CHERUBINI A510083 Meta Double Switch 7 Instruction Manual

May 15, 2024
Cherubini

CHERUBINI logo A510083-A510084-A510090
META DOUBLE SWITCH 7CHERUBINI A510083 Meta Double Switch
7 Actuator with two independent 230V outputs

A510083 Meta Double Switch 7

EU declaration of conformity
CHERUBINI S.p.A. declares that the product is in conformity with the relevant Union harmonisation legislation: Directive 2014/53/EU, Directive 2011/65/EU.
The full text of the EU declaration of conformity is available upon request at the following website: www.cherubini.it.
Failure to comply with these instructions annuls CHERUBINI’s responsibilities and guarantee.
**** The crossed-out wheelie bin symbol indicates that the product must be collected separately from other waste at the end of its useful life. Therefore, users should deliver this product to appropriate waste collection points or return it to their dealers at the end of its service life. See your local authority’s regulations.
Adequate waste sorting for subsequent processing and environmentally compatible disposal helps to avoid possible negative effects on the environment and public health and promotes reuse and/or recycling of the materials used to make the equipment.

DEVICE DESCRIPTION

META Double Switch 7 is an ON/OFF control device designed to independently control two separate loads, suited for being controlled by both remote and local switches.
Similarly to the other META Serie 7 devices, it can be fully integrated into pre-existing systems and configured to associate configurable behaviors to a specific number of clicks, in full integration with the Z-Wave™ home automation ecosystem.
There are two versions of META Double Switch 7:
L version – controlled by Line signal;
N version – controlled by Neutral signal.
Each of the device versions indicated above can be supplied without meter functionalities.
Each of its two channels features an integrated consumption measurement device.
META Double Switch 7 also boasts the lowest energy consumption on the market. It is very easy to install and works with both momentary and toggle switch. At the same time, it is completely configurable so that it can adapt to the most varied needs while also being ready to be used without needing additional configurations in order to operate.
The device is equipped with contact protection technology (Zero Crossing) which reduces the electrical stress on the relay contacts and ensures a longer life. The open / closed switching of the device always occur when the instantaneous value of voltage is 0.
It operates in any Z-Wave™ network with other Z-Wave™/Z-Wave Plus™ certified devices and controllers from any other manufacturer. As a constantly powered node, the device will act as repeater regardless of the vendor in order to increase the reliability
of the network.
This device is a security enabled Z-Wave Plus™ product that is able to use encrypted Z-Wave Plus™ messages to communicate to other security enabled Z-Wave Plus™ products.
This device must be used in conjunction with a Security Enabled Z-Wave™ Controller in order to fully utilize all implemented functions.
CHERUBINI A510083 Meta Double Switch 7 - Integrated
Button

Integrated Button| 1 or 3 clicks to enter in Learn Mode
6 clicks to reset the system to manufacturer’s settings
2 clicks to enter in setup mode
---|---
Power Supply| 1 – Null
6 – Line
Input Switch| 2 – Input 2 Line signal/Null signal in version L/N
3 – Input 1 Line signal/Null signal in version L/N
Output| 4 – Output 2 Line referred to Null
5 – Output 1 Line referred to Null

TECHNICAL SPECIFICATIONS

Power supply 110 – 230 VAC ± 10% 50/60 Hz
Maximum Load on Relay >24 VDC
System temperature limitation 105 °C
Work temperature From -10° to 40° C
Power consumption < 260 mW in standby

< 480 mW with working load
< 700 mW with working load
Radio frequency| 868,4 MHz
Protection system| S2 Security
Maximum distance| Up to 100 m outdoor Up to 40 m indoor
Dimensions| 37x37x17 mm
Actuator element| Relay
Compliance| CE, RoHs
Electrical IP Rating| IP20

SAFETY INFORMATION

INFO: The device is designed to be installed in flush mounting junction boxes or close to the load to be controlled.
WARNING: The device must be installed by electricians qualified to intervene on electrical systems in compliance with safety requirements set out by the regulations in force.
DANGER: The device must be connected with a voltage of 230 VAC, before carrying out any operation, please make sure the power main switch is in OFF position.
DANGER: Any procedure requiring the use of the Integrated Button is related only to the installation phase and is to be considered a service procedure that must be performed by qualified personnel. This operation must be performed with all necessary precautions for operating in areas with a single level of insulation.
WARNING: Do not connect loads that exceed the maximum load permitted by the actuator element.
WARNING: All connections must be performed according to the electrical diagrams provided.
WARNING: The device must be installed in norm-compliant systems suitably protected from overloads and short circuits.

