Alpha ESS SMILE-B3-PLUS Battery ESS with 3kw Integrated AC Charger Instruction Manual
- May 15, 2024
- Alpha-ESS
Table of Contents
- SMILE-B3-PLUS Battery ESS with 3kw Integrated AC Charger
- Information on this Document
- Safety
- Product Introduction and Application Scenarios
- Storage
- Unpacking
- Mounting
- Electrical Connection
- WiFi Setting
- Commissioning
- Maintenance and Troubleshooting
- Uninstallation & Return
- Specification
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
INSTALLATION MANUAL ENERGY STORAGE SYSTEM (ESS)
SMILE-B3-PLUS
SMILE-B3-PLUS Battery ESS with 3kw Integrated AC Charger
Copyright Statement
This manual is under the copyright of AlphaESS Co., Ltd. with all rights
reserved. Please keep the manual properly and operate in strict accordance
with all safety and operating instructions in this manual. Please do not
operate the product before read-ing through the manual.
Information on this Document
1.1 Content and Structure of this Document
This document is valid for product of SMILE-B3-PLUS (SMILE-B3-PLUS II,
SMILE-B3-PLUS III, SMILE-B3-PLUS IV, SMILE-B3-PLUS V, SMILE-B3-PLUS VI) which
has integrated 3 kW AC-coupled inverter with 1~6 battery packs — SMILE-BAT-5P.
This document describes the installation, commissioning, configuration,
operation, troubleshooting and decommissioning of the product .
Comply with the provisions of all documents shipped with the product, and keep
them properly to ensure that they are available at any time.
The illustrations in this document are abbreviated versions, which may deviate
from the actual product
1.2 Target Group
This document is intended for qualified persons and end users. Only qualified
per-sons are allowed to perform the operations marked with a warning symbol in
this document.
Tasks that do not require any specific qualifications will not be marked and can
be performed by the end user. Qualified persons must have
- knowledge of working principle of inverters.
- knowledge of how to deal with the dangers and risks associated with installing and using electrical devices, batteries and systems.
- knowledge of the installation and commissioning of electrical devices and systems.
- knowledge of the applicable standards and directives.
- understood and complied with this document, including all safety precautions.
- understood and complied with the documents of the battery manufacturer, including all safety precautions.
1.3 Levels of Warning Messages
The following levels of warning messages may occur when handling the product.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE indicates a situation which, if not avoided, can result in property
damage.
INFORMATION provides tips which are valuable for the optimal installation and
operation of the product.
1.4 Nomenclature
Complete designation | Designation in this document |
---|---|
SMILE-BAT-5P | Battery Pack |
Safety
2.1 Intended Use
The SMILE-B3-PLUS, expandable battery packs (SMILE-BAT-5P) and the ener-gy
meters make up a system for optimization of self-consumption for a house-hold.
The inverter can achieve bidirectional transfer between AC current and DC
current. The battery pack is used for the energy storage .
The product is suitable for indoor and outdoor installation
All components must operate in a scenario suitable for their operation.
Be sure to use this product in accordance with the information provided in the
accompanying documents and local applicable standards and directives. Any
other operation may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted
with the express written permission of AlphaESS. Unauthorized alterations will
void guarantee and warranty claims. AlphaESS shall not be held liable for any
damage caused by such changes.
Any use of the product other than that described in the Intended Use section
does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the
documentation in a convenient place for future reference and comply with all
instructions contained therein.
The type label must remain permanently attached to the product.
2.2 Safety Precaution for Battery Pack
2.2.1 General Safety Precautions
Overvoltage or wrong wiring can damage the battery pack and cause deflagration,
which can be extremely dangerous.
All types of breakdown of the battery may lead to a leakage of electrolyte or
flammable gas.
Battery pack is not user-serviceable. There is high voltage in the device.
Read the label with Warning Symbols and Precautions, which is on the right
side of the battery pack.
Do not connect any AC conductors or PV conductors directly to the Battery Pack
which should be only connected to the Inverter.
Do not charge or discharge damaged battery.
Do not damage the battery pack in such ways as dropping, deforming, impacting,
cutting or penetrating with a sharp object. It may cause a leakage of
electrolyte or fire.
Do not expose battery to open flame.
2.2.2 Response to Emergency Situations
The battery pack is composed of multiple batteries and designed to prevent the
danger caused by malfunction.
If the user touches the inner material of the battery cells due to damage to
the shell, the following actions are recommended.
Inhalation: Leave the contaminated area immediately and seek medical
attention.
Eye injuries : Rinse eyes with running water for 15 minutes and seek medical
attention.
Skin injuries : Wash the contacted area with soap thoroughly and seek medical
attention.
Ingestion: Induce vomiting and seek medical attention.
If a fire breaks out in the place where the battery pack is installed, perform
the following countermeasures:
Fire extinguishing media
Respirator is not required during normal operations.
Use FM-200 or CO2 extinguisher for battery fire.
Use an ABC fire extinguisher, if the fire is not from battery and not spread to
it yet.
Firefighting instructions
- If fire occurs when charging batteries, if it is safe to do so, disconnect the battery pack circuit breaker to shut off the power to charge.
- If the battery pack is not on fire yet, extinguish the fire before the battery pack catches fire.
- If the battery pack is on fire, do not try to extinguish but evacuate people immediately.
WARNING
There may be a possible explosion when batteries are heated above 150°C.
When the battery pack is burning, it leaks poisonous gases. Do not approach.
Effective ways to deal with accidents
On land: Place damaged battery into a segregated place and call local fire
department or service engineer.
In water: Stay out of the water and don’t touch anything if any part of the
battery, inverter, or wiring is submerged.
Do not use submerged battery again and contact the service engineer.
2.3 Important Safety Instructions
This section contains safety precautions that must be observed at all times
when working on or with the product.
To prevent personal injury and property damage and to ensure longterm
operation of the product, please read this section carefully and follow all
safety precautions at all times.
DANGER
Danger to life due to electric shock when live components or cables are
touched High voltages are present in the conductive components or cables of
the product.
Touching live parts and cables results in death or lethal injuries due to
electric shock.
Do not touch non-insulated parts or cables.
Disconnect the product from voltage sources and make sure it cannot be
reconnected before working on the inverter or the battery pack.
After disconnection, wait for 5 minutes until the capacitors have discharged.
Do not open the product.
Wear suitable personal protective equipment for all operations on the product.
