Danfoss BB012DS Solenoid coil Installation Guide
- May 15, 2024
- Danfoss
Table of Contents
Danfoss BB012DS Solenoid coil
Parts List
-
IP00/PD3 Spade
-
IP65/PD3 IP67/PD4 Cable plug
-
IP67/PD4 Terminal box
-
IP67/PD4 Molded cable
Installation Instruction
Technical Specification
Type of control | 1 |
---|---|
Class of protection | Class I |
Ambient temperature | See Tambien on coil |
Voltage variation Voltage tolerances | For voltage variation, see print on coil |
For voltage tolerances see datasheet, when ordering the coil
Humidity| Only none-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation is to be expected.
Ball pressure test| 200 °C (392 °F)
Impulse withstand voltage| Terminal box Cable Spade| 4.0 kV at altitude <4000
m (13123 ft)
4.0 kV at altitude <4000 m (13123 ft)
4.0 kV at altitude <4000 m (13123 ft)
Plug| 4.0 kV at altitude <2000 m (6561 ft)
3.1 kV 2000 m<altitude<4000 m (6561<altitude<13123 ft)
Overvoltage category| III
Degree of protection IPXX Pollution degree PDX| Enclosure rating according to
IEC standard 60529 Pollution degree according to EN 60664-1| IP67 plug| PD4
IP65 plug
IP20 pre attentional IPOD spade| PD3
Installation| Integrated control (picture A – D)
Incorporated control (picture A – D)
Independently mounted control (IP65 and IP67) (picture B – D)
Suitable cable and conductor size for terminal box| 06.6 — 011 mm (00.26 —
00.43 in)
0.75 — 1.5 mm2 (21 — 15 AWG flexible cord)
Suitable cable for cable plug| See datasheet when ordering the coil
Molded cable size Cable conductor size| Ø6.6 mm (00.26 in )
3 x 0.75 mm2 (3 x 0.001 in2)
Molded cable| The supply cord of this control cannot be replaced, if the cord
is damaged. The control should be discarded
Plugs can be removed/mounted| 10 times
Surface temperature| Independently mounted controls should be sealed of if the
coil temperature exceed higher than 85°C
- Only qualified personnel is allowed to install or maintain this product
- Disconnect the power when dismounting the coil
- Avoid direct exposure to alkaline conditions, use in neutral conditions is recommended
- If the coil is used as independently mounted control, the end-user shall use a plastic cable gland with strain relief
- Technical specifications are according to EN60730-1.
Customers Support
Visit www.products.danfoss.com for further
technical data
For more information, visit
www.products.danfoss.es
Visit the website www.products.danfoss.fr
for more technical data
References
- Danfoss Global Product Store | Homepage
- Danfoss Spain Product Store | Homepage
- Danfoss France Product Store | Homepage
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>