PURMO Radiator Manifold Flex Instruction Manual
- June 8, 2024
- PURMO
Table of Contents
Radiator Manifold Flex
Instruction Manual
Assembly instruction
MAH 1/2″.
Diverter.
Nut and olive M22K12.
Valve type AN/FVRe/VRM.
Connect to heating system.
Pull tight check for leakage.
Pre-setting
Radiatorflode ettrorssystem | Kv2K | Kvs |
---|
VRVM-koppel
FVRe-koppel| 26%
20%| 29%
**Settings diverter FA/FEA
**
FEA VRVM (Kvs)
Vary| % till radiators| Kv total| Kv radiator
0| 0%| 1,81| 0,00
0,25| 0%| 1,82| 0,01
0,5| 0%| 1,82| 0,01
0,75| 1%| 1,83| 0,02
1| 3%| 1,85| 0,05
1,25| 4%| 1,89| 0,08
1,5| 7%| 1,94| 0,14
1,75| 11%| 2,01| 0,22
2| 16%| 2,12| 0,34
2,25| 23%| 2,26| 0,53
2,5| 27%| 2,34| 0,64
2,75| 29%| 2,37| 0,68
3| 29%| 2,38| 0,69
FEA VRVM (Kv2K)
Vary| % till radiators| Kv total| Kv radiator
0| 0%| 1,82| 0,00
0,25| 0%| 1,82| 0,01
0,5| 0%| 1,82| 0,01
0,75| 1%| 1,83| 0,02
1| 3%| 1,86| 0,05
1,25| 5%| 1,89| 0,09
1,5| 7%| 1,94| 0,14
1,75| 11%| 2,01| 0,22
2| 16%| 2,10| 0,33
2,25| 22%| 2,23| 0,48
2,5| 25%| 2,31| 0,58
2,75| 26%| 2,33| 0,60
3| 26%| 2,34| 0,61
Purmo Group Sweden AB
Tel. +46 (0)433 737 00
482 80 40
220127 rev. 09
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>