Traulsen RDT232WUT-FHS Flex Drawer Convertible Two Drawer Refrigerator/Freezer Owner’s Manual

June 1, 2024
Traulsen

Traulsen RDT232WUT-FHS Flex Drawer Convertible Two Drawer

Refrigerator/Freezer

Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-
Freezer-PRODUCT

Product Information

  • Specifications
    • Model: RDT232WUT-FHS
    • Refrigerant Type: R-134a
    • Input Power: 115-208/230V, 60Hz, 8.0A
    • Hi Pressure: 500psi (3.45 MPa)
    • Lo Pressure: 250psi (1.72 Mpa)
    • Capacity: Convertible Two Drawer Refrigerator/Freezer

Product Usage Instructions

  • Installation
    • Location: Choose a suitable location away from extreme heat.
    • Packaging: Inspect the packaging upon receipt for any damages.
    • Legs or Casters: Ensure proper installation of legs or casters for mobility.
    • Cord & Plug: Connect the power cord to a suitable power supply.
    • Power Supply: Use a power supply within the specified input power range.
    • Clearance: Provide adequate clearance for air circulation as per guidelines.
  • Operation
    • Operation Display Indicators: Familiarize yourself with the display indicators.
    • Freezers: Utilize the freezer compartments as needed.
    • Refrigerators: Use the refrigerator sections for storing items.
    • Refrigerating Product: Store products requiring refrigeration accordingly.
    • Drawer Loading: Load drawers with items as per recommended capacity.
  • Care and Maintenance
    • Cleaning the Exterior: Regularly clean the exterior of the unit with a mild detergent.
    • Cleaning the Interior: Clean the interior compartments with a damp cloth.
    • Cleaning the Condenser Fan Guard: Maintain the condenser fan guard clean for efficient operation.
    • Condensate Removal System Care: Follow guidelines for maintaining the condensate removal system.
    • Preparing for Extended Shut Down: Prepare the unit correctly for extended periods of shutdown.
    • Adjusting the Drawers: Adjust drawer settings if needed for proper functionality.
    • Drawer Gasket Replacement: Replace drawer gaskets when necessary.
  • Control Basics
    • Information Menu: Access the information menu for control settings.
    • Adjusting Cabinet Setpoint: Set the desired temperature for the cabinet.
    • Initiating a Defrost: Initiate defrost cycles as required.
    • Configuration Parameters: Configure settings based on operational requirements.
    • Technical Data: Refer to technical data for detailed specifications.

FAQs

  • Q: Where is the serial tag located?
    • A: The serial tag is located in the upper interior compartment of the unit.
  • Q: How do I adjust the drawers?
    • A: To adjust the drawers, refer to section V.g in the manual for detailed instructions on adjusting drawer settings.

THE SERIAL TAG

SERIAL TAG & LOCATION

  • The serial tag is a permanently affixed label on which vital electrical and refrigeration data about your Traulsen product, as well as the model and serial number.
  • This tag is located in the upper interior compartment.

READING THE SERIAL TAG

  • Model = The model # of your Traulsen unit

  • (S/N) Serial Number = The permanent ID# of your Traulsen unit

  • Refrigerant SYS1 = System 1 Refrigerant type used and refrigerant charge

  • Design Pressure = System 1 High and Low Pressure

  • Refrigerant SYS2 = System 2 Refrigerant type used and refrigerant charge

  • Design Pressure = System 2 High and Low Pressure

  • Volts = Voltage

  • Hz = Cycle

  • PH = Phase

  • Total Current = Maximum amp draw

  • Min Circuit Amps = Minimum circuit ampacity

  • Lights = Light wattage

  • Agency Labels = Designates agency listings

  • Components = Component Ratings

  • 4401 Blue Mound Rd.

  • Ft. Worth, TX 76106

  • 800-825-8220

MODEL: MODELO: MODELE:|
---|---
S/N:|
REFRIGERANT / REFRIGERANTE / RÉFRIGÉRANT

SYS1 (REFM):|
Hi Press. (PRESH):|
Lo Press. (PRESL):|
SYS2 (REFA):|
Hi Press. (PRESH):|
Lo Press. (PRESL):|
Input Power (ELIN) – FOR INDOOR USE ONLY

115-208/230V ~ 60Hz 8.0A (8,0A)
(Symbol 1) (Alt Safety / Other

| (Symbol 2) (Alt. San / Other 2)| (Symbol 3) (Alt. En. / Other 3)| (Symbol 4) (WEEE)
(Symbol 5) (Safety)| (Symbol 6)

(Sanitation)

| (Symbol 7) (Energy)| (Symbol 8) (Customer QR Code / Other 4)
Device/Part Number: PartNum| (UL/NSF Notes)
COMPONENTS / COMPOSANTS / COMPONENTES

COMP AMPS:|  | EVAP FAN AMPS:|
COND FAN AMPS:|  | LIGHT WATTS:|
DEF HTR AMPS:|  | CTRL AMPS:|
DOOR HTR AMPS:|  | MIN AMPS:|
MAX AMPS:|  |

RECEIPT INSPECTION

RECEIPT INSPECTION

  • All Traulsen products are factory-tested for performance and are free from defects when shipped. The utmost care has been taken in creating this product to protect against damage in transit.
  • You should carefully inspect your Traulsen unit for damage upon delivery.
  • If damage is detected, you should save all the crating materials and make a note on the carrier’s Bill of Lading describing the damage.
  • A freight claim should be filed immediately. If damage is subsequently noted during or immediately after installation, contact our customer care team to file a freight claim.
  • There is a fifteen (15) day limit to file freight damage with the carrier.
  • Under no condition may a damaged unit be returned to Traulsen without first obtaining written permission (return authorization).
  • You may contact Hobart/Traulsen customer care at 800-333-7447 to request a return or file a claim.

INSTALLATION

LOCATION

  • Select a proper location for your Traulsen unit, away from extreme heat and allow proper clearance for air circulation (see section III.f).

PACKAGING

  • The Traulsen unit is shipped from the factory secured to a sturdy wooden pallet with a steel strap and packaged in durable wood crating.
  • Most exterior stainless steel and aluminium surfaces have a protective vinyl covering to prevent scratching during manufacturing, shipping and installation.
  • After the unit is installed in place of service, remove and discard the covering from all surfaces.
  • To remove the wooden pallet, first if at all possible, we suggest that the cabinet remain strapped to the pallet during all transportation to the point of final installation.
  • The strap can then be removed with metal shears. Be careful as the steel strap is under tension and will release once cut.
  • NOTE: Traulsen does not recommend laying the unit down on its front side or back.
  • However, if you must only lay the unit on the front of the side, not the back please be certain to allow the unit to remain in an upright position afterwards for 24 hours before plugging it in so that the compressor oils and refrigerant may settle.

LEGS OR CASTERS

  • This Traulsen product is shipped from the factory with casters installed. Level the cabinet using a level or pan of water at the bottom of the cabinet.
  • Legs are available as an optional accessory kit. These are shipped inside the cabinet in a cardboard box.
  • THE CABINET MUST BE BLOCKED AND STABLE BEFORE INSTALLING LEGS.
  • UNITS ARE NOT DESIGNED TO BE MOVED WHILE ON LEGS. IF THE UNIT REQUIRES MOVING, A PALLET JACK OR FORKLIFT SHOULD BE USED TO PREVENT DAMAGE.
  • To install the legs, first raise and block the cabinet a minimum of 7” from the floor.
  • Thread the legs into the threaded holes on the bottom of the cabinet (see Figure 1).
  • Be certain that all legs are tightly secured. When the unit is set in its final position, it is important for proper operation that the unit be level.
  • The legs are adjustable for this purpose; turn the bottom of the leg counterclockwise to raise it, and clockwise to lower it. Level the unit from front to back as well as side to side in this manner.

CORD & PLUG

  • All Traulsen models are supplied with a cord & plug attached.
  • It is shipped coiled and secured by a nylon strip to the back of the cabinet near the condensing unit area. For your safety and protection, all units supplied with a cord and plug include a special three-prong grounding plug on the service cord.
  • Select only a dedicated electrical outlet with a grounding plug for a power source.
  • NOTE: Do not under any circumstances cut or remove the round grounding prong from the plug or use an extension cord.

POWER SUPPLY

  • The supply voltage should be checked before connection to be certain that the proper voltage for the cabinet wiring is available (refer to the serial tag to determine the correct-unit voltage).
  • Make connections under local electrical codes.
  • Use qualified electricians.
  • The use of a separate, dedicated circuit is required. Size wiring to handle the indicated load and provide the necessary over-current protector in a circuit (see amperage requirements on the unit’s serial tag).

CLEARANCE

  • To assure optimum performance, the condensing unit of your Traulsen unit MUST have an adequate supply of air for cooling purposes.
  • Therefore, 1” stoppers in the back are integral part of the unit. Space around these stoppers should not be blocked to provide proper air exhaust.
  • There are no clearance requirements for the sides.
  • NOTE: Do not install the cabinet without casters.

OPERATION

Both refrigerators and freezers do not require manual defrosting. However, a manual defrost option is available on the control, if required.

OPERATION DISPLAY INDICATORS

During normal operation, the display shows either the temperature measured or one of the following indications:

FREEZERS

  • During normal operation, a freezer continuously circulates below-freezing cabinet air through the evaporator coil.
  • The coil requires periodic defrosting for proper operation An electric defrost occurs every 7 hours for a maximum length of 30 minutes to melt any frost which may accumulate on the coil during the compressor “ON” cycle.
  • At the start of a freezer defrost cycle, both the compressor and evaporator fans are off.
  • The microprocessor control will read “dEF” (see Figure 1).Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-Freezer-FIG-1 \(4\)
  • The electric heaters (attached to the evaporator coil and drain tube) are energized. When the temperature sensor affixed to the coil senses 50°F, the coil and drain pan are fully defrosted.
  • Both heaters and compressor are off for 5 minutes to let the defrost water drip out completely. After drip time, the compressor will resume operation.
  • The evaporator coil fans are delayed from starting at the termination of a defrost cycle. Fan operation is automatically resumed, after a short time or temp delay (whichever comes first). After completion, the total refrigeration system operation is then resumed.
  • During defrost operation, heat is confined to the coil enclosure to prevent any significant rise in temperature within the food zone.
  • The fan delay control function upon termination of a defrost cycle is two-fold. First, to prevent blowing warm air into the food storage area. Second, to prevent any condensation on the defrost coil from being blown into the food storage area.
  • The microprocessor control is set from the factory to terminate defrost at 30 minutes for freezers in the event of a sensor failure. This setting should never be tampered with, without first consulting the factory.