DANGER
Danger to life due to electric shock when touching live system components in
case of a ground fault
If a ground fault occurs, parts of the system may still be live. Touching live
parts and cables results in death or lethal injuries due to electric shock.
Disconnect the product from voltage sources and make sure it cannot be
reconnected before working on the device.
DANGER
Danger to life due to high voltages on the battery pack
Lethal voltage is present at the pin connector for the power cable. Reaching
into the pin connector for the power cable can result in lethal electric
shock.
Do not open the battery pack.
Do not wipe over the battery pack with a damp cloth.
Leave the protective caps on the pin connectors for the batteries power
connection until the inverter cables are connected to the battery pack.
Disconnect the product from voltage sources and make sure it cannot be
reconnected before working on the inverter or the battery pack.
WARNING
Risk of chemical burns from electrolyte or toxic gases
During normal operation, no electrolyte would leak from the battery pack and
no toxic gases would form. Despite careful construction, if the battery pack
is damaged or a fault occurs, it is possible that electrolyte may be leaked or
toxic gases may form.
Store the battery pack in a cool and dry place.
Do not drop the battery pack or damage it with sharp objects.
Only set the battery pack down on its back or its bottom.
Do not open the battery pack.
Do not install or operate the battery pack in potentially explosive atmosphere
or areas of high humidity.
If moisture has penetrated the battery pack (e.g. due to a damaged housing),
do not install or operate the battery pack.
In case of contact with electrolyte, rinse the affected areas immediately with
water and consult a doctor without delay.
CAUTION
Risk of burns due to hot heatsink and housing
The heatsink and housing can get hot during operation.
During operation, do not touch any parts other than the cover of the inverter.
NOTICE
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter
through electrostatic discharge.
Ground yourself before touching any component.
NOTICE
Damage due to cleaning agents
The use of cleaning agents may cause damage to the product and its components.
Clean the product and all its components only with a cloth moistened with
clear water.
2.4 Symbols on the Label
Symbols on the type label of the inverter
Symbol | Explanation |
---|---|
Beware of a danger zone |
This symbol indicates that the product must be additionally grounded if
additional grounding or equipotential bonding is required at the installation
site.
| Beware of electrical voltage
The product operates at high voltages.
| Beware of hot surface
The product can get hot during operation.
| Danger to life due to high voltages in the inverter, observe a waiting time
of 5 minutes.
High voltages that can cause lethal electric shocks are present in the live
components of the inverter. Prior to performing any work on the inverter,
disconnect it from all voltage sources as described in this document.
| WEEE designation
Do not dispose of the product together with the household waste but in
accordance with the disposal regulations for electronic waste applicable at
the installation site.
| Observe the documentation
| Certified safety
The product is TUV-tested and complies with the requirements of the EU
Equipment and Product Safety Act.
| CE marking
The product complies with the requirements of the applicable EU directives.
| RCM (Regulatory Compliance Mark)
The product complies with the requirements of the applicable Australian
standards.
Symbols on the type label and warning label of the battery pack
Symbol | Explanation |
---|---|
Beware of a danger zone |
This symbol indicates that the product must be additionally grounded if
additional grounding or equipotential bonding is required at the installation
site.
| Beware of electrical voltage
The product operates at high voltages.
| Risk of chemical burns.
| Risk of explosion.
| Observe the documentation
| Risk of electrolyte leakage.
| CE marking
The product complies with the requirements of the applicable EU directives.
| Refer to the instruction for operation.
| Use eye protection.
| Fire, naked light and smoking prohibited.
| No nearing.
| Do not dispose of the battery pack together with the household waste but in
accordance with the locally applicable disposal regulations for batteries.
| Recycling code.
UN38.3| Marking for transport of dangerous goods
The product passes the certifications of the UN38.3
Product Introduction and Application Scenarios
3.1 Product Description
Appearance and Dimensions (mm)Inverter LED Signals
LED Indictor | Status | Description |
---|---|---|
Normal | On: system is in working mode normally | |
Flicker: system is in standby mode or |
self-checking process
| Off: system is in fault mode or off
Fault| | Off: system is in working mode normally or off
| On: system is in fault mode
COM| | On: network connection is normal
| Flicker: connecting to the server
| Off: system is not connected network
Battery LED Signals
Different colors represent different states: green for SOC state yellow for
protection state red for error state.
The LED indicators provide information about the SOC operational status of the
battery pack.
| SOC Status| Description
---|---|---
SOC Instruction| | SOC<5%
| 5%=<SOC<25%
| 25%=<SOC<50%
| 50%=<SOC<75%
| 75%=<SOC<95%
| SOC>95%
The LED Border Flashes Status| | Standby mode: The green light flashes every
second
Work mode: The green light flashes every 10 seconds
3.2 Application Scenarios
SMILE-B3-PLUS is an AC-coupled all-in-one battery energy storage system
(BESS). It can help to achieve the optimal usage of renewable energy.
SMILE-B3-PLUS can control the bi-directional flow of electric power, work under
auto/manual & time-of-use (TOU) modes, charge/discharge the battery as per
customer’ s setting. Under the auto mode, SMILE-B3-PLUS stores surplus
renewable energy onto the battery and discharge battery to supply power to
local loads when renewable energy is not enough.
The standard schematic is as below: NOTE:
For the AC coupled system with PV, if only install Grid CT, the system cannot
display power generated by PV inverter, electric energy production etc.
Storage
4.1 Product Storage
The following requirements should be met if the product is not put into use
directly:
-
Do not unpack the product.
-
The product should be stored in a clean and dry place and be protected from dust and water vapor corrosion.
-
Place product according to the signs on the packing case during storage
A maximum of 2 layers can be stacked. To avoid personal injury or device damage, stack products with caution to prevent them from falling over. -
Store the product out of reach of children and animals.
-
Handle product with caution to avoid damage.
-
The storage environment requirements are as follows:
– Ambient temperature: -10~55°C, recommended storage temperature: 15~30°C
– Relative humidity: 15%~ 85%
– Place products in a place that is away from corrosive organic solvents and gases.
– Keep products away from direct sunlight.
– Keep products at least 2 meters away from heat sources. -
The product in storage must be disconnected from external devices. The indica-tors (if any) on the products should be off.
-
Products should be delivered based on the “first in, first out” rule.
-
The warehouse keeper should collect battery storage information every month and periodically report the battery inventory information to the planning department. The batteries that have been stored for nearly 6 months should be recharged timely.
-
If a lithium battery is stored for a long time, capacity loss may occur. After a lithi-um battery is stored for 12 months in the recommended storage temperature, the irreversible capacity loss rate is 3%~10%. It is recommended that batteries not be stored for a long period. If the batteries need to be stored for more than 6 months, it is recommended to recharge the batteries to 65 ~ 75% of the SOC. For example, they should be recharged every 6 months at least, and must be recharged to at least 50% of the SOC.
Unpacking
5.1 Checking the Outer Packing
Before unpacking the battery pack and inverter, check the outer packing for
damage, such as holes and cracks. If any damage is found, do not unpack the
product and contact your distributor as soon as possible.
5.2 Scope of Delivery
Check the scope of delivery for completeness and any externally visible
damage.
Contact your distributor if the scope of delivery is incomplete or
damaged.
Mounting
6.1 Requirements for Mounting
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
Do not mount the product in areas containing highly flammable materials or
gases.
Do not mount the product in potentially explosive atmospheres.
Basic Requirements
SMILE-B3-PLUS and SMILE-BAT-5P are suitable for indoor and outdoor use.
Do not install the product in a place where a person can easily touch it
because its housing and heatsink are hot during operation.
Do not mount the product in areas with flammable or explosive materials.
Do not mount the product at a place within children’s reach.
Do not mount the product outdoors in salt areas because it will be corroded
there and may cause fire. A salt area refers to the region within 500m from the
coast or prone to sea breeze. The regions prone to sea breeze vary depending
on weather conditions (such as typhoons and monsoons) or terrains (such as
dams and hills).
Mounting Environment Requirements
The product must be mounted in a well-ventilated environment to ensure good
heat dissipation.
When mounted under direct sunlight, the power of the product may be derated
due to additional temperature rise.
Mount the product in a sheltered place or mount an awning over the product.
The optimal temperature range for the battery pack to operate is from15 to
30℃.
Do not expose or place near water sources like downspouts or sprinklers.
If the battery pack is mounted in the garage, then ensure that it is above the
height of the vehicle bumper and/ or door.
Mounting Structure Requirements
The mounting structure where the product is mounted must be fireproof.
Do not mount the product on flammable building materials.
Ensure that the mounting surface is solid enough to bear the weight load.
In residential areas, do not mount the product on drywalls or walls made of
similar materials which have a weak sound insulation performance because the
noise generated by the product is noticeable.
Mounting Angle and Stack Requirement
SMILE-B3-PLUS and SMILE-BAT-5P should be mounted on the wall.
The installation angle requirement is as follow:
- Do not mount the product at forward tilted, side tilted, horizontal, or upside down positions.Mounting Space Requirements
- Reserve sufficient clearance around the product to ensure sufficient space for installation, maintenance and heat dissipation.
6.2 Preparing Tools and Instruments
6.3 Mounting Inverter and Expansion Battery Pack
WARNING
Risk of injury due to weight of product
Injuries may be caused if the product is lifted incorrectly or dropped while
being transported or mounted.
Transport and lift the product carefully. Take the weight of the product into
account.
Wear suitable personal protective equipment for all work on the product.
CAUTION
Risk of injury due to damaged cables
There may be power cables or other supply lines (e.g., gas or water) routed in
the wall.
Ensure that no lines are laid in the wall which could be damaged when drilling
holes.
6.3.1 Mounting the SMILE-B3-PLUS
Dimensions of wall bracket (mm) The steps to mount the SMILE-B3-PLUS are
listed below:
-
Remove the wall bracket from SMILE-B3-PLUS, place it on the wall where the system will be installed, and use a marker to locate the bracket.
NOTE:
Considering the battery expansion, the bottom of the wall bracket should be at least 500 mm above the ground. -
Drill 8 holes on the wall with Φ10mm drill and insert 8 screw anchors into the drill holes.
-
Attach the wall bracket to the wall and tighten the screws with the tool of SW10 hexagon sleeve.
-
Hold the handles on both sides of the inverter and install SMILE-B3-PLUS on the wall bracket. This step should take two people to complete.
-
Tighten the wall bracket and SMILE-B3-PLUS with screw M6*16 (X6) (tool: T20 screwdriver, torque: 3.0 Nm).
-
Install the holders for cable box cover (tool: T20 screwdriver, torque: 2.5 Nm)
-
Perform electrical connection work (please refer to Section 7 Electrical Connection).
6.3.2 Mounting the Expansion Battery Pack
You can install up to 5 extra batteries in a system.
The steps for expanding the battery is as below. Expansion wiring refer to
chapter 7.7.
NOTE:
If there are no expansion batteries to install, please ignore Chapter 6.3.2
and skip to 6.3.3.
- Take out the expansion brackets and the battery wall bracket, then fix them together with four M4 flange nuts (tools: SW7 sleeve or other tools for M4 flange, torque: 1.6 Nm).
- Use two M4 flange nuts to fix the wall bracket assembled in the step 1 to the wall bracket of SMILE-B3-PLUS (tools: SW7 sleeve or other tools for M4 flange, torque: 1.6 Nm).
- Mark the points according to holes on the bracket and remove the assembled wall bracket.
- Drill 6 holes on the wall with Φ10mm drill and insert 6 screw anchors into the drill holes.
- Use four M4 flange nuts to fix the wall bracket assembled in the step 1 to the wall bracket of SMILE-B3-PLUS again (tools: SW7 sleeve or other tools for M4 flange, torque: 1.6 Nm).
- Attach the wall bracket for expansion to the wall by tightening the screws with SW10 hexagon sleeve.
- Hold the handles on both sides of the battery pack and install the battery pack on the wall bracket. This step should take two people to complete. (Please install the expansion battery by pushing it from the side)
- Tighten the wall bracket and the battery pack with screw M6*16 (X4) (tool: T20 screwdriver, torque: 3.0 Nm).
- Remove the rubber plugs from the battery, and then remove the front cover after unscrewing screws with T20 screwdriver.
- Remove the cable box cover by unscrewing the screws at the top of the inverter by hand and perform electrical connection work (please refer to Chapter 7.7).
6.3.3 Mounting the WiFi Module
- Remove the WiFi cover from the top of the inverter with Torx 20 screwdriver.
- Tighten the WiFi module on the top of SMILE-B3-PLUS.
Electrical Connection
Precautions
DANGER
Before connecting cables, ensure that all breakers of the SMILE-B3-PLUS and
the battery pack and all the switches connected to SMILE-B3-PLUS and the
battery pack are set to OFF. Otherwise, the danger voltage of the product may
result in electric shocks.
WARNING
The device damage caused by incorrect cable connections is not covered under
any warranty.
Only certified electricians are allowed to connect cables.
Operation personnel must wear proper PPE when connecting cables.
NOTICE
The cable colors shown in the electrical connection diagrams provided in this
chapter are for reference only.
Select cables in accordance with local cable specifications (green-and-yellow
cables are only used for PE).
7.1 Overview of the Connection Area
Position | Designation |
---|---|
1 | Battery breaker* of battery pack |
2 | Power button of battery pack |
3 | BAT+ connection port |
4 | BAT- connection port |
5 | BMS Communication connectors |
6 | Grid connection port |
7 | Backup connection port ; |
8 | Connection point for an additional grounding |
9 | Communication port(CAN/RS485,BMS, LAN, Meter/Grid-CT, DRM**, PV-CT, AUX) |
10 | Battery breaker* of SMILE-B3-PLUS |
11 | Connection port for the WiFi module |
*All breakers of SMILE-B3-PLUS are switched off when shipped.
**The DRM is only for regions with AS/NZW 4777.2 safety regulations.
The following table is about DRM interface definition, only for Australia.
Mode | Requirement |
---|---|
DRM0 | Operate the disconnection device |
DRM1 | Do not consume power |
DRM2 | Do not consume at more than 50% of rate power |
DRM3 | Do not consume at more than 75% of rate power AND Source reactive power |
if capable
DRM4| Increase power consumption (subject to constraints from other active
DRMs)
DRM5| Do not generate power
DRM6| Do not generate at more than 50% of rate power
DRM7| Do not generate at more than 75% of rate power AND Sink reactive power
if capable
DRM8| Increase power generation (subject to constraints from other active
DRMs)
7.2 Preparing Cables
No| Cable| Type| Conductor Cross
Section Area Range| Outer
Diameter| Source
---|---|---|---|---|---
1| Battery power cable| Standard PV cable in the
industry (recommended
type: PV1-F)| 16 mm2| 13-18 mm| Delivered with the battery pack
2| Battery communication
cable| Standard network cable in the industry (recommended type: Cat5e, UTP,
UV-resistant
for outdoor use)| 0.12 ~ 0.2 mm2
(AWG26~AWG24)| 6-12 mm| Delivered with the
battery pack
3| CT communication
cable| Standard network cable in the industry (recommended type: Cat5e, FTP,
UV-resistant for outdoor use)| 0.12 ~ 0.2 mm2
(AWG26~AWG24)| N/A| Delivered with the
battery pack
4※1| Signal cable| Standard network cable in the industry (recommended type:
Cat5e, FTP, UV-resistant
for outdoor use)| 0.12 ~ 0.2 mm2
(AWG26~AWG24)| N/A| Purchased by the installer
5※2| Signal cable| Multiple-core outdoor
shielded twisted pair cable| 0.1 ~ 1.3 mm2| N/A| Purchased by the installer
6| Grid power cable| Three-core (L, N and PE)
outdoor copper cable| 4 ~ 6 mm2| 4 ~ 6 mm| Purchased by the installer
7| Backup power cable| Three-core (L, N and PE)
outdoor copper cable| 2.5 ~ 6 mm2| 4~6 mm| Purchased by the installer
8| PE cable| Single-core outdoor
copper cable| 6 ~ 10 mm2| N/A| Purchased by the installer
※1 For CAN/RS485, LAN, Meter, DRM communication connection with inverter.
※2 For AUX communication connection with inverter
7.3 Connecting Additional Grounding
An external grounding connection is provided at the left side of the
SMILE-B3-PLUS.
Prepare M5 OT terminals, strip the grounding cable insulation, insert the
stripped part of the grounding cable into the ring terminal lug and crimp
using a crimping tool.
Connect the OT terminal with ground point using the torque is 2.5 Nm with T20
screwdriver. Connect the expanded battery to the ground point of SMILE-B3-PLUS
with the grounding cable. 7.4 AC Connection
7.4.1 Conditions for the AC Connection
AC breakers must be installed on the AC side of the SMILE-B3-PLUS to ensure
that the system can be safely disconnected from the power grid and the load.
DANGER
Danger to life due to fire!
You must protect each SMILE-B3-PLUS with an individual AC circuit breaker in
or-der to ensure that the system can be disconnected safely.
Do not connect loads between the SMILE-B3-PLUS and the grid breaker.
For load switching, please use dedicated circuit breakers with load switch
function. The selection of the AC circuit breaker rating depends on the wiring
design (wire cross section area), cable type, wiring method, ambient
temperature, inverter current rating, etc.
Derating of the AC circuit breaker rating may be necessary due to self-heating
or if exposed to heat.
The maximum AC current of SMILE-B3-PLUS can be found in the following table.
We recommend the following AC circuit breaker for AC connection.
Description | Max Current | Recommend AC Circuit Breaker Rating |
---|---|---|
Grid side | 26A | 40A |
Backup side | 13A | 25A |
7.4.2 Grid and Backup Connection
There are two AC terminal blocks for grid and backup connection which have the
same installation steps.
Following cable requirements for AC connection are recommended.
Description | Value |
---|---|
Cable diameter | 9-16 mm |
Copper conductor cross section area range | 4~6 mm2 |
Stripping length of the insulated conductors | 10~12 mm |
- Take out the cord end terminals and remove AC connection cover from SMILE-B3-PLUS.
- Lead the AC cable through the cable gland of the AC connection cover, don’ t tighten the pressure cap of the cable gland.
- Dismantle the AC cable by 80mm, and strip the insulation of L, N and PE conductors by 10mm.
- Insert the stripped part of the conductors into the cord end terminals and crimp them by using a crimping tool.
- Fix the terminals with different color conductors on the corresponding electrode holders, and use a #2 Phillips screwdriver to tighten them one by one with a torque of 2 Nm.
- Place the AC connection cover against the inverter and tighten it.
NOTICE
For Australia and New Zealand installation site, the neutral cable of grid
side and backup side must be connected together, otherwise backup output
function will not work.
Residual Current Protection
The inverter is equipped with an all-pole sensitive residual current
monitoring unit (RCMU) with an integrated differential current sensor which
fulfills the requirement of DIN VDE0100-712(IEC60364-7-712:2002).
Therefore, an external residual current device (RCD) is not required. If an
external RCD needs to be installed because of local regulations, a RCD type A
or type B can be installed as an additional safety measure.
The all-pole sensitive residual current monitoring unit (RCMU) detects
alternating and direct differential currents. The integrated differential
current sensor detects the current difference between the neutral conductor and
the line conductor. If the current difference increases suddenly, the inverter
will disconnect from the grid. The function of the all-pole sensitive residual
current monitoring unit (RCMU) has been tested according to IEC62109-2.
Notice of installing an external residual current device (RCD) for installa-
tion of Australia and New Zealand
Where an external residual current device (RCD)is required in a TT or TN-S
sys-tem, install a residual current device which trips at a residual current
of 30 mA.
7.5.1 CT Connection
7.5 Meter & CT Connection
The CT cables have been installed with SMILE-B3-PLUS when shipped.
Please take out 2 CTs (Grid CT and PV CT) provided as accessory.
Step 1: Buckle the Grid CT on the house-service live wire. The arrow of the
Grid CT should point to the Grid port of SMILE-B3-PLUS.
Step 2: Buckle the PV CT on the grid live wire. The arrow of the PV CT should
point to the Grid port of PV inverter.
Step 3: Connect the CT cables to the Grid CT and PV CT respectively.
NOTE:
The CT cable marked Grid CT should be connected to the Grid CT, and the CT
cable marked PV CT should be connected to the PV CT. Meter Setting
Model | Grid Meter Address | PV Meter Address |
---|---|---|
DTSU666-3*230V 5A (with-out CT) | 1 | 2 |
DTSU666-100/40mA (with CT) | 1 | N/A |
-
DTSU666-3*230V 5A: Three-phase meter (without CT)
When the meter is used as Grid meter, please follow the steps below to complete the address setting.When the meter is used as PV meter, please follow the steps below to complete the address setting. -
DTSU666-100/40mA: Three-phase meter (with CT)
When the meter is used as Grid meter, please follow the steps below to complete the address setting.
Meter Setting on AlphaCloud
Step 1
When the system work mode is selected as DC, click the button under the “Grid
Me-ter” to turn the “Meter” icon green.
When the system work mode is selected as AC or Hybrid, click the buttons under
the “Grid Meter” and “PV side meter” to turn the “Meter” icon green.
Step 2
Click “Save” and wait a few minutes to refresh the page.
When the “Meter Model” displays DTSU666 model, the setting is successful.
NOTE:
It is forbidden to tick CT to modify the CT ratio. Meter Setting on AlphaAPP
Step 1
When the system work mode is selected as DC, only tick “Meter” icon on the
right of the “Grid Meter”.
When the system work mode is selected as AC or Hybrid, both tick “Meter” icon
on the right of the “Grid Meter” and “PV side meter”.
Step 2
Click “Submit” and enter the “System information” page to check the meter
model. When the “Meter Model” displays DTSU666 model, the setting is
successful.
NOTE:
It is forbidden to tick CT to modify the CT ratio.
7.5.2 Meter Connection (Optional)
The system supports the following two different metering schemes in order to
record the feed-in energy and consumption from grid:
- DTSU666-3*230V 5A: Three/single-phase meter (without CT)
- DTSU666-100/40mA: Three/single-phase meter (with 3 or 6 CTs)
Meter wiring introduction
Loosen the waterproof connectors on the COM connection cover, and then remove
the screws on the COM connection cover.
- DTSU666-3*230V 5A: Three/single -phase meter (without CT) connection
- DTSU666-100/40mA: Three/single-phase meter (with CT) connection
Grid CT | PV CT |
---|---|
1——–IC (White) | 31——–IC (White) |
3——–IC (Blue) | 33——–IC (Blue) |
4——–IB (White) | 34——–IB (White) |
6——–IB (Blue) | 36——–IB (Blue) |
7——–IA (White) | 37——–IA (White) |
9——–IA (Blue) | 39——–IA (Blue) |
7.6 Communication Connection
For other communication (AUX, DRM, Meter, CAN/RS485) connection, please follow
the below steps.
Loosen the waterproof connectors on the COM connection cover, and then remove
the screws on the COM connection cover.
Communication connection port as follows:
- Lead the communication cables through the cable glands of the COM connection cover, don’t tighten the pressure caps of the cable glands. Insert the RJ45 plugs to the relative RJ45 sockets.1) For meter wiring, please refer to Chapter 7.4.4 Meter Connection.
- If DRM support is specified, the system may only be used in conjunction with
a Demand Response Enabling Device (DRED). This ensures that the system im-
plements the commands from the grid operator for active power limitation at
all times. The system and the Demand Response Enabling Device (DRED) must be
connected in the same network.
Only DRM0 is available for SMILE-B3-PLUS. - Take out 6 pin terminal block for AUX connection. Tighten them one by one
us-ing the torque of 0.2 Nm with tool of #0 slotted screwdriver.
For AUX position definition, please see the AUX wiring documentation.
- Place the COM connection cover against the inverter housing and tighten them.
7.7 Electrical Connection of Expansion Battery Packs
-
Remove the terminal resistance from the battery and insert it into the BMS communication port of the last battery (the battery furthest from the inverter).
-
Connect the positive power cable from battery 2 to battery 1 (tool: T20 screwdriver, torque: 3 Nm).
-
Connect the negative power cable from battery 2 to battery 1 (tool: T20 screwdriver, torque: 3 Nm).
-
Connect the BMS communication cables from battery 2 to battery 1.
-
Assemble front cover and side cover of the expanded battery with 3 M4 flange nuts (tools: SW7 sleeve or other tools for M4 flange, torque: 1.6 Nm).
-
Attach the cover to the battery pack.
Fasten the cover on the battery with screws in sequence 1-7 and screw M5*12 (X4) (tool: T20 screwdriver, torque: 2.5 Nm).
NOTE:
Seven screws should be pre-locked and then fastened together at the end. -
Insert the rubber plugs of the battery.
7.8 Mounting the Cable Box Cover
Take out the cable box cover which is provided as accessory.
- Insert the wire shield in the order shown by the arrow as shown in Figure 1 until the wire shield is installed in place as shown in Figure 2.
- Fix the cable box cover by tightening the screws by hand.
WiFi Setting
8.1 Download and Install APP
- Android device users can download the application through major Android application markets such as Google Play.
- IOS device users can search for “AlphaESS” in Appstore and download the application.
http://www.alphaess.com/app/download.html
8.2 Overview of Functions for Installer Account 8.3 WiFi Module Setting
This section is for users who have a system with a WiFi module.
AlphaESS App is able to complete network configuration, change setting of the
system basic parameter, and monitor system operation and configuration
information. Step 1: Open AlphaESS APP, click the “Wi-Fi Configuration” button
and enter the WiFi configuration interface. Step 2: After that, please check
whether your mobile phone has connected to the system’s hotspot.Step 3: If your
mobile phone hasn’t connected to the system’s hotspot, please open the Wi-Fi
network list and find the hotspot named by the product SN, then enter the
password “12345678” and connect to it. After successfully setting it, please
go back to the APP and click “Next”.Step 4 Select the WiFi of your home, enter
the password, complete the WiFi configuration and submit. If there is no
network currently, you can click Jump over to skip the WiFi configuration step
and directly set the system parameters.
NOTE:
The system will not be able to connect to the Internet without WiFi
configuration.
Step 5 Set basic parameters, including PV capacity on the grid side, the type
of meters, safe-ty regulations and regional application standard. Click
“Submit” when the settings are complete.
Please set the safety standard appropriate for your country or purpose via APP
or Web during pilot run;
The safety standard must be set correctly
If you select a safety standard which is not valid for your country and
purpose, it can cause a disturbance in the energy storage system and lead to
problems with the grid operator. When selecting the safety standard, you must
always observe the locally applicable standards and directives as well as the
properties of the PV system (e.g. PV system size, grid-connection point).
- If you are not sure which safety standard is valid for your country or purpose, con-tact your grid operator for information on which safety standard is to be configured.
NOTE:
When the safety regulation is set as AS4777.2, the secondary sub-options can
be selected according to the region or local grid company (Please refer to
Appendix 2).
Commissioning
9.1 Checking Before Power-On
No. | Check Item | Acceptance Criteria |
---|---|---|
1 | Mounting environment | The mounting space is proper, and the mounting |
environment is clean and tidy, without foreign object.
2| Battery pack and inverter mounting| SMILE-B3-PLUS and expansion battery
packs are mounted correctly, securely, and reliably.
3| WiFi mounting| The WiFi module is mounted correctly, securely, and reliably
4| Cable layout| Cables are routed properly as required by the customer.
5| Cable tie| Cable ties are secured evenly and no burr exists.
6| Grounding| The ground cable is connected correctly, securely, and reliably.
7| Switches and breakers status| The battery switches and all the breakers
connecting to the product are OFF.
8| Cable connections| The AC cable, battery cable, and communication cables
are connected correctly, securely, and reliably.
9| Unused power terminals| Unused cable glands are blocked by rubber sealings
which are secured by pressure caps.
9.2 Check the Running State
Prerequisites
Before switching on the AC breaker between the inverter and the grid, check
that the AC voltage on the power grid side of the AC breaker is within the
specified range.
Please select the acceptance of installation on site when the light intensity
is strong.
Procedure
-
Ensure that the battery switches and all breakers connecting to the product are OFF.
-
Check the grid-connected state of the product and the installation of two CTs.
Short press the power button on the right side of battery pack, then switch on the battery breaker .
Switch on the breaker located at the middle left of SMILE-B3-PLUS.
Switch on the external AC breaker between the grid and SMILE-B3-PLUS.
Switch on PV and PV Inverter.
Set the operating parameters through the APP.
Wait about 3 minutes for the SMILE-B3-PLUS and the PV Inverter to enter the grid-connected status, and observe the LED states on the front panel. At this time, the 2 LEDs (“Normal”, “COM”) and battery indictors on the front panel will show green always.
Check the running status through the APP.
When PV power is not more than 3kW, PV supplies power to the battery and load. If the grid power is not more than 100W in this scenario, then the installation is normal. -
Check the UPS status of the product
Switch off the external AC breaker between the grid and the SMILE-B3-PLUS.
The SMILE-B3-PLUS will enter the UPS status at once, and observe the LED states on the front panel. At this time, the following 2 LEDs (“Normal”, “COM”) and battery indictors on the front panel will show green always.
NOTICE
During the running test , if the “Fault” LED indictor of the inverter or LED
indictors of the battery pack show red, please refer to Section 10.2 for
troubleshooting.
9.3 Powering Off the Product
WARNING
After the product is powered off, the remaining electricity and heat may still
cause electric shocks and body burns. Therefore, put on protective gloves and
operate the product 5 minutes after the power-off.
Procedure
- Long press the power button of battery pack for 6 seconds, then switch off the battery breaker of battery pack.
- Switch off the battery breaker located at the middle left of the inverter.
- Switch off the AC breaker between the SMILE-B3-PLUS and the load.
- Switch off the AC breaker between the SMILE-B3-PLUS and the grid.
Maintenance and Troubleshooting
10.1 Routine Maintenance
Normally, SMILE-B3-PLUS need no maintenance or calibration.
Disconnect SMILE-B3-PLUS from all power sources before cleaning. Clean the
housing, cover and display with a soft cloth.
To ensure that the SMILE-B3-PLUS can operate properly in the long term, you
are advised to perform routine maintenance on it as described in this chapter.
Maintenance checklist
Check Item | Acceptance Criteria | Maintenance Interval |
---|---|---|
Product cleanliness | The heatsink at the back of SMILE-B3-PLUS are free from | |
obstacles or dust. | Once every 6 to 12 months | |
Product visible damage | The SMILE-B3-PLUS are not damaged or deformed. | Once |
every 6 months
Product running status| 1.SMILE-B3-PLUS operate with no abnormal sound.
2.All parameters of SMILE-B3-PLUS are correctly set. Perform this check when
SMILE-B3-PLUS is running.| Once every 6 months
Electrical connections| 1.Cables are securely connected.
2.Cables are intact, and in particular, the cable jackets touching the
metallic surface are not scratched.
3.Unused cable glands are blocked by rubber sealing which are secured by
pressure caps. commissioning.| Perform the first maintenance 6 months after
the initial
From then on, perform the maintenance once every 6 to 12 months.
CAUTION
Risk of burns due to hot heatsink and housing of the inverter The heatsink
and housing can get hot during operation.
During operation, do not touch any parts other than the cover.
Wait approx. 30 minutes before cleaning until the heatsink has cooled down.
10.2 Troubleshooting
10.2.1 Inverter Error Troubleshooting
Inverter LED Signals
LED Indictor | Status | Description |
---|---|---|
Normal | On: system is in working mode normally | |
Flicker: system is in standby mode or self-checking process | ||
On: network connection is normal | ||
Fault | Flicker: connecting to the server | |
Off: system is not connected network | ||
COM | Off: system is in fault mode or off | |
Off: system is in working mode normally or off | ||
On: system is in fault mode | ||
Description | Solution | |
--- | --- | --- |
Warning | Grid AC over voltage | 1. If these warnings occur occasionally, it is |
a short-time fault
of the grid. The inverter will resume work after the grid is
normal. No action is required.
2. If these warnings occur frequently but can be automatically
cleared, contact the local power operator for permission and modify
the grid protection parameters of the inverter.
3. If the recovery fails for a long time, please confirm:
- Whether the AC circuit breaker is switched off.
- Whether the AC terminal is in good contact
- Whether the grid is disconnected.
Grid AC under voltage
Grid AC absent
Grid AC over frequency
Grid AC under frequency
Grid abnormal
Inverter over tempera-ture| 1. If the warning occurs occasionally and the inverter can
resume work automatically. No action is required.
2. If this warning occurs frequently or continuously, check
whether the installation site is exposed to direct sunlight,
with good ventilation and high ambient temperature. If
there is no direct sunlight and there is good ventilation and
heat dis-sipation, please contact AlphaESS after-sales team.
Ground disconnection alarm| Please check whether the grounding cable is connected
properly.
| Description| Solution
---|---|---
Warning| Zero firewire reverse alarm| Please check whether the live line and neutral line are inversely connected.
NTC fail| Please check whether the cable connection to the NTC terminal is loose.
Battery voltage very high| If the warning occurs at the first installation, please check whether the battery voltage is within the allowable range. If this warning occurs during operation, check whether the
battery cable is loose and whether the BMS communication is abnormal.
Eps capacitance decrease| If the warning occurs occasionally, please restart the system. If the warning still occurs after restart, please contact AlphaESS after-sales team.
Fault| Leakage current abnormal| 1.If this warning occurs occasionally, it may be caused by the occasional exception of the external line. When the exception disappears, the system will return to normal. No action is required.
2. If this warning occurs continuously, please contact AlphaESS after-sales team.
Control power low| 1.If this warning occurs occasionally, the inverter will resume work automatically. No action is required
2.If this warning occurs continuously, please contact AlphaESS after-sales team.
Output DC over current| 1.If the warning occurs occasionally, it is a short- time fault of the grid. The inverter will resume work after the grid is normal. No action is required.
2.If this warning occurs continuously, please contact AlphaESS after-sales team.
Inverter relay abnormal| 1.If the warning occurs occasionally, it is a short- time fault of the grid. The inverter will resume work after the grid is normal. No action is required
2.If this warning occurs continuously, please contact AlphaESS after-sales team.
Leakage current HCT abnormal| 1.If this warning occurs occasionally, it may be caused by the occasional exception of the external line. When the exception disappears, the system will return to normal. No action is required.
2. If this warning occurs frequently or cannot be cleared for a long time, please use a multimeter to measure the resistance between the Grid port, L, N and the ground. If the resistance are less than 100 Kg, please check whether cables are
damaged, connected, or flooded.
Bus over voltage| 1.If this warning occurs occasionally, please restart the inverter.
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
Internal communica- tion error| Please contact AlphaESS after-sales team.
EEPROM error| Please contact AlphaESS after-sales team.
| Description| Solution
---|---|---
Fault| Consistent warning| 1.If the warning occurs occasionally, please restart the inverter.
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
Inverter abnormal| 1.If this warning occurs occasionally, please restart the inverter.
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
Boost abnormal| 1.If this warning occurs occasionally, please restart the inverter.
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
Battery absent| 1.Check whether battery cables are connected properly;
2.Check whether the DC Switch is on ;
3.Check whether the BMS communication is normal.
EMS communication error| Check whether the connection terminal between the EMS board and the inverter control board is loose.
UPS overload| Please reduce the loads on the Backup port and restart the inverter, or wait for the warning to be cleared after 5 minutes .
EPS output short| Disconnect the loads on the Backup port and restart the inverter. If the problem is not been solved, please contact AlphaESS after- sales team.
Inv HW over current| 1.If the warning occurs occasionally, please restart the inverter.
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
Bus under voltage| 1.If this warning occurs occasionally, please restart the inverter.
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
Battery Over Total Voltage| If the warning occurs occasionally, check whether it is cleared after three minutes ;
If the warning occurs frequently, please contact AlphaESS after-sales team.
Battery Under Total Voltage
Inv over current| 1.If this warning occurs occasionally, please restart the inverter.
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
DC HW over current| 1.If this warning occurs occasionally, please restart the inverter;
2.If this warning occurs frequently or cannot be cleared for a long time, please contact AlphaESS after-sales team.
Battery Discharge over current| Please reduce the loads on the Backup port and restart the inverter, or wait for the warning to be cleared after 5 minutes .
10.2.2 Battery Protection Description
LED Ring| Protection Code| LED Display|
Description| Troubleshooting
---|---|---|---|---
Green LEDs
flash once every 3s.| 1| | Temperature difference| Wait for automated
recovery. In case the problem is not recovery for a long time, call for
service.
3| | High temperature| Stop discharging and charging until this code is
eliminated and wait for the temperature to drop.
4| | Low-tempera-ture discharge| Stop discharging until this code is
eliminated and wait for the temperature to rise.
5| | Overcurrent charge| Wait for automated recovery. In case the problem is
not recovery for a long time, call for service.
6| | Overcurrent discharge
8| | Cell overvoltage
9| | Cell under voltage| Stop discharging and call service immediately.
11| | Low temperature charge| Stop discharging until this code is eliminated
and wait for the temperature to rise.
NOTE:
In work mode, if the No. 9 protection code appears, please push the power
button of the battery 5 times within 10 seconds. The BMS will then be forced
to turn on the MOSFET of discharge so that the inverter will detect the
battery open voltage and charge the battery.
10.2.3 Battery Error Description
LED Indictor| Error Code| DispLEDlay| Description|
Troubleshooting
---|---|---|---|---
Red LEDs flash once every 3s.| Error 01| | Temperature sensor failure| Please
restart the battery. If the problem is not resolved, please call for service.
Error 05| | MOSFET error
Error 06| | Circuit breaker open| Switch on circuit breaker after powering off
the battery.
Error 08| | LMU disconnect (slave)| Reconnect the BMS communication cable.
Error 09| | SN missingry| Call for service.
Error 10| | LMU disconnect (master)| Reconnect the BMS communication cable.
Error 11| | Software ver-sion inconsistent| Call for service.
Error 12| | Multi master| After shutting down the battery system, please
restart all batteries within 30s.
Error 13| | MOS over temperature| Please power off the battery and turn on the
battery after about 2 hours.
Uninstallation & Return
11.1 Removing the Product
Procedure
Step 1: Power off the product by following instructions in Chapter 9.3 Powering
Off the Product.
Step 2: Disconnect all cables from the product, including communication
cables, battery power cables, AC cables, and PE cables.
Step 3: Remove the WiFi module.
Step 4: Remove SMILE-B3-PLUS from the wall bracket.
Step 5: Remove the mounting bracket.
11.2 Packing the Product
If the original packaging is available, put SMILE-B3-PLUS inside it and then
seal it using adhesive tape.
If the original packaging is not available, put SMILE-B3-PLUS inside a
suitable cardboard box and seal it properly.
11.3 Disposing of the Product
If SMILE-B3-PLUS service life expires, dispose of it according to the local
disposal rules for electrical equipment and electronic component waste.
**** Dispose of the packaging and replaced parts according to the rules at
the installation site where the device is installed.
Do not dispose SMILE-B3-PLUS with normal domestic waste.
Specification
12.1 Technical Data of SMILE-B3-PLUS
Model | SMILE-B3-PLUS |
---|
Battery (Inverter side)
Battery Type| Li-ion
Battery Voltage Range| 40 ~ 58 V
Maximum Charge/
Discharge Power| 3 kW
Maximum Charge/ Discharge Current| 60 A / 60 A
Communication| CAN
Output AC (Back-up side)
Rated output power| 3 kW
Max. Apparent Output Power| 3 kVA
Back-up Switch Time| <10 ms
Rated Output Voltage| L/N/PE, 230 V
Rated Frequency| 50/60 Hz
Rated Output Current| 13 A
THDv(@linear load)| 0.03
Input AC (Grid side)
Rated Input Voltage| L/N/PE, 230 V
Rated Frequency| 50/60 Hz
Rated Input Power| 6 kW
Max. Input Current| 26 A
Output AC(Grid side)
Rated Output Power| 3 kW
Max. Apparent Output Powe| 3 kVA
Phase| Single phase
Rated Grid Voltage| L/N/PE, 230 V
Grid Voltage Range| 180 ~ 270 V
Rated Grid Frequency| 50 / 60 Hz
Rating Grid Output Current| 13 A
Power Factor| >0.99 (0.8 leading – 0.8 lagging)
THDi| < 3%
Protection Class| l
Overvoltage category| lll
Efficiency (Inverter side)
Max Efficiency| >94.5%
Protection
Anti-Islanding Protec-tion| Integrated
Insulation Resistor Detection| Integrated
Residual Current Monitoring Unit| Integrated
Output Over Current Protection| Integrated
Output Short Protection| Integrated
Output Overvoltage Protection| Integrated
Battery Reverse Protection| Integrated
Battery Breaker| Integrated
Features
Communication| Terminal block
BAT Connection| Terminal block
AC Connection| LAN, WiFi (optional)
Warranty| 5 years standard
General Data
Dimensions(WHD)| LED
Display| IP65
Weight| 640725250 mm
Topology| 64 kg
Operation Temperature Range| Transformerless
Relative Humidity| -10 ~ +50 °C
Ingress Protection| 0 ~ 100%
Noise Emission| <30 dB(A) @1m
Cooling Concept| Natural convection
Max. Operation Altitude| 3000 m
Battery pack (SMILE-BAT-5P)
Battery Type| LFP (LiFePO4)
Weight| 48 kg
Dimension for One Pack (WHD)| 640345250 mm
Ingress Protection| IP65
Energy Capacity| 5.04 kWh
Usable Capacity| 4.79 kWh
DoD| 95%
Nominal Voltage| 48 V
Operating Voltage Range| 45 ~ 54 V
Internal Resistance| ≤ 20 mΩ
Max. Charging / Discharging Current*| 60 A
Operating Temperature Range| Charge:0<T<50℃ / Discharge:-10<T<50℃
Monitoring Parameters| System voltage, current, cell voltage, cell
temperature, PCBA temperature
BMS Communication| CAN and RS485 compatible
System
Grid Connection Standard| AS 4777.2, G98-1
Safety| IEC62040, IEC62619,
EMC Standard| EN61000-6-1/-2/-3/-4
Warranty| 5 Year product warranty,10 Year performance warranty
Transportation| UN38.3
- Max. charge/discharge current derating will occur related to temperature and SOC.
Appendix 1: Communication Connection Figure
Appendix 2: Regional Application Standard
Choose the correspond Regional Application Standard, the power quality modes
Volt-var and VoltWatt will running automatically. (Only for regions with
AS/NZW 4777.2 safety regulations).
Regional application Standard | Electric Company |
---|---|
Australia A | N/A |
Australia B | N/A |
Australia C | N/A |
Victoria | Ausnet Services |
Jemena
Citipower
Powercor
United Energy
Queensland| Energex
Ergon Energy
South Austra lia| SA Power
Networks
New South Wales| Ausgrid
Endeavour Energy
Essential Energy
Western Australia| Horizon Power
Western Power
Australian Capital Territory| Evoenergy
Northern Territory| NT Power and Water
Tasmania| Tas Networks
New Zealand| Vector
@AlphaEnergy Storage System
@AlphaESS
@alpha_ess
@AlphaESS
www.alpha-ess.com
Alpha ESS USA, Inc.
USA@alpha-ess.com
638 S Ahwanee Ter Sunnyvale, California,
94085 United States of America
Alpha ESS UK Co., Ltd
uk@alpha-ess.com
Drake House, Long Street, Dursley, gl11 4hh
References
- ESS | K-12 Education Staffing & Management Solution
- Verlag Matthias Ess: Verlag Matthias Ess
- ESS Stauder - Percha | Technik ist unsere Leidenschaft
- AlphaESS:Energy Storage Solutions-Battery Energy Storage System Company
- Home - Alpha ESS Stromspeicher & Batteriespeicher
- alpha-ess.it
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>