PURMO YALI DIGITAL Oil Filled Radiators Instruction Manual
- June 2, 2024
- PURMO
Table of Contents
YALI DIGITAL Oil Filled Radiators
“`html
Product Specifications
-
Model: YALI DIGITAL, YALI PARADA, YALI
RAMO -
Panel Type: Single Panel and Double Panel
-
Height (H): 300mm (for all models)
-
Recommended Dimensions:
-
YALI DIGITAL: A* (100-150mm), B (37mm), C (173mm)
-
YALI PARADA/RAMO: A (100-150mm), B (150-200mm), C (89mm), D
(173mm) -
DOUBLE PANEL: A* (100-150mm), B (46mm), C (173mm)
-
Product Usage Instructions
Installation
-
Ensure a minimum clearance of 100mm on all sides for single
panel radiators. -
For double panel radiators, maintain a minimum clearance of
200mm on one side and 100mm on the other side. -
Refer to the manufacturer’s recommended dimensions for precise
installation.
Operating Instructions
-
Connect the radiator to the power source as per the electrical
requirements. -
Adjust the temperature settings as needed using the control
panel. -
Monitor the heat output and adjust settings for optimal
comfort.
Frequently Asked Questions (FAQ)
Q: How do I clean the radiator?
A: To clean the radiator, ensure it is turned off and cool. Use
a soft cloth to wipe the surface gently. Avoid abrasive
cleaners.
Q: Can I paint the radiator?
A: It is not recommended to paint the radiator as it may affect
its heat distribution and efficiency.
Q: What should I do if the radiator malfunctions?
A: If you experience any issues with the radiator, contact our
customer support for assistance and do not attempt to repair it
yourself.
“`
YALI DIGITAL YALI PARADA YALI RAMO
AU INSTALLATION AND OPERATING MANUAL
A NEW GENERATION THAT TURNS EVOLUTION INTO A REVOLUTION CLASS I 230V 50 HZ
PRODUCT INFORMATION
1
Min. 100mm Min. 100mm
Min. 100mm
Min. 200mm
Min. 100mm
2
3m 2.25m
Zone 1
OUTSIDE ZONES Zone 2
Zone 2
0.6m
Zone 0
0.6m
2
3A
A
SINGLE PANEL YALI DIGITAL RADIATOR
H (mm)
300
A* (mm) 100-150
B (mm)
37
C (mm)
173
500 100-150 37
373
- Manufacturer’s recommended dimensions
H C B
3B
SINGLE PANEL YALI PARADA/RAMO
A
RADIATOR
H (mm)
300
A* (mm)
B* (mm)
100-150 150-200
C (mm)
89
D (mm)
173
500 100-150 150-200 89
373
- Manufacturer’s recommended dimensions
H D C
3C
A
DOUBLE PANEL RADIATOR
H
A*
B
C
(mm) (mm) (mm) (mm)
A
300 100-150 46
173
H
500 100-150 46
373
C
- Manufacturer’s recommended dimensions
H
C
B
B
PRODUCT INFORMATION
A
B
A A
3
PRODUCT INFORMATION
3D
SINGLE PANEL YALI DIGITAL
SINGLE PANEL YALI PARADA/RAMO
DOUBLE PANEL
3E
CLICK!
3mm
4
NO
4
5
A B
C
6
= =
PRODUCT INFORMATION
d1 1
0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
d3 1
0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
d5 1
0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
d7 1
0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
d9 1
0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
d2 1
0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 d4
1 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 d6
1 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 d8
1 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
2 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 0h 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
5
PRODUCT INFORMATION
AU SAFETY INFORMATION
Due to the safety standard AS/NZS 60335-1, the text below is obligatory for
all electric products, not only radiators.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children unless they are older than 8 and supervised.
Keep the appliance and its cord
out of reach of children aged less than 8 years. Children of less than 3 years should be kept away from the unit unless continuously supervised. Children aged from 3 years and less than 8 years shall only switch on/off the appliance provided that it has been placed or installed in its normal operating position and they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children aged from 3 years and less than 8 years shall not plug in, regulate and clean the appliance or perform user maintenance.
