Danfoss EV260B 6B – 20B Proportional Solenoid Valve Without Signal Converter Instructions

June 1, 2024
Danfoss

Danfoss EV260B 6B – 20B Proportional Solenoid Valve Without Signal

Converter

Danfoss-EV260B-6B-20B-Proportional-Solenoid-Valve-Without-Signal-Converter-
PRODUCT

Product Specifications

  • Product Name: Proportional Solenoid Valve
  • Type: EV260B 6B – 20B
  • Signal Converter: ESIC (Optional)
  • Coil Type: BK024D (without signal converter), BM024D (with signal converter)
  • Voltage: 24 V d.c. (full-wave rectified unsmoothed a.c.)
  • Control Signal Range: 0.5 – 10 V with ESIC (BM024D), 4 – 20 mA with ESIC (BL024D)
  • Pressure Range: 0.5 – 10 bar

Product Usage Instructions

Installation

  1. Ensure the power source matches the required voltage (24 V d.c.).
  2. Connect the coil as per the type specified (BK024D for without signal converter, BM024D for with signal converter).
  3. If using the signal converter, ensure proper connection of the ESIC unit.
  4. Mount the solenoid valve securely in the desired location.

Operation

  1. Apply the appropriate control signal within the specified range for the desired valve flow percentage.
  2. Monitor pressure levels to ensure they are within the recommended range of 0.5 – 10 bar.
  3. Observe valve response to control signals and adjust as needed for desired flow rates.

Maintenance

  1. Regularly check for any leaks or malfunctions in the valve assembly.
  2. Clean the valve components periodically to prevent debris buildup.
  3. Replace coils or signal converters if they show signs of wear or damage.

FAQ

Q: What is the voltage requirement for the solenoid valve?

A: The solenoid valve operates on 24 V d.c. power supply.

Q: How do I adjust the flow percentage of the valve?

A: Adjust the control signal within the specified range of 0.5 - 10 V or 4 - 20 mA based on the type of ESIC unit used.

Q: What pressure range can the valve handle?

A: The valve is designed to operate within a pressure range of 0.5 - 10 bar.

Proportional solenoid valve, type EV260B 6B – 20B without signal converter

Product Overview

Dimensions

Valve Code no. Coil
EV260B 6B, G ¼ 032U8052 ****

018Z6987

type BK024D (without signal converter)

EV260B 6B, G 3/s| 032U8053
EV260B 10B, G 3/s| 032U8054
EV260B 10B, G ½| 032U8055
EV260B 15B, G ½| 032U8056
EV260B 20B, G ¾| 032U8057

  • Supply voltage: 24 V d.c. (full-wave rectified unsmoothed a.c.)

Spare parts

Proportional solenoid valve, Type EV260B Spare parts

Danfoss-EV260B-6B-20B-Proportional-Solenoid-Valve-Without-Signal-Converter-
FIG-4

Signal converter with coil

 Type Control signal Code no.
ESIC (BM024D) 0,5→ 10 V 018Z0290
ESIC (BL024D) 4→ 20 mA 018Z0291

EV260B 6B – 20B

Proportional solenoid valve, type EV260B 6B – 20B with signal converter, type ESIC

Product Overview

Dimensions

Pilot signal 0 – 10 V

Valve Code no. Coil
EV260B 6B, G ¼ 032U8052 ****

018Z0290

type BM024D (inkl./incl./mit/avec signal converter)

EV260B 6B, G 3/s| 032U8053
EV260B 10B, G 3/s| 032U8054
EV260B 10B, G ½| 032U8055
EV260B 15B, G ½| 032U8056
EV260B 20B, G ¾| 032U8057

  • A: Blue (neutral) common neutral
  • B: Brown
  • C: Black

Yellow/green lead not used

Pilot signal 4 – 20 mA

Valve Code no. Coil
EV260B 6B, G ¼ 032U8052 ****

018Z0291

type BL024D (inkl./incl./mit/avec signal converter)

EV260B 6B, G 3/s| 032U8053
EV260B 10B, G 3/s| 032U8054
EV260B 10B, G ½| 032U8055
EV260B 15B, G ½| 032U8056
EV260B 20B, G ¾| 032U8057

  • A: Blue (neutral) common neutral
  • B: Brown
  • C: Black

Yellow/green lead not used

Danfoss-EV260B-6B-20B-Proportional-Solenoid-Valve-Without-Signal-Converter-
FIG-13

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals