Weidm ller 4058570000 Klippon Relay Termseries User Guide
- June 2, 2024
- Weidm ller
Table of Contents
Weidm ller 4058570000 Klippon Relay Termseries
The table below helps you to select suitable relay loads.
A service life of around 100,000 switching operations is assumed.
SPECIFICATIONS
|
---|---
Example Part No. Single relay 24 V DC input| 4058570000
Example Part No. KIT 24 V DC input| 2618400000
Insulation between input and output| reinforced insulation
Contact material| AgNi
Width plugged on socket| 12.8 mm
Socket connection technologies| PUSH IN and Screw
Max. Operating temperature| 60°C
Resistive AC load| AC1 loads:
Heaters 250 V AC
| < 6 A
Inductive AC load| AC15 loads:
Valves, contactors 250 VAC
| < 1.5 A
Inductive AC load| AC3 loads:
1-phase motors 250 VAC
| < 0.7 A
Resistive DC load| DC1 loads:
Heaters 24 V DC
| < 4 A
Induktive DC Last| DC13 loads:
Valves, contactors 24 V DC
| < 1 A
Inrush current optimized| –
Recommended field of application
| Miniature industrial relay for decoupling PLCs, multiplying signals, and switching industrial small loads < 2 A.
Using Instructions
The indicated currents only apply to the normally open contact. The data of the normally closed contact are to be set at approx. one-third of the specified values. The real service life can be both above and below the specified value because each load stresses the switching contact differently and other environmental factors influence the service life of the switching contact, e.g. ambient temperature, mounting position, switching frequency, and many more. Therefore, these values are without guarantee and serve as orientation for better dimensioning. They may not be used as B10 or B10d values for the calculation of failure data such as MTTF or MTTFd either. The assessment of the maximum load capacity was carried out based on many years of practical experience as well as life cycle tests under laboratory conditions.
Additional information on the selection tables
Simple formulas for calculating individual values
Calculating the service life of the relay contacts for different switching currents
In the previous tables, we gave you the maximum recommended currents at
various loads for a service life of approx. 100,000 switching cycles. If you
switch lower currents, the service life of the relay contacts will be
extended. With the following formulas, you can approximately calculate how the
service life of the relay contacts will change.
Example: A 24 V DC solenoid valve with 200 mA current consumption should
be switched with a 6.4 mm wide TERMSERIES RSS 1 CO relay. A solenoid valve
corresponds to a DC13 load. According to the table, a switching current of
max. 1 A is specified for the relay at this load. To calculate the expected
service life, proceed as follows:
- The expected service life when switching a 200 mA solenoid valve should be approx. 500,000 switching cycles.
Calculating the switching currents for voltages that deviate from the values in the table
AC switching voltage:
With AC loads, the switching current has the greatest influence on the service
life. Therefore, the switching currents from the table can also be used for
switching voltages up to 100 V AC. For values below 100 V AC, the service life
increases at the same switching current:
- at 24 V AC four times the service life
- at 60 V AC twice the service life
Example: If the table shows a switching current of 2 A for a 250 V AC AC15 load, then these 2 A are also applicable for 120 V AC. At 24 V AC switching voltage, the expected service life increases four times to 400,000 switching cycles.
DC switching voltage:
When switching DC loads, the switched voltage has a large influence on the
maximum switching current of the relay contact. This can also be seen from the
DC load-breaking curve given in the datasheet. The following formulas can be
used to roughly determine the maximal switching current for other DC switching
voltages:
Example: A TERMSERIES RCL 1 CO relay with a DC13 load and a switching voltage of 110 V DC. According to the table, a maximum of 2 A at 24 V DC applies to a DC13 load for a service life of 100,000 switching cycles.
- The curve shows a maximum switching current of approx. 0.45 A with resistive load. This must now be set about the rated current of the relay (16 A) from the data sheet and the value for a DC13 load from the table.
- To achieve 100,000 switching cycles, a DC13 load of 56 mA can be switched with a switching voltage of 110 V DC.