AU CAUTION
SOME PARTS OF THIS PRODUCT CAN BECOME VERY HOT AND CAUSE BURNS. PARTICULAR
ATTENTION HAS TO BE GIVEN WHERE CHILDREN AND VULNERABLE PEOPLE ARE PRESENT. IN
ORDER TO AVOID OVERHEATING, DO NOT COVER THE RADIATOR. “DO NOT COVER” MEANS
THAT THE RADIATOR MUST NOT BE USED FOR DRYING CLOTHES, FOR EXAMPLE, BY PLACING
THEM DIRECTLY ON THE RADIATOR.
6
AU SAFETY INFORMATION
1. GENERAL INFO
· This appliance is a sealed electric radiator designed for fixed wall-mounted
installation.
· This appliance conforms to the standards AS/NZS 60335-1 and AS/NZS
60335-2-30.
· The appliance is insulation class I and has electrical protection level
IP44.
· This appliance complies with European Directive 2014/30/EU (CE Marking on
all appliances).
· Supplied with 3 core cable and fitted with an earthed plug, wall brackets,
screws and feet.
2. INSTALLATION
POSITIONING
· The radiator must be positioned horizontally in order for it to function
correctly.
· The radiator must be positioned according to the applicable standards. The
minimum distances as specified in picture 1 should be carefully observed.
· The radiator may be positioned “outside” zone 2 with the standard connection
box and inside zone 2 if the connection box is equipped with a splash proof
cover (picture 2), insofar as no operating controls (button, switches, etc …)
are in reach of persons in the bath or under the shower.
· The radiator must be fixed to the wall using the wall brackets supplied.
· The radiator must not be located underneath an electrical socket.
FIXING
· Mark out the distance between the brackets and the positions of the screw
holes as shown in the table in picture 3A (single panel YALI D) or 3B (single
panel YALI P and YALI R) or 3C (double panel). Note that 2000 mm long products
are supplied with extra brackets as a 3rd bracket must be fitted in the middle
of the product.
· Note that the brackets can be used to measure the height of the bottom
fixing hole, see picture 3D (excludes 300 mm high YALI P and YALI R single
radiators).
· For the correct installation of radiators it is essential that the fixing of
the radiator is carried out in such a way that it is suitable for intended use
AND predictable misuse. A number of elements need to be taken into
consideration including the fixing method used to secure the radiator to the
wall, the type and condition of the wall itself, and any additional potential
forces or weights, prior to finalising installation.
· The fixing materials provided are only intended for installation on walls
made of solid wood, bricks, concrete or on timber-frame stud walls where the
fixing is directly into the timber. All walls being considered should have no
more than a maximum of 3 mm wall finishing. For walls made of other materials,
for example hollow bricks; please consult your installer and/or specialist
supplier. In all cases it is strongly recommended that a suitably qualified
professional installer or similar tradesperson carries out the installation.
CONNECTION
· The electrical installation must comply with local or national regulations.
· The radiator must be connected to the electrical supply using the supply
cable fitted to the unit.
· If the radiator is installed in a bathroom or shower room, it must be
protected with a residual current device (RCD) with a rated residual current
not exceeding 30 mA.
· The radiator is equipped with a non-resettable overheat protection that
trips off if the radiator overheats. If the radiator is removed from the wall
brackets, even for a short time, it must without exception be switched off,
see picture 4. This may even trip the non-resettable overheat protection. If
the overheat protection trips, its thermal fuse must be replaced; contact your
supplier.
7
AU GENERAL INFORMATION
3. OPERATION
· The On/Off button is located at the bottom of the control side of the radiator (C, picture 5). The radiator should only be switched “on” when it is correctly installed and secured to the wall brackets (picture 3E). When the radiator is switched “on”, the LCD screen will illuminate and all segments will be displayed for a few seconds, then disappear, before displaying the software version. The “Comfort” or previously selected operating mode screen will appear. The backlight will switch off after a further 5 seconds.
· Display (A, picture 5)
1 2
3 18
4
17
5
16
15
6
7
14
8
13
12
9
11
10
1. Program information bar or “behaviour” indicator.
2. Day of week indicator.
3. Cloud icon (with Unisenza+ Gateway).
4. “RF connection” indicator (with Unisenza+ Gateway).
5. Adaptive Start indicator.
6. “Room temperature” indicator.
7. Operating mode menu.
8. “Open Window” function indicator.
9. Master/Follower indicator (with Unisenza+ Gateway).
10. Warning indicator.
11. Installation parameter indicator.
12. Parameters number when icon “11” is displayed.
13. Front panel temperature limit indicator.
14. Heating demand indicator.
15. Pilot wire indicator.
16. Display zone for temperatures or time.
17. Hand icon.
18. “Key lock” function indicator.
GENERAL
HOW TO CHANGE BETWEEN THE OPERATING MODES In basic mode, only Comfort and
Program mode are available.
– Press any button to turn on the backlight. – Press the “<” or “>” buttons to
enable scrolling between modes. · Use the left “” or right “” buttons to move
to the
desired operating mode and press “OK” to confirm your choice.
HOW TO CHANGE COMFORT AND PROGRAM MODE TEMPERATURES · Press any button to turn
on the backlight. · By pressing the “+” or “” buttons, the set
temperature will start to blink and can be adjusted to the desired temperature
level. · Wait 6 seconds until the new set temperature stops blinking or press
the “OK” button to confirm immediately. NOTE: The comfort temperature setting
must always be higher than the reduced temperature setting. If it is not
possible to lower the comfort temperature to the desired value, first set the
reduced temperature to an even lower value, or, if it is not possible to
increase the reduced temperature to the desired value (maximum 19 °C), first
increase the comfort temperature.
HOW TO VIEW THE MEASURED ROOM TEMPERATURE
· Keypad (B, Picture 5) Right navigation key Left navigation key + Plus key
Minus key OK Validation key
8
· Press the “OK” button twice. On the first press, the screen will illuminate, and on the second press, the measured room temperature will be displayed together with the room temperature icon , in section 6 of the LCD display. · The display will return automatically to the active operation mode after 8 seconds.
HEATING
· When the radiator is heating, the , in section 14 of the LCD display, is
constantly displayed. As the radiator regulates, the may not always be
displayed due to the required heating demand.
ADVANCED MODE
To gain access to all operating modes, please refer to section 4.0, and set
parameter number 01 to “YES”.
STAND ALONE RADIATOR
COMFORT MODE This mode is to be used during periods of normal occupancy.
AU GENERAL INFORMATION
To select a heating program, please refer to section 4.0, and select parameter
number 11 to view the available heating programs.
· Default value: 19.0°C NOTE: If connected to a gateway, it is not possible to
set the time. ANTI-FREEZE MODE (Advanced mode only) This mode is to be used
when the house is unoccupied for extended periods of time.
· Default value: 19.0°C
REDUCED MODE (Advanced mode only) This mode is to be used at night-time or
when the house is unoccupied for a few hours or more.
· Default value: 7.0°C
STANDBY MODE (Advanced mode only) In this mode the radiator is switched off
and the word “OFF” will be shown on the LCD display.
· Default value: 15.5°C
PROGRAM MODE
NOTE: By default, the product will follow the commands of an external
programmer when set in this mode. Program D1 must be selected (default).
To enable the product to follow the internal clock, please refer to section
4.0, setting parameter number 10 to “YES” to set the time, and selecting a
heating program in parameter number 11.
When you return to the main screen, the selected program and time settings
will now be displayed.
· The radiator will no longer receive signals from a wired external
programmer.
· At any time you can check the measured room temperature by pressing the “OK”
button.
· ATTENTION: Please be aware, if there is no heating in your property then
your pipes could freeze. For the protection of product and property in very
low temperatures we recommend the “Anti-Freeze” mode is used.
· ATTENTION: In this mode the radiators are still connected to the electrical
supply.
9
AU GENERAL INFORMATION
RADIATOR CONNECTED TO A WIRED PROGRAMMER
· When connected to a wired programmer, Program mode must be selected on the
radiator so that it follows the orders of the external programmer. NOTE:
Preset program D1 must be selected (default).
· Comfort mode/temperature is active. The , in section 7 of the LCD display is
displayed.
KEY LOCK FUNCTION Use the Key Lock function to prevent any changes to your
settings (in a child’s room, public area… etc)
· To activate the Key Lock function, simultaneously press and hold the “<“,
“OK”, and “>” buttons for 10 seconds.
· The key lock icon, in section 18 of the LCD display, will be displayed on
the screen.
· Repeat the same procedure to unlock the keypad. This function is available
in all operating modes.
· Reduced mode/temperature is active. The , in
section 7, and
, in section 15 of the LCD
display are displayed.
