SIEMENS OOH740 Cerberus PRO Cerberus FIT Automatic Fire Detectors User Manual

June 11, 2024
SIEMENS

SIEMENS OOH740 Cerberus PRO Cerberus FIT Automatic Fire Detectors
logo

SIEMENS OOH740 Cerberus PRO Cerberus FIT Automatic Fire Detectors

Product Information

The CerberusTM PRO / CerberusTM FIT automatic fire detectors, models OOH740 and OOHC740, are designed to be resistant to
environmental and interfering influences such as dust, fibers, insects, moisture, extreme temperatures, electromagnetic interference, corrosive vapors, vibration, artificial aerosols, and atypical fire phenomena. They are shock-resistant and offer protection against sabotage. These detectors feature signal processing with ASA technology (Advanced Signal Analysis), time and process-dependent detection behavior, and a high degree of immunity to faults in power electronics. They also have protected electronics and high-quality components, sophisticated sensors and electronic monitoring, and an integrated line separator that locates the defective part on the detector bus of the recess-mounted supply lines. The OOH740 model can also be used on a collective detector line or a conventional detector line. These detectors are environmentally friendly, with reusable materials, and electronic parts and synthetic materials that can be easily separated.

Product Usage Instructions

The OOH740 multi-sensor fire detector is designed for early detection of flaming fires of solid and liquid substances, as well as smoldering fires. It can also be used for early and reliable fire detection in an environment with deceptive phenomena. The detector can be set as a multi-sensor smoke detector, smoke detector, or heat detector by the software. Its selectable detection behavior is thanks to application-specific ASA parameter sets. This detector can be used on an addressed detector line, a collective detector line, or a conventional detector line.|
The OOHC740 fire and CO detector is also a multi-sensor fire detector with an additional CO sensor that increases the point detector’s response behavior and immunity to deceptive phenomena.
It functions using an electro-chemical CO cell and sends a technical message if the temperature or CO concentration exceeds/falls below the preset limits. The CO concentration alarm is transmitted to an independent technical CO alarm channel, and the detector has independent processing of the CO signal for the CO alarm channel and CO signal for fire detection. The detector’s selectable detection behavior of the CO alarm channel is regardless of ASA parameter sets for fire detection.
AS technology™. For the automatically addressed detector bus C-NET collective / conventional (OOH740 only)

  • Signal processing with ASAtechnology
  • Event-controlled detection behavior
  • Evaluation of the criteria heat, warmth for OOH740, and gas for OOHC740
  • Quick response to all fires that generate carbon monoxide (CO) for OOHC740
  • Separate detection of toxic CO for OOHC740
  • Highly developed immunity to deceptive phenomena
  • Prepared for future requirements thanks to its programmability
  • Address automatically issued during commissioning
  • Supports disturbance-free function testing with DFTtechnology™ (Disturbance-Free Test) (OOH740)

Properties

Design

Resistant to environmental and interfering influences such as dust, fibers, insects, moisture, extreme temperatures, electromagnetic interference, corrosive vapors, vibration, artificial aerosols, and atypical fire phenomena

Features
  • Shock resistant, protection against sabotage
  • Signal processing with AS technology (Advanced Signal Analysis)
  • Time and process-dependent detection behavior
  • High degree of immunity to faults in power electronics
  • Protected electronics, high-quality components
  • Sophisticated sensors and electronic monitoring
  • The integrated line separator that locates the defective part on the detector bus of the control panel and isolates between two detectors
  • Supports automatic detector test with DFTtechnology™ (OOH740)
  • Integrated alarm indicator (AI), 360° visibility
  • Up to two external alarm indicators can be connected per detector
  • Address automatically issued during commissioning
  • Same detector base can be used for every detector type, for surface-mounted and recess-mounted supply lines
  • OOH740 only: Can also be used on a collective detector line or a conventional detector line

Eco-friendly

  • Environmentally friendly processing
  • Reusable materials
  • Electronic parts and synthetic materials can be easily separated

Use

OOH740 multi-sensor fire detector, neural ASA

| Multi-sensor fire detector consisting of:

