Centrometal MHPP5RP24CM Heat pumps Mono Instruction Manual
- June 1, 2024
- Centrometal
Table of Contents
- MHPP5RP24CM Heat pumps Mono
- Specifications
- Product Information
- System Configurations
- Product Lineup
- Nomenclature
- System Design and Unit Selection
- Heat Pump Leaving Water Temperature (LWT) Selection
- Optimizing System Design
- Selection of Buffer Tank and DHW Tank
- Q: How do I determine the total heat load for the
- Q: Can I use the heat pump with an auxiliary heat source?
MHPP5RP24CM Heat pumps Mono
“`html
Specifications
- Manufacturer: Centrometal d.o.o.
- Model: Heat pumps Mono P-series
- Refrigerant: R32
Product Information
System Configurations
The heat pump can be configured to run with the electric heater
either enabled or disabled and can also be used in conjunction with
an auxiliary heat source such as a boiler. The chosen configuration
affects the size of the heat pump that is required.
Product Lineup
Model | Power supply (V/Ph/Hz) |
---|---|
MHPP5RP24CM | 220-240/1/50 |
MHPP9RP24CM | 220-240/1/50 |
MHPP16RP24P3CM | 380-415/3/50 |
Nomenclature
The nomenclature indicates the model series number, power
supply, refrigerant, and other specifications.
Product Usage Instructions
System Design and Unit Selection
Selection Procedure:
-
Total heat load calculation: Calculate total heat losses of the
building. Select the heat emitters. -
System configuration: Decide whether to include auxiliary heat
source and backup electric heater. -
Selection of outdoor units: Determine required total heat load
on outdoor units. Select power supply.
Heat Pump Leaving Water Temperature (LWT) Selection
Choose the appropriate leaving water temperature for optimal
performance.
Optimizing System Design
To maximize comfort and energy efficiency, consider important
factors in system design.
Selection of Buffer Tank and DHW Tank
Selection of Buffer Tank:
The heat pump must be connected to the buffer tank to ensure
system efficiency. Select the buffer tank volume according to the
provided table.
Table 1-4.1: Minimum buffer tank volume
Model | Buffer tank [L] |
---|---|
5-9 kW | 25 |
FAQ
Q: How do I determine the total heat load for the
building?
A: Calculate the total heat losses of the building and select
the appropriate heat emitters.
Q: Can I use the heat pump with an auxiliary heat source?
A: Yes, the heat pump can be used in conjunction with an
auxiliary heat source such as a boiler.
“`
HEATING TECHNIQUE
Centrometal d.o.o. – Glavna 12, 40306 Macinec, Croatia, tel: +385 40 372 600,
fax: +385 40 372 611
Technical manual
for installation, use and maintenance of heat pump
R32
ENG
Heat pumps Mono P-series
TU-DT-07-2023-ENG
CONTENTS
Part 1 General Informa on ………………………………………………………………. 3 Part 2 Engineering Data
……………………………………………………………………. 8
2
Technical manual Heat pumps – Mono
Part 1 General Informa on
1 System Configura ons …………………………………………………………………….. 4 2 Product lineup
……………………………………………………………………………….. 5 3 Nomenclature
……………………………………………………………………………….. 5 4 System Design and Unit Selec on
………………………………………………………. 6
Technical manual Heat pumps – Mono
3
Part 1
1 System Configura ons
Heat pump can be configured to run with the electric heater either enabled or
disabled and can also be used in conjunc on with an auxiliary heat source such
as a boiler.
The chosen configura on affects the size of the heat pump that is required.
Three typical configura ons are described below.
Configura on 1: Heat pump only § The heat pump covers the required capacity
and no extra hea ng capacity is necessary. § Requires selec on of larger
capacity heat pump and implies higher ini al investment. § Ideal for new
construc on in projects where energy efficiency is paramount.
Configura on 2: Heat pump and backup electric heater § Heat pump covers the
required capacity un l the ambient temperature drops below the point at which
the heat pump is able to provide sufficient capacity. When the ambient
temperature is below this equilibrium point, the backup electric heater
supplies the required addi onal hea ng capacity. § Best balance between ini al
investment and running costs, results in lowest lifecycle cost. § Ideal for
new construc on.