RADIATORS CONNECTED IN A WIRED MASTER /FOLLOWER SETUP
· When several radiators are installed in a room, one of them can be selected
as a “Master”, while the others function as “Followers”. The Followers will
follow the heating instructions from the Master radiator.
· This setup requires appropriate wiring (picture 4A).
NOTE: All radiators in a Master/Follower group must be connected to the same
phase on pin 1.
BEHAVIOUR INDICATOR These are the coloured indicators above the LCD display
that gives a visual indication of how much energy the current temperature
setting is using i.e.
red = high orange = medium green = low energy comsumption
As you increase the temperature setting, the behavior indicator segments in
section 1 of the LCD display, will appear under the orange or red indicators.
The opposite applies when decreasing the temperature setting.
NOTE: The behaviour indicator segments are replaced by the program information
bar when in Program mode. You can only view the behaviour indicator when in
Comfort mode.
· To set the radiator as a Follower, please refer to section 4.0, and set
parameter number 08 to “YES”.
· This radiator can only be connected as Master/ Follower to other Yali
Comfort/Digital/Parada/Ramo products.
· A maximum number of 10 Followers can be connected to each Master.
TROUBLE SHOOTING
Displayed icons
Sensor problem
Signal from Master
has been lost.
Contact the manufacturer or service agent.
Check the wiring. Check the Master.
10
AU GENERAL INFORMATION
4. PARAMETER MENU
The thermostat has a parameter menu. In order to enter this menu,
simultaneously press and hold the “<” and “>” keys for 8 seconds until , in
section 11 of the LCD display, and “rF” is displayed on the screen.
Parameters can be selected using the left “” and right “” navigation buttons.
Once the required parameter is displayed, press the “OK” button. Modify the
parameter settings with the “+” or “-” buttons and confirm your adjustment
with the “OK” button.
To exit the parameter menu, choose the parameter “END” and press the “OK”
button.
DEFAULT VALUE & OTHER POSSIBILITIES
00 rF: WIRELESS RADIO INITIALIZATION (PAIRING) Press “OK” to enter this
initialization sequence.
The digits will cycle showing that the digital thermostat is waiting for a
radio link signal from the gateway to be received (press “” to cancel radio
initialization). When the radio link signal is received, pairing is saved,
then it will return to the main screen, but now the cloud and antenna symbols
will be displayed.
01 ALL: EXPERT SETTING Press “OK” to enter this parameter. Select with “+” or
“-” and confirm by pressing the “OK” button:
no: Basic mode (only Program and Comfort modes available).
YES: Advanced mode (all modes available). NOTE: If connected to a Unisenza+
Gateway, this setting will not be available.
03 _. : CALIBRATION OF THE INTERNAL PROBE The calibration must be done after
1 day working with the same setting temperature in accordance with the
following description: Put a thermometer in the room at 1.5m distance from the
floor (like the thermostat) and check the real temperature in the room after 1
hour. When you enter the calibration parameter screen the actual temperature
value is displayed.
To enter the value shown on the thermometer, use the “-” or “+” buttons to
enter the real value. At this point the hand icon, in section 17 of the LCD
display, will be displayed and the value will blink. Press the “OK” key to
confirm and save. If you need to erase a calibration already saved use the “-”
or “+” buttons to alter the value, even just by 0.5°C , then press the left “”
navigation button. The hand symbol will disappear and the factory calibrated
temperature reading will be displayed.
NOTE: Only the heating elements (including follower radiators) managed by the
thermostat must be used during the calibration process. Do not have a
secondary heat source in the same room for a period of 24 hours before hand.
NOTE: If connected to a Unisenza+ Gateway, this setting will only be
accessible in the Unisenza+ App.
04 SurF: FRONT PANEL TEMPERATURE LIMITATION
This power setting can be used to limit the output of the heating element in
the front panel and as a consequence will limit the surface temperature of the
front panel.
02 dEG: TYPE OF DEGREES DISPLAYED Press “OK” to enter this parameter. Select
with “+” or “-” and confirm by pressing the “OK” button:
°C = Celsius °F = Fahrenheit
NOTE: If connected to a Unisenza+ Gateway, this setting will only be
accessible in the Unisenza+ App.
Press “OK” to enter this parameter. Select with “+” or “-” and confirm by
pressing the “OK” button:
no = 100% (default). Mid = 70% Lo = 55%
NOTE: If connected to a Unisenza+ Gateway, this setting will only be
accessible in the Unisenza+ App.
11
AU GENERAL INFORMATION
NOTE: When considering the permanent use of the radiator at 60°C or 75°C
maximum, the following correction factor should be applied for the output.
The , in section 5 of the LCD display, is constantly displayed (program mode
only). The adaptive start icon
will blink when pre-heating commences.
SETTING
SURFACE
SINGLE
TEMPERATURE PANEL
DOUBLE PANEL
NOTE: Heating start times will vary for each heating period when this function is enabled.
no
~ 90°C max
1
1
NOTE: If connected to a Unisenza+ Gateway, this setting
Mid
~ 75°C max
~ 0.70
~ 0.90
will only be accessible in the Unisenza+ App.
Lo
~ 60°C max
~ 0.55
~ 0.80
E.g. A 1000 Watt single panel programmed for a maximum surface temperature of 75°C will deliver maximum 700 Watts. A 1000 Watt double panel programmed for a maximum surface temperature of 60°C will deliver maximum 800 Watts. These values should be considered when selecting the number and type of panels to cover the calculated heat losses.
08 SLA: MASTER/FOLLOWER SET-UP Press the “OK” key to enter this parameter.
Select with “+” or “-” and confirm by pressing the “OK” key: no: radiator
control active (default). YES: radiator will function as Follower radiator and
follow the control instructions of the Master radiator.
NOTE: If connected to a Unisenza+ Gateway, this setting will only be
accessible in the Unisenza+ App.
05 FIRMWARE VERSION
Displays the MCU and ZigBee firmware alternately every 09 CLr: FACTORY SETTING
2 seconds.
Press and hold the “OK” key for 6 seconds to reset Set
point temperatures and all user parameters in this menu to
06 Wind: OPEN WINDOW DETECTION
factory default settings.
(the text “Uind” is displayed) Press the “OK” key to enter this parameter. Select with “+” NOTE: Pairing with the Unisenza+ Gateway will be lost.
or “-” and confirm by pressing the “OK” key: no: open window detection function disabled. YES: open window detection function enabled (default). The , in section 8 of the LCD display, is constantly displayed. This function will switch the radiator from any active mode to “Frost Protection” mode when an open window is detected (room temperature drops within a certain time). The open window icon will start to blink, and continue
The screen will go blank, the LCD screen will illuminate and all segments will
be displayed for a few seconds, before displaying the software version. The
“Comfort” mode screen will then appear.
10 hour: TIME SETTING NOTE: If power is lost, from a power cut or the product
is switched off, even just for a few seconds, the time and day setting will be
lost.
to blink as long as the function is active. To return to the previous or
automatic mode, press the “OK” key twice.
NOTE: If connected to a Unisenza+ Gateway, this setting will only be
accessible in the Unisenza+ App.
NOTE: If connected to a Unisenza+ Gateway, this setting will only be
accessible in the Unisenza+ App.
no: time setting disabled (default). YES: time setting enabled. · The hour
value will blink. Adjust the hour value by
07 ItCS: ADAPTIVE START Press the “OK” key to enter this parameter. Select
with “+” or “-” and confirm by pressing the “OK” key: no: adaptive start
function disabled. Heating up to reach the Comfort set temperature will start
at the programmed time. YES: adaptive start function enabled (default).
Heating up will start at the predicted optimal time to reach the Comfort set
temperature at the programmed time.
pressing the “+” or “-” keys, then confirm by pressing the “OK” key. · The minute value will blink. Adjust the minute value by pressing the “+” or “-” keys, then confirm by pressing the “OK” key. · The day values, in section 2 of the LCD display, will blink. Adjust the day value by pressing the “+” or “-” keys, then confirm by pressing the “OK” key. · The “Comfort” mode or previously selected operating mode screen will appear.
12
AU GENERAL INFORMATION
11 prog: SELECT/DEFINE HEATING PROGRAM
NOTE: If connected to a Unisenza+ Gateway, this setting will only be
accessible in the Unisenza+ App.
SELECTING A PROGRAM
· The above screen will be shown, where the symbol, the time value 00:00, and the time segment in the program information bar along the bottom of the screen will blink continuously.
· Use the “+” or “-” keys to select one of the preset programs, d1 to d9
(picture 6), or one of the user definable programs, U1 to U4. The program
number will blink. The heating schedule for the current day is displayed along
the top of the LCD screen. · To view the heating schedule for the other days,
press the “<” or “>” keys. Press the “OK” key to confirm the program to be
followed.
