Centrometal 69-96 kW Pei Tec Lambda Boilers Instruction Manual
- May 15, 2024
- Centrometal
Table of Contents
- GENERAL
- CONNECTING BOILERS IN CONFIGURATION 4 (BUF) OR IN CONFIGURATION 10 (CRO)
- CASCADE
- CASCADE MANAGER
- DEVICE NUMBER
- DEVICE ADDRESS
- TIME TO ON
- TIME TO OFF
- TIME DIFFERENCE
- COUNTER RESET
- BOILER ATTACHED TO
- BOILER ACTIVATED
- CONNECTING BOILERS IN CONFIGURATION 11 (CRO/BUF)
- EC DECLARATION OF COMPARMITY
- CUSTOMER SUPPORT
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Centro metal 69-96 kW Pei Tec Lambda Boilers
GENERAL
These instructions are valid for software versions v2.88f or later.
CONNECTING BOILERS IN CONFIGURATION 4 (BUF) OR IN CONFIGURATION 10 (CRO)
IN CASCADE
It is possible to connect a maximum of 7 PelTec/PelTec-lambda boilers in a
cascade.
Peltec/PelTec-lambda 12-48 kW: all boilers connected in cascade must have
configuration 4 (BUF) or configuration 10 (CRO) selected.
PelTec-lambda 69/96 kW: all boilers connected in cascade must have
configuration 4 (BUF) selected.
Important!
PelTec-lambda 69/96 kW boilers with selected configuration 10 (CRO) cannot be
connected in a cascade.
MASTER / LEADING BOILER
Boiler-1 is the “Master” (the boiler that leads the cascade). If Boiler-1 is
disconnected from the cascade (or runs out of electricity or shuts down at the
main switch), Boiler-2 (next by device address) automatically becomes
“Master”, but it can perform the function of “Master” only if the sensors of
the Accumulation (buffer) tank / Hydraulic crossover are also connected to it.
When Boiler-1 is connected to the cascade again, it automatically becomes
“Master”. This “Master” function, if the need arises, can be taken over by any
boiler in the cascade in order according to the address of the device.
The sensors of the Accumulation (buffer) tank / Hydraulic crossover must be
connected to the boiler control of the “Master” boiler (Boiler-1), but there
must also be additional sensors of the Accumulation (buffer) tank / Hydraulic
crossover that must be connected to the boiler controllers of the other
boilers in the cascade so that any of the boilers in cascade could become
“Master” if the previous “Master” was disconnected from the cascade for any
reason.
The “Master” boiler in cooperation with the CMNET module determines all
actions within the cascade (determines when the next boiler will start/shut
down, determines which boiler is “Leading Boiler”…). The “Leading” boiler is
the boiler that starts first, after the first start-up of the boilers in the
cascade, the leading boiler is the “Master”, but when it completes a certain
number of working hours, the “Leading” boiler becomes the next boiler
according to the serial number of the address, and so on.
POSSIBLE WAYS OF CONNECTING BOILERS IN CASCADE
EXAMPLE: CASCADE 2 boilers
EXAMPLE: CASCADE 3-7 boilers
SELECTION OF BOILER CONFIGURATION – (4 (BUF) / 10 (CRO))
Cascade can work (can be enabled) only on boilers that have selected
configuration 4 (BUF) or configuration 10 (CRO). All boilers in the cascade
must have the same configuration selected.
CONFIGURING THE CASCADE
CASCADE
Factory: OFF
Possible selection: OFF, 1 CMNET, 2 CMNET
OFF: Cascade is OFF
1 CMNET: cascade of 2 boilers
- 2 boilers in cascade with 1 CMNET device.
2 CMNET: cascade of 2-7 boilers
- 2 boilers in cascade with 2 CMNET devices.
- 3 boilers in cascade with 3 CMNET devices.
- 4 boilers in cascade with 4 CMNET devices.
- 5 boilers in cascade with 5 CMNET devices.
- 6 boilers in cascade with 6 CMNET devices.
- 7 boilers in cascade with 7 CMNET devices.
