ECR UH15B-K Cast Iron Gas Fired Boilers Instruction Manual
- May 15, 2024
- ECR
Table of Contents
- UH15B-K Cast Iron Gas Fired Boilers
- Specifications:
- Product Usage Instructions:
- 1 – Physical Data:
- 2 – Safety Symbols And Warnings:
- 3 – Locating The Boiler:
- 4 – Connecting Supply And Return Piping:
- Q: Where can I find the parts list for the boiler?
- Q: How often should I check for updates on the manufacturer’s
UH15B-K Cast Iron Gas Fired Boilers
Specifications:
- Model: 15B-K, UH15B-K
- Certification: C.S.A. Certified for Natural Gas or Propane
- Working Pressure: Tested for 50 psi. ASME
- Manufacturer: ECR International Inc.
- Address: 2201 Dwyer Avenue, Utica, NY 13501
- Contact: Tel. 800 325 5479, Website: www.ecrinternational.com
Product Usage Instructions:
1 – Physical Data:
Refer to the manual for detailed physical data such as
dimensions, weight, and other relevant information.
2 – Safety Symbols And Warnings:
Review the safety symbols and warnings provided in the manual to
ensure safe operation of the boiler.
3 – Locating The Boiler:
Follow the installation requirements outlined in the manual for
proper location of the boiler. Ensure minimum clearances to
combustible construction are maintained.
3.1 Installation Requirements:
Adhere to the installation requirements specified in the manual
to ensure proper functioning of the boiler.
3.2 Minimum Clearances To Combustible Construction:
Maintain minimum clearances to combustible construction as per
the guidelines provided in the manual.
3.3 Recommended Clearances For Service:
Recommended clearances for service should be followed to
facilitate maintenance and servicing of the boiler.
3.4 Boiler Location Considerations:
Consider various factors for determining the optimal location
for the boiler as detailed in the manual.
4 – Connecting Supply And Return Piping:
Follow the steps below for connecting supply and return
piping:
4.1 Connection Locations:
Identify and connect supply and return piping at the designated
locations specified in the manual.
4.2 Safety Relief Valve Installation:
Install the safety relief valve according to the instructions
provided to ensure proper operation of the system.
4.3 Flush And Rinse System:
Flush and rinse the system as outlined in the manual to remove
any impurities before operation.
4.4 Water Treatment:
Implement water treatment measures as recommended to maintain
the efficiency and longevity of the boiler.
4.5 Supply And Return Requirements:
Ensure that supply and return requirements are met to optimize
performance and efficiency.
4.6 Special Conditions:
Take into account any special conditions specified in the manual
for proper installation and operation.
Frequently Asked Questions (FAQ):
Q: Where can I find the parts list for the boiler?
A: Refer to manual 240013663 included with your boiler
literature package for the parts list.
Q: How often should I check for updates on the manufacturer’s
website?
A: It is recommended to check the manufacturer’s website
frequently for updates related to your boiler model.
CAST IRON GAS FIRED BOILERS FOR FORCED HOT WATER
With Hydrolevel 4200 Control
INSTALLATION, OPERATION & MAINTENANCE MANUAL
Models
15B-K
UH15B-K
C.S.A. Certified For Natural Gas Or
Propane
Tested For 50 psi. ASME
Working Pressure
Manufactured by: ECR International Inc. 2201 Dwyer Avenue, Utica, NY 13501
Tel. 800 325 5479 www.ecrinternational.com PN 240013661 REV. B [02/10/2023]
VERIFY CONTENTS RECEIVED
Fully Assembled Boiler
Vent Damper
Draft Hood
Pump (Optional)
*Drain Valve
*ASME Safety Relief Valve
A. This Instruction, Parts List and User Manual
B.Warranty Information
C. Wire Diagram
*Tridicator
*Black Iron Fittings (see parts list for sizes
and use)
Document Package
*Junction Box
- Items found in parts box included with your boiler.
*Circulator Harness
For Parts lists see manual 240013663 included with your boiler literature package.
KEEP THIS MANUAL NEAR BOILER RETAIN FOR FUTURE REFERENCE
Check our website frequently for updates: www.ecrinternational.com
Information and specifications outlined in this manual in effect at the time
of printing of this manual. ECR International reserves the right to
discontinue, change specifications or system design at any time without
notice and without incurring any obligation, whatsoever.
2
PN 240013661 Rev. B [02/10/2023]
TABLE OF CONTENTS
1 – Physical Data ……………………………………………………………………………………………………………………… 4
2 – Safety Symbols And Warnings……………………………………………………………………………………………….. 5
3 – Locating The Boiler ……………………………………………………………………………………………………………… 7
3.1 Installation Requirements …………………………………………………………………………………………………… 7
3.2 Minimum Clearances To Combustible Construction
7
3.3 Recommended Clearances For Service……………………………………………………………………………………. 7
3.4 Boiler Location Considerations …………………………………………………………………………………………….. 8
4 – Connecting Supply And Return Piping …………………………………………………………………………………….. 9
4.1 Connection Locations ………………………………………………………………………………………………………… 9
4.2 Safety Relief Valve Installation
10
4.3 Flush And Rinse System ………………………………………………………………………………………………….. 11
4.4 Water Treatment …………………………………………………………………………………………………………… 11
4.5 Supply And Return Requirements ……………………………………………………………………………………….. 12
4.6 Special Conditions ………………………………………………………………………………………………………….. 12
5- Ventilation & Combustion Air ……………………………………………………………………………………………….. 19 5.1 Requirements………………………………………………………………………………………………………………… 19
6 – Vent System Modification ……………………………………………………………………………………………………. 20 6.1 Removal Of Existing Boiler From Venting System …………………………………………………………………….. 20
7 – Vent Installation ……………………………………………………………………………………………………………….. 21 7.1 Check Your Chimney ……………………………………………………………………………………………………….. 21 7.2 Requirements………………………………………………………………………………………………………………… 21 7.3 Chimney Inspection ………………………………………………………………………………………………………… 21 7.4 Vent Pipe……………………………………………………………………………………………………………………… 21
8 – Vent Damper Installation & Instructions……………………………………………………………………………….. 22 8.1 Vent Damper ………………………………………………………………………………………………………………… 22
9 – Connecting Gas Service ………………………………………………………………………………………………………. 24 9.1
General ……………………………………………………………………………………………………………………….. 24
9.2 Leak Check Gas Piping …………………………………………………………………………………………………….. 24
10 – Electrical ………………………………………………………………………………………………………………………… 25 10.1
Electrical Wiring……………………………………………………………………………………………………………. 25
10.2 Thermostat Installation…………………………………………………………………………………………………… 25
11 – Wiring Diagrams …………………………………………………………………………………………………………….. 26
12 – Lighting Instructions………………………………………………………………………………………………………… 28 12.1 Lighting Procedure For Boiler With Intermittent Pilot System……………………………………………………….28 12.2 Operating Instructions For Intermittent Pilot System…………………………………………………………………28 12.3 To Turn Off Gas To The Appliance ………………………………………………………………………………………. 28
13 – Normal Sequence Of Operation ………………………………………………………………………………………….. 29 13.1 General ……………………………………………………………………………………………………………………… 29
14 – General Maintenance And Care Instructions………………………………………………………………………… 30 14.1 Seasonal Startup ………………………………………………………………………………………………………….. 30 14.2 Clean Flue Gas Passageways …………………………………………………………………………………………… 30 14.3 General Maintenance……………………………………………………………………………………………………… 31 14.4 Adjusting Gas Input ………………………………………………………………………………………………………. 32
15 – Ratings And Capacities……………………………………………………………………………………………………… 33
Appendix A – Control Function ………………………………………………………………………………………………….. 34 A-1. Intermittent Pilot…………………………………………………………………………………………………………… 35
Appendix B – Vent Damper Installation ……………………………………………………………………………………… 37 B.1 Damper Installation ………………………………………………………………………………………………………… 37 B.2 Vent Damper ………………………………………………………………………………………………………………… 37 B.3 Vent Damper Harness – Molex Plugs…………………………………………………………………………………….. 38 B.4 Vent Damper Troubleshooting Guide…………………………………………………………………………………….. 39
3
PN 240013661 Rev. B [02/10/2023]
Model # Sections A Width with Jacket
B Vent Location (Half Width)
C Height
D Damper Height
E Depth w/o Draft Hood Installed
F Depth W/ Draft Hood Installed
G Flue Diameter Supply & Return Tappings Natural Gas Inlet Relief Valve NPT
Drain Valve NPT Heating Water Content, Gal (Liters) Air Cushion Tank, Gal
(Liters) Estimate.*
(Actual Based on System Size)
Boiler Weight, less pkg – Lbs (KG) Shipping Weight, lbs (KG)
15B-060K UH15B-060K
3 13-³/8″ 340 mm 6-³/4″ 171 mm 32-¹/8″ 816 mm
6″ 153 mm
22″ 559 mm
26″ 660 mm
4″ 102 mm 1-¹/4″ NPT 1/2″ NPT 3/4″ NPT 3/4″ NPT 1.9 (7.2)
15 (27)*
170 (77) 215 (98)
1 – PHYSICAL DATA
15B-095K UH15B-095K
4 13-³/8″ 340 mm 6-³/4″ 171 mm 32-¹/8″ 816 mm
6″ 153 mm
22″ 559 mm
26″ 660 mm
5″ 127 mm
1-¹/4″ NPT 1/2″ NPT 3/4″ NPT 3/4″ NPT 2.3 (8.8)
15B-120K UH15B-120K
5 16-1/4″ 411 mm 8-¹/8″ 206 mm 32-¹/8″ 816 mm 6-¹/2″ 165 mm
22″ 559 mm
26″ 660 mm
6″ 152 mm
1-¹/4″ NPT 1/2″ NPT 3/4″ NPT 3/4″ NPT 2.8 (10.5)
15B-150K UH15B-150K
6 19″ 483 mm 9-¹/2″ 241 mm 32-¹/8″ 816 mm 6-¹/2″ 165 mm 22″ 559 mm 26″ 660 mm
6″ 152 mm 1-¹/4″ NPT 1/2″ NPT 3/4″ NPT 3/4″ NPT 3.2 (12.2)
30 (114)*
30 (114)*
30 (114)*
210 (96) 250 (114)
250 (114) 295 (134)
280 (128) 335 (152)
15B-175K UH15B-175K
7 21-7/8″ 555 mm 10-¹5/16″ 278 mm 32-¹/8″ 816 mm
7″ 178 mm
22″ 559 mm
26″ 660 mm
7″ 178 mm 1-¹/4″ NPT 1/2″ NPT 3/4″ NPT 3/4″ NPT 3.7 (13.9)
30 (114)*
320 (145) 385 (175)
15B-205K UH15B-205K
8 27-¹/2″ 700 mm 13-³/4″ 349 mm 32-¹/8″ 816 mm
7″ 178 mm
22″ 559 mm
26″ 660 mm
7″ 178 mm 1-¹/4″ NPT 3/4″ NPT 3/4″ NPT 3/4″ NPT 4.1 (15.6)
30 (114)*
350 (159) 420 (191)
15B-235K UH15B-235K
9 27-¹/2″ 700 mm 13-³/4″ 349 mm 32-¹/8″ 816 mm
7″ 178 mm
22″ 559 mm
26″ 660 mm
7″ 178 mm 1-¹/4″ NPT 3/4″ NPT 3/4″ NPT 3/4″ NPT 4.6 (17.3)
30 (114)*
390 (177) 465 (211)
Figure 1 – Dimensions Front View
“A” “B”
“G”
Right Side View “F”
“E”
“D”
2″ (50.8 mm)
“C”
21/8″ (549.3 mm)
7″ (117.8mm)
12¹/2″ (317.5 mm)
4
GAS SUPPLY
16³/8″ (416mm)
23″ (584mm) 7¹/8″ (181mm)
PN 240013661 Rev. B [02/10/2023]
2 – SAFETY SYMBOLS AND WARNINGS
Become familiar with symbols identifying potential hazards. FOR YOUR SAFETY READ BEFORE OPERATING
This is the safety alert symbol. Symbol alerts you to potential personal injury hazards. Obey all safety messages following this symbol to avoid possible injury or death.
! DANGER
! DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or
serious injury.
! WARNING
Indicates a hazardous situation which, if not avoided, could result in death
or serious injury.
! CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor
or moderate injury.
NOTICE
Used to address practices not related to personal injury.
2.1. Safety Information
Boiler installation shall be completed by qualified agency.
! WARNING
Fire, explosion, asphyxiation and electrical shock hazard. Improper
installation could result in death or serious injury. Read this manual and
understand all requirements before beginning installation.
! WARNING
Do not tamper with or use this boiler for any purpose other than its intended
use. Failure to follow these instructions could result in death or serious
injury. Use only manufacturer recommended parts and accessories.
! CAUTION
Laceration, burn hazard. Metal edges and parts may have sharp edges and/or may
be hot. Use appropriate personal protection equipment to include safety
glasses and gloves when installing or servicing this boiler. Failure to follow
these instructions could result in minor or moderate injury.
Hot Water Can Scald! Water heated to temperature for clothes washing, dish
washing and other sanitizing needs can scald and cause permanent injury.
Children, elderly, and infirm or physically handicapped persons are more
likely to be permanently injured by hot water. Never leave them unattended in
bathtub or shower. Never allow small children to use a hot water tap or draw
their own bath.
If anyone using hot water in the building fits the above description, or if
state laws or local codes require certain water temperatures at hot water
taps, you must take special precautions:
· Use lowest possible temperature setting.
· Install some type of tempering device, such as an automatic mixing valve, at
hot water tap or water heater. Automatic mixing valve must be selected and
installed according to manufacturer’s recommendations and instructions.
· Water passing out of drain valves may be extremely hot. To avoid injury: ·
Make sure all connections are tight. · Direct water flow away from any person.
Water
Temperature Setting 120° F
1st Degree Burn Exposure Time For
An Adult
1 minute
2nd and 3rd Degree Burn Exposure Time For An Adult 5 minutes
130° F
5 seconds
30 seconds
140° F
2 seconds
5 seconds
150° F
1 second
1.5 seconds
160° F
Instantaneous
0.5 seconds
Note: Warning for Infants, Children, and Elderly: Great care must be taken when exposing the aforementioned groups to warm or hot water as they can be badly burned in exposure times less than half of the time for an adult.
5
PN 240013661 Rev. B [02/10/2023]
2 – SAFETY SYMBOLS AND WARNINGS
! WARNING
Combustion chamber insulation in this product contains ceramic fiber material.
Ceramic fibers can be converted to cristobalite in very high temperature
applications. The International Agency for Research on Cancer (IARC) has
concluded, Crystalline silica inhaled in the form of quartz or cristobalite
from occupational sources is carcinogenic to humans (Group1). Avoid breathing
dust and contact with skin and eyes. Use NIOSH certified dust respirator
(N95). This type of respirator is based on the OSHA requirements for
cristobalite at the time this document was written. Other types of respirators
may be needed depending on the job site conditions. Current NIOSH
recommendations can be found on the NIOSH website
https://www.cdc.gov/niosh/topics/ silica/. NIOSH approved respirators,
manufacturers, and phone numbers are also listed on this website. Wear long-
sleeved, loose fitting clothing, gloves, and eye protection. Apply enough
water to the combustion chamber lining to prevent dust. Wash potentially
contaminated clothes separately from other clothing. Rinse clothes washer
thoroughly.
NIOSH stated First Aid. Eye: Irrigate immediately. Breathing: Fresh air.
! WARNING
Keep boiler area clear and free from combustible materials, gasoline and other
flammable vapors and liquids. DO NOT obstruct air openings to the boiler room.
Modification, substitution or elimination of factory equipped, supplied or
specified components may result in personal injury or loss of life.
Installation and service of this boiler shall be performed by a qualified
installer. When this product is installed in the Commonwealth of Massachusetts
the installation shall be performed by a Licensed Plumber or Licensed Gas
Fitter.
!! WARNING
This product contains Fibrous glass. Fibrous glass is a synthetic fiber made
from tiny particles of glass. Fibrous glass has been classified as a possible
human carcinogen. When disturbed as a result of servicing or repair, fibrous
glass becomes airborne and, if inhaled, may be hazardous to your health. It
can harm the eyes, skin, and the lungs. Airborne fibers from these materials
have been listed by the State of California as a possible cause of cancer
through inhalation. Adhere to the following precautions and procedures. Avoid
breathing dust and contact with skin and eyes. Use NIOSH certified dust
respirator (e.g., N95). Other types of respirators may be needed depending on
the job site conditions. Current NIOSH recommendations can be found on the
NIOSH website https://www.cdc.gov/niosh/ Approved respirators, manufacturers,
and phone numbers are also listed on this website. Wear appropriate personal
protective clothing to prevent skin contact, as well as gloves and eye
protection. Wash skin daily at end of each work shift, and prior to eating,
drinking, smoking, etc. Workers whose clothing may have been contaminated
should change into uncontaminated clothing before leaving the work premises.
Wash potentially contaminated clothes separately from other clothing. Rinse
clothes washer thoroughly. Follow all Local, State and Federal guidelines for
disposal.
NIOSH stated First Aid. Eye: Irrigate immediately. Breathing: Fresh air.
! WARNING
Fire, Explosion, Asphyxiation, Electrical shock hazard! Flooding will result
in damages such as electrical problems, corrosion, inoperative parts, mold and
other unforeseen issues which can occur over time. Any equipment determined by
a professional as damaged by a flood, defined as excess of water or other
liquid, shall be replaced. Failure to follow these directions will result in a
Hazardous Situation.
2.2 For Your Safety Installer shall verify that at least one carbon monoxide alarm has been installed within a residential living space or home, following the alarm manufacturer’s instructions and applicable codes before putting the appliance into operation.
6
PN 240013661 Rev. B [02/10/2023]
3 – LOCATING THE BOILER
! WARNING
Fire hazard! Do not install boiler on carpeting. Failure to follow these
instructions could result in death or serious injury.
! CAUTION
Boiler weight exceeds 200 pounds (90.7 kg). Do not lift boiler without
assistance.
3.1 Installation Requirements
1. Installation shall conform to the requirements of the authority having
jurisdiction or, in the absence of such requirements, to the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane Installation Code,
CAN/CSA B149. Where required by the authority having jurisdiction, the
installation must conform to the Standard for Controls and Safety Devices for
Automatically fired Boilers, ANSI/ASME CSD-1.
2. Boiler series is classified as a Category I. Vent installation shall be in
accordance with “Venting of Equipment”, of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or “Venting Systems and Air Supply for Appliances,” of the
Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes.