REFRIGERATORS

  • During normal operation, a refrigerator continuously circulates above-freezing cabinet air through the evaporator coil.
  • An electric defrost occurs every 8 hours for a maximum length of 30 minutes to melt any frost that may accumulate on the coil during the compressor “ON” cycle.
  • The defrost process is the same as the freezer described in the previous section.
  • With standard holding refrigerators, high relative humidity is also maintained to prevent dehydration of stored products.

REFRIGERATING PRODUCT

  • The Flex Drawer will satisfactorily refrigerate an assorted load of food items.
  • Allow space above the food bin to permit free air circulation.
  • Do not overload at any one time with warm food products and expect immediate results. A certain amount of time is required to remove heat from items before operating temperatures can be attained.
  • The system is designed for the storage of refrigerated or frozen products.
  • Opening the drawer will increase the temperature in the cabinet and will require a certain amount of time to recover.
  • Also, after peak service periods or after the warm product is loaded, the refrigerator will require a certain amount of time for the temperature to return to the normal operating range.

DRAWER LOADING

  • The product should be placed in a way that ensures air can circulate.
  • Do not operate without the ABS bin in place (see Figure 2).Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-Freezer-FIG-1 \(5\)

CARE & MAINTENANCE

WARNING: DISCONNECT ELECTRICAL POWER SUPPLY BEFORE CLEANING ANY PARTS OF THE UNIT.

CLEANING THE EXTERIOR

  • Exterior stainless steel should be cleaned with warm water, mild soap and a soft cloth. Apply with a dampened cloth and wipe in the direction of the metal grain.
  • Avoid the use of strong detergents and gritty, abrasive cleaners as they may tend to mar and scratch the surface.
  • Do NOT use cleaners containing chlorine, this may promote corrosion of the stainless steel.

CLEANING THE INTERIOR

  • For cleaning the interior, use baking soda with warm water, and a soft cloth.
  • Apply with a dampened cloth and wipe in the direction of the metal grain Use on breaker strips as well as door and drawer gaskets.Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-Freezer-FIG-1 \(6\)

CLEANING THE CONDENSER FAN GUARD

  • The condenser fan guards function as a filter in this cabinet. Check the fan guard periodically by pulling outward on the lower louvre panel.
  • The operating environment will affect the required frequency of cleaning. Air must be able to freely circulate through the condenser.
  • The air intake of the fan guard must be kept free of dirt and grease for proper system operation.
  • The condenser fan guard is at the front of the cabinet, behind the louvre panel. Carefully clean dirt and lint from the condenser fan guard using a vacuum cleaner or soft brush; do not use a wire brush.Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-Freezer-FIG-1 \(7\)

CONDENSATE REMOVAL SYSTEM CARE

  • Condensate removal happens by evaporation at the bottom of the cabinet with a hot gas tube.
  • The unit does not need a drain. The evaporator coil, condensate loop and condensate pan can all be flushed with fresh water by a qualified service technician if needed.

PREPARING FOR EXTENDED SHUTDOWN

  • If the refrigerator is not to be used for an extended period, disconnect the electrical power supply and open the drawers.
  • As soon as the cabinet has warmed up to room temperature, wipe out the interior.
  • Leave the drawers open and check again to make sure that no moisture has collected on any parts.
  • To restart the refrigerator, follow the instructions under PRESTART CHECKS and OPERATION.

ADJUSTING THE DRAWERS

  • Occasionally the drawer(s) may require alignment adjustment.
  • To do so, first, open the drawer and loosen the drawer face mounting screws enough to move the drawer face.
  • Do not completely remove the screws. Next, adjust and level the drawer face as needed and tighten the screws.

DRAWER GASKET REPLACEMENT

  • To replace the gasket, grasp it firmly by one corner and pull it out.
  • Before attempting to install a new gasket, both the unit and gasket must be at room temperature.
  • Insert the four corners first by using a rubber mallet (or hammer with a block of wood).
  • After the corners are properly inserted, work your way towards the centre from both ends by gently hitting with a mallet until the gasket is completely seated in place (see Figure 5 for proper gasket placement).

CONTROL BASICS

Your new Traulsen unit is equipped with a digital control, which precisely regulates operation. It is supplied from the factory completely ready for use.

Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-
Freezer-FIG-1 \(9\)

INFORMATION MENU

The information available in this menu is:

  • Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-Freezer-FIG-1 \(10\) displayed only if enabled (see Configuration Parameters)
  • displayed only if ACC > 0

Access to the menu and information displayed:

  • Press and immediately release the button .
  • With a button or select the data to be displayed.
  • Press the button to display the value.
  • To exit from the menu, press a button or wait for 10 seconds.

Initiate Stand-By:

  • Keeping the button pressed for 3 seconds allows the controller to be put on standby or output control to be resumed (with SB=YES only).