CASCADE MANAGER
Factory: OFF
Possible selection: OFF, 1 CMNET, 2 CMNET
OFF: Cascade is OFF
1 CMNET: cascade of 2 boilers
- 2 boilers in cascade with 1 CMNET device.
2 CMNET: cascade of 2-7 boilers
- 2 boilers in cascade with 2 CMNET devices.
- 3 boilers in cascade with 3 CMNET devices.
- 4 boilers in cascade with 4 CMNET devices.
- 5 boilers in cascade with 5 CMNET devices.
- 6 boilers in cascade with 6 CMNET devices.
- 7 boilers in cascade with 7 CMNET devices.
DEVICE NUMBER
Factory: 2
Possible selection:
- Min: 2
- Max: 7
With this parameter, we define the number of boilers in the cascade. If we
selected 1 CMNET under “CASCADE”, then the number of devices must be 2. If we
chose 2 CMNET, then the number of devices must be as many as there are boilers
in the cascade (2-7). It is set on each boiler separately and must be the same
number on all boilers in the cascade.
DEVICE ADDRESS
Factory: 1
Possible selection:
- Min: 1
- Max: 7
This parameter determines the address (ordinal number) of the boiler. The
boiler with address 1 is the “Master”, and if the boiler with address 1 is
disconnected from the cascade (or remains without electricity or is turned off
at the main switch), the boiler with address 2 automatically becomes “Master”
(if the boiler with address 2 is ready in the cascade) and so on. The address
of the boilers is also used to determine the “leading boiler” – the boiler
that starts first (depending on the “Time difference” – after how many hours
of operation the boilers change priority of work). The “DEVICE ADDRESS” is
entered into the controller of each boiler in the cascade and each boiler must
have a different address.
TIME TO ON
a) Configuration 4 (BUF)
Factory: 3600s
Possible selection: min. 0s, max. 18000s
This parameter defines the time from the last arrival of the “Leading boiler”
(if several boilers in the cascade are currently working, then all boilers
that are working), to power D6, until the moment of checking the conditions
for the need to start the next boiler (with each modulation of any boiler in
the cascade, the time reset). If at that moment (the moment of checking the
conditions for the need to start the next boiler) the difference in the
Accumulation (buffer) tank (Taku_set – Taku_measured) is greater than
the dTaku_kz parameter, the next boiler will start.
After checking the conditions for the need to start the next boiler, the time
is reset, and when the “Leading boiler” (if several boilers are currently
working in a cascade, then all the boilers that are working) comes to power D6
starts a new countdown, if this condition is not met, the time stands at zero
and waits with the start of the countdown until this condition is fulfilled.
With each modulation of any boiler in the cascade, the time is reset.
b) Configuration 10 (CRO)
Factory: 3600s
Possible selection: min. 0s, max. 18000s
This parameter defines the time from the last arrival of the “Leading boiler”
(if several boilers in the cascade are currently working, then all boilers
that are working), to power D6, until the moment of checking the conditions
for the need to start the next boiler (with each modulation of any boiler in
the cascade, the time reset). If at that moment (the moment of checking the
conditions for the need to start the next boiler) the difference in the
Hydraulic crossover (Ths_set – Ths_measured) is greater than the
dThs_kz parameter, the next boiler will start.
After checking the conditions for the need to start the next boiler, the time
is reset, and when the “Leading boiler” (if several boilers are currently
working in a cascade, then all the boilers that are working) comes to power D6
starts a new countdown, if this condition is not met, the time stands at zero
and waits with the start of the countdown until this condition is fulfilled.
With each modulation of any boiler in the cascade, the time is reset.
TIME TO OFF
Factory: 600s
Possible selection: min. 0s, max. 3600s
This parameter determines after how long operate “Leading boiler” at power
(maximum) D3, last boiler go to extinction phase. It is set on each boiler
separately and can be a different value.
TIME DIFFERENCE
Factory: 100h
Possible selection: min. 0h, max. 500h
This parameter define after how many hours of work boilers change priority of
work. It is set on each boiler separately and can be a different value.
COUNTER RESET
This parameter enable reset of boiler work time counter. It can be reset on
each boiler separately.
ADJUSTMENT dTaku_kz / dThs_kz
Depending on the selected configuration, dTaku_kz or dThs_kz will
appear, if cascade is enabled. dTaku_kz – the temperature difference in
the Accumulation (buffer) tank (Taku_set – Taku_measured) occurs when
configuration 4 (BUF) is selected on the boilers. This parameter is used by
the controller at the moment of checking the conditions for the need to start
the next boiler. If at the moment of checking the conditions for the need to
start the next boiler, the difference in the Accumulation (buffer) tank
(Taku_set – Taku_measured) is greater than the dTaku_kz parameter, the
next boiler will be start. (For the definition of the moments of checking the
conditions for the need to start the next boiler, see under the point “TIME
TO ON”).
dThs_kz – the temperature difference in the Hydraulic crossover (Ths_set
– Ths_measured) occurs when configuration 10 (CRO) is selected on the boilers.
This parameter is used by the controller at the moment of checking the
conditions for the need to start the next boiler. If at the moment of checking
the conditions for the need to start the next boiler, the difference in the
Hydraulic crossover (Ths_set – Ths_measured) is greater than the dThs_kz
parameter, the next boiler will be start.(For the definition of the moments of
checking the conditions for the need to start the next boiler, see under the
point “TIMETOON”).
Factory: 6°C
Possible selection: min. 1°C, max. 15°C
Factory: 6°C
Possible selection: min. 1°C, max. 15°C
USER INTERFACE (disconnect the boiler from the cascade, disabling the start of the boiler)
BOILER ATTACHED TO
Factory: ON
Possible selection: OFF, ON
ON – The boiler is part of the cascade
OFF – The boiler has been removed from the cascade
- this boiler will be displayed in gray on the cascade screen
- this boiler will have a STOP/START switch on the boiler screen
Note:
Before taking off the boiler from the cascade, it is necessary to turn off the
“BOILER ACTIVATED” option, otherwise the boiler will start after removing it
from the cascade.
BOILER ACTIVATED
Factory: OFF
Possible selection: OFF, ON
ON – The boiler is active in the cascade system, and if the “BOILER
ATTACHED TO” option is turned on, the “cascade” can control that boiler
(start/stop).
OFF – The boiler is not active in the cascade system and “cascade” cannot
control it, on the cascade screen this boiler is shown in standard form except
that it is marked “STOP” (red square). Important:
- This option is turned off at the factory, if we want this boiler to be controlled by “cascade” it is necessary to turn on this option.
- If an individual boiler goes into error, the “BOILER ACTIVATED” option will automatically be turned off, after the error has been eliminated (corrected) and confirmed, the “BOILER ACTIVATED” option must be turned on if we want the “cascade” to control this boiler.
CASCADE SCREEN
Cascade screen can be displayed on each boiler in the cascade. The display on
the screen of the cascade of an individual boiler will highlight (frame) the
boiler on which we are viewing the cascade display.
A boiler in a cascade with the “BOILER ATTACHED TO” option turned off will be
displayed in gray.
Example:
Screen display of a cascade with two boilers, the review is performed on
boiler-1.
CONNECTING BOILERS IN CONFIGURATION 11 (CRO/BUF)
It is possible to connect a maximum of 7 PelTec/PelTec-lambda boilers in a
cascade.
Note: Scheme 11 (CRO/BUF) is used only in cascade and external start
(external control).
Important!
- in this configuration PelTec-lambda 69/96 boiler works only with CM2K module which must be installed and configurated
- in this configuration at PelTec-lambda 69/96 boiler shown is only Accumulation tank i.e. 2 sensors (at selection -/BUF)
MASTER / LEADING BOILER
Boiler-1 is the “Master” (the boiler that leads the cascade). If Boiler-1 is
disconnected from the cascade (or runs out of electricity or shuts down at the
main switch), Boiler-2 (next by device address) automatically becomes
“Master”, but it can perform the function of “Master”. When Boiler-1 is
connected to the cascade again, it automatically becomes “Master”. This
“Master” function, if the need arises, can be taken over by any boiler in the
cascade in order according to the address of the device.
Connecting the Accumulation (buffer) tank sensor / Hydraulic crossover sensor
is not required because these temperatures are only informative, if sensors
are not connected, regulation will show temperature ” – °C”. The boiler
regulation will not report any error even if the sensors are defective.
The “Master” boiler in cooperation with the CMNET module determines all
actions within the cascade (determines when the next boiler will start/shut
down, determines which boiler is “Leading Boiler”…). The “Leading” boiler is
the boiler that starts first, after the first start-up of the boilers in the
cascade, the leading boiler is the “Master”, but when it completes a certain
number of working hours, the “Leading” boiler becomes the next boiler
according to the serial number of the address, and so on.
POSSIBLE WAYS OF CONNECTING BOILERS IN CASCADE
EXAMPLE: CASCADE 2 boilers
EXAMPLE: CASCADE 3-7 boilers
SELECTION OF BOILER CONFIGURATION – (11 (CRO/BUF))
TEMPERATURE DISPLAYS
With this configuration, it is necessary to select the display of
temperatures.
Factory: 1 Temperature
Possible selection: 2 Temperatures
- TEMPERATURE: Hydraulic crossover (not possible for PelTec-lambda 69/96)
- TEMPERATURES: Accumulation (buffer) tank
When ’’1 Temperature’’ is selected, screen shows hydraulic crossover with 1
temperature (not possible at 69/96).
When ’’2 Temperatures’’ is selected, screen shows Accumulation (buffer) tank
with 2 temperatures.
This option can be changed only by authorized serviceman.
CONFIGURING THE CASCADE
CASCADE
Factory: OFF
Possible selection: OFF, 1 CMNET, 2 CMNET
OFF: Cascade is OFF
1 CMNET: cascade of 2 boilers
- 2 boilers in cascade with 1 CMNET device.
2 CMNET: cascade of 2-7 boilers
- 2 boilers in cascade with 2 CMNET devices.
- 3 boilers in cascade with 3 CMNET devices.
- 4 boilers in cascade with 4 CMNET devices.
- 5 boilers in cascade with 5 CMNET devices.
- 6 boilers in cascade with 6 CMNET devices.
- 7 boilers in cascade with 7 CMNET devices.
CASCADE MANAGER
Factory: ON
Possible selection: OFF, ON
This parameter must always be ON, on all boilers in the cascade. If this
parameter is turned OFF, the boiler on which it is turned OFF, as well as
boilers with an address that has a higher ordinal number, regardless of
whether this parameter is turned ON or OFF, will not be able to become
“Master”. This parameter must not be turned OFF on the boiler with the address
“Master” because the cascade will not work.
DEVICE NUMBER
Factory: 2
Possible selection:
- Min: 2
- Max: 7
With this parameter, we define the number of boilers in the cascade. If we
selected 1 CMNET under “CASCADE”, then the number of devices must be 2. If we
chose 2 CMNET, then the number of devices must be as many as there are boilers
in the cascade (2-7). It is set on each boiler separately and must be the same
number on all boilers in the cascade.
DEVICE ADDRESS
Factory: 1
Possible selection:
- Min: 1
- Max: 7
This parameter determines the address (ordinal number) of the boiler. The
boiler with address 1 is the “Master”, and if the boiler with address 1 is
disconnected from the cascade (or remains without electricity or is turned off
at the main switch), the boiler with address 2 automatically becomes “Master”
(if the boiler with address 2 is ready in the cascade) and so on. The address
of the boilers is also used to determine the “leading boiler” – the boiler
that starts first (depending on the “Time difference” – after how many hours
of operation the boilers change priority of work). The “DEVICE ADDRESS” is
entered into the controller of each boiler in the cascade and each boiler must
have a different address.
