EMERSON Rosemount 3410 Series Local Display Field Install Kit User Guide
- June 4, 2024
- Emerson
Table of Contents
EMERSON Rosemount 3410 Series Local Display Field Install Kit
Safety and approval information
This Rosemount product complies with all applicable European directives when
properly installed in accordance with the instructions in this manual. Refer
to the EU declaration of conformity for directives that apply to this product.
The EU declaration of conformity, with all applicable European directives, and
the complete ATEX Installation Drawings and Instructions are available on the
internet at www.emerson.com or through your local
Emerson support center.
Information affixed to equipment that complies with the Pressure Equipment
Directive can be found on the internet at http://www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if
national standards do not apply.
Other information
Full product specifications can be found in the product data sheet.
Troubleshooting information can be found in the user manual. Product data
sheets and manuals are available from the Emerson website at
http://www.emerson.com.
Return policy
Follow Emerson procedures when returning equipment. These procedures ensure
legal compliance with government transportation agencies and help provide a
safe working environment for Emerson employees. Emerson will not accept your
returned equipment if you fail to follow Emerson procedures. Return procedures
and forms are available on our web support site at Emerson.com, or by phoning
the Emerson Customer Service department.
Emerson Flow customer service
Email:
- Worldwide: http://flow.support@emerson.com
- Asia-Pacific: http://APflow.support@emerson.com
Telephone:
North and South America | Europe and Middle East | Asia Pacific |
---|---|---|
United States | 800 522 6277 | U.K. |
Canada | +1 303 527 5200 | The Netherlands |
666
| New Zealand| 099 128 804
Mexico| +41 (0) 41 7686
111
| France| 0800 917 901| India| 800 440 1468
Argentina| +54 11 4837 7000| Germany| 0800 182 5347| Pakistan| 888 550 2682
Brazil| +55 15 3413 8000| Italy| 8008 77334| China| +86 21 2892 9000
| | Central & Eastern| +41 (0) 41 7686
111
| Japan| +81 3 5769 6803
Russia/CIS| +7 495 981 9811| South Korea| +82 2 3438 4600
Egypt| 0800 000 0015| Singapore| +65 6 777 8211
Oman| 800 70101| Thailand| 001 800 441 6426
Qatar| 431 0044| Malaysia| 800 814 008
Kuwait| 663 299 01| |
South Africa| 800 991 390
Saudi Arabia| 800 844 9564
North and South America| Europe and Middle East| Asia Pacific
---|---|---
| | UAE| 800 0444 0684| |
Signal words and symbol
Pay special attention to the following signal words, safety alert symbols and statements:
Safety alert symbol
This is a safety alert symbol. It is used to alert you to potential physical
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
-
DANGER
Danger indicates a hazardous situation which, if not avoided, will result in death or serious injury. -
WARNING
Warning indicates a hazardous situation which, if not avoided, could result in death or serious injury. -
CAUTION
Caution indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. -
NOTICE
Notice is used to address safety messages or practices not related to personal injury.
Important
Important is a statement the user needs to know and consider.
Tip
Tip provides information or suggestions for improved efficiency or best
results.
Note
Note is “general by-the-way” content not essential to the main flow of
information.
Component disassembly
Local display field install kit includes
- A. LCD display board
- B. LCD display shroud
- C. Pan HD screw PH SEMS #6-32 X .38 M/S W/410 EXT 18-8 SST
- D. LCD module
- E. Cover – HSG LCD type FB100
- F. O-ring #2-245
- G. Backplane board 3410/3810
- H. Pan HD screw PH SEMS #6-32 X .88
Preassembled assemblies and parts:
- LCD display board, shroud, LCD module
- Cover – Housing (glass end cap) with O-ring— Backplane board
- Pan HD screws #6-32 X .88
Local display field install kit parts list
Item(1) | Quantity | Description |
---|---|---|
Preassembled: | ||
LCD display field install kit | ||
Item(1) | Quantity | Description |
--- | --- | --- |
A | 1 | LCD display board |
B | 1 | LCD display shroud |
C | 2 | Pan HD screw PH SEMS #6-32 X .38 M/S W/410 EXT 18-8 SST |
D | 1 | LCD module |
Preassembled: | ||
E | 1 | Cover – HSG LCD type FB100 |
F | 1 | O-ring #2-245 |
G | 1 | Backplane board 3410/3810 |
H | 4 | Pan HD screw PH SEMS #6-32 X .88 |
Check firmware version before powering off the meter
Application options:
- MeterLink
- AMS® Device Manager
- Field Communicator
- Requirements: Firmware Version 1.06 and Uboot Version January 31, 2013 or later
- If necessary to upgrade firmware
- Open MeterLink™ and connect to the meter
- Open an Internet browser
- Navigate to the Emerson website: emerson.com/Rosemount
- Use Quick Links and click MeterLink Registration and Download to access the latest firmware
- Go to MeterLink and use the Tools|Program Download menu to download a file to the meter. Click Open to display an Open Download File dialog. Select the desired file and click Open. MeterLink only downloads components that are different than what is currently installed in the meter.
Remove power to the equipment and remove transmitter electronics enclosure endcaps
- Remove endcap security seals, if installed, and security latches.
- Remove power from equipment before removing endcaps if possible and/or ensure explosive atmosphere is not present before opening the transmitter electronics enclosure.
- Unplug CPU Module terminal board connectors (TB-1 and TB-2).
- Unplug I/O Module, and Power Supply terminal board connectors.
- Pull the CPU and I/O Modules from the enclosure.
- A. CPU TB-2
- B. CPU TB-1
- C. I/O module connectors
- D. 24V loop power
- E. 10.4VDC – 36VDC power
Remove the backplane board
- A. Backplane board
- B. I.S. barrier board
- C. Power supply board
- Remove four screws with lock washers.
- Pull Backplane from housing.
- Remove Power Supply and I.S. Barrier boards from Backplane.
Disconnect the acquisition cable
- A. Acquisition cable
Component assembly
Backplane board with 14 pin connector
- A. 14 pin connector
- B. Backplane board
Note
Check existing 3410/3810 Series Backplane board minimum for 14 pin connector
(J8).
If equipped, use this board. If not, use board included with the Local Display
Field Install Kit.
- A. Acquisition cable
- Attach acquisition cable to backplane
- Tighten connector screws
Plug power supply board and I.S. barrier module onto backplane board with 14 pin connector
- A. I.S. barrier board
- B. Backplane board
- C. Power supply board
Plug local display board into the backplane 14 pin connector
- A. 14 pin connector
- B. Local display board
- Make sure LCD board is fully seated to backplane 14 pin connector.
Slide backplane, power supply, I.S. barrier module and local display module assembly into transmitter enclosure and fasten with 4 pan head screws.
- Make sure boards are aligned in the enclosure and I.S. barrier board is inside card cage key retainer.
- Use the long Pan HD Screws #6-32 X .88 provided with the kit.
Install endcap with sight glass
- Make sure endcap O-ring is installed.
Reinstall CPU module and I/O module in the enclosure
Install CPU module TB-1 and TB-2 and I/O module terminal connectors
- A. CPU TB-2
- B. CPU TB-1
- C. I/O module connectors
If explosive atmosphere is not present, connect the power supply terminal connectors and apply power to the unit
- A. 24V loop power
- B. 10.4VDC – 36VDC power
- Ensure all CPU LEDs are green
- A. CPU LEDs
- Observe Local Display startup sequence (see Observe local display startup sequence)
If explosive atmosphere is present, install endcaps and apply site power to equipment
- A. Endcap security latch
- Reinstall endcap security latches
- Apply site power
Note
If an explosive atmosphere is present and site power initializes the unit, a
Service technician should observe the Local Display startup sequence (see
Observe local display startup sequence).
Observe local display startup sequence
- A. Local display
- B. Startup sequence – All segments displayed
- Two seconds after power up, the “Rosemount” logo appears at the bottom of the LCD screen.
- The Checksum displays.
- Make sure all segments are displayed (all the segments will come on and stay on for about 4 seconds). Pay careful attention and make sure that all segments are functioning and no segments are missing.
- The Wait command displays, and then the four default Display Items scroll on the display.
Configure display items, measurement units, and scroll delay
Configuration applications options:
- MeterLink™ – Field Setup Wizard
- AMS® Device Manager
- Field Communicator
- Reference manuals:
- HART® Field Device Specification 3410 Series Gas Ultrasonic Meters— HART Field Device Specification 3810 Series Liquid Ultrasonic Meters— 3410 Series Gas Ultrasonic Meters Installation Manual
- 3810 Series Liquid Ultrasonic Meters Installation Manual
- 3812 Liquid Ultrasonic Meters Installation Manual
Reinstall wire security seals on the endcaps, if necessary
Installation complete
- A. 3410/3810 series transmitter with local display
For more information: www.emerson.com
©2022 Emerson. All rights reserved. Unauthorized duplication in whole or part
is prohibited. Printed in the USA.
The Emerson logo is a trademark and service mark of Emerson Electric Co. All
other trademarks are the property of their respective companies.