Locking the Keypad:

  • The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the controller is operating in a public place.
  • In the INFO menu, set parameter LOC = YES to inhibit all functions of the buttons. To resume normal operation of the keypad, adjust the setting so that LOC = NO.

INFORMATION MENU

Selection of Second Parameter Group: It’s possible to select control parameters between two different pre-programmed groups, for the fundamental control parameters to be adapted quickly to changing needs. Changeover from Group I to Group II (and vice versa) may take place MANUALLY by pressing the button for 2 seconds (with IISM = MAN), or AUTOMATICALLY when ECO conditions are detected (with ISM = ECO), or when IISM = DI, DxO = IISM and the digital input is activated (the activation of DIx selects Group II, x = 1,2,3). If IISM = NON, switchover to Group II is inhibited. The activation of Group II is signalled by the lighting up of the relevant LED on the controller display.

ADJUSTING CABINET SETPOINT

  • Setpoint display and modification:
    • Press the button for at least a half second to display the setpoint value.
    • While keeping the button pressed, use a button or to set the desired value (adjustment is within the minimum SPL and the maximum SPH limit).
    • When the button is released, the new value is stored.

INITIATING A DEFROST

  • Automatic defrost: Defrost starts automatically as soon as the time set with parameter DFT has elapsed.
  • Timed defrost: With DFM = TIM defrosts take place at regular intervals when the timer reaches the value of DFT. For example, with DFM = TIM and DFT = 36, a defrost will take place every 6 hours.
  • Optimized defrost: With DFM = FRO the timer is only increased when the conditions occur for frost to form on the evaporator, until the time set with parameter DFT is matched. If the evaporator works at 0°F, defrost frequency depends on the thermal load and climatic conditions. With setpoints much lower than 0°F, defrost frequency mainly depends on the refrigerator operating time.
  • Defrost time count backup: At the power-up, if DFB = YES, the defrost timer resumes the time count from where it was left off before the power interruption. Vice versa, with DFB = NO, the time count re-starts from 0. On standby, the accumulated time count is frozen.
  • Manual or remote defrost start: It’s possible to manually start a defrost, by pressing the button for 2 seconds.
  • Defrost type: Once the defrost has started, the Compressor and Defrost outputs are controlled according to parameter DTY. If FID = YES, the evaporator fans are active during defrost.
  • Defrost termination: The actual defrost duration is influenced by a series of parameters.
  • Time termination: T2 = NO and T3 different from 2EU: the evaporator temperature is not monitored and defrost will last as long as time DTO.
  • Temperature monitoring of one evaporator: T2 = YES and T3 different from 2EU. In this case, if the sensor T2 measures the temperature DLI before the time DTO elapses, defrost will be terminated in advance.

Resuming thermostatic cycle:

  • When defrost is over, if DRN is greater than 0, all outputs will remain off for DRN minutes, for the ice to melt completely and the resulting water to drain.
  • Moreover, if probe T2 is active (T2 = YES), the fans will re-start when the evaporator gets to a temperature lower than FDD; Vice versa, if probe T2 is not active (T2 = NO) or after defrost has come to an end, such condition does not occur by end of the time FTO after FTO minutes have elapsed the fans will be switched on anyway.
  • Caution: if DFM = NON or C-H = HEA all defrost functions are inhibited; if DFT = 0, automatic defrost functions are excluded.

CONFIGURATION PARAMETERS

  • Parameter Configuration:
    • To get access to the parameter configuration menu, press a button and for 5 seconds.
    • With button or select the parameter to be modified.
    • Press the button to display the value.
    • By keeping the button pressed, use a button or to set the desired value.
    • When the button is released, the newly programmed value is stored and the following parameter is displayed.
    • To exit from the setup, press the button or wait for 30 seconds.

TECHNICAL DATA

  • Power supply
    • TRL-002….W 100-240Vac ±10%, 50/60Hz, 3W
    • Relay output max loads (240Vac)
  TRL-002..S/T..-. TRL-002..Q/R..-.
Compressor 16A resistive 12 FLA 48 RLA 12A resistive 12 FLA 48 RLA
Evap. Fan 16A resistive 4 FLA 12 RLA 8A resistive

4 FLA 12 RLA

Defrost| 16A resistive 4 FLA 12 RLA| 16A resistive 4 FLA 12 RLA
Auxiliary loads 1| 7A resistive| 7A resistive
Auxiliary loads 2| 7A resistive| 7A resistive

Input

  • NTC 10KΩ@25°C LAE Part No. SN4…

Measurement Range

  • <0.5 within the measurement range

Operating Conditions

  • -10… +50°C; 15%…80% r.H.

CE (Approvals and Reference Norms)

  • EN60730-1; EN60730-2-9; EN55022 (Class B); EN50082-1
PAR RANGE DESCRIPTION
SPL -58..SPH Minimum limit for SP setting.
SPH SPL…180° The maximum limit for SP setting.
SP SPL… SPH Setpoint (value to be maintained in the room).
C- H REF; HEA Refrigerating (REF) or Heating (HEA) control mode.
HY0 1…10° Thermostat OFF -> ON differential.
HY1 0…10° Thermostat ON -> OFF differential.
CRT 0…30min Compressor rest time. The output is switched on again

after CRT minutes have elapsed since

the previous switchover. We recommend to set CRT=03 with HY0<2.0°.

