Centrometal MHPP5RP24CM Heat pumps Mono Instruction Manual

June 1, 2024
Centrometal

MHPP5RP24CM Heat pumps Mono

“`html

Specifications

  • Manufacturer: Centrometal d.o.o.
  • Model: Heat pumps Mono P-series
  • Refrigerant: R32

Product Information

System Configurations

The heat pump can be configured to run with the electric heater
either enabled or disabled and can also be used in conjunction with
an auxiliary heat source such as a boiler. The chosen configuration
affects the size of the heat pump that is required.

Product Lineup

Model Power supply (V/Ph/Hz)
MHPP5RP24CM 220-240/1/50
MHPP9RP24CM 220-240/1/50
MHPP16RP24P3CM 380-415/3/50

Nomenclature

The nomenclature indicates the model series number, power
supply, refrigerant, and other specifications.

Product Usage Instructions

System Design and Unit Selection

Selection Procedure:

  1. Total heat load calculation: Calculate total heat losses of the
    building. Select the heat emitters.

  2. System configuration: Decide whether to include auxiliary heat
    source and backup electric heater.

  3. Selection of outdoor units: Determine required total heat load
    on outdoor units. Select power supply.

Heat Pump Leaving Water Temperature (LWT) Selection

Choose the appropriate leaving water temperature for optimal
performance.

Optimizing System Design

To maximize comfort and energy efficiency, consider important
factors in system design.

Selection of Buffer Tank and DHW Tank

Selection of Buffer Tank:

The heat pump must be connected to the buffer tank to ensure
system efficiency. Select the buffer tank volume according to the
provided table.

Table 1-4.1: Minimum buffer tank volume

Model Buffer tank [L]
5-9 kW 25

FAQ

Q: How do I determine the total heat load for the

building?

A: Calculate the total heat losses of the building and select
the appropriate heat emitters.

Q: Can I use the heat pump with an auxiliary heat source?

A: Yes, the heat pump can be used in conjunction with an
auxiliary heat source such as a boiler.

“`

HEATING TECHNIQUE
Centrometal d.o.o. – Glavna 12, 40306 Macinec, Croatia, tel: +385 40 372 600, fax: +385 40 372 611

Technical manual
for installation, use and maintenance of heat pump

R32

ENG

Heat pumps Mono P-series
TU-DT-07-2023-ENG

CONTENTS
Part 1 General Informa on ………………………………………………………………. 3 Part 2 Engineering Data ……………………………………………………………………. 8

2

Technical manual Heat pumps – Mono

Part 1 General Informa on
1 System Configura ons …………………………………………………………………….. 4 2 Product lineup ……………………………………………………………………………….. 5 3 Nomenclature ……………………………………………………………………………….. 5 4 System Design and Unit Selec on ………………………………………………………. 6

Technical manual Heat pumps – Mono

3

Part 1
1 System Configura ons
Heat pump can be configured to run with the electric heater either enabled or disabled and can also be used in conjunc on with an auxiliary heat source such as a boiler.
The chosen configura on affects the size of the heat pump that is required. Three typical configura ons are described below.
Configura on 1: Heat pump only § The heat pump covers the required capacity and no extra hea ng capacity is necessary. § Requires selec on of larger capacity heat pump and implies higher ini al investment. § Ideal for new construc on in projects where energy efficiency is paramount.
Configura on 2: Heat pump and backup electric heater § Heat pump covers the required capacity un l the ambient temperature drops below the point at which the heat pump is able to provide sufficient capacity. When the ambient temperature is below this equilibrium point, the backup electric heater supplies the required addi onal hea ng capacity. § Best balance between ini al investment and running costs, results in lowest lifecycle cost. § Ideal for new construc on.
Configura on 3: Heat pump with auxiliary heat source § Heat pump covers the required capacity un l the ambient temperature drops below the point at which the heat pump is able to provide sufficient capacity. When the ambient temperature is below this equilibrium point, depending on the system se ngs, either the auxiliary heat source supplies the required addi onal hea ng capacity or the heat pump does not run and the auxiliary heat source covers the required capacity. § Enables selec on of lower capacity heat pump. § Ideal for refurbishments and upgrades.
Figure 1-1.1: System configura ons

4

Technical manual Heat pumps – Mono

2 Product lineup

Table 1-2.1: Heat pump models

Model

Power supply (V/Ph/Hz)

MHPP5RP24CM

220-240/1/50

MHPP9RP24CM

220-240/1/50

MHPP16RP24P3CM

380-415/3/50

Refrigerant R32 R32 R32

Part 1
Appearance

3 Nomenclature
M HP P 9 R P 24 P3 CM

Centrometal Power supply P3: 3-phase, 380-415V, 50Hz Omi ed: 1-phase, 220-240V, 50Hz Model series number
Refrigerant P: R32
Hea ng and cooling
Unit capacity in kW P-series
Heat pump
Mono series

Technical manual Heat pumps – Mono

5

Part 1
4 System Design and Unit Selec on
4.1 Selec on Procedure
Step 1: Total heat load calcula on Calculate total heat losses of the building. Select the heat emi ers (type, quan ty, water temperature and heat load).
Step 2: System configura on
Decide whether to include AHS and set AHS’s switching temperature. Decide whether backup electric heater is enabled or disabled.
Step 3: Selec on of outdoor units
Determine required total heat load on outdoor units. Set capacity safety factor. Select power supply.

Provisionally select heat pump unit capacity based on nominal capacity.

Correct capacity of the outdoor units for the following items: Outdoor air temperature / Outdoor humidity / Water outlet temperature¹ / Al tude / An -freeze fluid.

Is corrected heat pump unit capacity Required total heat load on outdoor units².

Yes

No

Heat pump system selec on is complete.

Select a larger model or enable backup electric heater opera on.

Notes: 1. If the required water temperatures of the heat emi ers are not all the same, the heat pump unit’s outlet water temperature se ng should be set at the highest of the heat emi er required water temperatures. If the water outlet design temperature falls between two temperatures listed in the outdoor unit’s capacity table, calculate corrected capacity by interpola on. 2. If the outdoor unit selec on is to be based on total hea ng load and total cooling load, select Mono units which sa sfy not only the total hea ng load requirements but also the total cooling load requirements.

6

Technical manual Heat pumps – Mono

Part 1
4.2 Heat Pump Leaving Water Temperature (LWT) Selec on
The recommended design LWT ranges for different types of heat emi er are: § For floor hea ng: 30 to 35°C; § For fan coil units: 30 to 45°C; § For low temperature radiators: 40 to 50°C.
4.3 Op mizing System Design
To get the most comfort with the lowest energy consump on with heat pump, it is important to take account of the following considera ons:
§ Choose heat emi ers that allow the heat pump system to operate at as low a hot water temperature as possible whilst s ll providing sufficient hea ng.
§ Make sure the correct weather dependency curve is selected to match the installa on enviroment (building structure, climate) as well as ender user’s demands.
§ Connec ng room thermostats (field supplied) to the hydronic system helps prevent excessive space hea ng by stopping the outdoor unit and circulator pump when the room temperature is above the thermostat set point.

4.4 Selec on of the buffer tank and DHW tank

4.4.1 Selec on of the buffer tank
The heat pump must be connected to the buffer tank in order to sa sfy the minimum amount of water in the system. The volume of the buffer tank must be selected according to table 1-4.1.

Table 1-4.1: Minimum buffer tank volume

Model

Buffer tank [L]

5-9 kW

25

16 kW

40

Cascade

40*n

n = number of heat pumps in cascade

4.4.2 Selec on of the DHW tank
The heat pump can be connected to the DHW tank. The tank can be with or without a built-in electric heater. The electric heater of the DHW tank must be installed below the tank temperature sensor. The tank temperature sensor must be above the heat exchangers in the tank. For the correct opera on of the DHW hea ng system with a heat pump, it is necessary to comply with the minimum requirements of the DHW tank given in table 1-4.2.

