INSTALLATION LEAFLET
EV-DUO-CORE(-B)
EV-DUO-CORE-B Duo Core Emergency Weatherproof Light
-
Remove front by inserting a screwdriver into two slots and levering from body.
-
To mount to wall,screw through marked points in corners of case.
Ensure holes are sealed appropriately to maintain IP rating. -
To mount to wallvia hanging,screw hooks to body using the marked points. Secure screws to wallin marked positions. (Optional)
-
Wire terminal block
Strip length: 8-10mm
Wire range: 0.5:6 0rm?
-
Set LED configuration via switch located inside housing
-
Replace front panel and ensure it is secured properly
COMPLIANCE STANDARDS ASINZS 60598.1 AS60598222 ASINZS 22933
INSTALLATION LEAFLET
DIMENSIONS
SPECIFICATIONS
Voltage | 230V~ 50Hz |
---|---|
Class | I I |
Working Temp. | 40 |
Max power consumption | 2.5W |
Average power consumption | 1.0W |
CCT | 6000K |
1P Rating | IP65 |
Mounting Type | Wall Mounted |
Wiring | Terminal Block |
Duration | 90min |
Battery Type | LiFePO4 |
Battery Capacity | 3.2V 3400mAn |
Battery Code | T8096 |
Charging Time | T6 Hours |
Charger Type | Verigble |
BATTERY LIFE
To maintain the economnic lfe of this product it s required that the battery
be discharged and recharged at least once every 6 months. The battery lfe can
be reduced if the battery is not discharged as per the requirements of AS/NZS
2293 or an equivalent standard. Increasing the number of duration tests above
that as defined in AS/NZS 223 or an equivalent standard can have a positive
effect on the battery performance as long as 12 discharge cycles per year is
not exceeded. The recharging device will operate normally after removal of
short circuit fault.
TEST SWITCH
Action | Function |
---|---|
Hold | Run in emergency mode |
STATUS CHARGE LEDS (GREEN)
Indicator | Meaning |
---|---|
on | Battery charging |
Battery test*
2xflash| Battery full
4xflash| NTC noncharge
5xflash| Battery charge
3xflash| Lamp failure
off| Battery charger off/disconnected
- After emergency test mode is activated via test switch
ORDERING INFORMATION
SKU | Productcode | Description |
---|---|---|
12164 | ELOUOCORE | Do CoreEmergeney umiae |
12145 | EVDUOCORES | Duo Core Emergency Luminie- Block |
REPLA CING THE BATTERY
Access the battery by removing the gear tray. Disconnect and remove battery,
Replace battery as was previously installed, Battery can be connected in one
direction only,do not force. Allow a minimurm 24 hours charging time before
carrying out any. discharge tests as per the requirements in AS/NZS 2293
SAFETY WARNINGS
- This product must only be installed by a licensed electrician.
- Before commencing installation turn off and isolate the electrical supply.
- Risk of accidental contact with live parts. do not energise with product open or disassembled.
- Mains supply and battery circuit separated by reinforced insulation.
- The only user serviceable / replaceable part is the battery pack.
- Do not attempt to service other parts of the fitting as this will void the warranty.
- After installation allow the battery to charge for 24 hours before carrying out discharge testing.
- As the installer, it is your responsibility to ensure you comply to all relevant building and safety codes.
- The light source contained in this luminaire shall only be replaced by the manufacturer or their service agent or a similar qualified person.
- The replacement of the battery is needed when they no longer meet their rated duration of operation after the corresponding recharge period.
- This luminaire is intended only for mounting in locations where the plug and socket are protected from unauthorized disconnection.
- All maintenance, such as battery change on this luminaire to be performed by qualified personnel only. De-energise all supplies before maintenance.
The leaflet is subject to change without notice See separate leaflet for Warranty EV-DUO-CORE LAST UPDATED: 20.10.23 V1.3
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>