CT1| 0…30min| Compressor/Heater output runs when probe T1 is faulty. With CT1=0 the output will always remain OFF.
CT2| 0…30min| Compressor/Heater output stops when probe T1 is faulty. With CT2=0 and CT1>0, the output will always be ON.

Example: CT1=4, CT2=6: In case of probe T1 failure, the compressor will cycle 4 minutes ON and 6 minutes OFF.

DFM| NON; TIM; FRO CRN| Defrost start mode

NON : The defrost function is disabled (the following parameter will be FCM).

TIM : regular time defrost.

FRO : the defrost time count is only increased when the conditions occur for frost to form on the evaporator (optimized time increase).

CRN : defrost is based on compressor run time (time is based on DAT).

DFT| 0…250| Time interval among defrosts in x10 minutes. When this time has elapsed since the last defrost, a new defrost cycle is started. Each number is multiplied by 10 minutes. 0-250 indicates 0-2500 minutes.
DAT| 0…100

hours

| Frost accumulation timeout.
DFB| NO/YES| Defrost timer backup. With DFB=YES, after a power interruption, the timer resumes the count from where it was left off with ±30 min. approximation. With DFB=NO, after a power interruption, the defrost timer will restart to count from zero.
DLI| -58…180°| Defrost end temperature.
DMD| 0…30min| Minimum defrost duration.
DTO| 1…120min| Maximum defrost duration.
DTY| OFF; ELE; GAS| Defrost type

OFF: off-cycle defrost (Compressor and Heater OFF). ELE: electric defrost (Compressor OFF and

Heater ON). GAS: hot gas defrost

(Compressor and Heater ON).

DSO| OFF; LO; HI| Defrost start optimization OFF: no optimization.

LO: defrost waits until the compressor is cut out.

HI: defrost waits until the compressor cuts in.

SOD| 0…30 min| Start optimization delay.
DPD| 0…240sec| The evaporator pump is down. At the beginning of defrost, defrost outputs (determined by DTY) are OFF for DPD seconds.
DRN| 0…30min| Pause after defrosting (evaporator drain downtime).
PAR| RANGE| DESCRIPTION
---|---|---
DDM| RT;

LT;

SP; DEF

| Defrost display mode. During defrosting, the display will show:

RT : the real temperature;

LT : the last temperature before defrosting;

SP : the current setpoint value;

DEF : “dEF”.

DDY| 0…60min| Display delay. The display shows the information selected with parameter DDM during defrost and for DDY minutes after defrost termination.
FID| NO/YES| Fans are active during defrosting.
FDD| -58…180°| Evaporator fan restart temperature after defrosting.
FTO| 0…120min| Maximum evaporator fan stops after defrosting.
FCM| NON; TMP; TIM| Fan mode during thermostatic control.

NON : The fans remain ON all the time;

TMP : Temperature-based control. The fans are ON when the compressor is ON. When the compressor is turned OFF, the fans remain ON as long as the temperature difference Te-Ta is greater than FDT. The fans are turned ON again with FDH differential. (Te = Evaporator temperature, Ta = Air temperature);

TIM : Timed-based control. The fans are ON when the compressor is ON. When the compressor is OFF, the fans switch ON and OFF according to parameters FT1, FT2, FT3

FDT| -12…0°| Evaporator-Air temperature difference for the fans to turn OFF after the compressor has stopped.
FDH| 1…12°| Temperature differential for fan re-start.
 |  | Example: FDT = -1, FDH=3. In this case, after the compressor has stopped, the fans are OFF when Te > Ta – 1 (FDT), whereas the fans are ON when Te < Ta – 4 (FDT-FDH).
FT1| 0…180sec| Fan stop delay after compressor/heater stop. See Fig. 2
FT2| 0…180| Timed fan stop in x10 seconds. With FT2=0 the fans remain on all the time.
FT3| 0…180| A timed fan run in x10 seconds. With FT3=0, and FT2 > 0, the fans remain off all the time.
ATM| NON; ABS; REL| Alarm threshold management.

NON : all temperature alarms are inhibited (the following parameter will be ACC).

ABS : the values programmed in ALA and AHA represent the real alarm thresholds.

REL : the alarm threshold is obtained by the sum of setpoint, thermostat differential and ALR/AHR.

ALA| -58… 180°| Low-temperature alarm threshold.
AHA| -58… 180°| High-temperature alarm threshold.
ALR| -12… 0°| Low-temperature alarm differential. With ALR=0 the low temperature alarm is excluded.
AHR| 0… 12°| High-temperature alarm differential. With AHR=0 the high temperature alarm is excluded.
ATI| T1; T2; T3| Probe used for temperature alarm detection.
ATD| 0… 120 min| Delay before alarm temperature warning.
ACC| 0…52 weeks| Condenser periodic cleaning. When the compressor operation time, expressed in weeks, matches the ACC value programmed, “CL” flashes in the display. With ACC=0 the condenser cleaning warning is disabled and CND disappears from Info Menu.
IISM| NON; MAN; ECO; DI| Switchover mode to the second parameter set

NON : inhibition to use the second parameter group (the following parameter will be SB).

MAN : button switches the two parameter groups over.

ECO : automatic switchover to the second parameter group, when ECO conditions are detected.

DI : switchover to the second parameter group when DIx input is on.

IISL| -58… IRISH| Minimum limit for IISP setting.
IRISH| IISL… 180°| The maximum limit for the IISP setting.
IISP| IISL… IRISH| Setpoint in mode 2.
IIH0| 1… 10°| Thermostat OFF->ON differential in mode 2.
PAR| RANGE| DESCRIPTION
---|---|---
IIH1| 0… 10°| Thermostat ON->OFF differential in mode 2.
IIDF| 0…250| Time interval among defrosts in mode 2 in x10 minutes.
IIFC| NON; TMP;

TIM

| Fan control in mode 2. See FCM.
 |  |
ECS| 1…5| Controller sensitivity for the automatic switchover from Group I to Group II (1=minimum, 5=maximum).
ECS| 1…5| Controller sensitivity for the automatic switchover.
EPT| 0…240 min| Eco pull-down time. Only with IISM=ECO. Group I parameters are used in regulation for at least EPT minutes. See Fig.3
SB| NO/YES| Stand-by button enabling.
DSM| NON; ALR; STP| Door switch input mode:

NON : door switch inhibited

ALR : when DIx=DOR and the digital input is on, an alarm is generated after ADO minutes

STP : when DIx=DOR and the digital input is on, in addition to the alarm, the fans are immediately stopped and the compressor is stopped after CSD minutes.

DAD| 0…30 min| Delay before the door open alarm warning.
CSD| 0…30 min| Compressor/heater stop delay after the door has been opened.
D1O| NON; DOR; ALR; IISM; RDS| DI1 digital input operation
NON : digital input 1 is not active.
DOR : door input.
ALR : when the input is on, an alarm is generated (if AHM=STP, the compressor is stopped and the defrosts are suspended).
IISM : when the input is on, the controller will use group 2 parameters.
RDS : when the input is on, a defrost is started (remote control).
D1A| OPN; CLS.| DI1 digital input activation.

OPN : on open

CLS : on close

D2O| See D1O| DI2 digital input operation. See D1O.
D2A| OPN; CLS.| DI2 digital input activation.

OPN : on open

CLS : on close

PSL| -58…158| Minimum setpoint adjusted via potentiometer.
PSR| 0…15| Range of setpoint adjusted via potentiometer.
LSM| NON; MAN; ECO; DI1; DI2;

DI3.

| Light control mode

NON : light output not controlled.

MAN : light output controlled through button (if OAx=LGT). ECO : lights activated/deactivated following the ECO state. DIx : lights activated/deactivated following the DIx state.

LSA| OPN; CLS| Light activation (only with LSM=ECO or LSM=DIx).

OPN : lights on with DIx open or ECO mode deactivated.

CLS : lights on with DIx closed or ECO mode activated.

OT1| 0…600 sec| Activation time of OA1
OT2| 0…600 sec| Pause between OA1 activation
PAR| RANGE| DESCRIPTION
---|---|---
OA1| NON; LGT; 0-1;

2CU;

2EU; ALO; ALC

| AUX 1 output operation

NON: output disabled (always off).

LGT: output enabled for light control.

0-1: the relay contacts follow the on/standby state of the controller. 2CU: output programmed for the control of an auxiliary compressor.

2EU: output enabled for the control of the electrical defrost of a second evaporator.

ALO: contacts open when an alarm condition occurs. ALC: contacts made when an alarm condition occurs.

2CD| 0…120 sec| Auxiliary compressor start delay. If OAx=2CU the auxiliary output is switched on with a delay of 2CD seconds after the main compressor has cut-in. Both compressors are turned off at the same time.
OS1| -12.5..12.5°| Probe T1 offset.
T2| NO/YES| Probe T2 enabling (evaporator).
OS2| -12.5..12.5°| Probe T2 offset.
T3| NON; DSP; CND; 2EU| Auxiliary probe T3 operation

NON : probe T3 not fitted.

DSP : temperature T3 to be displayed.

CND : condenser temperature measurement.

2EU : second evaporator temperature measurement.

OS3| -12.5..12.5°| Probe 3 offset.
AHM| NON; ALR; STP;| Operation in case of high condenser alarm

NON : high condenser alarm inhibited.

ALR : in case of alarm, “HC” flashes in the display and the buzzer is switched on.

STP : in addition to the alarm symbols displayed, the compressor is stopped and defrosts are suspended.

ART| -50…110°| Condensation temperature alarm (referred to T3 probe).
TLD| 1…30 min| Delay for minimum temperature (TLO) and maximum temperature (THI) logging.
TDS| T1; 1-2; T3| Selects the temperature probe to be displayed.

T1 : probe T1

1-2 : the AVG-weighted average between T1 and T2

T3 : probe T3

AVG| 0…100%| The relative weight of T2 on T1 (if TDS = 1-2)

Example 1: T1 = -5°, T2 = -20°, AVG = 100%. The displayed temperature will be -20° (T1 has no effect)

Example 2: T1 = -5°, T2 = -20°, AVG = 60%. The displayed temperature will be -14.

SCL| 1°C;

2°C;

°F

| Readout scale.

1°C : measuring range -50…110°C (0.1°C resolution within -9.9 ÷ 19.9°C interval, 1°C outside)

2°C : measuring range -50 … 110°C

°F : measuring range -55 … 180°F

SIM| 0…100| Display slowdown.
ADS| 1…255| TRL-002 address for PC communication.
NPR| 0…1| Setup programmed.
STT| 0…255| Setup traceability.

COMPONENTS AND WIRING DIAGRAM

Indications:

  • Thermostat output
  • Fan output
  • Defrost output
  • Activation of 2nd parameter set
  • Alarm
  • Manual activation / Increase button
  • Exit / Stand-by button

Control Wiring Diagram:

TROUBLESHOOTING GUIDE

FIND YOUR PROBLEM HERE REMEDY
1. The condensing unit fails to start. a.Check if the cord & plug have been

disconnected. b.Check the control temperature setting.
2. Condensing unit operates for prolonged periods or continuously.| a.Are doors closing properly?

b.Dirty condenser or filter. Clean properly.

c.Evaporator coil iced. Needs to defrost. See instructions for setting a manual defrost cycle in section VI.c.

3. The food compartment is too warm.| a.Check door(s) and gasket(s) for proper seal

b.Perhaps a large quantity of warm food has recently been added or the door was kept open for a long period, in both cases, allow adequate time for the cabinet to recover its normal operating temperature.

c.Control setting too high, readjust per instructions in section VI.b.

d.Check that the condensing coil is clean.

4. Food compartment is too cold.| a.Perhaps a large quantity of very cold or frozen food has recently been added. Allow adequate time for the cabinet to recover its normal operating temperature.

b.Adjust the control to a warmer setting, see section VI.b.

5. Condensation on the exterior surface.| a.Check door alignment and gaskets for proper seal. b.Condensation on the exterior surface of the unit is perfectly normal during periods of high humidity.
6. The compressor hums but does not start.| a.Call for service.
7. No power to unit| a.Check if the cord & plug has been disconnected. b.Check the power supply breaker.

WARRANTY

SERVICE/WARRANTY INFORMATION

  • SERVICE INFORMATION Before calling for service, please check the following:
    • Is the electrical cord plugged in?
    • Is the fuse OK or circuit breaker on?
    • Is the condenser coil clean?
    • Is the power switch on?

If after checking the above items the unit is still not operating properly, please contact an authorized Traulsen service agent:

  • Traulsen
  • 4401 Blue Mound Road
  • Fort Worth, TX 76106
  • 800-825-8220.

Traulsen reserves the right to change specifications or discontinue models without notice.

SPARE PARTS INFORMATION

Spare or replacement parts may be obtained through a parts supplier or one of our authorized service agents. A list of authorized service agents is posted on our company’s official website Service tab at www.Traulsen.com.
Note: When calling for spare parts or service support, please make sure you have the model and serial number of the unit available.

Traulsen-RDT232WUT-FHS-Flex-Drawer-Convertible-Two-Drawer-Refrigerator-
Freezer-FIG-1 \(27\)

WARRANTY REGISTRATION

  • The warranty for your new Traulsen unit may be registered with us by completing warranty information online, via our website www.Traulsen.com.
  • Click on Service Tab on the home page. You may also register your product by calling us directly at 800-825-8220.

WARRANTY STATEMENT

TRAULSEN/KAIRAK EQUIPMENT WARRANTY U.S. Domestic Warranty

SIX-YEAR PARTS AND LABOR WARRANTY
FEG Refrigeration, a division of ITW Food Equipment Group LLC d/b/a Traulsen (“Traulsen”) warrants to the original end-user (the “Owner”) of the Equipment (as defined below) that Traulsen will convey the Equipment free and clear of all liens, security interests, and encumbrances created by, through or under Traulsen. Traulsen further warrants to the Owner that for six (6) years from the later of either (a) the date of delivery to the common carrier or (b) the date of original installation (the “Domestic Warranty Period”) (provided that in no event shall the Domestic Warranty Period commence later than 3 months from the date of delivery to the common carrier by Traulsen unless otherwise agreed upon by the parties in writing), under normal use and given proper installation and maintenance as determined by Traulsen, the Equipment: (a) will conform to the written specifications as provided by Traulsen (“Specifications”) and (b) will be free from substantial defects in material and workmanship. “Equipment” means serialized units of refrigeration equipment sold by Traulsen and branded as “Traulsen”, “Kairak” or “Centerline by Traulsen”. “Equipment” does not include, Air Curtains, equipment for export, spare parts, parts, replacement parts, service parts, products not branded as Traulsen, Kairak or Centerline by Traulsen, products sold by Traulsen that are expressly subject to a different warranty and/or warranty period,- and other products whose product documentation reference a different warranty policy and/or exclude this warranty policy (collectively, the “Excluded Products”).

SEVEN-YEAR COMPRESSOR WARRANTY
The warranty period for compressors (the “Compressor Warranty Period”) shall extend for an additional one (1) year beyond the Domestic Warranty Period. In the case of a nonconforming compressor, Traulsen shall provide a single replacement compressor; however, all installation, recharging, and repair costs shall be the responsibility of the Owner. For Equipment purchased for use with a condenser provided by a third party, the six-year parts and labour warranty will apply only to those components contained within the Equipment to the point of connection of the refrigeration lines leading to the third-party condenser.

