Smart Pump PCS11 Pump Controller Instruction Manual
- May 15, 2024
- Smart Pump
Table of Contents
Smart Pump PCS11 Pump Controller
Specifications
- Main technical characteristics of controller:
- Control functions: Double liquid level control, Pressure switch control, Temperature control
- Main technical data: Rated output power, Rated input voltage, Liquid level transfer distance
- Protection function:
- Dry run
- Pump stall
- Overload
- Open phase
- Under/Over voltage
- Phase reversal
- Main installation data:
- Working temperature
- Working humidity
- Degree of protection
- Installation position
- Unit dimensions (L x W x H)
- Unit weight (net)
Product Usage Instructions
Button & Operations
- START: Press to start the pump.
- STOP: Press to stop the pump.
- STOP then MODE: Display shows last five failure records.
- STOP then START: Display shows accumulative running time.
- MODE SET: Set mode.
Parameter Calibration
To calibrate the controller parameters:
- In Manual mode, press START and let the pump run normally.
- Hold START for approximately 5-10 seconds or press the STORE button on the mainboard with a yellow cap.
- The controller will make a sound (Di sound) indicating calibration completion.
Parameter Erasing
To erase parameters:
- Ensure the pump has stopped running.
- Hold STOP until the controller makes a sound (Di sound) indicating parameter erasure.
Frequently Asked Questions (FAQ)
-
Q: How do I adjust the application settings?
A: Turn off power to the controller, toggle switches to desired settings, then re-energize power. -
Q: When should parameter settings be adjusted?
A: Parameter settings should be adjusted after Auto calibration with the pump not running and the controller in manual mode.
Installation & Operation Manual
Pump Controller(PCS11 &31)
OVERVIEW
The Pump Controller(PCS11&31) abbreviated to PCS is a programmable control panel that is used to protect and control pumps. Primarily deep well submersible pumps, but also centrifugal; in-line; circulation and multistage pumps. The PCS has four general operating modes namely tank to tank; booster by pressure switch; drainage by sensor; timed pumping. The PCS ’s protection features are dry run; overload; stalled pump; over voltage; under voltage; open phase, phase reversal and thermal control.
BUTTON & OPERATIONS
BUTTON | OPERATION [MANUAL mode unless otherwise stipulated] |
---|---|
START | Pump should start if not running. |
STOP | Pump should stop if running. |
STOP then
MODE
| Display shows last five failure records.
STOP then
START
| Display shows accumulative running time.
MODE
SET
| [Parameter 012 set to 00] – Manual to Auto / Auto to Manual
[Parameter 012 set to 01] – All buttons locked in Auto mode. To deactivate hold “MODE” for 5sec. Pump will then stop, and controller will switch to manual mode.
To ensure pump and motor is protected it is essential to calibrate the controller parameters as
soon as pump is running to operational standards. Perform calibration after each installation or maintenance operation.
START| Parameter calibration:
In Manual mode press “START”, give the pump time to run as it would normally then hold “START” ( approximately 5-10 sec ) or press the “STORE” button (Button on mainboard with yellow cap). The controller will make a “Di” sound. The controller should now be calibrated to the current spec of the motor.
STOP| Parameter erasing:
Ensure pump has stopped running then hold “STOP” until the controller makes a “Di” sound. ( Hold for approximately 5-10 sec ). The controller should now be cleared of all calibrations.
SPECIFICATIONS
Main technical characteristics of controller
Control functions| Double liquid level control
Pressure switch control
Temperature control
Main technical data
Rated output power| Refer to label on controller
Rated input voltage| Refer to label on controller
Liquid level transfer distance| ≤200m
Protection function| Dry run| Pump stall
Overload| Open phase
Under/Over voltage| Phase reversal
Main installation data
Working temperature| -25°C – +55°C
Working humidity| 20% – 90% Relative Humidity
Degree of protection| IP65
Installation position| Vertical
Unit dimensions (L x W x H)| 270205130 mm
Unit weight (net)| 1.6 kg
APPLICATION SETTING
There are two different controllers namely the PCS and the PCS PT 100. The PCS
and PCS PT 100 function the same except that the PCS PT 100 has an additional
switch to toggle on for thermal sensing enabling the controller to read the
temperature through a thermal probe.
Whenever the controller is to be adjusted for application the power to the
controller needs to be off and only re-energized once the switches have been
toggled to the desired settings.
Application | 2 Pole Switch | Description |
---|---|---|
1 | 0 0 | Tank to tank. |
2 | 1 1 | Booster pump control by pressure switch. |
3 | 0 1 | Drainage by level sensor. |
4 | 1 0 | Timed start and stop. [Cancels out sensor terminal] |
1 Pole Switch (Option)
5| 1| Thermal control.
PARAMETER SETTINGS
PLEASE NOTE : Parameter settings should be adjusted after “Auto” calibration.
- To access parameter settings the controller should be in manual mode and the pump should NOT be running.
- Press and hold “MODE” for 5sec to enter the parameter menu.
- To enter a parameter, press the “MODE” button. This will display the current value for the parameter.
- To change the value, press the “START” or “STOP” buttons respectively to increase or decrease the value.
- To store the value and return to the main menu press the “MODE” button.
- To store all changes and exit the parameter menu either press the yellow button on the circuit board or hold the “MODE” button for 5 sec if yellow button is not on circuit board.
Para- meter | Description | Range | Default value |
---|---|---|---|
001 | Dry run protection trip amps. | 0.0 A | |
002 | Overload protection trip amps. | 26 A (0.75-7.5kW) 52 A (11-15kW) | |
003 | Stall protection trip amps. | 33 A (0.75-7.5kW) 66 A (11-15kW) | |
004 | Under voltage protection trip voltage. | 175 V (Single Phase) |
300 V (Three Phase)
005| Over voltage protection trip voltage.| | 253 V (Single Phase)
439 V (Three Phase)
006| Dry run protection trip response time.| 0 – 254 sec| 6 seconds
007| Dry run protection recovery time.| 0 – 254 min| 5 minutes
008| Timer function.| 00 – 01| 00 (Disabled) [01 Enabled]
009| Pump running time.| 0 – 254 min| 5 minutes (Only if Enabled)
010| Pump stop time.| 0 – 254 min| 5 minutes (Only if Enabled)
011| Pump stop timer under manual state.| 0 – 254 min| 0 minutes (0 =
inactive)
012| LCD & button operation lock function.| 00 – 01| 00 (unlocked) [01
locked]
013| Open phase & phase reversal protection.
[00 (open phase & phase reversal OFF)] [01 (open phase OFF, phase reversal
ON)] [02 (open phase ON, phase reversal OFF)] [03 (open phase & phase reversal
ON)]| 00 – 03| 03(parameter 013 only available for three phase)
The following parameters are only visible for thermal control when
connection with PT 100
The expansion module is equipped.
014|
- Pump start temperature.
- Pump will start below set temp.
| 0 – 100 °C| 35 °C
---|---|---|---
015|
- Pump stop temperature.
- Pump will stop above set temp.
| 0 – 100 °C| 45 °C
POWER WIRING DIAGRAMS
Single phase/Three phase input and output wiring.
NOTE: Sensor terminal block can be removed for ease of connection.
SENSOR WIRING DIAGRAMS
Remark :
The probe / sensor free in the water well as the Product has reliable and
automatic stop function against pump dry-run (dewatering), if it is used in
submersible pump for deep well, pipeline pump or other situations when it is
inconvenient to install lower liquid probe in the well, pump users can put
terminals ①、②、③in short circuit, which minimize the cost .
- Tank to tank.
- Booster pump control by pressure switch.
- Drainage by level sensor.
- Optional temperature control.
Pump Controller(PCS11&31)
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>