INFORMATION
The control panel complements the function of the heat pump and acts as a room thermostat. Parameters are edited by touching the selected symbol on the control panel screen.
INSTALLATION
The control panel is designed for mounting on the wall, inside the room and
should be mounted at a height allowing comfortable operation, typically 1.5 m
above the floor. To reduce temperature measurement disturbances, avoid
locations exposed to strong sunlight, with poor air circulation, near heating
equipment, and directly at the door and windows, typically 0.2 m from the edge
of the door (1).
The control panel installation should be done according to the following
guidelines.
Disconnect the mounting frame (2) from the back of room panel housing
**(3).
The frame is attached to the panel housing with latches. Use a flat
screwdriver to detach the frame.
Using sharp tool cut out hole (4) for the terminal blocks. Connect
transmission cable, connecting room panel with the control unit, to the
terminal blocks (5), as described on the plate. The cable connecting
control panel with the heat pump can be recessed in the wall or it can run
over its surface – in this case the cable should be additionally placed in the
cable channel (6).** The cable should not be routed near devices emitting
strong electromagnetic field.
Drill holes in the wall and use screws to fix the mounting frame in the chosen place of the wall, maintaining its proper position **(7).
Then attach the control panel to the mounting frame using latches.
To place the control panel on a flat surface, use a dedicated stand (8).
**
CONNECTIONS
The connection between the controller and the heat pump must be:
- 2×1 shielded and twisted wire (for Modbus communication), that must be connected to D+ and D- terminal blocks.
- The 12Vdc power supply has got red (12Vdc) and black (GND) wires in its output, that must be connected to e-LITE terminal blocks (5-12V and GND).