  • Point detector
  • Detector dust cap to protect the point detector during the construction phase

Function:

  • Functions according to the scattered light principle with two sensors, optical forward and backward scattering
  • Opto-electronic measuring chamber that obstructs disruptive extraneous light but provides excellent detection of both light and dark smoke particles
  • Two additional heat sensors increase the point detector’s immunity to deceptive phenomena
  • Can be set as a multi-sensor smoke detector, smoke detector, or heat detector by the software
  • Selectable detection behavior thanks to application-specific ASA parameter sets

Use :

  • For early detection of flaming fires of solid and liquid substances, as well as of smoldering fires
  • For early and reliable fire detection in an environment with deceptive phenomena
  • Can be used on an addressed detector line, a collective detector line, or a conventional detector line

OOHC740 fire and CO detector, neural ASA

| Multi-sensor fire detector consisting of:

  • Point detector
  • Detector dust cap to protect the point detector during the construction phase

Function:

  • Functions according to the scattered light principle with two sensors, optical forward and backward scattering
  • Opto-electronic measuring chamber that obstructs disruptive extraneous light but provides excellent detection of both light and dark smoke particles
  • Two additional heat sensors and an additional CO sensor increase the point detector’s response behavior and immunity to deceptive phenomena
  • Technical message, ambient supervision: Technical message if the temperature or CO concentration exceeds/falls below the preset limits
  • Functions using an electro-chemical CO cell
  • CO concentration alarm is transmitted to an independent technical CO alarm channel
  • Independent processing of the CO signal for the CO alarm channel and CO signal for fire detection
  • Selectable detection behavior of the CO alarm channel, regardless of ASA parameter sets for fire detection
  • Selectable detection behavior thanks to application-specific ASA parameter sets

Use :

  • For early detection of smoldering fires that generate CO (e.g., mattress fires in homes)
  • Areas with increased CO exposure, e.g., heating rooms, combustion plants, fermentation plants, garages, automotive workshops, animal stalls, chemical laboratories, or production sites
  • For reliable fire detection in an environment with deceptive phenomena
  • Can be used addressed

Detector base DB721

| Function:

  • Universal base for all point detectors of the Cerberus™ PRO FD720 series

Use :

  • For recess-mounted supply lines
  • For surface-mounted supply lines with cables up to max. Ø 8 mm

The detector base DB721 has a loop contact. When using the DB721, the detector line is also not interrupted when there is no point detector mounted in the detector base.

Detector base DB721D

| Function:

  • Collective mode
    • Universal base for the point detector OOH740 in collective mode (with BS 5839-1)
  • Addressed mode
    • Universal base for the point detector OOH740 of the Cerberus™ PRO FD720 series
    • When used in the addressed mode, the diode must be removed

Use :

  • For recess-mounted supply lines
  • For surface-mounted supply lines with cables up to max. Ø 8 mm
    The detector base DB721D has a loop contact. When using the DB721D, the detector line is also not interrupted when there is no point detector mounted in the detector base.

Detector base DB722

| Function:

  • Universal base with base seal for point detectors OH720 and OP720 of the Cerberus™ PRO FD720 series

Use :

  • For recess-mounted supply lines
  • For surface-mounted supply lines with cables up to max. Ø 8 mm

The detector base DB722 has a loop contact. When using the DB722, the detector line is also not interrupted when there is no point detector mounted in the detector base.

Detector base DB110 (parameter set 1)

| Function:

  • Universal base for all point detectors of the 110 and OOH740 series
  • Selects parameter set 1 within the point detector

Use :

  • For recess-mounted supply lines
  • For surface-mounted supply lines with cables up to max. Ø 8 mm

Sounder base DBS720

| Function:

  • Addressable sounder base for the acoustic alarm
  • Compatible with all point detectors from the Cerberus™ PRO FD720 series You will find more information on the sounder base DBS720 in document A6V10218037.

Intended Use

The automatic fire detectors OOH740 and OOHC740 may only be used on a C-NET detector line in a fire detection system FS720 or FC360.
The automatic fire detector OOH740 may also be used on a collective detector line or a conventional detector line.

Type Overview

Type Designation Order number Weight [kg]
OOH740 Multi-sensor fire detector, ASA S54320-F7-A3 0.124
OOHC740 Fire and CO detector, ASA S54320-F8-A3 0.128
DB721 Detector base with loop contact S54319-F11-A1 0.052
DB721D Detector base with loop contact S54319-F15-A1 0.054
DB722 Detector base S54319-F19-A1 0.052
DB110 Detector base (collective) S54372-F5-A1 0.052
DBS720 Sounder base S54319-F5-A1 0.090

Accessories
BA720| Base attachment| S54319-F20-A1| 0.051
BA721| Base attachment wet| S54319-F29-A1| 0.272
FDBZ291| Designation plate| A5Q00002621| 0.002
DBZ1193A| Designation plate| BPZ:4864330001| 0.076
RS720| Detector base seal| S54319-F8-A1| 0.012
LP720| Detector locking device| S54319-F9-A1| 0.001
FDBH291| Detector heating unit| A5Q00004439| 0.015
DBZ1194| Protective cage| BPZ:4677110001| 0.138
DBZ1190-AA| Micro terminal 0.28…0.5 mm²| BPZ:4677080001| 0.001
DBZ1190-AB| Connection terminals 0.5…2.5 mm²| BPZ:4942340001| 0.001
PSR720-1| Parameter set resistor 33k| S54319-F16-A1| 0.001
PSR720-2| Parameter set resistor 68k| S54319-F17-A1| 0.001

Accessories

Base attachment BA720

| Function:

  • For routing surface-mounted ducts (max. 20 mm) and cable ducts (max. 25 x 15 mm)
  • Detector base mounted quickly: The detector base clicks into place in base attachment BA720.

Base attachment wet BA721

****|

  • Base attachment wet with additional integrated rubber seal for mounting in wet or humid environments
  • For achieving a higher protection category
  • For mounting in wet or humid environments
  • Required when using detector heating unit FDBH291
  • Required when using protective cage DBZ1194
  • Mounted between detector base and ceiling
  • Detector base mounted quickly: The detector base simply clicks into place in base attachment wet BA721.

Protective cage DBZ1194

|

  • To protect the point detector from damage
  • Can only be mounted in combination with base attachment wet BA721

Detector heating unit FDBH291

|

  • For operating point detectors in critical ambient conditions during icy conditions or when there is a danger of moisture condensation. Examples of application: Cold stores, attics, loading ramps, cheese cellars
  • Optimum function is only guaranteed in conjunction with base attachment wet BA721.
  • The point detector temperature increases by approximately 2 °C over the operating temperature and thus avoids moisture condensation on the detector.
  • Mounted quickly: The detector heating unit clicks into place in the detector base.

Designation plate FDBZ291

|

  • For labeling with the location address
  • Can only be used without detector base seal FDBZ295

Designation plate DBZ1193A

|

  • For labeling with the location address
  • Can only be used with base attachment wet BA721

Detector base seal RS720

|

  • For achieving a higher IP protection category
  • Mounted between detector base and ceiling

Detector locking device LP720

|

  • For protection against theft of the point detector
  • Set screw M3 x 12 mm prevents the point detector being unscrewed from the detector base
  • Point detector can only be removed with the appropriate Allen key

Parameter set resistor 33k PSR720-1

| Function:

  • Prefabricated resistor with flat plugs for use in DB110 and DB721D. Brings the OOH740 in parameter set 1.

Parameter set resistor 68k PSR720-2

| Function:

  • Prefabricated resistor with flat plugs for use in DB110 and DB721D. Brings the OOH740 in parameter set 2.