3. Boiler has met safe lighting and other performance criteria with the gas
manifold and control assembly on the boiler per the latest revision of ANSI
Z21.13/CSA 4.9.
4. Install boiler such that gas ignition system components are protected from
water (dripping, spraying, rain, etc.) during appliance operation and service,
(circulator replacement, condensate trap, control replacement, etc.).
5. Locate boiler on level, solid base as near chimney as possible and
centrally located with respect to heat distribution system as practical.
6. Horizontal vent run to chimney shall be as short as practicable. Refer to
NFPA 54 to determine maximum permissible horizontal run for chimney type and
height.
7. Verify floor will support weight of boiler, water and equipment.
8. Boiler may be installed on combustible floor. Do not install boiler on
carpeting.
9. Do not install where gasoline or other flammable liquids or vapors will be
stored or used. See Table 3-1 page 8, Contaminants.
10. Chimney shall be lined in a manner acceptable to the authority having
jurisdiction.
11. Garage installation boiler shall be 18″ above floor.
3.2 Minimum Clearances to Combustible Construction
1. Minimum clearances to combustible construction are:
Top Front Flue Connector Rear Both Sides Hot Water Piping
10 inches (254mm) Alcove* 6 inches (152mm) 6 inches (152mm) 2 inches (51 mm) Per Local Code
- Definition of Alcove is three sided space with no wall in front of boiler. ANSI standard for alcove is 18 inches from front of appliance to leading edge of side walls as shown below.
Minimum Clearances to Combustible Construction (as seen from above)
6″
2″
2″
BOILER
18″
Front NOTE: Greater clearances for access and servicing should
supersede fire protection clearances.
3.3 Recommended Clearances for Service 1. Allow 24 inches (610 mm) at front
and one side for
servicing and cleaning. 2. When installed in utillity room, door should be
wide
enough to allow largest boiler part to enter, or to permit replacement of
another applicance such as a water heater.
7
PN 240013661 Rev. B [02/10/2023]
3 – LOCATING THE BOILER
3.4 Boiler Location Considerations · Ambient room temperature always above
32°F (0°C) to prevent the potential of freezing.
· Drainage of water (or water/ antifreeze solution) during boiler service or
from safety relief valve discharge.
· Access to system water piping, gas supply, and electrical service.
· Boiler shall be installed on flat level surface which is capable of
supporting the weight of the boiler, water, and equipment.
· Raise boiler above the floor on blocks if floor may get wet.
· Water, gas, and electrical may connect to either side of boiler as desired.
· Horizontal run to chimney shall be as short as possible.
· System piping exposed to freezing conditions: Use
inhibited propylene glycol solutions certified by fluid manufacturer for use
with closed water heating system. Do not use automotive or ethylene glycol.
Maximum recommended mixture 50% glycol.
Table 3-1: CONTAMINANTS
Items to Avoid Chlorine, Fluorine, and Compounds
Products Which May Contain These Items
Spray cans containing chlorofluorocarbons Chlorinated waxes/cleaners Chlorine-
based swimming pool chemicals Calcium chloride used for thawing Sodium
chloride used for water softening Swimming pool or spa chemicals De-icing
salts or chemicals Carbon Tetrachloride
Areas Where These Items May Be Found
Swimming pools and pool storage areas Laundry room (Note 2) Confined storage
areas
Airborne Particulates
Drywall dust Road or gravel dust Dryer lint Cat litter
Construction or remodelling areas (Note 1) Laundry room (Note 2)
Acids, Solvents, etc.
Paint, Varnish, Turpentine, etc. Cleaning Solvents Hydrochloric acid/muriatic acid Cements, adhesives and glues
Photo processing plants Garages with workshops Furniture refinishing areas and establishments
Laundry Chemicals Other Notes:
Laundry detergents, bleaches, fabric softeners, etc.
Antistatic fabric softeners (dryer sheets)
Dry cleaning/laundry areas and establishments
Permanent wave solutions
Refrigerants (Freon, etc) (only where the refrigerant may be leaking from the
appliance)
Beauty shops Refrigeration repair shops
1. It is recommended the boiler be isolated and not operated during
construction/ renovation. Excessive particles ingested by the boiler may
accumulate in the flueway passages possibly resulting in unsafe operation. In
this case, unit servicing shall include cleaning of flueway passages and
burner ports.
2. If locating boiler in laundry room is unavoidable, it is manufacturer
recommended the room be generously ventilated (well in excess of combustible
air requirements), and homeowner seal laundry supply containers, and minimize
room vapors.
3. Piping allowing fresh air in should also be considered. See Section 5-1.
8
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING
! WARNING
Burn and scald hazard. Boiler supplied with dust caps on supply and return
tappings (4). Shall remove all four (4) caps and plumb before filling boiler
with water. Failure to follow these instructions could result in death or
serious injury.
