key to return
- Press the up or down key to select on or off, or press the mode key to return
- Press the enter key to confirm the setting or press the mode key to cancel the setting
Cycle Display and Back-light Sleep Time Setting
The RAD-0502 CO2 Grow Controller can set cycle display and back-light sleep time. The following illustration below is an example of cycle display time settings.
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down key to select display or press and hold the mode key for 3 seconds to return to the main display mode
- Press the enter key to enter into the setting screen of the display
- Press the up or down keys to select “show all intervals” or press mode to return
- Press the enter key to enter into “show all intervals”
- Press the up or down keys to set the desired value or press the mode key to return
- Press the enter key to confirm the setting or the mode key to cancel the setting
Buzzer Setting
The RAD-0502 CO2 Grow Controller can choose to turn ON or OFF the buzzer alarm.
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down keys to select time or press and hold the mode key for 3 seconds to return to the main buzzer mode
- Press the enter key to enter into the setting screen of the buzzer
- Press the enter key to enter the state setting or press the mode key to return
- Press the up or down key to select whether to turn ON the buzzer alarm
- Press the enter key to confirm the setting or the mode key to cancel the setting
The Buzzer Alarm Setting
The RAD-0502 CO2 Grow Controller can set the buzzer alarm when the concentration of CO2 exceeds the threshold.
- Press and hold the mode key for 3 seconds to enter the setting mode
- Press the up or down key to select Buzzer or press and hold the mode key for 3 seconds to return to the main display mode
- Press the enter key to enter into the setting screen for the buzzer
- Press the up or down keys to select CO2 alarm or press the mode key to return
- Press the enter key to enter into the CO2 alarm
- Press the up or down key to set the desired value or press the mode key to return
- Press the enter key to confirm the setting or the mode key to cancel
Calibration “Clear” Setting
The RAD-0502 CO2 Grow Controller can clear the calibration data for CO2, TEMP, and RH.
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down keys to select calibration or press and hold the mode key for 3 seconds to return to the main display
- Press enter to enter into the calibration setting
- Press the up or down key to select clear or press the mode key to return
- Press the enter key to enter into the clear setting
- Press the up or down keys to select “yes” or press the mode key to return
- Press the enter key to confirm the setting or the mode key to cancel the setting
Recovery Setting
- Press and hold the mode key for 3 seconds to enter into the setting mode
- Press the up or down keys to select recovery setting or press and hold the mode key for 3 seconds to return to the main display mode
- Press the enter key to enter into recovery settings
- Press the up or down key to select “yes” or press the mode key to return
- Press the enter key to confirm the setting or the mode key to cancel the setting
Technical Specifications
CO2 Sensing Method | Non-Dispersive Infrared (NDIR) |
---|---|
CO2 Measurement Range | 0-3,000ppm |
CO2 Accuracy | 0~2,000ppm: ± 70ppm or ± 5% of the reading whichever is greater |
Display Resolution | 1ppm at 0~1,000ppm, 10ppm above 1,000ppm |
Repeatability | ± 20ppm @ 400ppm |
Pressure Dependence | 0.13% of reading per mm Hg |
Temperature | 32°F to 122°F (0°C to 50°C) |
Storage Temperature | -4°F to 140°F (-20°C to 60°C) |
Humidity | 0~95% RH Non-condensing |
Response Time | < 2 minutes for 63% response to step change |
Warm-up Time | < 60 seconds at 71.6°F (22°C) |
Splash Rating | IP54 |
Power Supply & Relay Output
Power Supply | AC Adapter | 110/220 VAC |
---|---|---|
AC Input
| Voltage| 100~240 VAC
Frequency| 50/60 Hz
Power Requirement| 1 W Maximum @ 115VAC 60 Hz, 2 W Maximum @ 230VAC 50 Hz
AC Output| 12.0V
Relay Socket| 1 Relay Output, peak current < 5A @ 250 VAC, SPST. Normally open
Dimensions
Main Indoor CO2 Grow Controller Unit
Fault Codes and Troubleshooting
This section includes a list of Frequently Asked Questions for problems you may encounter with the RAD-0502 CO2 Indoor controller for grow rooms.
No
| LCD
Fault Icon D
|
Description of the fault
| Suggested Action EU
---|---|---|---
1| Er3| Ambient temperature exceeded the temperature range 0° C to 50°C (32°F
to 122°F)| This error will disappear when the temperature returns to the range
between 0°C and 50°C (32°F to 122°F)
2| Er4| Inaccurate Measurement or the sensor has exceeded its expected life|
Please unplug the AC adapter and reconnect it. If the “Er4” is always
appearing, contact CO2Meter.
3| Er5 Er6| EEPROM System Problem| Please unplug the AC adapter and reconnect
it. If the “Er5, Er6” still appear, please contact CO2Meter.
4| Er8| The accuracy of CO2 Sensor may deviate from the actual concentration|
1. Please unplug the AC adapter and reconnect. If the “Er8” still appear,
please contact CO2Meter.
2. Please calibrate the unit. After calibration, if “Er8” still appears, please contact the local dealer.
5| Er9| Calibration failure is caused by the large difference between the calibration value and ambient value. (Usually done by mistake)| Please set the correct calibration value before doing the calibration
Support and Warranty
Contact Us, We Are Here to Help!
If the troubleshooting guide above doesn’t help you solving your problem or for more information, please contact us using the information below:
- Support@CO2Meter.com
- (386)256-4910 (M-F 9:00am–5:00pm EST)
- www.CO2Meter.com