SplusS 814x-MB Humidity Temperature And Pressure Sensor Instruction Manual

May 15, 2024
SplusS

SplusS 814x-MB Humidity Temperature And Pressure Sensor

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
PRODUCT

Product Specifications

  • Power Supply: < 0.2 W / 24 V DC typical
  • Unit System: SI (default), Imperial
  • Data Points: Modbus (RTU-Mode), Address range 0…247 adjustable
  • Baud Rate: 9600, 19200, 38400 Baud
  • Signal Filtering: 4 s / 32 s for Temperature / Humidity, 0 s / 1 s / 10 s for Pressure
  • Temperature Range: See table
  • Pressure Type: See table

Product Usage Instructions

Mounting and Installation

  1. Ensure the power supply matches the specified requirements.
  2. Mount the device using the plastic mounting flange included in the delivery package.
  3. Connect the device using the provided connection set.
  4. Secure the cable connection using the plastic cable gland (M16 x 1.5).

Data Configuration
Set the bus address and parameters (such as baud rate and parity) using the DIP switches on the device.

Sensor Calibration
Perform manual or automatic zero-point calibration for pressure measurements as needed.

Display and Controls
The device features LEDs for internal status indication, a reset button, and offset adjustment controls for pressure readings.

Frequently Asked Questions (FAQ)

  • Q: What is the default unit system for the device?
    A: The default unit system is SI, but it can also be set to Imperial.

  • Q: How do I calibrate the sensors on the device?
    A: You can perform manual or automatic zero-point calibration for pressure measurements.

  • Q: What is included in the delivery package?
    A: The delivery package includes the device, mounting flange, connection set, and plastic cable gland for installation.

Operating and Mounting Instructions

Multifunctional duct sensors and measuring transducers for humidity, temperature, pressure, differential pressure and volume flow, incl. mounting flange and connection set, calibratable, with Modbus connection

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(1\)

Humidity & Temperature & Pressure Type 814x-MB

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(2\)

Dimensional drawing

ASD – 06

  • Anschluss-Set (im Lieferumfang enthalten)
  • Connection set (included in the scope of deliveryl)
  • Kit de raccordement (compris dans la livraison)

SF -K
Kunststoff -Sinterfilter
Plastic sinter filter
Fitre fritté en matière synthétique

Type 814x-MB

Maintenance-free microprocessor-controlled Type 814x-MB (Series) with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, connection nozzles for pressure hose (Ø 6 mm / 0.236 in), plastic sinter filter (exchangeable), to exactly detect the relative humidity (0…100% RH) and the temperature (–35…+80 °C / –31…+176 °F) in ducts and to measure the differential pressure (max. ± 7000 Pa / ± 28 inWC) in air. International system of units SI (default) can be switched to Imperial (via Modbus). Incl. mounting flange and connection set ASD-06 (2 m / 78.74 in connecting hose, two pressure port nipples, screws).
The pressure sensor is applied to measure positive, negative or differential pressure in clean air and gaseous media. It is used in the clean room, medical and filter technology, ventilation and air conditioning ducts, spray booths, large-scale catering facilities, for filter monitoring and level measurement or for triggering frequency converters.
A long-term stable, digital humidity and temperature sensor and a pressure sensor with piezoresistive measuring element guarantee exact measurement results. These measurands are used to internally calculate the following parameters that can be retrieved via Modbus: temperature, relative humidity, dew point, absolute humidity, mixture ratio, enthalpy (ignoring atmospheric air pressure), differential pressure, volume flow, air density.
Innovative Modbus sensor with galvanically separated RS485-Modbus-interface, selectable bus t ermination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals. The sensor is factory- calibrated; an environmental precision adjustment by an expert is possible.

TECHNICAL DATA

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(6\) SplusS-814x-MB-Humidity-
Temperature-And-Pressure-Sensor- \(7\) SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(8\) SplusS-814x-MB-Humidity-
Temperature-And-Pressure-Sensor- \(9\)

Switchable system of units

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(10\)

Type 814x – MB
Measuring transducers for humidity, temperature, pressure, differential pressure and volume flow

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(11\)

ACCESSOIRES

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(12\)

Type 814x-MB SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(13\)

TYPES OF MONITORING:

Pressure connections at the pressure switch are marked with

P1 (+) for higher pressure and
P2 (–) for lower pressure.

  • (A) Below-atmospheric pressure
    • P1 (+) is not connected, but open to the atmosphere
    • P2 (–) connected to inside of duct
  • (B) Filter
    • P1 (+) connected upstream of filter
    • P2 (–) connected downstream of filter
  • (C) Ventilator
    • P1 (+) connected downstream of ventilator
    • P2 (–) connected upstream of ventilator
  • (D) Volume flow
    • P1 (+) dynamic pressure, connected in flow direction
    • P2 (–) static pressure, connected free of  dynamic pressure components

Conversion table for pressure values

Unit = bar mbar Pa kPa inWC
1 Pa 0.00001 bar 0.01 mbar 1 Pa 0.001 kPa 0.00401865 inWC
1 kPa 0.01 bar 10 mbar 1000 Pa 1 kPa 4.01865 inWC
1 bar 1 bar 1000 mbar 100000 Pa 100 kPa 401.865 inWC
1 mbar 0.001 bar 1 mbar 100 Pa 0.1 kPa 0.401865 inWC
1 inWC 0.0980665 bar 98.0665 mbar 9806.65 Pa 9.80665 kPa 1 inWC

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(14\)

Manual zero point calibration (Pressure)

  1. The device must be operative for at least 60 minutes before zero point setting is started.
  2. Connect the two pressure inputs each P (+) and P (–) with a hose (differential pressure between the connections = 0).
  3. To set the zero point, press the “auto zero” pushbutton for 10 seconds without interruption.

By pressing the pushbutton, a countdown of approx. 10 seconds is started. The yellow LED is blinking.
After the countdown period has elapsed, zero point calibration takes place. This is indicated by continuous LED light.

Note:
When releasing the pushbutton during countdown, zero point setting is immediately aborted!

Automatic zero point calibration (Pressure)

  • A zero point calibration is carried out cyclically via an internal valve.
  • The cycle time can be set between 15 minutes and 24 hours using the Register 4×0025.
  • During the automatic calibration, the output value remains at its last pressure value.

Manual setting of the offset

  • The sensors are pre-set and calibrated at the factory.
  • Each measuring channel has a separate offset potentiometer for subsequent adjustment of the measurement.
  • The adjusting range is ± 10 % of the measuring range (humidity / pressure) and approx. ± 5 K / 0.9 °F (temperature).

BUS ADDRESS

Bus address
(binary coded, value selectable from 1 to 247)

DIP 1| DIP 2| DIP 3| DIP 4| DIP 5| DIP 6| DIP 7| DIP 8
128| 64| 32| 16| 8| 4| 2| 1
O N| O N| OFF| OFF| OFF| OFF| OFF| O N
Example shows 128 + 64 + 1 = 193 as Modbus address.

The device address in the range of 1 to 247 is set at DIP switch [A].
For switch positions 1 to 8 see the table on the back!
Address 0 is reserved for broadcast messages.
Addresses greater than 247 must not be assigned and are ignored by the device. The DIP switches are binary-coded with the following values:

  • DIP 1 = 128 ………… DIP 1 = ON
  • DIP 2 = 64 ………… DIP 2 = ON
  • DIP 3 = 32 ………… DIP 3 = OFF
  • DIP 4 = 16 ………… DIP 4 = OFF
  • DIP 5 = 8 ………… DIP 5 = OFF
  • DIP 6 = 4 ………… DIP 6 = OFF
  • DIP 7 = 2 ………… DIP 7 = OFF
  • DIP 8 = 1 ………… DIP 8 = ON

The switch positions shown here result in the Modbus address 128 + 64 + 1 = 193

BUS PARAMETERS

Baud rate

(selectable)

| DIP 1| DIP 2
---|---|---
9600 baud| O N| OFF
19200 baud| O N| O N
38400 baud| OFF| O N
Reserved| OFF| OFF

Parity (selectable) DIP 3
EVEN (numbered) **O N**
ODD (numbered) **** OFF

Parity check
(on / off)| DIP 4
---|---
Active (1 stop bit)| O N
Inactive (no parity) (2 stop bits)| OFF
8N1 mode
(on / off)| DIP 5
---|---
Active| O N
Inactive (default)| OFF
Bus termination

(on/off)

| DIP 6
---|---
Active| O N
Inactive| OFF

The baud rate (speed of transmission) is set at DIP switches 1 and 2 of DIP switch block [B].
Selectable are 9600 baud, 19200 baud, or 38400 baud – see table!

  • Parity is set at DIP switch 3 of DIP switch block [B].

  • Selectable are EVEN or ODD – see table!

  • Parity check is activated via DIP switch 4 of DIP switch block [B].

  • Selectable are active (1 stop bit), or inactive (2 stop bits), i.e. no parity check – see table!
    The 8N1 mode is activated via DIP switch 5 of DIP switch block [B].

  • The functionality of DIP switch 3 (parity) and DIP switch 4 (parity check) of DIP switch block [B] is therefore deactivated. Selectable are 8N1 active or inactive (default) – see table !.

  • Bus termination is activated via DIP switch 6 of DIP switch block [B].

  • Selectable are active (bus termination resistance of 120 Ohm), or inactive (no bus termination) – see table!

COMMUNICATION INDICATOR
Communication is indicated via two LEDs. Error-free received telegrams are signalized by the green LED lighting up, regardless of the device address. Faulty telegrams or triggered Modbus exception telegrams are depicted by the red LED lighting up.

DIAGNOSTICS
An error diagnostic function is integrated

TELEGRAMS
Function 04 Read Input Register

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
01 SplusS-814x-MB-Humidity-Temperature-
And-Pressure-Sensor- 02

Function 05 Write Single Coil

Register| Parameter| Data Type| Value| Range|
---|---|---|---|---|---
0x0001| Auto zero (Differential pressure)| Bit 0| 0 / 1| OFF – ON|
0x0002| System of units| SI| →| Imperial| Bit 1| 0 / 1| SI (Default) –|
| | | Imperial|
Differential pressure| [Pa]| →| [inWC]|
| Volume flow| [m3/h]| →| [CFM]| | | |
| Temperature| [°C]| →| [°F]| | | |
| Relative humidity| [%RH]| | [%RH]| | | |
| Dew point| [°C]| →| [°F]| | | |
| Absolute humidity| [g/m3]| →| [gr/ft3]| | | |
| Mixing ratio| [g/kg]| →| [gr/ lb]| | | |
| Enthalpy| [kJ/kg]| →| [Btu/lb]| | | |
| Air density| [kg/m3]| →| [lb/ft3]| | | |

Function 06 Write Single Register & Function 16 Write Multiple Register

Register Parameter Data Type Value Range
4×0023 ***** k value Unsigned 16 Bit 1…2000 1…2000
4×0024 Function type ** Unsigned 8 Bit 1…3 1…3
4×0025 ***** Auto zero time Unsigned 16 Bit 15…1440 15…1440 min
4×0026 ***** Height above sea level Signed 16 Bit –500…5000 –500…5000 m

**Note*** (Register 4×0023, 4×0025, 4×0026)

The computed coefficients for the volume flow display are not saved in the permanent memory and are lost at zero voltage. They must be reset when the communication begins.

**Selection of the function type **** (Register 4×0024)

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
03

Function 08 Diagnostics
The following sub function codes are supported

Sub Function Code Parameter Data Type Answer
00 Echo of transmission data (Loopback) Echo data
01 Restart Modbus

(Reset listen-only mode)

| | Echo telegram
04| Activation listen-only mode| | No answer
10| Delete counter| | Echo telegram
11| Counter bus telegrams| Unsigned 16 Bit| All valid bus telegrams
12| Counter communication errors (Parity, CRC, frame errors, etc.)| Unsigned 16 Bit| Faulty bus telegrams
13| Counter exception telegrams| Unsigned 16 Bit| Error counter
14| Counter slave telegrams| Unsigned 16 Bit| Slave telegrams
15| Counter telegrams without answer| Unsigned 16 Bit| Broadcast messages (address 0)

Function 17 Report Slave ID
Composition of answer telegram

Byte No. Parameter Data Type Answer
00 Number of bytes Unsigned 8 Bit 6
01 Slave ID (device type) Unsigned 8 Bit 18 = Type 814x
02 Slave ID (device class) Unsigned 8 Bit 30 = Pressure Transmitter
03 Status Unsigned 8 Bit 255 = RUN, 0 = STOP
04 Version number (release) Unsigned 8 Bit 1…9
05 Version number (version) Unsigned 8 Bit 1…99
06 Version number (index) Unsigned 8 Bit 1

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(20\)

SplusS-814x-MB-Humidity-Temperature-And-Pressure-Sensor-
\(21\)

  • Terminating resistor may only be installed at the ends of the bus line.
  • In networks with repeaters not more than two line terminations are allowed.
  • Line termination at the device can be activated via DIP switch 6.
  • The bias resistors for bus level definition in the resting state are usually activated at the Modbus master / repeater.
  • The maximum number of subscribers per Modbus segment is 32 devices.
  • When the number of subscribers is greater, the bus must be subdivided into several segments separated by repeaters. The subscriber address can be set from 1 to 247.
  • For the bus line, a twisted-pair cable data line / power supply line and copper mesh wire shield must be used. Therefore, the line capacitance should be less than 100 pF / m (e.g. Profibus cable).

Installation and Commissioning

Notes on installation:
Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding instructions, etc.). Particularly the following shall be regarded:

  • VDE ⁄ VDI directive technical temperature measurements, measurement set – up for temperature measurements.
  • The EMC directives must be adhered to.
  • It is imperative to avoid parallel laying of current-carrying lines.
  • We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC.

Before mounting, make sure that the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in particular in respect of:

  • Measuring range
  • Permissible maximum pressure, flow velocity
  • Installation length, tube dimensions
  • Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

Attention! In any case, please observe the mechanical and thermal load limits of the protective tubes according to DIN 43763 or according to specific S+S standards!

Flange mounting:
In case of flange mounting, screws in the flange part must be equally tightened. The lateral pressure screw must clamp securely, otherwise the feeler shaft might slip through.

Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions.
When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals.
Commissioning is mandatory and may only be performed by qualified personnel!

General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In addition, the following points are to be observed:

  • Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current carrying lines is to be avoided, and EMC directives are to be observed.
  • This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
  • No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
  • Consequential damages caused by a fault in this device are excluded from warranty or liability.
  • These devices must be installed and commissioned by authorised specialists.
  • The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
  • In case of any modifications made by the user, all warranty claims are forfeited.
  • This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.
  • Direct sun irradiation or heat i rradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
  • Operating this device close to other devices that do not comply with EMC directives may influence functionality.
  • This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
  • Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
  • Modifications of these records are not permitted.
  • In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!
134r0065/002;1: Frozen :29-Jan-2024

© Copyright by S+S Regeltechnik GmbH
Nachdruck, auch auszugsweise, nur mit Genehmigung der S+S Regeltechnik GmbH.
Reprint in full or in parts requires permission from S+S Regeltechnik GmbH.

Bus address, binary coded

1 00000001 51 00110011 101 01100101 151 10010111 201 11001001
2 00000010 52 00110100 102 01100110 152 10011000 202 11001010
3 00000011 53 00110101 103 01100111 153 10011001 203 11001011
4 00000100 54 00110110 104 01101000 154 10011010 204 11001100
5 00000101 55 00110111 105 01101001 155 10011011 205 11001101
6 00000110 56 00111000 106 01101010 156 10011100 206 11001110
7 00000111 57 00111001 107 01101011 157 10011101 207 11001111
8 00001000 58 00111010 108 01101100 158 10011110 208 11010000
9 00001001 59 00111011 109 01101101 159 10011111 209 11010001
10 00001010 60 00111100 110 01101110 160 10100000 210 11010010
11 00001011 61 00111101 111 01101111 161 10100001 211 11010011
12 00001100 62 00111110 112 01110000 162 10100010 212 11010100
13 00001101 63 00111111 113 01110001 163 10100011 213 11010101
14 00001110 64 01000000 114 01110010 164 10100100 214 11010110
15 00001111 65 01000001 115 01110011 165 10100101 215 11010111
16 00010000 66 01000010 116 01110100 166 10100110 216 11011000
17 00010001 67 01000011 117 01110101 167 10100111 217 11011001
18 00010010 68 01000100 118 01110110 168 10101000 218 11011010
19 00010011 69 01000101 119 01110111 169 10101001 219 11011011
20 00010100 70 01000110 120 01111000 170 10101010 220 11011100
21 00010101 71 01000111 121 01111001 171 10101011 221 11011101
22 00010110 72 01001000 122 01111010 172 10101100 222 11011110
23 00010111 73 01001001 123 01111011 173 10101101 223 11011111
24 00011000 74 01001010 124 01111100 174 10101110 224 11100000
25 00011001 75 01001011 125 01111101 175 10101111 225 11100001
26 00011010 76 01001100 126 01111110 176 10110000 226 11100010
27 00011011 77 01001101 127 01111111 177 10110001 227 11100011
28 00011100 78 01001110 128 10000000 178 10110010 228 11100100
29 00011101 79 01001111 129 10000001 179 10110011 229 11100101
30 00011110 80 01010000 130 10000010 180 10110100 230 11100110
31 00011111 81 01010001 131 10000011 181 10110101 231 11100111
32 00100000 82 01010010 132 10000100 182 10110110 232 11101000
33 00100001 83 01010011 133 10000101 183 10110111 233 11101001
34 00100010 84 01010100 134 10000110 184 10111000 234 11101010
35 00100011 85 01010101 135 10000111 185 10111001 235 11101011
36 00100100 86 01010110 136 10001000 186 10111010 236 11101100
37 00100101 87 01010111 137 10001001 187 10111011 237 11101101
38 00100110 88 01011000 138 10001010 188 10111100 238 11101110
39 00100111 89 01011001 139 10001011 189 10111101 239 11101111
40 00101000 90 01011010 140 10001100 190 10111110 240 11110000
41 00101001 91 01011011 141 10001101 191 10111111 241 11110001
42 00101010 92 01011100 142 10001110 192 11000000 242 11110010
43 00101011 93 01011101 143 10001111 193 11000001 243 11110011
44 00101100 94 01011110 144 10010000 194 11000010 244 11110100
45 00101101 95 01011111 145 10010001 195 11000011 245 11110101
46 00101110 96 01100000 146 10010010 196 11000100 246 11110110
47 00101111 97 01100001 147 10010011 197 11000101 247 11110111
48 00110000 98 01100010 148 10010100 198 11000110
49 00110001 99 01100011 149 10010101 199 11000111
50 00110010 100 01100100 150 10010110 200 11001000

S+S REGELTECHNIK GMBH

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SplusS User Manuals

Related Manuals