4.1 Connection Locations
· Boiler has one supply and one return tapping on each side (4 total). Boiler
supplied with dust caps only. Remove all four (4) caps and plumb before
filling boiler with water.
· Supply and return may be piped to either side of boiler, as desired. Both
supply and return shall be on same side of boiler. Do not “cross pipe” as
boiler may not deliver adequate heat with cross piping.
· ASME relief valve may be located off unused supply tapping IN UPRIGHT
POSITION ONLY.
· Drain valve may be located off of unused return tapping using a contractor
supplied tee, piped right or left side as desired. See Figure 4-3
· Unused supply and return tappings may be capped, as desired. Relief valve
and drain valve may be located on near boiler piping using contractor supplied
tees with no valves.
Figure 4-1 Piping Options
PIPING OPTIONS THIS BOILER HAS TWO SUPPLY (OUTLET) AND TWO RETURN (INLET)
TAPPINGS. PIPE SUPPLY AND RETURN ON THE SAME SIDE (SEE FIG. A AND B)
DO NOT CROSS PIPE – (SEE FIG. C AND D)
SUPPLY
FRONT
FRONT
SUPPLY
RETURN
FIG.1A.
RETURN
FIG. 2B
FRONT
FRONT
FIG .3C.
FIG.4D.
9
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING
! WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water
during operation. Install discharge piping per these instructions. Failure to
follow these instructions could result in death or serious injury.
! WARNING
Burn and scald hazard. Safety relief valve shall be installed with spindle in
upright position only, following ASME BPV code. Failure to follow these
instructions could result in death or serious injury.
Figure 4-2 – Safety Relief Valve
RELIEF VALVE On Opposite side of supply
DISCHARGE LINE
Alternate Location Piped in Supply Line
(Contractor supplied fittings)
4.2 Safety Relief Valve Installation See Figure 4-2
Discharge line shall be installed to relief valve outlet connection to avoid
burns, scalding, or water damage due to discharge of steam and/or hot water
during operation. Discharge line shall:
A. connect to relief valve outlet and piped down to safe point of disposal.
Check local codes for
maximum distance from floor or allowable safe point of discharge. B. be of
pipe size equal to or greater than that of the relief valve outlet over the
entire length of discharge line; C. have no intervening shutoff valve between
safety relief valve and discharge to atmosphere (do not plug or place any
obstruction in discharge line. D. terminate freely to atmosphere where any
discharge will be clearly visible and at no risk of freezing; E. allow
complete drainage of the valve and the discharge line; F. be independently
supported and securely anchored to avoid applied stress on the relief valve;
G. be as short and straight as possible; H. terminate with plain end (not
threaded); I. be constructed of material suitable for exposure to temperatures
of 375° F (191°C); or greater. J. Terminate freely to atmosphere where
discharge is clearly visible and no risk of freezing.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for
additional installation requirements.
Check local codes for maximum distance from floor or allowable
safe point of discharge.
Do Not Install Pressure
Relief Valve Horizontally
Figure 4-3 Optional Locations for Drain Valve
Left Side Drain Valve Location With
Standard
Manufacturer Supplied Hardware
Optional Right side Drain Valve Location
with Contractor Supplied Tee
10
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING
! WARNING
· Poison hazard. Ethylene glycol is toxic. Do not use ethylene glycol.
· Never use automotive or standard glycol antifreeze, even ethylene glycol
made for hydronic systems.
· Ethylene glycol can attack gaskets and seals used in hydronic systems.
· Do not use petroleum based cleaning or sealing compounds boiler system.
· Do not fill boiler or boiler system with softened water.
· Use only inhibited propylene glycol solutions certified by fluid
manufacturer as acceptable for use with closed water heating system.
· Thoroughly clean and flush any system that used glycol before installing new
Boiler.
· Provide user with Material Safety Data Sheet (MSDS) on fluid used.
4.4 Water Treatment
Manufacturer recommends a water analysis be done on
water used to fill the system. Treatment may be required based on the analysis
results.
For hard water or pH below 7.0 consult your local water treatment company.
· If CH water is very hard or full of impurities, it must be
adequately filtered and treated, otherwise damage and/ or malfunction could be
caused. Recommended water quality is:
o Hardness
Less than 150 mg/L
o Acidity level 7-8 pH
o Sediments Particle size less than 50 micron
· If the water quality is outside these ranges, consult a local water treatment specialist for recommendations.
· If the water is treated, do not use petroleum based products or products containing mineral oil or hydrocarbons in order to avoid likely damage to parts made from rubber compounds (o-rings).
NOTICE
If damage due to frozen pipes is a possibility, install appropriate safeguards
and alarms on the heating system to prevent property damage due to frozen and
burst pipes should the boiler heating system become inoperative due to a power
outage, safety lockout or component failure.
