Product Information
Specifications
- Product Name: CP 660/CFS-F FX
- Manufacturer: Hilti
- Application: Firestop System
- Not suitable for outdoor applications
- Sensitive to UV light and not weather-resistant
- For professional use only
Product Usage Instructions
- Before handling and for specific application details, refer to Hilti product literature, 3rd party published listings, and national approvals.
- Ensure the area to be sealed is clean, dry, and free of dust and grease.
- Check the foil pack holder for damage and ensure it functions correctly.
- Slide the foil pack into the holder carefully.
- After application, remove the cartridge from the holder.
- Avoid allowing the hardened foam to remain in contact with standing water.
- Do not use the firestop foam for outdoor applications.
- Avoid exposing the foam to UV light as it is sensitive.
- Keep the product away from children and untrained personnel.
FAQ
Q: Can the firestop foam be used outdoors?
A: No, the firestop foam is not suitable for outdoor applications.
Q: Is the foam weather-resistant?
A: No, the foam is sensitive to UV light and is not weather-resistant.
Q: What precautions should be taken while using the product?
A: Keep the product away from children and untrained personnel. Avoid pointing the opened pack towards yourself or others.
qr.hilti.com/manual/?id=391791
Before handling and for specific application details, refer to Hilti product literature, 3rd party published listings and national approvals. For professional use only.
Product Information
- Foil pack temperature: Must be between +10 °C and +35 °C / +50 °F and +97 °F during application.
- Base material temperature: Must be between 0 °C and +40 °C/32 °F and +104 °F during application.
Read and follow the Safety Data Sheet (SDS) before use.
Installation Instructions
The operations to be carried out are illustrated in pictograms 1 – 7
-
Clean the opening to be sealed. The material around the opening must be dry, in sound condition and free from dust or grease.
-
Check the foil pack holder for damage and ensure that it functions correctly. Slide the foil pack into the holder.
- Caution: Never use damaged foil packs and/or damaged or badly soiled foil pack holders.
- Remove the cap. Screw the mixing nozzle onto the foil pack and tighten it securely. Check that the black mixing element is in place inside the nozzle! Do not use damaged mixing nozzles. Do not, under any circumstances, modify or tamper with the mixing nozzle. The foil pack should only be used together with the mixing nozzle supplied. A new mixing nozzle must be used with each new foil pack.
- Insert the holder containing the foil pack into the dispenser: Press the release button on the dispenser, pull the piston rod back as far as it will go and then insert the holder containing the foil pack into the dispenser.
-
The foil pack opens automatically when dispensing begins. Never pierce a hole in the foil pack!
Discard the unevenly mixed initial quantity: The foam dispensed by the first stroke of the dispenser must be discarded. -
Apply the firestop foam in the opening to be sealed. The mixed components of the foam react and begin to expand approx. 30 seconds after application (at 23 °C). Fill the opening with firestop foam, including gaps between individual cables, etc.
NOTE
It is generally best to begin in the middle of the opening, building up the foam by working from bottom to top. In openings with access from only one side, begin at the rear and work toward the front. The foam will harden in the mixing nozzle during pauses (i.e. >1 minute at 23 °C; >20 seconds at 35 °C). Use formwork made from an air-permeable material (e.g. perforated cardboard) when filling openings in ceilings. -
The foam can be shaped or smoothed by hand (if necessary) after approx. 5 minutes (at 23 °C). Wear protective gloves!
-
After approx. 10 minutes (at 23 °C) the foam becomes hard and it can then be cut.
NOTE
After hardening, any projecting foam can be trimmed off to the specified minimum depth. Trimmed-off scraps of hardened foam can be placed in the next opening and fresh foam applied around these. Residues in the foil pack can be completely dispensed and used for the next opening. -
Subsequent installation of cables or pipes:
Additional cables or pipes can be installed in the opening without difficulty. Do not exceed the approved maximum number and size of cables or pipes. -
The cable or pipe may be pushed directly through the foam. Where necessary, use a suitable tool (screwdriver or drill bit, etc.) to make a hole in the foam before pushing the cable or pipe through. Do not damage existing cables.
-
Seal any remaining gaps carefully with Firestop Foam CP 660/CFS-F FX.
Additional instructions
The firestop foam is not suitable for outdoor applications. The firestop foam is sensitive to UV light and is not weather-resistant. Do not allow the hardened foam to remain in contact with standing water.
CAUTION
- The product may present hazards when used incorrectly by untrained personnel or when not used as directed.
- The firestop compound may squirt out when the pack is opened. Never point the opened pack toward yourself or anyone else.
- Keep other persons, especially children, away from the working area.
Made in Germany