ELECTRICAL CONNECTIONS DIAGRAM

The device must be supplied by phase and neutral.
There are two versions of META Double Switch 7 available, in order that you can choose the most suitable for your electrical system:

  • Version N: used in systems that require to be controlled by Neutral signal
  • Version L: used in systems that require to be controlled by Line signal
  • Both version N and version L can be connected in a VDC system.

Connections must be made according to one of the diagrams below.CHERUBINI
A510083 Meta Double Switch 7 - diagrams WARNING: The line must be properly protected from overloads and short circuits related to a possible failure of the loads connected to the output O1 and O2.

DEVICE INSTALLATION

  1. Make sure the main switch is set to the OFF position
  2. Connect the device based on the diagrams provided
  3. Turn the main switch to the ON position
  4. Include the device in the Z-WaveTM network

TIP: The antenna must not be shortened, removed or modified. To ensure maximum efficiency, it must be installed as shown. Large size metal equipment near the antenna can negatively affect reception. Each device is a node in a mesh network. If there are metal obstacles, the obstacle can often be overcome with a further triangulation node.

LED STATUS INDICATOR

The system includes an RGB LED that shows the device’s status during installation:
Solid RED: the device is not included in any network
Solid BLUE : the device is Offline setup mode
4 GREEN blinks then OFF: the device has been just added to a Z-WaveTM network in S2 Authenticate Mode
4 BLUE blinks then OFF: the device has been just added to a Z-Wave TM network in S2 Unauthenticated Mode
4 RED blinks then OFF: the device has been just added to a Z-Wave TM network without security
Sequence of GREEN-BLUE Learn Mode for inclusion
Sequence of RED-BLUE Learn Mode for exclusion
Rapid sequence of GREEN-BLUE-RED: the event on the input (external switch) is not valid.
TIP: To test if the electrical connections are correct, before the inclusion of the device, while pressing n times the external switch, the RGB LED should flash green for the same amount of times. If it does not, check the wire connections.

ADD/REMOVE THE DEVICE INTO A Z-WAVE TM NETWORK (classic)

Standard Inclusion (add)
All META Serie 7 devices are compatible with all Z-WaveTM /Z-Wave PlusTM certifiedcontrollers. The devices support both the Network Wide Inclusion mechanism (whichoffers the ability to be included in a network, even if the device is not directly connected
to the controller) and Normal Inclusion.
By default, the inclusion procedure starts in Normal Inclusion mode and after a short timeout the procedure continues in Network Wide Inclusion mode that lasts for about 20 Seconds.
Only a controller can add the device into the network. After activating the inclusion function by the controller, the device can be added by setting it in Learn Mode.
Before including the device, the LED status indicator is solid RED. The adding of a device is executed by activating the adding procedure in the inclusion section of the controller interface and then executing 1 or 3 click on the integrated button. As soon as the inclusion procedure initiates the LED indicator starts a sequence of GREENBLUE blinks. The device is included in the network when the LED status is OFF and the interview is completed.
Standard exclusion (remove)
Only a controller can remove the device from the network. After activating the exclusion function by the controller, the device can be removed by setting it in Learn Mode.
The procedure of exclusion can be activated by Removing a node from the Z-WaveTM network and executing 1 or 3 click on the integrated button; as soon as the exclusion initiates, the LED indicator starts a sequence of RED-BLUE blinks. The device is excluded
from the network when the LED status indicator is solid RED and the App_status in the interface is OK.

SMARTSTART INCLUSION

Z-WaveTM SmartStart aims to shift the tasks related to inclusion of an end device into a Z-WaveTM network away from the end device itself, and towards the more user-friendly interface of the gateway.
Z-WaveTM SmartStart removes the need for initiating the end device to start inclusion.
Inclusion is initiated automatically on power-ON and repeated at dynamic intervals for as long as the device is not included into a Z-Wave TM network. As the new device announces itself on power-ON, the protocol will provide notifications, and the gateway can initiate the inclusion process in the background, without the need for user interaction or any interruption of normal operation. The SmartStart inclusion process only includes authenticated devices.
META Serie 7 devices can be added into a Z-Wave TM network by scanning the Z-WaveTM QR Code present on the product with a controller providing SmartStart inclusion. No further action is required and the SmartStart product will be added automatically
within 10 minutes of being switched on in the network vicinity.
The SmartStart QR and the full DSK string code can be found on the back of the device. The PIN is the first group of 5 digits printed underlined. If you plan to use the DSK, it is important that you take a picture of the label and keep it in a safe place. S2 SECURE INCLUSION
When adding META Serie 7 devices to a Z-WaveTM network with a controller supporting Security 2 Authenticated (S2), the PIN code of the Z-Wave TM Device Specific Key (DSK) is required. The unique DSK code is printed on the product label. The first five digits of the key are highlighted and underlined to help the user identify the PIN code.

SUPPORTED COMMAND CLASSES

**Command Class| Version| Non-Secure CC| Secure CC**
---|---|---|---
BASIC| 2| | x
ZWAVEPLUS_INFO| 2| x|
ASSOCIATION| 2| | x
MULTI_CHANNEL_ASSOCIATION| 3| | x
ASSOCIATION_GRP_INFO| 3| | x
TRANSPORT_SERVICE| 2| x|
VERSION| 3| | x
MANUFACTURER_SPECIFIC| 2| | x
DEVICE_RESET_LOCALLY| 1| | x
INDICATOR| 3| | x
POWERLEVEL| 1| | x
SECURITY_2| 1| x|
SUPERVISION| 1| x|
FIRMWARE_UPDATE_MD| 5| | x
APPLICATION_STATUS| 1| x|
CONFIGURATION_V4| 4| | x
SWITCH_BINARY| 2| | x
CENTRAL_SCENE| 3| | x
METER| 5| | x

Supporting Command Class Basic
The basic command classes are mapped into the Switch Binary Command Class.

Basic Command received Mapped Command (Binary Switch)
Basic Set (0xFF) Switch Binary Set (0xFF)
Basic Set (0x00) Switch Binary Set (0x00)
Basic GET Basic Report 0x00 if the Binary Switch is in OFF state 0x00

Basic Report 0xFF if the Binary Switch is in ON state 0xFF

Supporting Command Class Indicator
The device supports the Command Class Indicator V3 (ID 0x50). When the device receives an indicator set, the led blinks accordingly to the Indicator set received.
The color shown by the indicator will be:
RED: if the device is included without Security
BLUE: if the device is included in S2 Unauthenticated Mode
GREEN: if the device is already included in S2 Authenticated Mode.
Meter Command Class
The product supports the meter command class and KWh is the default scale report send when the scale type is not present in the received Get.

Supported Scale Name Scale Value
Watt 2
KWh 0

DEVICE CONTROL

META Double Switch 7 can control two separate loads by using an external switch for each channel, or from remote through a controller.
Controlling the device by External Switches
For the operation of the device within the Z-Wave™ network and controlling the loads connected to the device, control actions are performed on the switches.
The CONTROL ACTIONS are EVENTS executed on EXTERNAL SWITCHES cconnected to the terminal of the device which can be Clicks, Hold Down and Up.

Event Type of switch Actions on the switch
Click Momentary switch (button) Press briefly & Release

(when pressed it autonomously returns to the initial position)
Toggle Switch (bistabile)| Press & Release
(a single click means one single flip of the switch)
MultiClick= n click| Momentary switch| Sequence of consecutive n clicks
Toggle Switch
Hold Down| Momentary switch| Press longer than click.
After a Hold Down always follows an UP event.
Up| Momentary switch| Release.
The event applies only if there has been a previous Hold Down event.

Since the device supports Central Scene Notification all the events described in the table will be notified with a Central Scene Notification Report to the Lifeline. The events that trigger a Central Scene Notification Report can be customized with the configuration
parameter in the Central Scene Notification Parameter section. Controlling the device by a Z-Wave TM controller
The device can be controlled by any Z-WaveTM / Z-Wave PlusTM certified controller available in the market.

ASSOCIATIONS

META Double Switch 7 can control other devices of both traditional and multi- channel type. It can also control other devices such as relays or dimmers. The device supports 7 association groups, each of which supports the association of up to 8 devices (nodes):
Lifeline Group: Nodes belonging to this group will receive: notifications about device reset; changes related to the relay status and meter reports.
Groups from 2 to 7: Nodes belonging to these groups will be controlled by a basic set if the external switch receives one or more clicks.

Group ID Group Name N° max nodes Description Command sent End Point ID
1 Lifeline 8 Lifeline Group. Nodes belon- ging to this group will recei-

ve: notifications about device reset changes related to the relay and Indicator Status and the Central Scene Notifi- cation.| DEVICE_RESETLOCALLY NOTIFICATION
SWITCH_BINARY_REPORT METER_REPORT
CENTRALSCENE NOTIFICATION
INDICATOR REPORT| 0
2| Follow ch1 state| 8| The state of the output 1 (ON/OFF) will be propagated to the associated device| BASIC SET| 1
3| clicks on button 1 G1| 8| The associated device will be controlled based on the click events and output propagation defined by configuration parameters on the Association group management section| 1
4| clicks on button 1G2| 8
1
5| Follow ch2
state| 8| The state of the output 2 (ON/OFF) will be propagated to the associated device| 2
6| clicks on button 2 G1| 8| The associated device will be controlled based on the click events and output propagation defined by configuration parameters on the Association group management section| 2
7| clicks on button 2 G2| 8| 2

INFO: Association ensures direct transfer of control commands between devices and is performed without participation of the main controller.

SPECIAL FEATURES

Timer Management
An independent timer for each channel can be set when switching On and/or Off. It also possible to define which event will start the timer (for example only the change on the output due to double clicks).
Power consumption management
META Double Switch 7 is equipped with a very precise power metering functionality, therefore you can easily monitor the instantaneous power and cumulated energy for each channel.

OFFLINE SETUP MODE

The device has a unique feature that allows to configure some parameters without using any user interface. This feature enables the professional user to setup the main features of the device in the field even if the device is not included in a Z-WaveTM Network. When the device will be included in the network all these configuration parameters will be maintained.
To enter in offline setup mode, operate 2 clicks on the integrated button.
When the device is in Offline setup mode the led becomes solid Blue and the following configurations are permitted:

1 click| Setup input type to toggle switch. Equivalent to set parameter n. 1 to 2.
---|---
2 clicks| Activate a switch Off timer of 10 minutes. Equivalent to set parameter n.30 to 15 and parameter n. 31 to 6000.
3 clicks| Activate a switch Off timer of 5 minutes. Equivalent to set parameter n. 30 to 15 and parameter n. 31 to 3000.
After receiving the command the led blinks a number of times equal to the number of clicks recognized.
6 clicks| Exit from Offline setup mode and return to normal operation.
Hold down for 5 seconds| Reset all configuration parameters to their default value and return to normal operation.

After entering in Offline setup mode, the device returns to normal operation if no action on the switch is detected for more than 20 Seconds.

RESET TO THE FACTORY SETTINGS

The device can be reset to the original factory with 6 consecutive clicks on the integrated button.
After the reset is completed, the device will reboot and a RED solid led is showed.
Please use this procedure only when the network primary controller is missing or otherwise inoperable.
INFO: If the reset is performed while the device is still part of a network, it notifies the other devices that it has been removed (Device Reset Locally Notification).

FIRMWARE UPDATE

The system supports over-the-air firmware updates that do not require the device to be removed from its location. The firmware update can be activated from all certified controllers supporting version 2 of the Firmware Update function.
WARNING: The system will be rebooted at the end of the firmware update procedure. It is advisable to carry out the firmware update procedure only when necessary and following careful planning of the intervention.

CONFIGURATIONS

Input Configuration

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
1| 1| IN1_TYPE| 1| Define the 1st input type
Parameters Values
Min: 0
Max: 2

Value| Description
0| No switch input
1| Momentary switch (button)
2| Toggle switch
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
2| 1| IN2_TYPE| 1| Define the 2nd input type
Parameters Values
Min: 0
Max: 2

Value| Description
0| No switch input
1| Momentary switch (button)
2| Toggle switch
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
10| 1| IN1_ TOGGLE| 15| Define which events on the input 1 tog- gle output 1.
Parameters Values
Min: 0
Max: 31

Value| Description
0| Disabled
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default Value: 1 click, 2 clicks, 3 clicks, Hold down →15.

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
11| 1| IN1ON EXCLUSION| 0| Define which events on the input 1 do not switch-On output 1.
Parameters Values| | Min: 0| Max: 31
Value| Description
0| Disable
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default Value: Disable →0

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
12| 1| IN1OFF EXCLUSION| 0| Define which events on the input 1 do not switch-Off output 1.
Parameters Values| | Min: 0| Max: 31
Value| Description
0| Disable
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default Value: Disable →0

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
15| 1| IN2_ TOGGLE| 15| Define which events on the input 2 tog- gle output 2.
Parameters Values| | Min: 0| Max: 31
Value| Description
0| Disable
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default Value: 1 click, 2 clicks, 3 clicks, Hold down →15

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
16| 1| IN2ON EXCLUSION| 0| Define which events on the input 2 do not switch-On output 2.
Parameters Values| | Min: 0| Max: 31
Value| Description
0| Disable
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default Value: Disable →0

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
17| 1| IN2OFF EXCLUSION| 0| Define which events on the input 2 do not switch-Off output 2.
Parameters Values
Min: 0
Max: 31

Value| Description
0| Disable
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default Value: Disable →0
Output Configuration:

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
21| 1| OUT1_TYPE| 0| Define the 1st output type.
Parameters Values
Min: 0
Max: 1

Value| Description
0| Direct load or normally Open relay
1| Normally Closed relay
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
22| 1| OUT2_TYPE| 0| Define the 2nd output type.
Parameters Values
Min: 0
Max: 1

Value| Description
0| Direct load or normally Open relay
1| Normally Closed relay
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
23| 1| STARTUP_ OUT1| 2| Define the 1st output level on startup
(status of the device following a restart)
Parameters Values Min: 0                      Max: 3
Value| Description
0| OFF
1| ON
2| Previous status
3| equal to input (ON if input close, OFF if input open)
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
24| 1| STARTUP_ OUT2| 2| Define the 2nd output level on startup

(status of the device following a restart)

Parameters Values Min: 0                      Max: 3
Value| Description
0| OFF
1| ON
2| Previous status
3| equal to input (ON if input close, OFF if input open)
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
25| 1| LOCAL_ SCENE| 0| Define the Local scene configuration.
Parameters Values
Min: 0
Max: 2

Value| Description
0| independent channel (External switch I1 controls output 1 load and external switch I2 controls output 2 load)
1| never both on (Both outputs can be OFF but they can never be ON simultaneously)
2| Sequencing (Outputs are toggled in this order: both loads ON, only load 1 ON, only load 2 ON, both loads OFF)

Timer management

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---


30

| ****

1

| TIMER_ CH1_SETUP| ****

0

| Define which trigger event on the Chan- nel 1 activate its timers when output 1 has changed
Parameters Values
Min: 0
Max: 127

Value| Description
0| Disabled
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up
32| Network (status change trigger by gateway or other devices in the Z-Wave network).
64| System (based on the startup status, or other timer event).

If more than 1 event are supported, the value for the configuration parameter is the sum of the event values.
For example: To control the load with
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
Default value: Disabled →0

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
**31| ****4| OFFEP1 TIMEOUT| ****0| Time in tenth of seconds after which the output on Channel 1 will be switched Off.
Parameters Values
Min: 0
Max: 360000
Value| Description
0-360000| Specific time expressed in tenth of seconds for Status change.
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
32| 4| ONEP1 TIMEOUT| 0| Time in tenth of seconds after which the output on Channel 1 will be switched On
Parameters Values
Min: 0
Max: 360000
Value| Description
0-360000| Specific time expressed in tenth of seconds for Status change.
Parameter Number| Size| Parameter Name| Default Value| Description**
---|---|---|---|---


33

| ****

1

| TIMER_ CH2_SETUP| ****

0

| Define which trigger events on the Channel 2 activate its timers when output 2 has changed
Parameters Value
Min: 0
Max: 31

Value| Description
0| Disabled
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up
32| Network (status change trigger by gateway or other devices in the Z-Wave™ network)
64| System (based on the startup status, or other timer event)

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example: To control the load with
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
Default Value: Disabled →0

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
34| 4| OFFEP2 TIMEOUT| 0| Time in tenth of seconds after which the output on Channel 2 will be switched Off
Parameters Values Min: 0                   Max: 360000
Value| Description
0-360000| Specific time expressed in tenth of seconds for Status change.
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
35| 4| ONEP2 TIMEOUT| 0| Time in tenth of seconds after which the output on Channel 2 will be switched On
Parameters Values
Min: 0
Max: 360000

Value| Description
0-360000| Specific time expressed in tenth of seconds for Status change.