Configura on 3: Heat pump with auxiliary heat source § Heat pump covers the
required capacity un l the ambient temperature drops below the point at which
the heat pump is able to provide sufficient capacity. When the ambient
temperature is below this equilibrium point, depending on the system se ngs,
either the auxiliary heat source supplies the required addi onal hea ng
capacity or the heat pump does not run and the auxiliary heat source covers
the required capacity. § Enables selec on of lower capacity heat pump. § Ideal
for refurbishments and upgrades.
Figure 1-1.1: System configura ons
4
Technical manual Heat pumps – Mono
2 Product lineup
Table 1-2.1: Heat pump models
Model
Power supply (V/Ph/Hz)
MHPP5RP24CM
220-240/1/50
MHPP9RP24CM
220-240/1/50
MHPP16RP24P3CM
380-415/3/50
Refrigerant R32 R32 R32
Part 1
Appearance
3 Nomenclature
M HP P 9 R P 24 P3 CM
Centrometal Power supply P3: 3-phase, 380-415V, 50Hz Omi ed: 1-phase,
220-240V, 50Hz Model series number
Refrigerant P: R32
Hea ng and cooling
Unit capacity in kW P-series
Heat pump
Mono series
Technical manual Heat pumps – Mono
5
Part 1
4 System Design and Unit Selec on
4.1 Selec on Procedure
Step 1: Total heat load calcula on Calculate total heat losses of the
building. Select the heat emi ers (type, quan ty, water temperature and heat
load).
Step 2: System configura on
Decide whether to include AHS and set AHS’s switching temperature. Decide
whether backup electric heater is enabled or disabled.
Step 3: Selec on of outdoor units
Determine required total heat load on outdoor units. Set capacity safety
factor. Select power supply.
Provisionally select heat pump unit capacity based on nominal capacity.
Correct capacity of the outdoor units for the following items: Outdoor air temperature / Outdoor humidity / Water outlet temperature¹ / Al tude / An -freeze fluid.
Is corrected heat pump unit capacity Required total heat load on outdoor units².
Yes
No
Heat pump system selec on is complete.
Select a larger model or enable backup electric heater opera on.
Notes: 1. If the required water temperatures of the heat emi ers are not all the same, the heat pump unit’s outlet water temperature se ng should be set at the highest of the heat emi er required water temperatures. If the water outlet design temperature falls between two temperatures listed in the outdoor unit’s capacity table, calculate corrected capacity by interpola on. 2. If the outdoor unit selec on is to be based on total hea ng load and total cooling load, select Mono units which sa sfy not only the total hea ng load requirements but also the total cooling load requirements.
6
Technical manual Heat pumps – Mono
Part 1
4.2 Heat Pump Leaving Water Temperature (LWT) Selec on
The recommended design LWT ranges for different types of heat emi er are: §
For floor hea ng: 30 to 35°C; § For fan coil units: 30 to 45°C; § For low
temperature radiators: 40 to 50°C.
4.3 Op mizing System Design
To get the most comfort with the lowest energy consump on with heat pump, it
is important to take account of the following considera ons:
§ Choose heat emi ers that allow the heat pump system to operate at as low a
hot water temperature as possible whilst s ll providing sufficient hea ng.
§ Make sure the correct weather dependency curve is selected to match the
installa on enviroment (building structure, climate) as well as ender user’s
demands.
§ Connec ng room thermostats (field supplied) to the hydronic system helps
prevent excessive space hea ng by stopping the outdoor unit and circulator
pump when the room temperature is above the thermostat set point.
4.4 Selec on of the buffer tank and DHW tank
4.4.1 Selec on of the buffer tank
The heat pump must be connected to the buffer tank in order to sa sfy the
minimum amount of water in the system. The volume of the buffer tank must be
selected according to table 1-4.1.
Table 1-4.1: Minimum buffer tank volume
Model
Buffer tank [L]
5-9 kW
25
16 kW
40
Cascade
40*n
n = number of heat pumps in cascade
4.4.2 Selec on of the DHW tank
The heat pump can be connected to the DHW tank. The tank can be with or
without a built-in electric heater. The electric heater of the DHW tank must
be installed below the tank temperature sensor. The tank temperature sensor
must be above the heat exchangers in the tank. For the correct opera on of the
DHW hea ng system with a heat pump, it is necessary to comply with the minimum
requirements of the DHW tank given in table 1-4.2.
Table 1-4.2: Minimum requirements of the DHW tank
Model
DHW tank volume [L] Heat exchanger area – stainless steel coil [m2] Heat
exchanger area – enamel coil [m2]
Recommended Mi ni mum Mi ni mum
5 kW 100-250
1,4
2,0
9 kW 150-300
1,4
2,0
16 kW 200-500
1,6
2,5
Temperature sensor
DHW tank
Heat exchanger
Outlet
Electric heater (DHWH) Inlet
Technical manual Heat pumps – Mono
7
Part 2 Engineering Data
1 Specifica ons ………………………………………………………………………………… 9 2 Electrical Characteris c
………………………………………………………………….. 11 3 Dimensions and Center of Gravity
…………………………………………………….. 11 4 Opera ng Limits …………………………………………………………………………… 12 5
Capacity Tables …………………………………………………………………………….. 13 6 Hydronic Performance
…………………………………………………………………… 28 7 Sound Levels ………………………………………………………………………………..
29
8
Technical manual Heat pumps – Mono
1 Specifica ons
Table 2-1.1: MHPP5(9,16)RP24(P3)CM specifica ons
Model
Power supply (V/Ph/Hz)
Capacity
W
Hea ng A7W35
Rated input
W
COP
Capacity
W
Hea ng A7W45
Rated input
W
COP
Capacity
W
Hea ng A7W55
Rated input
W
COP
Capacity
W
Hea ng A2W35
Rated input
W
COP
Capacity
W
Hea ng A2W45
Rated input
W
COP
Capacity
W
Hea ng A2W55
Rated input
W
COP
Capacity
W
Hea ng A-7W35
Rated input
W
COP
Capacity
W
Hea ng A-7W45
Rated input
W
COP
Capacity
W
Hea ng A-7W55
Rated input
W
COP
Capacity
W
Cooling A35W18
Rated input
W
EER
Capacity
W
Cooling A35W7
Rated input
W
EER
Seasonal space hea ng energy efficiency class
Water outlet at 35°C Water outlet at 55°C
35°C Warmer climate
55°C
SCOP
35°C Average climate
55°C
35°C Colder climate
55°C
MHPP5RP24CM 220-240/1/50
6500 1226 5.30 6600 1650 4.00 6300 1969 3.20 5600 1333 4.20 6500 2063 3.15
6300 2250 2.80 6200 1938 3.20 6100 2346 2.60 5700 2651 2.15 6500 1275 5.10
5500 1692 3.25 A+++ A++ 6.78 4.35 5.12 3.59 4.41 2.90
Part 2
MHPP9RP24CM 220-240/1/50
10000 2128 4.70 10200 2795 3.65 9400 3032 3.10 8200 2158 3.80 8500 2881 2.95
8400 3170 2.65 8000 2667 3.00 7400 3083 2.40 7200 3512 2.05 10000 2326 4.30
9000 3103 2.90 A+++ A++ 7.05 4.91 5.12 3.71 4.44 3.14
MHPP16RP24P3CM 380-415/3/50 16000 3556 4.50 16200 4696 3.45 16000 5614 2.85 14500 4462 3.25 14300 5296 2.70 13500 5870 2.30 13500 5000 2.70 13500 6000 2.25 12800 6244 2.05 15400 3667 4.20 14000 4828 2.90 A+++ A++ 6.46 4.72 4.84 3.59 4.35 3.18