TIME TO ON
Factory: 3600s
Possible selection: min. 0s, max. 18000s
This parameter define after how long of work previous boiler on nominal power
(D6) will be turned ON next boiler. It is adjust in each boiler separately and
each boiler can have different values.
TIME TO OFF
Factory: 600s
Possible selection: min. 0s, max. 3600s
This parameter determines after how long operate “Leading boiler” at power
(maximum) D3, last boiler go to extinction phase. It is set on each boiler
separately and can be a different value.
TIME DIFFERENCE
Factory: 100h
Possible selection: min. 0h, max. 500h
This parameter define after how many hours of work boilers change priority of
work. It is set on each boiler separately and can be a different value.
EXTERNAL CONTROL
Factory: OFF
Possible selection: OFF, ON
This parameter define if boiler can be turned on with external start (e.g.
heating regulator). It is adjust in each boiler separately and each boiler can
have different values (ON/OF). If previous boiler loses electrical power
management takes over next boiler. To make this possible, external start must
be performed with parallel connection on all boilers in cascade.
USER INTERFACE (disconnect the boiler from the cascade, disabling the start of the boiler)
BOILER ATTACHED TO
Factory: ON
Possible selection: OFF, ON
ON – The boiler is part of the cascade
OFF – The boiler has been removed from the cascade
- this boiler will be displayed in gray on the cascade screen
- this boiler will have a STOP/START switch on the boiler screen
Note:
Before taking off the boiler from the cascade, it is necessary to turn off the
“BOILER ACTIVATED” option, otherwise the boiler will start after removing it
from the cascade.
BOILER ACTIVATED
Factory: OFF
Possible selection: OFF, ON
ON – The boiler is active in the cascade system, and if the “BOILER
ATTACHED TO” option is turned on, the “cascade” can control that boiler
(start/stop).
OFF – The boiler is not active in the cascade system and “cascade” cannot
control it, on the cascade screen this boiler is shown in standard form except
that it is marked “STOP” (red square). Important:
- This option is turned off at the factory, if we want this boiler to be controlled by “cascade” it is necessary to turn on this option.
- If an individual boiler goes into error, the “BOILER ACTIVATED” option will automatically be turned off, after the error has been eliminated (corrected) and confirmed, the “BOILER ACTIVATED” option must be turned on if we want the “cascade” to control this boiler.
BOILER ACTIVATED
Factory: OFF
Possible selection: OFF, ON
ON – The boiler is active in the cascade system, and if the “BOILER ATTACHED
TO” option is turned on, the “cascade” can control that boiler (start/stop).
OFF – The boiler is not active in the cascade system and “cascade” cannot
control it, on the cascade screen this boiler is shown in standard form except
that it is marked “STOP” (red square).
Important:
- This option is turned off at the factory, if we want this boiler to be controlled by “cascade” it is necessary to turn on this option.
- If an individual boiler goes into error, the “BOILER ACTIVATED” option will automatically be turned off, after the error has been eliminated (corrected) and confirmed, the “BOILER ACTIVATED” option must be turned on if we want the “cascade” to control this boiler.
CASCADE SCREEN
Cascade screen can be displayed on each boiler in the cascade. The display on
the screen of the cascade of an individual boiler will highlight (frame) the
boiler on which we are viewing the cascade display.
Aboiler in a cascade with the “BOILER ATTACHED TO” option turned off will be
displayed in gray.
Example:
Screen display of a cascade with two boilers, the review is performed on
boiler-1.
EC DECLARATION OF COMPARMITY
CUSTOMER SUPPORT
Centro metal d.o.o. assumes no responsibility for possible inaccuracies in this book originated typographical errors or rewriting, all the pictures and diagrams are principal and it is necessary to adjust each actual situation on the field, in any case the company reserves the right to enter their own products such modifications as considered necessary.
Centro metal d.o.o. Glavna 12, 40306 Macinec, Croatia
central tel: +385 40 372 600, fax: +385 40 372 611
service tel: +385 40 372 622, fax: +385 40 372 621
www.centrometal.hr
e-mail: servis@centrometal.hr
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>