LIFETIME CAM-LIFT HINGE AND WORKFLOW HANDLE WARRANTY
Traulsen warrants to the Owner for the life of the Equipment (the “Cam-Lift Lifetime Warranty Period”) that the housing of camlift hinges and workflow handles will be free from substantial defects. In the case of non-conforming housing for the cam-lift hinge or workflow handle during the Cam-Lift Lifetime Warranty Period, Traulsen shall provide a replacement part; however, the Owner shall be responsible for any other replacement costs, including but not limited to, installation and labour.

WHAT IS NOT COVERED BY THIS WARRANTY

Traulsen’s responsibility under this warranty is subject to the additional limits below:

  • No Consequential Damages. Traulsen is not liable for loss of product or loss of profit, or any special, indirect, or consequential damages including, but not limited to, loss or damage resulting from the loss of product, whether or not due to refrigeration failure and whether or not Traulsen has been notified of the possibility of such damages.
  • Consumable Components or Ordinary Wear Items. This Warranty excludes all consumable components and ordinary wear items within the Equipment, such as but not limited to components that are removable without the use of tools, gaskets, shelf pins, and light bulbs. All Excluded Products sold separately are also excluded.
  • Non-OEM parts. Any use of non-OEM parts or parts not supplied by Traulsen or specified by Traulsen in the Operator’s Manual on the Traulsen website (such as but not limited to EZ Clean gaskets, sensors, controls, etc.) shall automatically void this Warranty for such parts and any damage, defect or wear caused by such parts.
  • Specified Causes. This Warranty does not cover any damage, defect or wear resulting from fire, water, burglary, accident, abuse, misuse, lack of preventive maintenance, transit, acts of God, terrorism, power surges, improper installation, or repairs or installation by unqualified third parties, or improper modifications outside published parameters or modifications implemented outside of the direction of Traulsen tech support. All warranty claims made outside of the Domestic Warranty  Period, Compressor Warranty Period or Cam-Lift Lifetime Warranty Period, as applicable, are expressly excluded from this Warranty.
  • Specified Uses. The Equipment is intended only for commercial use in conditioned spaces and shall not be used by residences, consumers, or households or in any non-commercial application or any non-conditioned spaces. This Warranty does not apply to, and shall not cover, any Equipment that is installed or used in any way in any residential, consumer or noncommercial application. No warranties, express or implied, are provided to any residential, consumer or non-commercial purchaser or owner of the Equipment.
  • Owner’s Use. The Owner is solely responsible for determining if the Equipment is fit for a particular purpose and suitable for the Owner’s application. Accordingly, and due to the nature and manner of the Equipment, Traulsen is not responsible for the results or consequences of any use, misuse, or application of its Equipment.

SOLE REMEDIES

In the event of a breach of the warranties set forth above, Traulsen will, at Traulsen’s option, and as Owner’s sole and exclusive remedy and Traulsen’s sole and exclusive obligation, repair (including labour costs), refund or replace any nonconforming
Equipment, provided that:

  • Traulsen is promptly notified during the Domestic Warranty Period, Compressor Warranty Period or Cam-Lift Lifetime Warranty Period, as applicable, in writing upon discovery of the nonconformance with a detailed explanation of any alleged deficiencies;
  • Traulsen is given a reasonable opportunity to investigate all claims;
  • Traulsen’s examination of any alleged defective part confirms such alleged deficiencies and that the deficiencies were not caused by misuse, neglect, improper installation, improper repair, improper alteration or improper testing; AND
  • In the case of a nonconforming part, the Owner must return the part to Traulsen within 30 days from the date of repair. Failure to return a claimed defective part to Traulsen within 30 days will waive the right to the warranty claim.

THIS DOMESTIC WARRANTY SETS FORTH THE EXTENT OF TRAULSEN’S LIABILITY FOR SALES WITHIN THE UNITED STATES. NO EQUIPMENT MAY BE RETURNED TO TRAULSEN WITHOUT TRAULSEN’S PRIOR WRITTEN APPROVAL. EXCEPT AS EXPRESSLY SET FORTH ABOVE IN THIS WARRANTY STATEMENT, TRAULSEN MAKES NO WARRANTY OR REPRESENTATION OF ANY KIND, EXPRESS OR IMPLIED (INCLUDING NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE). IN NO EVENT WILL TRAULSEN’S LIABILITY IN CONNECTION WITH THIS WARRANTY OR THE SALE OF THE EQUIPMENT EXCEED THE PURCHASE PRICE OF THE EQUIPMENT AS TO WHICH THE CLAIM IS MADE.

This warranty only applies to units shipped from Traulsen’s manufacturing facilities on or after January 1, 2023.

  • To report a warranty claim, please email service@traulsen.com or call 1.800.825.8220 and include the serial and model number of the affected unit.
  • All service for warranty claims must be dispatched by Traulsen.
  • Traulsen reserves the right to refuse warranty claims for warranty service conducted by unauthorized third-party providers.

CONTACT

Traulsen © All Rights Reserved

Please Note: This manual is intended for use with the above-referenced equipment manufactured after May 01, 2020.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Traulsen User Manuals

Related Manuals