Technical manual Heat pumps – Mono
9
Part 2
SEER
Sound power level²
Compressor
Fan Air side heat exchanger Thro le Refrigerant Water side heat exchanger
Rated water flow Water flow range Water pump
Expansion vessel Safety valve Flow switch Water side connec on Unit dimension
(W×H×D) Packing dimension (W×H×D) Net weight Gross weight
Ambient temperature range
Water se ng temperature range
Water outlet at 7°C
Water outlet at 18°C
Hea ng A7W35
dB
Hea ng max
dB
Hea ng silence mode 1
dB
Hea ng silence mode 2
dB
Cooling A35W18
dB
Cooling max
dB
Cooling silence mode 1
dB
Cooling silence mode 2
dB
Type
Type
Number
Air flow
m³/h
Type
Type
Type
Charged volume
kg
Type
m³/h
m³/h
Type
Maximum pump head
m
Volume
L
Maximum working pressure bar
MPa
m³/h
mm
mm
kg
kg
Cooling
°C
Hea ng
°C
DHW
°C
Cooling
°C
Hea ng
°C
DHW
°C
5.09
5.08
5.14
7.81
8.31
7.54
60
65
72
64
68
74
58
63
67
56
60
64
60
65
71
64
68
74
58
63
67
56
60
64
DC twin rotary
DC motor
1
1
1
3900
4500
5200
Fin coil
Electronic expansion valve
R32
1.25
1.25
1.8
Plate
1.12
1.72
2.75
0.4 ~ 1.25
0.4 ~ 2.10
0.7 ~ 3.00
DC
DC
DC
9
9
9
5
5
5
8
8
8
0.3
0.3
0.3
0.36
0.36
0.6
G1″BSP
G1″BSP
G5/4″BSP
865×1040×410
865×1040×410
865×1040×410
970×1190×560
970×1190×560
970×1190×560
87
87
120
103
103
136
-5 ~ 43
-5 ~ 43
-5 ~ 43
-25 ~ 35
-25 ~ 35
-25 ~ 35
-25 ~ 43
-25 ~ 43
-25 ~ 43
5 ~ 25
5 ~ 25
5 ~ 25
25 ~ 65
25 ~ 65
25 ~ 65
20 ~ 60
20 ~ 60
20 ~ 60
Notes: 1. The above data test reference standard EN14511; EN14825; EN50564; EN12102; (EU) No 811/2013; (EU) No 813/2013; OJ 2014/C 207/02. 2. Sound power test condi on: EN12102-1.
10
Technical manual Heat pumps – Mono
Part 2
2 Electrical Characteris cs
Table 2-2.1: Electrical characteris cs
Outdoor unit
System
Voltage (V)
Hz
Min. (V)
MHPP5RP24CM 220-240 50 198
MHPP9RP24CM 220-240 50 198
MHPP16RP24P3CM 380-415 50 342
Max. (V)
264 264 456
Power current
MCA
TOCA
MFA
(A)
(A)
(A)
13
18
25
16
18
25
11.5
14
16
Compressor
MSC
RLA
(A)
(A)
–
10.5
–
10.5
–
16
Fan
kW
FLA (A)
0.17 1.5
0.17 1.5
0.17 0.7
Table 2-2.2: Outdoor unit wiring and circuit breakers
Model
Power supply (V/Ph/Hz)
Nominal cross-sectional area (mm2)
MHPP5RP24CM
220-240/1/50
3×4.0
MHPP9RP24CM
220-240/1/50
3×4.0
MHPP16RP24P3CM
380-415/3/50
5×2.5
Circuit breaker (A)/Ph
B16/1ph B20/1ph B16/3ph
3 Dimensions and Center of Gravity
Table 2-3.1: Outdoor unit dimensions
Unit: mm
Model
A
B
C
MHPP5RP24CM
350
355
285
MHPP9RP24CM
350
355
285
MHPP16RP24P3CM
500
400
275
Technical manual Heat pumps – Mono
11
Part 2
4 Opera ng Limits
Figure 2-4.1: Hea ng opera ng limits
Figure 2-4.2: Cooling opera ng limits
Figure 2-4.3: Domes c hot water opera ng limits
Abbrevia ons: T4: Outdoor temperature (°C) T1: Leaving water temperature (°C) IBH: Backup electric heater AHS: Addi onal heat source
Notes: If IBH/AHS se ng is valid, only IBH/AHS turns on; If IBH/AHS se ng is
invalid, only heat pump turns on, limita on and protec on may occur.
Heat pump turns off, only IBH/AHS turns on. (IBH can heat the water
temperature up to 65°C, AHS can heat the water temperature up to 70°C)
Opera on range by heat pump with possible limita on and protec on.
Maximum inlet water temperature line for heat pump opera on.
12
Technical manual Heat pumps – Mono
Part 2
5 Capacity Tables
5.1 Hea ng Capacity Tables (Test standard: EN14511)
Table 2-5.1: MHPP5RP24CM hea ng capacity
Part load: Maximum
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
Part load: 130%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
Part load: 100%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
30 PI COP HC
30 PI COP HC
35 PI COP HC
35 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
LWT
40
45
PI COP HC PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
50 PI COP HC
50 PI COP HC
55 PI COP HC
55 PI COP HC
55 PI COP HC
60 PI COP HC
60 PI COP HC
60 PI COP HC
65 PI COP
65 PI COP
65 PI COP
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
Technical manual Heat pumps – Mono
13
Part 2
Part load: 90%
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: 70%
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: 50%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
14
Technical manual Heat pumps – Mono
Part 2
Part load: 30%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: Minimum
LWT
DB
25
30
35
40
45
HC PI COP HC PI COP HC PI COP HC PI COP HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Technical manual Heat pumps – Mono
15
Part 2
Table 2-5.2: MHPP9RP24CM hea ng capacity
Part load: Maximum
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
Part load: 130%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
30 PI COP HC
35 PI COP HC
35 PI COP HC
40 PI COP HC
LWT 45 PI COP HC
LWT
40
45
PI COP HC PI COP HC
Part load: 100%
LWT
DB
25
30
35
40
45
HC PI COP HC PI COP HC PI COP HC PI COP HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
Abbrevia ons:
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for Outdoor air temperature (°C)
HC: Total hea ng capacity (kW)
PI: Power input (kW)
50 PI COP HC
50 PI COP HC
50 PI COP HC
55 PI COP HC
55 PI COP HC
55 PI COP HC
60 PI COP HC
60 PI COP HC
60 PI COP HC
65 PI COP
65 PI COP
65 PI COP
16
Technical manual Heat pumps – Mono
Part 2
Part load: 90%
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: 70%
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: 50%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
Technical manual Heat pumps – Mono
17
Part 2
Part load: 30%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: Minimum
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
18
Technical manual Heat pumps – Mono
Part 2
Table 2-5.3: MHPP16RP24P3CM hea ng capacity
Part load: Maximum
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: 130%
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
Part load: 100%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
50 PI COP HC
50 PI COP HC
55 PI COP HC
55 PI COP HC
60 PI COP HC
60 PI COP HC
65 PI COP
65 PI COP
Technical manual Heat pumps – Mono
19
Part 2
Part load: 90%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
40 PI COP HC
LWT 45 PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: 70%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Part load: 50%
DB
25
HC PI COP HC
-25
-20
-15
-10
-7
-5
-2
0
2
5
7
10
12
15
20
25
30
35
30 PI COP HC
35 PI COP HC
40 PI COP HC
LWT 45 PI COP HC
50 PI COP HC
55 PI COP HC
60 PI COP HC
65 PI COP
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
20
Technical manual Heat pumps – Mono
Part 2
Part load: 30%
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
40 PI COP HC
LWT 45 PI COP HC
Part load: Minimum
DB HC
-25 -20 -15 -10 -7 -5 -2
0 2 5 7 10 12 15 20 25 30 35
25 PI COP HC
30 PI COP HC
35 PI COP HC
LWT
40
45
PI COP HC PI COP HC
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) HC: Total hea ng capacity (kW) PI: Power input (kW)
50 PI COP HC
50 PI COP HC
55 PI COP HC
55 PI COP HC
60 PI COP HC
60 PI COP HC
65 PI COP
65 PI COP
Technical manual Heat pumps – Mono
21
Part 2
5.2 Cooling Capacity Tables (Test standard: EN14511)
Table 2-5.4: MHPP5RP24CM cooling capacity
Part load: Maximum
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI
EER
CC
18 PI EER CC
20 PI EER CC
25 PI EER
Part load: 130%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI
EER
CC
18 PI EER CC
20 PI EER CC
25 PI EER
Part load: 100%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI
EER
CC
18 PI EER CC
20 PI EER CC
25 PI EER
Part load: 90%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI
EER
CC
18 PI EER CC
20 PI EER CC
25 PI EER
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)
22
Technical manual Heat pumps – Mono
Part 2
Part load: 70%
DB CC
5 PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 50%
DB
5
CC
PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 30%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7
PI
EER
CC
7
PI
EER
CC
7
PI
EER
CC
LWT
10
15
PI EER CC
PI EER CC
LWT
10
15
PI EER CC
PI EER CC
LWT
10
15
PI EER CC
PI EER CC
Part load: Minimum
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7
PI
EER
CC
LWT
10
15
PI EER CC
PI EER CC
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)
18
PI
EER
CC
18
PI
EER
CC
18
PI
EER
CC
18
PI
EER
CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
25 PI EER
25 PI EER
25 PI EER
25 PI EER
Technical manual Heat pumps – Mono
23
Part 2
Table 2-5.5: MHPP9RP24CM cooling capacity
Part load: Maximum
DB
5
CC
PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 130%
DB CC
5 PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 100%
DB CC
5 PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 90%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7
PI
EER
CC
7
PI
EER
CC
7
PI
EER
CC
7
PI
EER
CC
LWT
10
15
PI EER CC
PI EER CC
LWT
10
15
PI EER CC
PI EER CC
LWT
10
15
PI EER CC
PI EER CC
LWT
10
15
PI EER CC
PI EER CC
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)
18
PI
EER
CC
18
PI
EER
CC
18
PI
EER
CC
18
PI
EER
CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
25 PI EER
25 PI EER
25 PI EER
25 PI EER
24
Technical manual Heat pumps – Mono
Part 2
Part load: 70%
DB CC
5 PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 50%
DB CC
5 PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 30%
DB CC
5 PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: Minimum
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
7 PI EER CC
7 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI
EER
CC
LWT
10
15
PI EER CC
PI
EER
CC
LWT
10
15
PI EER CC
PI
EER
CC
LWT
10
15
PI EER CC
PI
EER
CC
18 PI EER CC
18 PI EER CC
18 PI EER CC
18 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
25 PI EER
25 PI EER
25 PI EER
25 PI EER
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)
Technical manual Heat pumps – Mono
25
Part 2
Table 2-5.6: MHPP16RP24P3CM cooling capacity
Part load: Maximum
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI EER CC
Part load: 130%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI EER CC
Part load: 100%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI EER CC
Part load: 90%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI EER CC
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)
18 PI EER CC
18 PI EER CC
18 PI EER CC
18 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
25 PI EER
25 PI EER
25 PI EER
25 PI EER
26
Technical manual Heat pumps – Mono
Part 2
Part load: 70%
DB CC
-5 0 5 10 15 20 25 30 35 40 43
5 PI EER CC
7 PI EER CC
LWT
10
15
PI EER CC
PI EER CC
Part load: 50%
LWT
DB
5
7
10
15
CC
PI EER CC
PI EER CC
PI EER CC
PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: 30%
LWT
DB
5
7
10
15
CC
PI EER CC
PI EER CC
PI EER CC
PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Part load: Minimum LWT
DB
5
7
10
15
CC
PI EER CC
PI EER CC
PI EER CC
PI EER CC
-5
0
5
10
15
20
25
30
35
40
43
Abbrevia ons: LWT: Leaving water temperature (°C) DB: Dry-bulb temperature for Outdoor air temperature (°C) CC: Total cooling capacity (kW) PI: Power input (kW)
18 PI EER CC
18 PI EER CC
18 PI EER CC
18 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
20 PI EER CC
25 PI EER
25 PI EER
25 PI EER
25 PI EER
Technical manual Heat pumps – Mono
27
External sta c pressure (kPa)
Part 2
6 Hydronic Performance
Figure 2-6.1: MHPP5RP24CM / MHPP9RP24CM hydronic performance 100 90 80 70 60
50 40 30 20 10 0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
3.2 3.4 Water flow (m³/h)
Figure 2-6.2: MHPP16RP24P3CM hydronic performance 90 80 70 60 50 40 30 20 10 0
0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 Water
flow (m³/h)
External sta c pressure (kPa)
28
Technical manual Heat pumps – Mono
Part 2
7 Sound Levels
7.1 Overall
Table 2-7.1: Sound pressure levels¹
Model name
MHPP5RP24CM MHPP9RP24CM MHPP16RP24P3CM
dB(A)²
48 53 59
Notes: 1. Sound pressure level is measured at a posi on 1m in front of the unit and (1+H)/2m (where H is the height of the unit) above the floor in a semianechoic chamber. During in-situ opera on, sound pressure levels may be higher as a result of ambient noise.
