FAGERHULT VTB Multilume Slim Instruction Manual

May 15, 2024
FAGERHULT

FAGERHULT VTB Multilume Slim

Product Specifications

  • Model: Multilume Slim VTB
  • Input Voltage: 220-240 V
  • Insulation: IP20 (Indoor use only), IP44
  • Manufacturer: Fagerhult Sweden

Product Usage Instructions

Connection and Installation

  • Before plugging in the mains voltage, ensure that the luminaire is connected properly. Basic insulation between mains and control wiring is essential for safe operation.

Replacement

  • The light source, control gear, and external cable should only be replaced by the manufacturer or their designated personnel.

Mounting

  • For optimal performance, install the luminaire in ventilated or unventilated spaces. Avoid covering the luminaire with insulating material to prevent overheating.

Maintenance

  • It is important to pass on all relevant information regarding installation and usage to users. Regular maintenance and inspections are recommended to ensure safe operation.

Frequently Asked Questions (FAQ):

Q: Can I replace the light source or control gear myself?

  • A: No, the light source, control gear, and external cable should only be replaced by the manufacturer or their designated personnel to maintain safety and warranty.

Q: Can I cover the luminaire with insulating material?

  • A: It is advised not to cover the luminaire with insulating material as it may lead to overheating. Always refer to the manufacturer’s guidelines for proper installation.

Q: Where can I find the manufacturer’s contact information?

  • A: The luminaire is manufactured by Fagerhult Sweden. For UK market inquiries, contact Fagerhult UK at 33-34 Dolben Street, London, SE1 OUQ.

Dimension

Multilume Slim VTB

Multilume Slim Organic Response

Multilume Slim HB

Multilume Slim TW & Organic Response VTB

Installation instructions LED

  • The product contains electronics that may be sensitive to electrostatic discharges (ESD) as well as mechanical stress.
  • To avoid damage, any open circuit board like LED modules should never be directly touched by hand or by a tool.
  • This is valid both during installation and normal maintenance.
  • A Pro lights mares with this replaced by the manufacturer or his designated person.

Products with an external driver

  • Some luminaires are for use with an external LED driver. If any other driver than standard is intended to be used it must be adapted for the luminaire.
  • It should be with corresponding functionality (constant current resp. constant voltage) and electrical parameters.

Insulation test

  • To avoid damaging the electronic ballast or other sensitive electronic devices, the phase and neutral must be connected before any insulation test (max 500V DC).
  • Automatic circuit breakers (MCB) and Residual current device (RCD)
  • Due to the high peak connection current MCB:s type C is recommended.
  • Peak-current-proof RCDs:s adapted for electronics are recommended. Normally a luminaire has a leakage current of 1 mA.

Luminaires for dimming

  • An amplifier may be required for long cable lengths or a large number of luminaires.
  • Digital technology permits cable lengths up to 250 meters.
  • Basic insulation between mains and control wiring.
  • Control voltage cables may be routed with mains cables if they are mains voltage insulated.
  • National regulations should be adopted. Control voltage cables for 1-10V are polarised (+/-) and must be connected correctly to all luminaires.
  • If pulse switching via a momentary push button is used, the connected luminaires must due to functional reasons be equipped with DALI drivers of the same brand!

Troubleshooting

  • No light? Check the supply voltage. Measure the voltage at the terminal in the luminaire.
  • For spotlights with track adapter: please check the positioning of the phase selector and the fixation to the track system.
  • According to REACH (EC 1907/2006) we are obliged to inform you that this product may contain a low concentration of Lead (Pb) CAS 7439-92-1.
  • Normal instructions for safe use apply, lead does not cause harm as it is incorporated in the chemical composition of the product and is not released in normal use.
  • Please contact reach@fagerhult.se for more information.
  • It is appropriate to give this information to the user of the installation.