SUNAMP D0085-1 AC Thor Solar Diverter Instructions
- May 15, 2024
- SUNAMP
Table of Contents
my-PV AC
THOR Solar Diverter
Wiring & Settings Instructions
D0085-1 AC Thor Solar Diverter
WARNING
All Electrical wiring must be carried out by a competent person and be in
accordance with the latest local wiring codes and regulations.
Risk of electric shock – potential dual-supply. Always isolate the power
supply/ies to the Heat Battery & Solar Diverter controller before working on
the appliances.
These settings are applicable to the following products:
- Thermino ePlus with PV02 Optimino Key (D0083 – Section 6.3.2 for wiring instructions & Figure 1 below)
- Thermino xPlus with any “02” Optimino Key (D0084 – Section 6.3.2 for wiring instructions & Figure 1 below)
Wiring Setup – my-PV AC•THOR & Thermino ePlus & xPlus
Note:
Heat Battery Controller Connection above only shows Power Terminal
connections, for other Heat Battery wiring, please reference to Installation
Manual provided with Heat Battery.
AC•THOR Quickstartguide and Operation manual
|
---|---
https://www.my-
pv.com/en/info/downloads/?lang=&docart=&product=AC%E2%80%A2THOR&search=Quickstart|
https://www.my-
pv.com/en/info/downloads?alias=AC%E2%80%A2THOR%20Operation%20manual
System overview (on-grid systems)
Optional signal sources
my-PV WiFi Meter | Compatible manufacturers |
---|---|
https://www.my- pv.com/en/info/downloads?product=WiFi%20Meter&lang=en&docart=Montage%20und%20Betriebsanleitung| https://www.my-pv.com/en/info/compatible-manufacturers
Settings to be applied on AC•THOR
Operate the AC•THOR in operating mode M1 – Hot water
AC•THOR Temperature Sensor: Route the Temperature sensor into the Heat Battery
Case between the top Insulation layers of the Heat Battery. Please do not
insert this into the Heat Battery inner cell or temperature sensor pocket.
Setting Boost Times: Boost times can be set by accessing the “Hot Water”
section in the Main Menu. Here, it is also possible to set the time, duration
and days of the week to which to apply the Boost Times.
Applying a Manual Boost: A Manual Boost can be applied by pressing the button
“Single-boost” on the Main Page of the my-PV AC•THOR. The Boost can be
cancelled by pressing the button once again.
Legionella: Ensure that all Legionella functions on the my-PV AC•THOR are
disabled. This can be done by accessing the “Legionella-Mode” in the Main
Menu, and setting “Prevention of Legionella” to “Off”.
Part Number: D0085-1