DEFINING A USER PROGRAM
NOTE: Once saved, the user defined programs are not lost in the event of a
power cut. However, the time will reset to 00:00 and day 1 when the power
returns, if not set, so the product may not heat at the expected times.
NOTE: If a user defined program has already been created and saved, it will be
overwritten when the newly defined user program is saved.
· Use the “+” or “-” keys to adjust the time at which the first Reduced period
will end.
· As the time indexes, the blinking segment on the program information bar
will move horizontally along the time scale according to the time value.
· Press the “OK” key to confirm the time at which the mode will change over
from Reduced to Comfort. The symbol will start to blink instead of the symbol,
signifying the start of this Comfort period.
· Use the “+” or “-” keys to select a user definable program, U1 to U4, to be modified, then press and hold the “OK” key for 3 seconds.
· Use the “+” and “-” keys to adjust the time at which the first Comfort period will end. The segments in the program information bar will populate to show the Comfort period.
13
AU GENERAL INFORMATION
· Press the “OK” key to confirm the time at which the mode will change over from Comfort to Reduced. The symbol will start to blink instead of the symbol, signifying the start of this Reduced period.
· Press the “OK” key to confirm the time at which the mode will change over
from Comfort to Reduced. The symbol will start to blink instead of the symbol,
signifying the start of this Reduced period.
· If more than two Comfort periods are required, repeat the previous steps.
· Use the “+” and “-” keys to adjust the time at which this Reduced period will end.
· Press the “OK” key to confirm the time at which the mode will change over from Reduced to Comfort. The symbol will start to blink instead of the symbol, signifying the start of this Comfort period.
· When all Comfort periods have been defined, use the “+” key to advance
beyond the time “23:30”. The above screen will then be shown, asking if the
program that has just been defined for that day is to be copied to the next
day.
· To copy the program onto the next day, press the “OK” key. Press the “OK”
key for any further days the program is to be copied over to.
· Use the “+” and “-” keys to adjust the time at which this Reduced period will end. The segments in the program information bar will populate to show the Comfort period.
· If a different program is to be defined for the next day, press the “+” or “-” key until the word “no” is displayed. Press the “OK” key to confirm.
14
· The day number will increment to the next day and the time will be set back
to “00:00”.
· When all of the days have been defined, the word “SAVE” will be displayed.
To save the program, press the “OK” key to confirm.
· If the program is not to be saved, so that any previously user defined
program is not overwritten, press the left “” arrow key. The screen will
revert back to the Program Selection screen.
13 MAC: ZIGBEE MODULE MAC ADDRESS Press “OK” to enter this parameter. The 16
digits of the MAC address will be displayed, 4 digits at a time. Each of the 4
digits will be displayed for 3 seconds.
14 & RG( =,*% ( ( 02’8/ ( ,16 7$ / / $ 7,21& 2′( 3UHVV³2.
´WRHQWHUWKLVSDUDPHWHU7KHGLJLWVRIWKH 0$& DGGUHVVZLOOEHGLVSODHGGLJLWVDWDWLPH(
DFK RIWKHGLJLWVZLOOEHGLVSODHGIRUVHFRQGV
15 RESNOT USED
16 End: EXIT THE PARAMETER MENU Press the “OK” key to exit installation
parameter menu and return to normal operation.
AU GENERAL INFORMATION
15
AU GENERAL INFORMATION
5. MAINTENANCE,
7. TECHNICAL
REPAIR AND DISPOSAL CHARACTERISTICS
· WARNING: Disconnect electrical supply before carrying out any maintenance
activity.
· The product should be cleaned using a soft damp cloth. Do NOT use chemical
or abrasive cleaners as they will damage the surface finish.
· The radiator is equipped with overheat protection that cannot be reset (melt
fuse). This overheat protection disconnects the current if the radiator
becomes too hot (e.g. when covered).
· If the supply cord is damaged, it must be replaced by the manufacturer, a
service agent or similar qualified persons in order to avoid a hazard.
· The radiator is filled with an exact amount of environmental friendly
vegetable oil. Any repairs that require the radiator to be opened shall
therefore only be carried out by the manufacturer or an approved agent.
· In case of leakage contact the manufacturer or service agent. · When the
radiator reaches the end of its service life
follow the regulations concerning the disposal of oil.
