Hawkeye H735 Current Switches with Relay User Guide

May 15, 2024
hawkeye

Hawkeye-LOGO

Hawkeye H735 Current Switches with Relay

Specifications

  • Sensor Power: Insulation Class
  • Frequency Range:
  • Temperature Range:
  • Humidity Range:
  • Hysteresis:
  • Terminal Block Wire Size:
  • Terminal Block Torque:
  • Warranty: Limited Warranty 5 years
  • Agency Approvals: UL 508 open device listing,CAT III, Pollution Degree 2, basic insulation E150462

Product Information

The Hawkeye Relay Combination Series is designed to maximize reliability and minimize installed cost for automation installers.
These units combine a current switch and relay into a single package, offering status and control in one convenient solution.
The devices allow for start/stop control and status monitoring with a single device, simplifying installation and reducing space requirements.

Key Features:

  • Combined relay & status sensor
  • Two outputs for increased control
  • Fan & pump status monitoring
  • Added flexibility with multiple installation configurations
  • Polarity insensitive for easy setup
  • Relay and status LEDs for quick visual indication

Applications:

  • Detects belt loss/coupling shear
  • Fan/pump status monitoring
  • Electrical failure detection

Product Usage Instructions

Installation:

  1. Ensure power is disconnected before installation.
  2. Mount the unit securely using the provided brackets in the desired configuration.
  3. Connect the appropriate wires to the terminal block following the specified wire size and torque requirements.

Setting Trip Point:

  1. Determine the desired trip point for current monitoring based on your application requirements.
  2. Adjust the trip point using the provided settings on the device.
  3. Test the functionality by simulating different current levels.

Status Monitoring:

  1. Observe the relay and status LEDs for indication of device operation.
  2. Monitor fan and pump status regularly to detect any issues such as belt loss or motor failure.

Frequently Asked Questions (FAQ)

Q: What are the typical coil performance specifications for the product?
A: The typical coil performance includes voltage ratings for AC and DC operation, pull-in voltage, and drop-out voltage for different models within the series.

Q: How can I detect belt loss or coupling shear using the product?
A: The product is designed to detect belt loss or coupling shear by monitoring changes in current draw, allowing you to easily identify issues such as slipping belts or sheared couplings.

H735, HX38, HX48,HX58 SERIES
Status and Control in One Package

The Hawkeye Relay Combination Series is the ideal solution for the automation installer. These units combine a current switch and relay into a single package, reducing the space required for total control of fans and pumps. The current switch and relay operate independently of one another. These devices allow start/stop control and status monitoring with one device instead of two.

SPECIFICATIONS

Sensor Power Induced from monitored conductor
Insulation Class 600 Vac RMS
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10 to 90% RH non-condensing
Hysteresis 10% Typical
Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

WARRANTY

  • Limited Warranty 5 years

AGENCY APPROVALS

  • Agency Approvals UL 508 open device listing, CAT III, Pollution
    Degree 2, basic insulation

Note: Do not use the LED status indicators as evidence of applied voltage.

Combined relay & status
Combines command relay and fan/pump status sensor in a single, easy-to-install unit

Fan & pump status
Detect belt loss and motor failure…ideal for fan and pump status

Polarity insensitive
Polarity insensitive status outputs…fast and easy installation

Two outputs
H748 and H948 feature a SPDT command relay…control two outputs with a single relay

Added flexibility
Bracket on H938, H948, and H958 can be installed in three different configurations

Easy setup
Relay and status LEDs

APPLICATIONS

  • Starting/stopping and monitoring positive status of motors
  • Detecting belt loss and coupling shear

Hawkeye-H735-Current-Switches-with-Relay-1

RELAY CONTACT RATINGS

H735 (SPST, N.O.)

  • Resistive 5 A @ 250 Vac, 30 Vdc
  • Inductive 3 A @ 250 Vac, 30 Vdc
  • Hx38, Hx58 (SPDT N.O.)
  • Resistive 10 A @ 250 Vac, 30 Vdc
  • Inductive 5 A @ 250 Vac, 30 Vdc
  • Hx48 (SPDT)
  • Resistive 8 A @ 250 Vac, 30 Vdc
  • Inductive 3.5 A @ 250 Vac, 30 Vdc

TYPICAL COIL PERFORMANCE

H735/738/748
Dimensional Drawing

Hawkeye-H735-Current-Switches-with-Relay-2

  • Terminal block may extend up to 1/8” over the height dimensions shown.
  • Slide switch may extend up to 1/4” over the height dimensions shown.

H938/948/958
Dimensional Drawing

START/STOP MONITORING OF FAN /PUMP MOTORS
Wiring Diagram

Hawkeye-H735-Current-Switches-with-Relay-4

RELAY CONTROLLED DIRECTLY BY STATUS CONTACTS
Wiring Diagram

ORDERING INFORMATION

Hawkeye-H735-Current-Switches-with-Relay-7

800.354.8556 | +1 503.598.4564
sales@veris.com 
intl@veris.com 
veris.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals