legrand 26144 Motor Driven Handle Instructions
- June 1, 2024
- Legrand
Table of Contents
legrand 26144 Motor Driven Handle
Product Information
Specifications:
- Model Number: LE14036AA
- Components: A1, B4, C1, D1, E1, F2, G, G1, H1, H
- Input Voltage: 70-260V
- Operating Temperature: 51-94°F
- Max Load Capacity: 198A
- Weight: 105g
Product Usage Instructions
Automatic Operation:
- Opening can be done through a single impulse, continuous control, or push button 4.
- Electrical closing operation is available through impulsive or continuous control.
- Reset can be done either through the motor or with lever 1.
NOTE: The cover shield must not be removed in this operation mode.
Manual Operation:
- Closing and opening are done exclusively through push buttons 3 and 4.
- Reset is only possible through lever 1.
Lock in Open Position:
- This function stops any operation and trips the breaker.
FAQ (Frequently Asked Questions)
Q: How can I switch between automatic and manual operation modes?
A: To switch between modes, push the padlock (12) inside to enable the
Aut/Man mode.
Q: What do the indicator colors signify?
A: RED indicates closed status while GREEN indicates open status.
Q: What should I do if the springs are discharged?
A: If the springs are discharged, use lever 1 for manual reset.
TOOLS
A | 1 |
---|---|
B | 4 |
C | 1 |
D | 1 |
E | 1 |
F | 2 |
G | 1 |
H | 1 |
INSTRUCTION
-
Manual reset lever
-
Springs indicator
DISCHARGED
CHARGED
springs unloaded
DISCHARGED
CHARGED spings loaded -
Closing push button
-
Opening push button
-
Mode selector
AUTOMATIC OPERATION-
Opening through single impulse or continuous control or push button 4.
-
Electrical closing operation only (through impulsive or continuous control).
-
Reset through the motor or with lever 1.
ATT.: The cover shield must not be removed in this operation mode.
MANUAL OPERATION
Closing and opening only through the push bottons (3 – 4). -
Reset only through the lever (1).
LOCK IN OPEN POSITION -
Stops any operation.
-
Trips the breaker.
-
-
Breaker contacts indicator
-
Padlock in open position.
Att.: The padlock (12) have to be pushed inside to get in “Aut/Man” mode.
ASSEMBLY
SETUP
WHATS IN THE BOX
TOOLS FIXING
Automatic C.B. or isolator
Motor operator
Opening/trip push button
Contacts for cover’s protection
Cam control – spring loaded indication
Auxiliary contact MCCB (Ref. 26160)
Release 2 N.O.
Release N.O.
Closing coil
Auxiliary contact MCCB (Ref. 26160)
Closing push button
Contact for volontary reset
COLOUR TABLE
- Bk: Black
- Wh: White
- Rd: Red
- Bl: – Blue
USE FOR AUTOMATIC CHANGEOVER
Caution: according to the use mode of the motor that is:
- without tripping device or
- with tripping device
(26164-8;26181-4)
The changeover time between main and secondary line (time between the opening of the breakers of the main line and the closing of the breakers of the secondary line and viceversa) should be setted at a value bigger or equal respectively to:
- 6 sec or
- 0,5 sec
Switch Operated
Volontary reset
Push button Operated
Volontary reset
Automatic reset after trip
Att.: In the figures the C.B. is represented in open position, with spring’s motor loaded.
BORNE A CAGE LUG / KLEMMEN / BORNA / MORSETTO / TERMINAIS
/ ВЫВОД /| FUNCTION
---|---
1| Closing power supply
2
3| Opening power supply
4
5|
NO (250
Vac/2A)
| Spring loaded
6
7| Not connected
8
TECHNICAL CHARACTERISTICS
TENSION / VOLTAGE / SPANNING / TENSIÓN / TENSIONE / TENSÃO / НАПРЯЖЕНИЕ / NAPIĘCIE / GERİLİM /
电压
| PUISSANCE ABSORBEE / START INPUT POWER / START / POTENCIA ABSORBIDA AL ARRANQUE /
POTENZA ASSORBITA ALLO SPUNTO / POTÊNCIA ABSORVIDA / ПОТР. МОЩНОСТЬ ПРИ ПУСКЕ /
POBÓR MOCY / BAŞLATMA GİRİŞ GÜCÜ /
启动输入电源
| TEMPS D’OUVERTURE TOTAL + REARMEMENT /
TOTAL OPENING TIME + RESET / TOTALE OPENINGSTIJD + RESET / TIEMPO TOTAL DE APERTURA+ REINICIO /
TEMPO TOTALE DI APERTURA + RIPRISTINO /
TEMPO DE ABERTURA TOTAL
+ REARME / ПОЛНОЕ ВРЕМЯ ОТКЛЮЧЕНИЯ + ВОЗВРАТА /
CZAS WYŁĄCZENIA + ZAZBROJENIE
/ TOPLAM AÇTIRMA ZAMANI +
RESET / 完整断开时间 + 复位
| TEMPS DE FERMETURE / CLOSING TIME / SLUITTIJD / TIEMPO
DE CIERRE / TEMPO CHIUSURA / TEMPO
DE FECHO / ВРЕМЯ ВКЛЮЧЕНИЯ /
CZAS ZAŁĄCZENIA / KAPAMA ZAMANI /
合闸时间
24V dc|
300 W
|
2 s
|
<_100 ms
48V dc
110 – 125 V dc
220-250V dc
24V ac|
300 VA
|
2 s
|
<_100 ms
48V ac
110V ac
230V ac
Safety instructions
This product should be installed in compliance with installation rules,
preferably by a qualified electrician. Incorrect installation and use can lead
to risk of electric shock or fire. Before carrying out the installation, read
the instructions and take account of the product’s specific mounting location.
Do not open up, dismantle, alter or modify the device except where
specifically required to do so by the instructions. All Legrand products must
be opened and repaired exclusively by personnel trained and approved by
Legrand. Any unauthorised opening or repair completely cancels all liabilities
and the rights to replacement and guarantees. Use only Legrand brand
accessories.