Association group management

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
40| 1| G1EP1 SETUP| 1| Define which events on the input 1 con- trol G1 association group on Channel 1.
Parameters Values
Min:
Max: 31

Value| Description
0| No control
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default value: 1 click →1

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
41| 1| G2EP1 SETUP| 2| Define which events on the input 1 con- trol G2 association group on Channel 1.
Parameters Values| | Min: 0| Max: 31
Value| Description
0| No control
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default value: 2 clicks →2

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
42| 1| G1EP2 SETUP| 2| Define which events on the input 2 con- trol G1 association group on Channel 2.
Parameters Values| | Min: 0| Max: 31
Value| Description
0| No control
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
for example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default value: 1 click →1

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
43| 1| G2EP2 SETUP| 2| Define which events on the input 2 con- trol G2 association group on Channel 2.
Parameters Value
Min: 0
Max: 31

Value| Description
0| No control
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If you support more than 1 event, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default value: 2 clicks →2

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
44| 1| G1EP1 ASS_VALUE| 101| The value used to control G1 association group on Channel 1.
Parameters Values
Min: 0
Max: 102

Value| Description
0-99| Specific value
100| ON
101| Propagate (output 1 status to the associated device)
102| Toggle remote (change status ON/OFF of associated devices)
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
45| 1| G2EP1 ASS_VALUE| 101| The value used to control G2 association group on Channel 1.
Parameters Values
Min: 0
Max: 102

Value| Description
0-99| Specific value
100| ON
101| Propagate (output 1 status to the associated device)
102| Toggle remote (change status ON/OFF of associated devices)
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
46| 1| G1EP2 ASS_VALUE| 101| The value used to control G1 association group on Channel 2.
Parameters Values
Min: 0
Max: 102

Value| Description
0-99| Specific value
100| ON
101| Propagate (output 2 status to the associated device)
102| Toggle remote (change status ON/OFF of associated devices)
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
47| 1| G2EP2 ASS_VALUE| 101| The value used to control G2 association group on Channel 2.
Parameters Value
Min: 0
Max: 102

Value| Description
0-99| Specific value
100| ON
101| Propagate (output 2 status to the associated device)
102| Toggle remote (change status ON/OFF of associated devices)

Central Scene management

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
60| 1| SCENE_ SETUP| 31| Define which event on the input trigger a central scene notification.
Parameters Value
Min: 0
Max: 31

Value| Description
0| None
1| 1 click
2| 2 clicks
4| 3 clicks
8| Hold down
16| Up

If more than 1 event are supported, the value for the configuration parameter is the sum of the event values.
For example:
1 click and 2 clicks -> Parameter value must be 1 + 2 = 3
1 click and 3 clicks -> Parameter value must be 1 + 4 = 5
Default value: all event →31
Meter management

Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
70| 1| EREPORT DELAY| 10| Time in minutes after which the next Energy report will be sent
Parameters Values
Min: 1
Max: 120

Value| Description
1-120| Report generation in a specific time in minutes
Parameter Number| Size| Parameter Name| Default Value| Description
---|---|---|---|---
**71| ****1| W REPORT DELAY| ****10| Time in minutes after which the next Energy report will be sent
Parameters Values
Min: 1
Max: 120
Value| Description
1-120| Report generation in a specific time in minutes
Parameter Number| Size| Parameter Name| Default Value| Description**
---|---|---|---|---


75

| ****

1

| W ISTANT REPORT| ****

30

| The percentage change from the last sent report that trigger a new Power report
Parameters Values
Min: 0
Max: 100

Value| Description
0| No report is sent (for any power change)
1-100| The percentage of Power change from the last sent report that triggers a new meter report sequence

CHERUBINI logoCHERUBINI S.p.A.
Via Adige 55
25081 Bedizzole (BS) – Italy
Tel. +39 030 6872.039 | Fax +39 030 6872.040
info@cherubini.it | www.cherubini.it
CHERUBINI Iberia S.L.
Avda. Unión Europea 11-H
Apdo. 283 – P. I. El Castillo
03630 Sax Alicante – Spain
Tel. +34 (0) 966 967 504 | Fax +34 (0) 966 967 505
info@cherubini.es | www.cherubini.es
CHERUBINI France S.a.r.l.
ZI Du Mas Barbet
165 Impasse Ampère
30600 Vauvert – France
Tél. +33 (0) 466 77 88 58 | Fax +33 (0) 466 77 92 32
info@cherubini.fr | www.cherubini.fr
CHERUBINI Deutschland GmbH
Siemensstrasse, 40 – 53121 Bonn – Deutschland
Tel. +49 (0) 228 962 976 34 / 35 | Fax +49 (0) 228 962 976 36
info@cherubini-group.de | www.cherubini- group.de

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals