SATEC EM132 Multi Function Meter User Guide

June 2, 2024
SATEC

Quick Start Guide
EM132-133SATEC EM132 Multi Function Meter

Mechanical Installation

SATEC EM132 Multi Function Meter - InstallationSATEC EM132 Multi Function Meter - Installation
2

IMPORTANT
Only qualified personnel can perform setup.
All incoming power sources must be turned off during installation. During operation of the Powermeter, hazardous voltages are present on the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment.
Please refer to the installation and operation manual for further information.

Typical Electrical Installation

SATEC EM132 Multi Function Meter - Installation 3

Wiring Configuration Setup Code
3-wire 2-element Direct connection using 2 CTs 3dir2
4-wire Wye 3-element direct connection using 3 CTs 4Ln3 or 4LL3
4-wire Wye 3-element connection using 3 PTs, 3 CTs 4Ln3 or 4LL3
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs 3OP2
4-wire Wye 2½ -element connection using 2 PTs, 3 CTs 3Ln3 or 3LL3
3-wire 2½ -element Open Delta connection using 2 PTs, 3 CTs 3OP3
4-wire 3-element Delta direct connection using 3 CTs 4Ln3 or 4LL3
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs 3bLn3 or 3bLL3

NOTE:
Refer to the Installation and operation manual for the wiring schematics diagrams

Electrical Installation

SATEC EM132 Multi Function Meter - Installation 4

MODULE Installation

This section applies to the I/O and Communication modules.

SATEC EM132 Multi Function Meter - Installation 5

CAUTION
Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.

Basic Setup

All setups can be performed directly from the display panel or via communication ports using PAS communication software, except for Communications and Display setups, which must be performed directly at the instrument panel. SATEC EM132 Multi Function Meter -
Setup

To set the CT Primary current, perform the following steps:

  • Press for 5sec, until password no. blinks:
  • Enter Password number using , then press for 2sec then new display with blinking “Reset”
  • Navigate by pressing shortly (less than 1sec) move to Basic setup
  • Press for 2sec, until “Conf” blinks:
  • Navigate by pressing shortly (less than 1sec) move to CT setup
  • Press for 2sec, until “5000” blinks, then press shortly using to the desired value
  • Press for 2sec, until “CT” blinks, then press for 2sec, until “Basic” blinks, then press for 2sec, until “Reset” blinks, press shortly using to move to blinking “Exit” and press for 2sec to return to initial screen
    SATEC EM132 Multi Function Meter - Setup 2

DATA DISPLAY

Navigating in Display Mode
The front panel has a simple interface that allows you to display numerous measurement parameters in up to 38 display pages. For easier reading, the parameters are divided into three groups; each group is accessible by pressing the key and each group page is  accessible by pressing the key.
The initial display is as described below: ![SATEC EM132 Multi Function Meter

First push on will display Energy measurement parameters, by pushing will navigate to imp., exp. active/reactive, etc …as described below: SATEC EM132
Multi Function Meter - DISPLAY 2

Second push on will display MAX DMD parameters, by pushing will navigate to MAX DMD P, Q, S, I, etc …as described below: SATEC EM132 Multi Function
Meter - DISPLAY 3

Third push on will display Votage/Current measurements, by pushing will navigate to V (L-N), V (L-L), I, Power, PF, THD, TDD, F, etc …as described below: SATEC EM132 Multi Function Meter - DISPLAY 4

Basic Menu

Code Parameter Options Description
ConF Wiring mode 3OP2 3-wire open delta using 2 CTs
4Ln3 4-wire Wye using 3 PTs (default)
3dir2 3-wire direct connection using 2 CTs
4LL3 4-wire Wye using 3 PTs
3OP3 3-wire open delta using 3 CTs
3Ln3 4-wire Wye using 2 PTs
3LL3 4-wire Wye using 2 PTs
3bLn3 3-wire Broken delta using 2 PTs, 3 CTs
3bLL3 3-wire Broken delta using 2 PTs, 3 CTs
Pt Ratio PT ratio 1.0* – 6,500.0 The potential transformer ratio
Pt Factor
Ct CT primary current 1-50,000A

(5*)

| The primary rating of the current transformer
PowDmdPer| Power demand period| 1, 2, 5, 10, 15*, 20,

30, 60, E

| The length of the period for power demand calculations, in minutes. E = external synchronization
Num.Per.| Number of power demand periods| 1-15 (1)| The number of demand periods to be averaged for sliding window demands 1 = block interval demand calculation
ADmdPer.| Ampere/Volt demand period| 0-1800 (900
)| The length of the period for volt/ampere demand calculations, in seconds. 0 = measuring peak current
Frequency| Nominal frequency| 25, 50, 60, 400 (Hz)| The nominal power utility frequency
MaxDmdLd| | |

Communication Port Menu

COM1 setting

Code Parameter Options Description
Protocol Communications protocol ASCII*, rtu, dnP3 ASCII, Modbus RTU

(default) or DNP3.0 protocol
Interface| Interface standard| 485| RS-485 interface (default)
Address| Address| ASCII: 0 (default) – 99 , Modbus: 1 (default) -247 , DNP3.0: 0 (default) -255
Baud Rate| Baud rate| 110, 300, 600, 1200, 2400, 4800, 9600 (default), up to 115,200 bps
Data/Party| Data format| 7E, 8E (7/8 bits, even parity), 8n (default) (8 bits, no parity)
Snd.Delay| |

Input and Output Ratings

3 voltage inputs| 57/98-400/690 VAC| DIRECT INPUT – Nominal: 690V line-to-line voltage, 828V maximum; 400V line-to-neutral, 480V maximum – Burden: <0.5 VA. INPUT USING PT – Burden: <0.15 VA
---|---|---
Voltage input terminals| 4 x Maximum wire section: 2.5 mm² (12 AWG)
3 current nputs (Galvanic isolation)| /5A(10A)| INPUT VIA CT with 5A secondary output – Burden: <0.2VA, Overload withstands: 20A RMS continuous, 300A RMS for 0.5 second.
/1A(2A)| INPUT VIA CT with 1A secondary output – Burden: <0.05VA, Overload withstands: 3A RMS continuous, 80A RMS for 0.5 second.
50A(100A)| INPUT VIA CT with 50A direct connection – Burden: < 0.05VA, Overload withstands: 120A RMS continuous, 2000A RMS for 0.5 second.
40mA:(optional)| INPUT VIA CT with 40mA secondary output, using external CT – Split Core CT or Solid Core CT – primary 100-1200A maximum rating
Current input terminals| 3 x Maximum wire section: 16 mm²
Communication port COM1| EIA RS-485 standard| Optically isolated, max. speed 115.2Kb/s
COM1 terminals| 3 x Maximum wire section: 2.5 mm²
Communication port COM3| IR COM port| Infra Red, max. speed 38.4Kb/s
Power Supply (Galvanically isolated)| 40-300V AC/DC (standard)| 50/60 Hz – 9VA
Power Supply input terminals| 3 x Maximum wire section: 2.5 mm²
MODULE 2DI/DO| DIGITAL INPUT x 2 optically isolated inputs| Dry contact, internally wetted @ 5VDC
DIGITAL OUTPUT x 1| 0.15A/250 VAC – 400 VDC, 1 contact (SPST Form A)
2DI/DO terminals| 5 x Maximum wire section: 2.5 mm²
MODULE 4DI/2DO

( Optional )

| DIGITAL INPUT x 2 optically isolated inputs| Dry contact, internally wetted @ 24VDC
DIGITAL OUTPUT x 2| EMR| 5A/250 VAC; 5A/30 VDC, 1 contact (SPST Form A)
SSR| 0.15A/250 VAC – 400 VDC, 1 contact (SPST Form A)
4DI/2DO terminals| 9 x Maximum wire section: 2.5 mm²
MODULE 4 AO ( Optional )| ANALOG OUT x 4 optically  isolated outputs (4 different options)| ±1 mA, maximum load 5 kW (100% overload)
0-20 mA, maximum load 510 W
4-20 mA, maximum load 510 W
0-1 mA, maximum load 5 k W (100% overload)
4 AO terminals| 5 x Maximum wire section: 2.5 mm²
Communication port COM2 (Optional)| Ethernet| 10/100 Base T, auto adaptation speed, Max. speed 100Mb/s
ETH connector| Shielded RJ45 cable
Communication port COM2 (Optional)| Profibus| Max. speed 12 Mb/s
Profibus terminals| 5 x Maximum wire section: 2.5 mm2 (12 AWG) or using terminal to DB9 converter: P/N AC0153 REV.A2
Communication port COM2 (Optional)| EIA RS-232-422/485 standard| Optically isolated, max. speed 115.2Kb/s – to be connected to GPRS modem if ordered
COM2 terminals| 5 x Maximum wire section: 2.5 mm² And DB9 connector

BG0504 REV.A3

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals