Our SMART PUMP condensate pump is designed as an automatic condensate removal pump for water dripping off an air conditioner evaporative coil. The pump is controlled by a float/switch mechanism which turns the pump on when approximately 2″ of water collects in the tank, and automatically switches off when the tank
drains to approximately 1″.
The SMART PUMP unit you have purchased is of the highest quality workmanship and material. It has been engineered to give you long and reliable service.
SMART PUMP are carefully packaged, inspected and tested to ensure safe operation and delivery. When you receive your pump, examine it carefully to determine that there are no broken or damaged parts that may have occurred during shipment. If damage has occurred, make notation and notify the firm that you purchased the pump from. They will assist you in replacement or repair, if required.
READ INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THE SMART PUMP. KNOW THE PUMP APPLICATION, LIMITATIONS AND POTENTIAL HAZARDS. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE! RETAIN INSTRUCTIONS FOR FUTURE REFERENCE. INSTALLATION AND CONNECTIONS ARE TO BE MADE BY A QUALIFIED PERSON.
SAFETY GUIDELINES

WARNING

DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE, ETC. DO NOT USE IN EXPLOSIVE ATMOSPHERES. PUMP SHOULD BE USED WITH LIQUIDS COMPATIBLE WITH PUMP COMPONENT MATERIALS. DO NOT HANDLE PUMP WITH WET HANDS OR WHEN STANDING ON A WET OR DAMP SURFACE, OR IN WATER.THIS PUMP IS SUPPLIED WITH A GROUNDING CONDUCTOR AND/OR GROUNDING

TECHNICAL DATA

  • Pump rating:110-240VAC 50/60Hz Single Phase
  • Max. water flow rate (@0m/ft): 40L / 10.6 US Gal / H
  • Max rec. head: 20m / 66ft
  • Max.suction lift: 1m / 3.3ft
  • Sound level: 19dB(A)@ 1m
  • Rated: Non-continuous
  • Class: II appliance
  • Safety switch: 3A normally closed
  • Max.water temperature :70℃ / 158°F
  • Inlet size: Ø 7.5mm / 19/64’’
  • Outlet size: Ø 7.5mm / 19/64’’
  • IP Protection: IP x 1
  • Thermal protection: √
  • Fully potted: √
  • Self priming: √

TYPICAL PERFORMANCE

Smart-Pump-Series-Mini-Box-Smart-Condensate-
Pump-1

PARTS IN THE BOX

Smart-Pump-Series-Mini-Box-Smart-Condensate-
Pump-2

PRODUCT SAFETY

  • CAUTION: The Pump has been evaluated for use with water only.
  • WARNING: Risk of electric shock. This pump has not been investigated for use in swimming pool or marine areas.
  • The means for isolation must be incorporated in the fixed wiring in accordance with wiring regulations.
  • Ensure this pump is disconnected from the mains supply before carrying out any adjustments or servicing.
  • If the cord is damaged, it must be replaced with a special cord or assembly available from the manufacturer or its service agent.
  • Do not run this pump dry.
  • Always ensure the metal magnet in the float is facing upwards.
  • Always ensure the reservoir is sitting flat and horizontal.
  • This Pump is ideal for most working and living environments. It is not recommended where the environment is oily or particularly dusty.
  • Acceptable for indoor use only.
  • Non-submersible pump.

INSTALLATION

Smart-Pump-Series-Mini-Box-Smart-Condensate-
Pump-4

Install a 1 amp inline fuse. The high-level safety switch should be wired to prevent the continued operation of the air conditioning unit in the event of this pump failing. IMPORTANT: This diagram is an example of how this pump could be installed and is therefore for reference only. All pump units must be installed by qualified engineers, who have assessed the set-up of the individual a/c unit.

  1. Pump unit
  2. Indoor unit
  3. Interconnecting Cables
  4. Outdoor unit
  5. POWER:
    (L)LIVE: Brown (N)NEUTRAL: BlueSmart-Pump-Series-Mini-Box-Smart-Condensate-
Pump-10

SERVICE INSTRUCTIONS

  1. Every six months the reservoir should be removed, clean the filter, float and reservoir thoroughly prior to reassembly . We recommend this is done in the Spring and the Autumn, using an anti-bacterial wash.
  2. Take great care to replace the float with the magnet facing upwards.

FAULT

Fault: Pump runs all the time

  1. Is the float positioned with magnet uppermost?
  2. Is the reservoir lid (sensor)located firmly onto the reservoir, with the float located inside the reservoir, around the sensor column?
  3. Is there sludge inside the reservoir, preventing float from resting on the bottom? (This may occur if pump has been in operation for some time without cleaning. Clean using an anti-bacterial wash.)

Please note:

  • After installation and during operation, if you notice air in the pipe between the reservoir and the pump, you have a siphoning problem. Follow advice in ‘Preventing Siphoning’ section.
  • The pump will only switch off when the float is at the bottom of the reservoir.

Fault: Pump stops and starts and makes a loud noise.

  • The water is siphoning back through the pump. Follow advice in ‘ Preventing Siphoning’ section.

Fault: Pump runs but does not pump any water.

  • Is there any air-leaks in the pipe running to the pump?
  • Check that reservoir and inlet tube are free of sludge and debris.

Fault: Pump isn’t operating at all.

  • Is power reaching the pump? Is it correctly wired?
    Is the voltage correct?

  • Is pump very hot? A thermal cut-out may have been activated to protect pump. This will automatically reset once pump has cooled down.

LIMITED WARRANTY

Your product is guaranteed to be in perfect condition when it leaves our factory. It is warranted against defective materials and workmanship for a period of 12 months from date of purchase by the user.
Any product that should fail for either of the above two reasons and is still within the warranty period will be repaired or replaced at the option of SMART PUMP as the sole remedy of buyer.
For our customers in the CONTINENTAL UNITED STATES: Please return the defective unit, postage paid, to the factory at 12201 NW 107th Ave. MEDLEY, FL 33178.
All defective products returned under warranty will
be fully inspected to determine the cause of failure before warranty is approved. For our customers located elsewhere; it is not economical, due to duties and freight, to return the pump to the factory for inspection. Please return the defective unit to any authorized distributor or dealer with a brief written explanation of the problem.
If there are no apparent signs of customer abuse, unit will be repaired or replaced. If dispute arises over replacement of the pump, the distributor or dealer is to segregate such items and hold for inspection by a representative of Smart Electric. or notify factory with details of the problem for factory disposition and settlement of warranty claim.

DISCLAIMER: THE FOREGOING WARRANTY IS AN EXCLUSIVE WARRANTY IN LIEU OF ANY OTHER EXPRESS WARRANTIES. ANY IMPLIED WARRANTIES (INCLUDING, BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE) TO THE EXTENT EITHER APPLIES TO A PUMP SHALL BE LIMITED IN DURATION TO THE PERIODS OF THE EXPRESS WARRANTIES GIVEN ABOVE.

Warranty will be VOID if any of the following conditions are found:

  1. Sealed motor housing opened.
  2. Product connected to voltage other than indicated on nameplate.
  3. Cord cut off to a length less than three feet.
  4. Pump allowed to operate dry (fluid supply cut off).
  5. Pump used to circulate anything other than water.
  6. Product abuse by customer.

Any oral statements about the product made by the seller, the manufacturer, the representatives or any other parties, do not constitute warranties, shall not be relied upon by the user and are not part of the contract for sale. Seller’s and manufacturer’s only obligation, and buyer’s only remedy, shall be the replacement and/or repair by the manufacturer of the product as described above.

NEITHER SELLER NOR THE MANUFACTURER SHALL BE LIABLE FOR ANY INJURY, LOSSOR DAMAGE, DIRECT, INCIDENTAL OR CONSEQUENTIAL (INCLUDING, BUT NOT
LIMITED TO INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR LOST PROFITS, LOST SALES, INJURY TO PERSON OR PROPERTY, OR ANY OTHER INCIDENTAL OR CONSEQUENTIAL LOSS), ARISING OUT OF THE USE OR THE INABILITY TO USE THE PRODUCT AND THE USER AGREES THAT NO OTHER REMEDY SHALL BE AVAILABLE TO IT.

Before using, the user shall determine the suitability of the product for the intended use, and user assumes all risk and liability whatsoever in connection therewith.Some states and countries do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state and country to country.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Smart Pump User Manuals

Related Manuals