DBZ1190-AA micro terminal and DBZ1190-AB connection terminal

|

  • Micro terminal DBZ1190-AA
    • Cable cross section up to max. 0.5 mm²
  • Connection terminal DBZ1190-AB
    • Cable cross section up to max. 2.5 mm²
    • For connecting two external alarm indicators or the cable shielding

Product documentation

Document ID Title
008115 Installation Detector heating FDBH291
A6V10200373 Installation Detector base with loop contact DB721, DB722,

detector base DB720, sounder base DBS720, detector base seal RS720, detector locking device LP720, base attachment BA720
A6V10203222| Data Sheet Testequipment and accessories FDUL221, DX791, RE6, RE7T, RE8ST, RE8STCO, FDUM29x, LE3, StabexHF
A6V10218037| Technical Manual Sounder base DBS720
A6V10229261| List of compatibility (for ‘Cerberus™ PRO’ product line)
A6V10305793| Technical Manual Automatic fire detectors OOH740, OOHC740
A6V10393192| List of compatibility (for ‘Cerberus™ FIT’ product line)
A6V10406006| Installation Base attachment wet BA721, Detector designation plate DBZ1193A, Protective cage DBZ1194, EMC-protective cage FDBZ294
A6V10882301| List of compatibility (for ‘FC360’ product line)

Notes

Installation

Easy mounting

  • Universal detector base

    • Two break-out points for surface-mounted cable entry at the side.
      Max. cable diameter: 8 mm.

    • Extra-large opening for single recess-mounted cable entry.

  • Extra-long mounting slits allow existing drill holes from other systems to be reused.

  • Screw terminals for conductors up to max. 1.6 mm²

  • Space for auxiliary terminals:

    • 2x micro terminals DBZ1190-AA and
    • 2x connection terminals DBZ1190-AB

The detector can be screwed into the base easily either manually or using the detector exchanger DX791 and the corresponding adapter FDUD491.
The internal alarm indicator is centered in the detector, which makes alignment of the point detector superfluous.SIEMENS OOH740 Cerberus PRO
Cerberus FIT Automatic Fire Detectors 19

1 Detector base 5 Mounting slits
2 Auxiliary terminals DBZ1190‑AA, DBZ1190‑AB 6 Point detector
3 Screw terminals for detector line and external alarm indicator 7 Internal

alarm indicator
4| Opening for cable entry| |

Disposal

The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste.

  • Use only designated channels for disposing the devices.
  • Comply with all local and currently applicable laws and regulations.
  • Dispose of empty batteries at designated collection points.

Technical data

| OOH740| OOHC740
---|---|---
Operating voltage (modulated)| DC 12…33 V| DC 12…33 V
Operating current (quiescent)| ~170…250 µA| ~300…380 µA
Max. number of external alarm indicators that can be connected| 2| 2
Operating temperature| -25…+55 °C| -10…+50 °C
Storage temperature| -30…+70 °C| -20…+55 °C
Air humidity (short-term moisture condensation permitted)| ≤95 % rel.| ≤95 % rel.
Communication protocol| C-NET, collective or conventional| C-NET
Color| ~RAL 9010 pure white| ~RAL 9010 pure white
Weight| 0.100 kg| 0.100 kg
Protection category (IEC 60529)| IP40| IP40
Protection category (IEC 60529) with detector base seal RS720/BA721| IP44| IP44
Standards| EN 54‑5, EN 54‑7, EN 54‑17,| EN 54-5, EN 54-7, EN 54-17,
| EN 54‑29| EN 54-29
| | Fulfills the requirements
| | according to EN 54-31
Approvals| |
VdS| G211070| G211047
LPCB| 126bv/04| 126bv/08
FM| 3051081| –
DNV GL (marine)| MEDB00003UK| –
Permissible wind speed| Max. 5 m/s| Max. 5 m/s
C-NET system compatibility| FC720, FC360
Collective system compatibility| FC10/FC120| –

Dimensional drawings

  • OOH740SIEMENS OOH740 Cerberus PRO Cerberus FIT Automatic Fire Detectors 20
  • OOHC740SIEMENS OOH740 Cerberus PRO Cerberus FIT Automatic Fire Detectors 21
  • OOH740 with base DB72x or DB110SIEMENS OOH740 Cerberus PRO Cerberus FIT Automatic Fire Detectors 22
  • OOHC740 with base DB72xSIEMENS OOH740 Cerberus PRO Cerberus FIT Automatic Fire Detectors 23

Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals