LG ARNU073MAA4 Ceiling Concealed Duct Mid Static Air Conditioner User Manual
- June 1, 2024
- LG
Table of Contents
LG ARNU073MAA4 Ceiling Concealed Duct Mid Static Air Conditioner
Specifications
-
Type: Ceiling Concealed Duct – Mid Static
-
Model: ARNU073MAA4, ARNU093MAA4,
ARNU123MAA4 -
Cooling Capacity: 2.20 kW – 4.00 kW
-
Heating Capacity: 1,900 kcal/h – 3,400 kcal/h
-
Casing: Galvanized Steel Plate
-
Dimensions (W x H x D): 900mm x 245mm x 700mm / 35-7/16″ x 9-21/32″ x 27-9/16″
-
Coil Rows x Columns x FPI: 2 x 13 x 18
-
Fan Type: Sirocco Fan
-
Motor Output: 165W x 1
-
Air Flow Rate: 8/7/6 CMM (High/Medium/Low) or 283/247/212 CFM
-
Drive: Direct
-
Motor Type: BLDC
-
Temperature Control: Microprocessor, Thermostat for cooling and heating
-
Air Filter: Pre-filter
-
Safety Device: Fuse
-
Pipe Connections: Liquid Side: 6.35mm (1/4″), Gas Side: 12.7mm (1/2″)
-
Drain Pipe (Internal Dia.): 25mm (1″)
-
Net Weight: 28.4kg (62.6lbs)
-
Sound Pressure Level: 28/27/25 dB(A)+1 (High/Medium/Low)
-
Power Supply: 1,208/230V, 60Hz
-
Refrigerant Control: EEV (Electronic Expansion Valve)
-
Communication Cable: AWG 18 x 2C
Installation
- Ensure the unit is placed in a suitable location with proper airflow and access for maintenance.
- Connect the liquid and gas side pipe connections securely according to the specified diameters.
Multi V Air Conditioner
SVC MANUAL(Exploded View)
MODEL : ARNU073MAA4
- ARNU093MAA4
- ARNU123MAA4
- ARNU153MAA4
- ARNU183MAA4
- ARNU243MAA4
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
Specification
Type | Ceiling Concealed Duct -Mid Static |
---|---|
Model | Unit |
Cooling Capacity
| kW| 2.20| 2.80| 3.60
kcal/ h| 1,900| 2,400| 3,100
Btu/ h| 7,500| 9,600| 12,300
Heating Capacity
| kW| 2.50| 3.20| 4.00
kcal/ h| 2,200| 2,800| 3,400
Btu/ h| 8,500| 10,900| 13,600
Casing| Galvanized Steel Plate| Galvanized Steel Plate| Galvanized Steel Plate
Dimensions (W x H x D)|
Body
| mm| 900 x 245 x 700| 900 x 245 x 700| 900 x 245 x 700
inch| 35-7/ 16 x 9-21/ 32 x 27-9/ 16| 35-7/ 16 x 9-21/ 32 x 27-9/ 16| 35-7/ 16
x 9-21/ 32 x 27-9/ 16
Coil
| Rows x Columns x FPI| 2 × 13 × 18| 2 x 13 x 18| 2 x 13 x 18
Face Area| m2(sq.ft)| 0.19 (2.05)| 0.19 (2.05)| 0.19 (2.05)
Fan
| Type| Sirocco Fan| Sirocco Fan| Sirocco Fan
Motor Output x Number| W| 165 x 1| 165 x 1| 165 x 1
Running Current| A| 1.7| 1.7| 1.7
Air Flow Rate(H/ M/ L) (High Mode-Factory Set) Ext Static Pressure| CMM| 8 /
7 / 6| 10 / 9 / 8| 14 / 12 / 10
CFM| 283 / 247 / 212| 353 / 318 / 283| 494 / 424 / 353
mmAq(in.Aq)| 6(0.24)| 6(0.24)| 6(0.24)
Drive| Direct| Direct| Direct
Motor Type| BLDC| BLDC| BLDC
Temperature Control| Microprocessor, Thermostat for
cooling and heating
| Microprocessor, Thermostat for
cooling and heating
| Microprocessor, Thermostat for
cooling and heating
Sound Absorbing Thermal Insulation Material| Foamed polystrene| Foamed
polystrene| Foamed polystrene
Air Filter| Pre-filter| Pre-filter| Pre-filter
Safety Divice| Fuse| Fuse| Fuse
Pipe Connections
| Liquid Side| mm(inch)| Φ6.35 (1/ 4)| Φ6.35 (1/ 4)| Φ6.35 (1/ 4)
Gas Side| mm(inch)| Φ12.7 (1/ 2)| Φ12.7 (1/ 2)| Φ12.7 (1/ 2)
Drain Pipe(Internal Dia.)| mm(inch)| 25 (1)| 25 (1)| 25 (1)
Net Weight| Body| kg(lbs)| 28.4(62.6)| 28.4(62.6)| 28.4(62.6)
Sound Pressure Level (H/ M/ L)| dB(A)+1| 28 / 27 / 25| 28 / 27 / 26| 31 / 29 /
28
Power Supply| Ø, V, H z| 1, 208 / 230, 60| 1, 208 / 230, 60| 1, 208 / 230, 60
Refrigerant Control| –| EEV| EEV| EEV
Communication Cable(VCTF-SB)| AWG × cores| AWG 18 x2C| AWG 18 x2C| AWG 18 x 2C
Notes:
-
Capacities are based on the following conditions:
Cooling-
Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
-
Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
-
Interconnecting Piping Length 7.5m(24.6ft)
-
Level Difference of Zero
Heating -
Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
-
Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
-
Interconnecting Piping Length 7.5m(24.6ft)
-
Level Difference of Zero
-
-
Capacities are net capacities
-
Due to our policy of innovation some specifications may be changed without prior notification
-
To be added for more available Models
-
EEV : Electronic Expansion Valve
-
Noise Level is High Mode (factory set)
Conversion Formula
- kcal/h= kW x 860
- Btu/h = kW x 3412
- cfm = m3/min x 35.3
- l/s = CMM x 1000/60
Type | Ceiling Concealed Duct -Mid Static |
---|---|
Model | Unit |
Cooling Capacity
| kW| 4.50| 5.60| 7.10
kcal/ h| 3,900| 4,800| 6,100
Btu/ h| 15,400| 19,100| 24,200
Heating Capacity
| kW| 5.00| 6.30| 8.00
kcal/ h| 4,300| 5,400| 6,900
Btu/ h| 17,100| 21,500| 27,300
Casing| Galvanized Steel Plate| Galvanized Steel Plate| Galvanized Steel Plate
Dimensions (W x H x D)|
Body
| mm| 900 x 245 x 700| 900 x 245 x 700| 900 x 245 x 700
inch| 35-7/ 16 x 9-21/ 32 x 27-9/ 16| 35-7/ 16 x 9-21/ 32 x 27-9/ 16| 35-7/ 16
x 9-21/ 32 x 27-9/ 16
Coil
| Rows x Columns x FPI| 2 x 13 x 18| 2 x 13 x 18| 3 x 13 x 18
Face Area| m2(sq.ft)| 0.19 (2.05)| 0.19 (2.05)| 0.19 (2.05)
Fan
| Type| Sirocco Fan| Sirocco Fan| Sirocco Fan
Motor Output x Number| W| 165 x 1| 165 x 1| 165 x 1
Running Current| A| 1.7| 1.7| 1.7
Air Flow Rate(H/ M/ L) (High Mode-Factory Set) Ext Static Pressure| CMM| 15 /
12 / 11| 18 / 15 / 12| 20 / 15.5 / 13
CFM| 530 / 424 / 388| 635 / 530 / 424| 706 / 547 / 459
mmAq(in.Aq)| 6(0.24)| 6(0.24)| 6(0.24)
Drive| Direct| Direct| Direct
Motor Type| BLDC| BLDC| BLDC
Temperature Control| Microprocessor, Thermostat for
cooling and heating
| Microprocessor, Thermostat for
cooling and heating
| Microprocessor, Thermostat for
cooling and heating
Sound Absorbing Thermal Insulation Material| Foamed polystrene| Foamed
polystrene| Foamed polystrene
Air Filter| Pre-filter| Pre-filter| Pre-filter
Safety Divice| Fuse| Fuse| Fuse
Pipe Connections
| Liquid Side| mm(inch)| Φ6.35 (1/ 4)| Φ6.35 (1/ 4)| Φ9.52 (3/ 8)
Gas Side| mm(inch)| Φ12.7 (1/ 2)| Φ12.7 (1/ 2)| Φ15.88 (5/ 8)
Drain Pipe(Internal Dia.)| mm(inch)| 25 (1)| 25 (1)| 25 (1)
Net Weight| Body| kg(lbs)| 28.4(62.6)| 28.4(62.6)| 29.7(65.5)
Sound Pressure Level (H/ M/ L)| d B (A )+ 1| 33 / 31 / 29| 36 / 32 / 29| 38 /
33 / 30
Power Supply| Ø, V, Hz| 1, 208 / 230, 60| 1, 208 / 230, 60| 1, 208 / 230, 60
Refrigerant Control| –| EEV| EEV| EEV
Communication Cable(VCTF-SB)| AWG × cores| AWG 18 x 2C| AWG 18 x 2C| AWG 18 x
2C
Notes:-
-
Capacities are based on the following conditions:
Cooling-
Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
-
Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
-
Interconnecting Piping Length 7.5m(24.6ft)
-
Level Difference of Zero
Heating -
Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
-
Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
-
Interconnecting Piping Length 7.5m(24.6ft)
-
Level Difference of Zero
-
-
Capacities are net capacities
-
Due to our policy of innovation some specifications may be changed without prior notification
-
To be added for more available Models
-
EEV : Electronic Expansion Valve
-
Noise Level is High Mode (factory set)
Conversion Formula
- kcal/h= kW x 860
- Btu/h = kW x 3412
- cfm = m3/min x 35.3
- l/s = CMM x 1000/60
List of Functions
Category
|
Function
|
ARNU073MAA4, ARNU093MAA4, ARNU123MAA4 ARNU153MAA4, ARNU183MAA4, ARNU243MAA4
---|---|---
Air flow
| Air supply outlet| 1
Airflow direction control(left & right)| –
Airflow direction control(up & down)| –
Auto swing(left & right)| –
Auto swing(up & down)| –
Airflow steps(fan/cool/heat)| 3/3/3
Chaos swing| –
Chaos wind(auto wind)| –
Jet cool(Power wind)| –
Swirl wind| –
Air purifying
| Deodorizing filter| X
Plasma air purifier| X
Prefilter(washable)| O
Installation
| Drain pump| O
E.S.P. control| O
Electric heater(operation)| X
High ceiling operation| –
Vertical installation kit| ABDAMA0
Reliability| Hot start| O
Self diagnosis| O
Convenience
| Auto changeover| O (Heat recovery only)
Auto cleaning| O
Auto operation(artificial intelligence)| O (Heat pump or cooling only)
Auto restart operation| O
Child lock| O
Forced operation| –
Group control| O
Sleep mode| O
Timer(on/off)| O
Timer(weekly)| O
Two thermistor control| O
Individual control| LG Multi SITETM Remote Controller
(With Occupancy Sensor)
|
PREMTBVC1
LG Multi SITETM
Remote Controller
| PREMTBVC0
Premium| PREMTA000
Simple| PREMTC00U
Wireless Remote Controller| PQWRHQ0FDB
- O : Applied X : Not applied – : No relation
- Option : Model name & price are different according to options, and assembled in factory with main unit.
- Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Piping Diagrams
CHASSIS | MODEL | GAS | LIQUID |
---|---|---|---|
MA | ARNU073MAA4 | Ø12.7(1/2) | Ø6.35(1/4) |
ARNU093MAA4 | Ø12.7(1/2) | Ø6.35(1/4) | |
ARNU123MAA4 | Ø12.7(1/2) | Ø6.35(1/4) | |
ARNU153MAA4 | Ø12.7(1/2) | Ø6.35(1/4) | |
ARNU183MAA4 | Ø12.7(1/2) | Ø6.35(1/4) | |
ARNU243MAA4 | Ø15.88(5/8) | Ø9.52(3/8) | |
LOC. | Description | PCB Connector (Color) | |
--- | --- | --- | |
Th1 | Thermistor for room air temperature | CN_ROOM (Yellow) | |
Th2 | Thermistor for pipe in temperature | CN_PIPE_IN (White) | |
Th3 | Thermistor for pipe out temperature | CN_PIPE_OUT (Red) |
Wiring Diagrams
ARNU073MAA4, ARNU093MAA4, ARNU123MAA4, ARNU153MAA4, ARNU183MAA4, ARNU243MAA4
DIP Switch Setting
Indoor Unit
| Function| Description| Setting Off| Setting On|
Default
---|---|---|---|---|---
SW1| Communication| N/A (Default)| –| –| Off
SW2| Cycle| N/A (Default)| –| –| Off
SW3| Group Control| Selection of Master or Slave| Master| Slave| Off
SW4| Dry Contact Mode| Selection of Dry Contact Mode| Wired/Wireless remote
controller
Selection of Manual or Auto operation Mode
| ****
Auto
| ****
Off
SW5| Installation| Fan continuous operation| Continuous operation Removall| –|
Off
SW6| Heater linkage| N/A| –| –| Off
SW7| Ventilator linkage| Selection of Ventilator linkage| Linkage Removal|
Working| ****
Off
Vane selection (Console)| Selection of up/down side Vane| Up side + Down side
Vane| Up side Vane Only
Region selection| Selection tropical region| General model| Tropical model
SW8| Etc.| Spare| –| –| Off
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function
can start automatically with the im-proved speed by turning the DIP switch #3
of the outdoor unit and resetting the power.
* Specific conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
Exploded View
Self-diagnosis function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit
number. Indicates unit number.
(* = 1:Master, 2 : Slave 1, 3 : Slave 2)
- Ex) 211 : No.21 error of master unit
- 213 : No.21 error of slave2
- 1051 : No.105 error of master unit
Refer to the DX-Venitilation manual for DX-Venitilation error code
Display | Title | Cause of Error |
---|---|---|
Indoor unit related error | 0 | 1 |
unit | Air temperature sensor of indoor unit is open or short | |
0 | 2 | – |
sensor of indoor unit is open or short
0
|
3
|
–
| Communication error : wired remote controller indoor unit|
Failing to receive wired remote controller signal in indoor unit PCB
0| 4| –| Drain pump| Malfunction of drain pump
0
|
5
|
–
| Communication error : Indoor communication PCB indoor unit| Indoor Unit
PCB did not receive signal from Indoor communication PCB for over 3 minutes
continuously
0| 6| –| Outlet pipe temperature sensor of indoor unit| Outlet pipe
temperature sensor of indoor unit is open or short
0
|
9
|
–
| Indoor EEPROM Error| In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF
1
|
0
|
–
| Poor fan motor operation| Disconnecting the fan motor connector / Failure of
indoor fan motor lock
2| 3| 0| Refrigerant leakage sensing error| Refrigerant leakage sensing error
and sensor defect error
2
|
3
|
7
| Communication defect in indoor communication PCB outdoor communication PCB| Indoor communication PCB did not receive signal from outdoor communication PCB for over 3 minutes continuously
2
|
3
|
8
| Communication error in outdoor communication PCB outdoor unit| Outdoor communication PCB did not receive communication sig- nal from outdoor unit for over 3 minutes continuously
Copyright © 2024 LG Electronics Inc. All rights reserved. Only training and service purposes.