Table 1-4.2: Minimum requirements of the DHW tank

Model
DHW tank volume [L] Heat exchanger area – stainless steel coil [m2] Heat exchanger area – enamel coil [m2]

Recommended Mi ni mum Mi ni mum

5 kW 100-250
1,4
2,0

9 kW 150-300
1,4
2,0

16 kW 200-500
1,6
2,5

Temperature sensor

DHW tank

Heat exchanger

Outlet
Electric heater (DHWH) Inlet

Technical manual Heat pumps – Mono

7

Part 2 Engineering Data
1 Specifica ons ………………………………………………………………………………… 9 2 Electrical Characteris c ………………………………………………………………….. 11 3 Dimensions and Center of Gravity …………………………………………………….. 11 4 Opera ng Limits …………………………………………………………………………… 12 5 Capacity Tables …………………………………………………………………………….. 13 6 Hydronic Performance …………………………………………………………………… 28 7 Sound Levels ……………………………………………………………………………….. 29

8

Technical manual Heat pumps – Mono

1 Specifica ons

Table 2-1.1: MHPP5(9,16)RP24(P3)CM specifica ons

Model

Power supply (V/Ph/Hz)

Capacity

W

Hea ng A7W35

Rated input

W

COP

Capacity

W

Hea ng A7W45

Rated input

W

COP

Capacity

W

Hea ng A7W55

Rated input

W

COP

Capacity

W

Hea ng A2W35

Rated input

W

COP

Capacity

W

Hea ng A2W45

Rated input

W

COP

Capacity

W

Hea ng A2W55

Rated input

W

COP

Capacity

W

Hea ng A-7W35

Rated input

W

COP

Capacity

W

Hea ng A-7W45

Rated input

W

COP

Capacity

W

Hea ng A-7W55

Rated input

W

COP

Capacity

W

Cooling A35W18

Rated input

W

EER

Capacity

W

Cooling A35W7

Rated input

W

EER

Seasonal space hea ng energy efficiency class

Water outlet at 35°C Water outlet at 55°C

35°C Warmer climate
55°C

SCOP

35°C Average climate
55°C

35°C Colder climate
55°C

MHPP5RP24CM 220-240/1/50
6500 1226 5.30 6600 1650 4.00 6300 1969 3.20 5600 1333 4.20 6500 2063 3.15 6300 2250 2.80 6200 1938 3.20 6100 2346 2.60 5700 2651 2.15 6500 1275 5.10 5500 1692 3.25 A+++ A++ 6.78 4.35 5.12 3.59 4.41 2.90

Part 2

MHPP9RP24CM 220-240/1/50
10000 2128 4.70 10200 2795 3.65 9400 3032 3.10 8200 2158 3.80 8500 2881 2.95 8400 3170 2.65 8000 2667 3.00 7400 3083 2.40 7200 3512 2.05 10000 2326 4.30 9000 3103 2.90 A+++ A++ 7.05 4.91 5.12 3.71 4.44 3.14

MHPP16RP24P3CM 380-415/3/50 16000 3556 4.50 16200 4696 3.45 16000 5614 2.85 14500 4462 3.25 14300 5296 2.70 13500 5870 2.30 13500 5000 2.70 13500 6000 2.25 12800 6244 2.05 15400 3667 4.20 14000 4828 2.90 A+++ A++ 6.46 4.72 4.84 3.59 4.35 3.18

Technical manual Heat pumps – Mono

9

Part 2

SEER
Sound power level²
Compressor
Fan Air side heat exchanger Thro le Refrigerant Water side heat exchanger Rated water flow Water flow range Water pump
Expansion vessel Safety valve Flow switch Water side connec on Unit dimension (W×H×D) Packing dimension (W×H×D) Net weight Gross weight
Ambient temperature range
Water se ng temperature range

Water outlet at 7°C

Water outlet at 18°C

Hea ng A7W35

dB

Hea ng max

dB

Hea ng silence mode 1

dB

Hea ng silence mode 2

dB

Cooling A35W18

dB

Cooling max

dB

Cooling silence mode 1

dB

Cooling silence mode 2

dB

Type

Type

Number

Air flow

m³/h

Type

Type

Type

Charged volume

kg

Type

m³/h

m³/h

Type

Maximum pump head

m

Volume

L

Maximum working pressure bar

MPa

m³/h

mm

mm

kg

kg

Cooling

°C

Hea ng

°C

DHW

°C

Cooling

°C

Hea ng

°C

DHW

°C

5.09

5.08

5.14

7.81

8.31

7.54

60

65

72

64

68

74

58

63

67

56

60

64

60

65

71

64

68

74

58

63

67

56

60

64

DC twin rotary

DC motor

1

1

1

3900

4500

5200

Fin coil

Electronic expansion valve

R32

1.25

1.25

1.8

Plate

1.12

1.72

2.75

0.4 ~ 1.25

0.4 ~ 2.10

0.7 ~ 3.00

DC

DC

DC

9

9

9

5

5

5

8

8

8

0.3

0.3

0.3

0.36

0.36

0.6

G1″BSP

G1″BSP

G5/4″BSP

865×1040×410

865×1040×410

865×1040×410

970×1190×560

970×1190×560

970×1190×560

87

87

120

103

103

136

-5 ~ 43

-5 ~ 43

-5 ~ 43

-25 ~ 35

-25 ~ 35

-25 ~ 35

-25 ~ 43

-25 ~ 43

-25 ~ 43

5 ~ 25

5 ~ 25

5 ~ 25

25 ~ 65

25 ~ 65

25 ~ 65

20 ~ 60

20 ~ 60

20 ~ 60

Notes: 1. The above data test reference standard EN14511; EN14825; EN50564; EN12102; (EU) No 811/2013; (EU) No 813/2013; OJ 2014/C 207/02. 2. Sound power test condi on: EN12102-1.

10

Technical manual Heat pumps – Mono

Part 2

2 Electrical Characteris cs

Table 2-2.1: Electrical characteris cs

Outdoor unit

System

Voltage (V)

Hz

Min. (V)

MHPP5RP24CM 220-240 50 198

MHPP9RP24CM 220-240 50 198

MHPP16RP24P3CM 380-415 50 342

Max. (V)
264 264 456

Power current

MCA

TOCA

MFA

(A)

(A)

(A)

13

18

25

16

18

25

11.5

14

16

Compressor

MSC

RLA

(A)

(A)

10.5

10.5

16

Fan

kW

FLA (A)

0.17 1.5

0.17 1.5

0.17 0.7

Table 2-2.2: Outdoor unit wiring and circuit breakers

Model

Power supply (V/Ph/Hz)

Nominal cross-sectional area (mm2)

MHPP5RP24CM

220-240/1/50

3×4.0

MHPP9RP24CM

220-240/1/50

3×4.0

MHPP16RP24P3CM

380-415/3/50

5×2.5

Circuit breaker (A)/Ph
B16/1ph B20/1ph B16/3ph

3 Dimensions and Center of Gravity

Table 2-3.1: Outdoor unit dimensions

Unit: mm

Model

A

B

C

MHPP5RP24CM

350

355

285

MHPP9RP24CM

350

355

285

MHPP16RP24P3CM

500

400

275

Technical manual Heat pumps – Mono

11

Part 2
4 Opera ng Limits
Figure 2-4.1: Hea ng opera ng limits

Figure 2-4.2: Cooling opera ng limits

Figure 2-4.3: Domes c hot water opera ng limits

Abbrevia ons: T4: Outdoor temperature (°C) T1: Leaving water temperature (°C) IBH: Backup electric heater AHS: Addi onal heat source

Notes: If IBH/AHS se ng is valid, only IBH/AHS turns on; If IBH/AHS se ng is invalid, only heat pump turns on, limita on and protec on may occur.
Heat pump turns off, only IBH/AHS turns on. (IBH can heat the water temperature up to 65°C, AHS can heat the water temperature up to 70°C)

Opera on range by heat pump with possible limita on and protec on.

Maximum inlet water temperature line for heat pump opera on.

12

Technical manual Heat pumps – Mono

Part 2

5 Capacity Tables

5.1 Hea ng Capacity Tables (Test standard: EN14511)

Table 2-5.1: MHPP5RP24CM hea ng capacity

Part load: Maximum

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

Part load: 130%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

Part load: 100%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC
30 PI COP HC
30 PI COP HC

35 PI COP HC
35 PI COP HC
35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

LWT

40

45

PI COP HC PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC
50 PI COP HC
50 PI COP HC

55 PI COP HC
55 PI COP HC
55 PI COP HC

60 PI COP HC
60 PI COP HC
60 PI COP HC

65 PI COP
65 PI COP
65 PI COP

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

Technical manual Heat pumps – Mono

13

Part 2

Part load: 90%

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: 70%

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: 50%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

14

Technical manual Heat pumps – Mono

Part 2

Part load: 30%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: Minimum

LWT

DB

25

30

35

40

45

HC PI COP HC PI COP HC PI COP HC PI COP HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Technical manual Heat pumps – Mono

15

Part 2

Table 2-5.2: MHPP9RP24CM hea ng capacity

Part load: Maximum

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

Part load: 130%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC
30 PI COP HC

35 PI COP HC
35 PI COP HC

40 PI COP HC

LWT 45 PI COP HC

LWT

40

45

PI COP HC PI COP HC

Part load: 100%

LWT

DB

25

30

35

40

45

HC PI COP HC PI COP HC PI COP HC PI COP HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

Abbrevia ons:

LWT: Leaving water temperature (°C)

DB: Dry-bulb temperature for Outdoor air temperature (°C)

HC: Total hea ng capacity (kW)

PI: Power input (kW)

50 PI COP HC
50 PI COP HC
50 PI COP HC

55 PI COP HC
55 PI COP HC
55 PI COP HC

60 PI COP HC
60 PI COP HC
60 PI COP HC

65 PI COP
65 PI COP
65 PI COP

16

Technical manual Heat pumps – Mono

Part 2

Part load: 90%

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: 70%

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: 50%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

Technical manual Heat pumps – Mono

17

Part 2

Part load: 30%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: Minimum

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

18

Technical manual Heat pumps – Mono

Part 2

Table 2-5.3: MHPP16RP24P3CM hea ng capacity

Part load: Maximum

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: 130%

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

Part load: 100%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

50 PI COP HC
50 PI COP HC

55 PI COP HC
55 PI COP HC

60 PI COP HC
60 PI COP HC

65 PI COP
65 PI COP

Technical manual Heat pumps – Mono

19

Part 2

Part load: 90%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

40 PI COP HC

LWT 45 PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: 70%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Part load: 50%

DB

25

HC PI COP HC

-25

-20

-15

-10

-7

-5

-2

0

2

5

7

10

12

15

20

25

30

35

30 PI COP HC

35 PI COP HC

40 PI COP HC

LWT 45 PI COP HC

50 PI COP HC

55 PI COP HC

60 PI COP HC

65 PI COP

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

20

Technical manual Heat pumps – Mono

Part 2

Part load: 30%

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

40 PI COP HC

LWT 45 PI COP HC

Part load: Minimum

DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35

25 PI COP HC

30 PI COP HC

35 PI COP HC

LWT

40

45

PI COP HC PI COP HC

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)

50 PI COP HC
50 PI COP HC

55 PI COP HC
55 PI COP HC

60 PI COP HC
60 PI COP HC

65 PI COP
65 PI COP

Technical manual Heat pumps – Mono

21

Part 2

5.2 Cooling Capacity Tables (Test standard: EN14511)

Table 2-5.4: MHPP5RP24CM cooling capacity

Part load: Maximum

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI

EER

CC

18 PI EER CC

20 PI EER CC

25 PI EER

Part load: 130%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI

EER

CC

18 PI EER CC

20 PI EER CC

25 PI EER

Part load: 100%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI

EER

CC

18 PI EER CC

20 PI EER CC

25 PI EER

Part load: 90%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI

EER

CC

18 PI EER CC

20 PI EER CC

25 PI EER

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)

22

Technical manual Heat pumps – Mono

Part 2

Part load: 70%

DB CC

5 PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 50%

DB

5

CC

PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 30%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7

PI

EER

CC

7

PI

EER

CC

7

PI

EER

CC

LWT

10

15

PI EER CC

PI EER CC

LWT

10

15

PI EER CC

PI EER CC

LWT

10

15

PI EER CC

PI EER CC

Part load: Minimum

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7

PI

EER

CC

LWT

10

15

PI EER CC

PI EER CC

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)

18

PI

EER

CC

18

PI

EER

CC

18

PI

EER

CC

18

PI

EER

CC

20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC

25 PI EER
25 PI EER
25 PI EER
25 PI EER

Technical manual Heat pumps – Mono

23

Part 2

Table 2-5.5: MHPP9RP24CM cooling capacity

Part load: Maximum

DB

5

CC

PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 130%

DB CC

5 PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 100%

DB CC

5 PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 90%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7

PI

EER

CC

7

PI

EER

CC

7

PI

EER

CC

7

PI

EER

CC

LWT

10

15

PI EER CC

PI EER CC

LWT

10

15

PI EER CC

PI EER CC

LWT

10

15

PI EER CC

PI EER CC

LWT

10

15

PI EER CC

PI EER CC

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)

18

PI

EER

CC

18

PI

EER

CC

18

PI

EER

CC

18

PI

EER

CC

20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC

25 PI EER
25 PI EER
25 PI EER
25 PI EER

24

Technical manual Heat pumps – Mono

Part 2

Part load: 70%

DB CC

5 PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 50%

DB CC

5 PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 30%

DB CC

5 PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: Minimum

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC
7 PI EER CC
7 PI EER CC
7 PI EER CC

LWT

10

15

PI EER CC

PI

EER

CC

LWT

10

15

PI EER CC

PI

EER

CC

LWT

10

15

PI EER CC

PI

EER

CC

LWT

10

15

PI EER CC

PI

EER

CC

18 PI EER CC
18 PI EER CC
18 PI EER CC
18 PI EER CC

20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC

25 PI EER
25 PI EER
25 PI EER
25 PI EER

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)

Technical manual Heat pumps – Mono

25

Part 2

Table 2-5.6: MHPP16RP24P3CM cooling capacity

Part load: Maximum

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI EER CC

Part load: 130%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI EER CC

Part load: 100%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI EER CC

Part load: 90%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI EER CC

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)

18 PI EER CC
18 PI EER CC
18 PI EER CC
18 PI EER CC

20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC

25 PI EER
25 PI EER
25 PI EER
25 PI EER

26

Technical manual Heat pumps – Mono

Part 2

Part load: 70%

DB CC
-5 0 5 10 15 20 25 30 35 40 43

5 PI EER CC

7 PI EER CC

LWT

10

15

PI EER CC

PI EER CC

Part load: 50%

LWT

DB

5

7

10

15

CC

PI EER CC

PI EER CC

PI EER CC

PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: 30%

LWT

DB

5

7

10

15

CC

PI EER CC

PI EER CC

PI EER CC

PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Part load: Minimum LWT

DB

5

7

10

15

CC

PI EER CC

PI EER CC

PI EER CC

PI EER CC

-5

0

5

10

15

20

25

30

35

40

43

Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)

18 PI EER CC
18 PI EER CC
18 PI EER CC
18 PI EER CC

20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC

25 PI EER
25 PI EER
25 PI EER
25 PI EER

Technical manual Heat pumps – Mono

27

External sta c pressure (kPa)

Part 2
6 Hydronic Performance
Figure 2-6.1: MHPP5RP24CM / MHPP9RP24CM hydronic performance 100 90 80 70 60 50 40 30 20 10 0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 Water flow (m³/h)
Figure 2-6.2: MHPP16RP24P3CM hydronic performance 90 80 70 60 50 40 30 20 10 0 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 Water flow (m³/h)

External sta c pressure (kPa)

28

Technical manual Heat pumps – Mono

Part 2

7 Sound Levels

7.1 Overall

Table 2-7.1: Sound pressure levels¹
Model name
MHPP5RP24CM MHPP9RP24CM MHPP16RP24P3CM

dB(A)²
48 53 59

Notes: 1. Sound pressure level is measured at a posi on 1m in front of the unit and (1+H)/2m (where H is the height of the unit) above the floor in a semianechoic chamber. During in-situ opera on, sound pressure levels may be higher as a result of ambient noise.

Figure 2-7.1: Sound pressure level measurement (unit: mm)
Front 1000

(H+1000) 2

2. dB(A) is the maximum value tested under the condi ons below: Outdoor air temperature 7°C DB, 6°C WB; EWT 30°C, LWT 35°C. Free compressor frequency. Outdoor air temperature 7°C DB, 6°C WB; EWT 47°C, LWT 55°C. Free compressor frequency.

Technical manual Heat pumps – Mono

29

Part 2

7.2 Octave Band Levels (NR)

Octave band sound pressure level (dB)

Figure 2-7.2: MHPP5RP24CM octave band levels 120 110 100 90 80 70 60 50 40 30 20 10 0 -10 31.5 63 125 250 500 1000 2000 Octave band center frequency (Hz)

4000

NR-90 NR-80 NR-70 NR-60 NR-50 NR-40 NR-30 NR-20 NR-10 NR-0 8000

Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 12°C, LWT 7°C
Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 23°C, LWT 18°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 30°C, LWT 35°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 40°C, LWT 45°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 47°C, LWT 55°C.

Figure 2-7.3: MHPP9RP24CM octave band levels

Octave band sound pressure level (dB)

120

Cooling in rated frequency

110

Outdoor air temperature 35°C

100

DB; EWT 12°C, LWT 7°C

90

80

NR-90 Cooling in rated frequency

70

NR-80

Outdoor air temperature 35°C DB; EWT 23°C, LWT 18°C

60

NR-70

50 40

NR-60 NR-50

Hea ng in rated frequency Outdoor air temperature 7°C DB;

30

NR-40 85% R.H.; EWT 30°C, LWT 35°C

NR-30 20

10

NR-20 Hea ng in rated frequency

NR-10 Outdoor air temperature 7°C DB;

0

NR-0

85% R.H.; EWT 40°C, LWT 45°C

-10

31.5 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Hea ng in rated frequency Outdoor air temperature 7°C DB;

85% R.H.; EWT 47°C, LWT 55°C.

30

Technical manual Heat pumps – Mono

Figure 2-7.4: MHPP16RP24P3CM octave band levels

Octave band sound pressure level (dB)

120

110

100

90 NR-90
80 NR-80
70 NR-70
60 NR-60
50
NR-50 40

NR-40 30

NR-30 20

10

NR-20

0

NR-10

-10

NR-0

31.5 63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Part 2
Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 12°C, LWT 7°C
Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 23°C, LWT 18°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 30°C, LWT 35°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 40°C, LWT 45°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 47°C, LWT 55°C.

Technical manual Heat pumps – Mono

31

Notes

32

Technical manual Heat pumps – Mono

Company assumes no responsibility for possible inaccuracies in this book originated typographical errors or rewriting. All the pictures and diagrams are principal and it is necessary to adjust each actual situation on the field, in any case the company reserves the right to enter their own products such modifications as considered necessary.
Centrometal d.o.o. Glavna 12, 40306 Macinec, Croatia
central tel: +385 40 372 600, fax: +385 40 372 611 service tel: +385 40 372 622, fax: +385 40 372 621

www.centrometal.hr e-mail: [email protected]

HEATING TECHNIQUE

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Centrometal User Manuals

Related Manuals