6. WARRANTY
The product is covered by a 10 years warranty except for the electrical and
electronic components that are covered by a 2 year warranty.
ENVIRONMENTAL: – Operating temperature – Storage temperature
SETTING TEMPERATURE RANGE – Comfort mode
– Reduced mode
– Frost protection mode
ELECTRICAL INSULATION ELECTRICAL PROTECTION
IMPACT PROTECTION
POWER SUPPLY DIRECTIVES & STANDARDS: The product has been designed to comply
with the following Directives and Standards.
-30°C to +50°C -30°C to +70°C
+5.5°C to +30.0°C, must be higher than the reduced mode setting. +5.0°C to
+19.0°C, must be lower than the comfort mode setting. +5.0°C to +10.0°C.
Class I
· IP44
IK08
230 VAC 50 Hz
· EN 60730-1 · AU/NZS 60335-1 · EN 60335-1 · AU/NZS 60335-2-30 · EN 60335-2-30
· EN 62233 · EN 55014-1 · EN 55014-2 · EN 61000-3-2 · EN 61000-3-3 · EN 60529
· LV Directive 2014/35/EU · EMC Directive 2014/30/EU · RED Directive
2014/53/EU · RoHS Directive 2011/65/EU · ECO Directive 2009/125/EC
16
Warranty
Our warranty
This warranty is given by Thermosoft Australia Pty Ltd ABN 90 657 190 004 (we,
our or us). It applies to goods and services that we supply to customers in
Australia.
You are entitled to a replacement or refund if there is a major failure in our
goods. You are also entitled to have the goods repaired or replaced if they
fail to be of acceptable quality and the failure does not amount to a major
failure.
This warranty applies during the warranty period and is subject to the
warranty limitations and limitations of liability below.
We limit our liability for indirect and consequential losses, loss of profit
or any reasonably foreseeable losses to the full extent permitted by the law.
Statutory warranty for consumers
Our goods and services come with guarantees that cannot be excluded under the
Australian Consumer Law. For major failures with the service, you are
entitled:
to cancel your service contract with us; and to a refund for the unused
portion, or to compensation for its reduced
value.
You are also entitled to choose a refund or replacement for major failures
with goods. If a failure with the goods or a service does not amount to a
major failure, you are entitled to have the failure rectified in a reasonable
time. If this is not done you are entitled to a refund for the goods and to
cancel the contract for the service and obtain a refund of any unused portion.
You are also entitled to be compensated for any other reasonably foreseeable
loss or damage from a failure in the goods or service.
Your benefits as a consumer under this warranty are in addition to your other
rights and remedies under a law in relation to the goods or services to which
this warranty related.
Warranty period For Purmo heating products, LVI radiators and FINIMETAL Towel
Rails:
10 years from the date the goods are purchased, in the case of the radiator or
towel rail body.
2 years from the date the goods are purchased, in the case of electronic
components and any spare parts sold separately. This includes, for example,
side covers, top grilles, plastic clips, plugs, fixing parts and electric and
electronic components. For services:
12 months from the date of repair services or until the end of the initial
warranty period for the repaired goods, whichever is later.
Costs of claiming the warranty You must bear the cost of returning the goods
to us for a warranty claim and we will bear the reasonable costs of returning
the goods to you if we accept the claim.
If the goods are not covered by the warranty, you will be responsible for the
costs of repairs, parts, handling and transport. If our initial evaluation is
that the warranty will not apply, we may require a purchase order and payment
for the anticipated costs before we inspect or repair the goods. We may hold
the goods until our costs are paid.
Thermosoft Australia Pty Ltd 1/3 Franklin Court, Frankston, Victoria 3199
www.lvi-thermosoft.com.au Email: info@lvithermosoft.com.au
Call: 1800 951 439
Warranty
Warranty limitations
Generally, the warranty may not apply if:
the goods are not stored or transported in dry conditions; mechanical damage
to the goods is caused by misuse (for example, due
to an overload as a result of sitting on the radiator or towel rail); a defect
in the goods is the result of ordinary wear and tear, external
factors, or causes damage that could be avoided if you were to promptly notify
us of the defect; or the goods are used other than in accordance with our
instructions or specifications, in abnormal conditions, operated above their
rated capacity, or improperly installed or maintained.
In addition, in the case of radiators and towel rails, the warranty may not
apply if:
the goods are not mounted in compliance with the instruction manual and
Australian standards;
the goods are used for heating outside of normal indoor environments; or
the goods are subject to internal or external corrosion or deformation caused
by excessive force or pressure;
the goods are exposed to corrosive substance activity or permanent or
temporary moistness (for example, where the goods are installed in commercial
laundries, public toilets, or other rooms with high activity of corrosive
substances in the air).
None of these limitations on the warranty will apply if they restrict or
exclude your rights under the Australian Consumer Law or any other
legislation.
Repairs We generally use new goods and parts for replacements and repairs.
However, in some cases, goods presented for repair may be replaced by
refurbished goods of the same type rather than being repaired. Refurbished
parts may be used to repair the goods. If the goods are capable of retaining
user-generated data, repair of the goods may result in loss of the data
Instructions for use
Radiators and convectors require periodic cleaning. It is recommended to use
only soft and gentle fabrics that can be slightly moistened. For cleaning the
radiators and towel rails it is not advised to use aggressive or corrosive
agents (e.g. acidic solvents or agents with chlorine). Panel radiators cannot
be used for drying wet or damp objects put on the radiator. We do not accept
claims for damages to painted surfaces due to improper handling or
maintenance.
Warranty claim procedure
To make a warranty claim, please contact us and provide an invoice as proof of
purchase. We may also require photographs of goods that you claim are
defective and we may inspect the area in which the goods are mounted.
The goods are to be returned to our o ce or an address nominated by us. Our
contact details are:
Freecall: 1800 951 439 Email: info@lvithermosoft.com.au 1/3 Franklin Court
Frankston VIC 3199
Thermosoft Australia Pty Ltd 1/3 Franklin Court, Frankston, Victoria 3199
www.lvi-thermosoft.com.au Email: info@lvithermosoft.com.au
Call: 1800 951 439
AU ECO DIRECTIVE TABLE 2
GB
Model identifier(s): YALI D x xx xxx xx 230 yy 1 1
YALI D x xx xxx xx 400 yy 1
YALI P x xx xxx xx 230 yy 1 YALI P x xx xxx xx 400 yy 1
YALI R x xx xxx xx 230 yy 1 YALI R x xx xxx xx 400 yy 1.
2 Heat Output
Type of heat input, for electric storage 11
local space heaters only
3 Nominal heat output
“yy” = 03
Pnom
0.25 kW
manual heat charge control, with 12 integrated thermostat
“yy” = 05 Pnom 0.50 kW
manual heat charge control with room and/ 13 or outdoor temperature feedback
“yy” = 08 Pnom
0.75 kW
electronic heat charge control with room 14 and/or outdoor temperature feedback
“yy” = 10 Pnom 1.00 kW 15 fan assisted heat output
“yy” = 13 Pnom 1.25 kW 16 Type of heat output/room temperature control
“yy” = 15 Pnom
1.50 kW
single stage heat output and no 17 room temperature control
“yy” = 20 Pnom
2.00 kW
Two or more manual stages, no 18 room temperature control
4 Minimum heat output (indicative)
Pnom
N.A. kW
with mechanic thermostat room 19 temperature control
5 Maximum continuous heat output “yy” = 03 Pnom 0.25 kW 20 with electronic room temperature control
“yy” = 05 Pnom “yy” = 08 Pnom “yy” = 10 Pnom
0.50 kW 0.75 kW 1.00 kW
21 electronic room temperature control plus day timer
electronic room temperature 22 control plus week timer
23 Other control options
“yy” = 13 Pnom “yy” = 15 Pnom “yy” = 20 Pnom 6 Auxiliary electricity consumption
1.25 kW 1.50 kW 2.00 kW
24 room temperature control, with presence detection
room temperature control, with 25 open window detection
26 with distance control option
27 with adaptive start control
7 At nominal heat output
eImax 0.00 kW 28 with working time limitation
8 At minimum heat output
eImin N.A. kW 29 with black bulb sensor
9 In standby mode
eISB <0.001 kW
10 Contact details
Purmo Group (UK) Ltd, Eastern Avenue, Team Valley, Gateshead, Tyne and Wear. NE11 0PG UK
Purmo Group (UK) Ltd Eastern Avenue, Team Valley, Gateshead, Tyne and Wear. NE11 0PG United Kingdom
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>