Figure 2-7.1: Sound pressure level measurement (unit: mm)
Front 1000
(H+1000) 2
2. dB(A) is the maximum value tested under the condi ons below: Outdoor air temperature 7°C DB, 6°C WB; EWT 30°C, LWT 35°C. Free compressor frequency. Outdoor air temperature 7°C DB, 6°C WB; EWT 47°C, LWT 55°C. Free compressor frequency.
Technical manual Heat pumps – Mono
29
Part 2
7.2 Octave Band Levels (NR)
Octave band sound pressure level (dB)
Figure 2-7.2: MHPP5RP24CM octave band levels 120 110 100 90 80 70 60 50 40 30 20 10 0 -10 31.5 63 125 250 500 1000 2000 Octave band center frequency (Hz)
4000
NR-90 NR-80 NR-70 NR-60 NR-50 NR-40 NR-30 NR-20 NR-10 NR-0 8000
Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 12°C, LWT 7°C
Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 23°C, LWT 18°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 30°C,
LWT 35°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 40°C,
LWT 45°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 47°C,
LWT 55°C.
Figure 2-7.3: MHPP9RP24CM octave band levels
Octave band sound pressure level (dB)
120
Cooling in rated frequency
110
Outdoor air temperature 35°C
100
DB; EWT 12°C, LWT 7°C
90
80
NR-90 Cooling in rated frequency
70
NR-80
Outdoor air temperature 35°C DB; EWT 23°C, LWT 18°C
60
NR-70
50 40
NR-60 NR-50
Hea ng in rated frequency Outdoor air temperature 7°C DB;
30
NR-40 85% R.H.; EWT 30°C, LWT 35°C
NR-30 20
10
NR-20 Hea ng in rated frequency
NR-10 Outdoor air temperature 7°C DB;
0
NR-0
85% R.H.; EWT 40°C, LWT 45°C
-10
31.5 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
Hea ng in rated frequency Outdoor air temperature 7°C DB;
85% R.H.; EWT 47°C, LWT 55°C.
30
Technical manual Heat pumps – Mono
Figure 2-7.4: MHPP16RP24P3CM octave band levels
Octave band sound pressure level (dB)
120
110
100
90 NR-90
80 NR-80
70 NR-70
60 NR-60
50
NR-50 40
NR-40 30
NR-30 20
10
NR-20
0
NR-10
-10
NR-0
31.5 63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
Part 2
Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 12°C, LWT 7°C
Cooling in rated frequency Outdoor air temperature 35°C DB; EWT 23°C, LWT 18°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 30°C,
LWT 35°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 40°C,
LWT 45°C
Hea ng in rated frequency Outdoor air temperature 7°C DB; 85% R.H.; EWT 47°C,
LWT 55°C.
Technical manual Heat pumps – Mono
31
Notes
32
Technical manual Heat pumps – Mono
Company assumes no responsibility for possible inaccuracies in this book
originated typographical errors or rewriting. All the pictures and diagrams
are principal and it is necessary to adjust each actual situation on the
field, in any case the company reserves the right to enter their own products
such modifications as considered necessary.
Centrometal d.o.o. Glavna 12, 40306 Macinec, Croatia
central tel: +385 40 372 600, fax: +385 40 372 611 service tel: +385 40 372
622, fax: +385 40 372 621
www.centrometal.hr e-mail: servis@centrometal.hr
HEATING TECHNIQUE
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>