4.3 Flush and Rinse System
Flush the entire system and rinse thoroughly to ensure no sludge will be
introduced into the heating body of the boiler.
11
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING
4.5 Supply and Return Requirements
1. Boiler used in connection with refrigeration system, install so chilled
medium is piped in parallel with boiler with appropriate valves to prevent
chilled medium from entering boiler. See Figure 4-4 page 13.
2. Boiler piping system of hot water boiler connected to heating coils
located in air handling units where they may be exposed to refrigerated air
circulation must be equipped with flow control valves or other automatic means
to prevent gravity circulation of boiler water during cooling cycle.
3. Hot water boilers installed above radiation level or as required by
authority having jurisdiction shall be provided with low water cut-off device
(Factory equipped).
4. Boiler connected to heating system utilizing multiple zoned circulators,
each circulator must be supplied with flow control valve to prevent gravity
circulation.
5. Hot water boilers and system must be filled with water and maintained to
minimum pressure of 12 psi.
! WARNING
Asphyxiation hazard! Gradual flueway blockage resulting from condensate
induced corrosion may block boiler passages, resulting in carbon monoxide and
or flame rollout. Install bypass piping if return temperature is under 130° F.
Failure to follow these instructions could result in death or serious injury.
7. Installation using circulators and zone valves are shown in Figures 4-4
through 4-9. For further piping information refer to AHRI Installation and
Piping Guide.
8. Install discharge piping from safety relief valve. See Warning, Page 10
and Figure 4-2.
4.6 Special Conditions
Note
Do not expose boiler and piping to freezing temperatures.
· System piping exposed to freezing conditions: Use inhibited propylene glycol
solutions certified by fluid manufacturer for use with closed water heating
system. Do not use automotive or ethylene glycol.
· Boiler installed above radiation level (or as required by authority having
jurisdiction). Integral low water cutoff is provided in boiler.
· Boiler used in connection with refrigeration system. Install piping in
parallel with boiler, with appropriate valves to prevent chilled medium from
entering boiler.
· System piping connected to heating coils located in air handling unit
exposed to refrigerated air circulation. Install flow control valves or other
automatic means to prevent gravity circulation of boiler water during cooling
cycle.
6. Bypass piping gives ability to adjust boiler water temperature to fit
system or condition of installation. This method of piping, however, is not
typically required for baseboard heating systems. Typical installations where
bypass piping is required are as follows:
A. This method is used to protect boilers from condensation forming due to low
temperature return water (Below 130° F). Generally noticed in large converted
gravity systems other large water volume systems, and in-floor heating
systems. Figures 4-5 and 4-6 pages 14-15.
B. These methods are used to protect systems using radiant panels and material
they are encased in from high temperature supply water from boiler and protect
boiler from condensation.
NOTE#1: When using bypass piping, adjust valves V1 & V2 until desired system
temperature is obtained.
NOTE#2: Bypass loop must be same size piping as supply and return piping.
12
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING PIPING LEGEND:
Circulators in following illustrations are mounted on system supply side,
mounting on system return side is also acceptable practice. Figure 4-4 –
Circulators Mounted on Supply System, Boiler Used In Configuration with
Chiller System. See Special Conditions, Below
13
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING PIPING LEGEND:
Figure 4-5 – Bypass Piping With Automatic Mixing Valve
BACK FLOW VALVE ASME RELIEF VALVE
14
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING PIPING LEGEND:
Figure 4-6 – Bypass Piping – Fixed Low Temp Only With Zone Valve
ASME RELIEF VALVE
- Manually adjust until proper system temperature is reached.
15
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING PIPING LEGEND:
Figure 4-7 – Bypass Piping (4-Way Valve Option With Circulator On Supply side)
FLOW CONTROL VALVE
ASME RELIEF VALVE
DRAIN VALVE
16
PN 240013661 Rev. B [02/10/2023]
4 – CONNECTING SUPPLY AND RETURN PIPING PIPING LEGEND:
Figure 4-8 – Single Zone System With DHW Priority
Back Flow Valve
ASME RELIEF VALVE
DRAIN VALVE
Purge Valve
17
PN 240013661 Rev. B [02/10/2023]
FROM SYSTEM
4 – CONNECTING SUPPLY AND RETURN PIPING PIPING LEGEND:
Figure 4-9 – Multi Zone System With Zone Valves And DHW Priority (With Zone Valve)
TO SYSTEM
Tank Sensor Optional Indirect DHW Tank DHW Pump
CH /System Pump Make-up Water Supply
Back Flow Valve
- Hot Water Supply Tempered
T & P Relief Valve to Drain
Cold Water Supply
1
ASME Relief Valve
Note
- Manufacturer requires all domestic hot water (DHW) installations use an anti-scald valve. Local codes may require additional equipment (expansion tank, relief valves, etc.) Select and size equipment to suit installation and meet code requirements.
Note Note
1
12 po (305 mm) Distance recommandée. Ne dépassez pas 12 po (305 mm).
Refer to pump manufacturer literature for proper pump sizing.
18
PN 240013661 Rev. B [02/10/2023]
5- VENTILATION & COMBUSTION AIR
5.1 Requirements
! WARNING
Asphyxiation Hazard! Provide enough air openings to boiler/combustion area to
dilute flue gases and allow for consistent, guality combustion. Do not
obstruct air openings. Follow instructions below, to maintain adequate
combustion air. Failure to follow these instructions good result in ignition
failure, overheating, carbon monoxide, and accumulation of flue gases.
Provide combustion air and ventilation air in accordance with the section “Air
for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or Sections 8.2, 8.3 or 8.4 of Natural Gas and Propane
Installation Code, CAN/CSA B149.1, or applicable provisions of local building
codes.
Provide make-up air where exhaust fans, clothes dryers, and kitchen
ventilation equipment interfere with proper operation. If inadequate makeup
air is suspected it is always acceptable to add additional ventilation.
National Fuel Gas Code recognizes several methods of obtaining adequate
ventilation and combustion air. Requirements of the authority having
jurisdiction may override these methods.
· Engineered Installations. Must be approved by authority having jurisdiction.
· Mechanical Air Supply. Provide minimum of 0.35 cfm per [(BTU/HR)/1,000] for
all appliances located within space. Additional requirements where exhaust
fans installed. Interlock each appliance to mechanical air supply system to
prevent main burner operation when mechanical air supply system not operating.
· All Indoor Air. Calculate minimum volume for all appliances in space. Use a
different method if minimum volume not available.
A. Standard Method. Cannot be used if known air infiltration rate is less than
0.40 air changes per hour. Use equation for multiple appliances. Volume 50 ft3
x Total Input [(BTU/HR)/1,000] Table 5-1 – Space With Boiler Only
B. Known Air Infiltration Rate. See Table 5-1 for space with boiler only. Use
equation for multiple appliances. Do not use an air infiltration rate (ACH)
greater than 0.60.
Volume 21 ft3/ACH x Total Input[(BTU/HR)/1,000] Refer to National Fuel Gas
Code for opening requirements between connected indoor spaces.
· All Outdoor Air. Provide permanent opening(s) communicating directly or by
ducts with outdoors.
A. Two Permanent Opening Method. Provide opening commencing within 12 inches
of top and second opening commencing within 12 inches of bottom of enclosure.
Direct communication with outdoors or communicating through vertical ducts.
Provide minimum free area of 1 in² per 4 [(BTU/ hr)/1,000] of total input
rating of all appliances in enclosure.
Communicating through horizontal ducts. Provide minimum free area of 1 in² per
2 [(BTU/HR)/1,000] of total input rating of all appliances in enclosure.
B. One Permanent Opening Method. Provide opening commencing within 12 inches
of top of enclosure. Provide minimum clearance of 1 inch on sides/back and 6
inches on front of boiler (does not supersede clearance to combustible
materials).
· Refer to National Fuel Gas Code for additional requirements for louvers,
grilles, screens and air ducts.
· Combination Indoor and Outdoor Air. Refer to National Fuel Gas Code for
application information.
National Gas and Propane Installation Code Requires providing air supply in
accordance with:
· Section 8.2 and 8.3 when combination of appliances has a total input of up
to and including 400 [(BTU/ hr)/1,000] (120 kW).
· Section 8.4 when combination of appliances has total input exceeding 400
[(BTU/hr)/1,000] (120 kW).
· Refer to Natural Gas and Propane Installation Code for specific air supply
requirements for enclosure or structure where boiler is installed, including
air supply openings and ducts.
Room Cubic Feet Volume
Sections
3
Input BTU/HR
59,000
Standard Method
2950
Known Air Infiltration Rate Method (ACH – Air Changes Per Hour)
0.1
0.2
0.3
0.4
0.5
0.6
12390
6195
4130
3098
2478
2065
4
92,500
4625
19425
9712.5
6475
4856
3885
3238
5
120,000
6000
25200
12600
8400
6300
5040
4200
6
149,000
7450
31290
15645
10430
7823
6258
5215
7
175,000
8800
36960
18480
12320
9240
7392
6160
8
205,000
10250
43050
21525
14350
10763
8610
7175
9
235,000
11750
49350
24675
16450
12338
9870
8225
19
PN 240013661 Rev. B [02/10/2023]
6 – VENT SYSTEM MODIFICATION
6.1 Removal Of Existing Boiler From Venting System
When an existing boiler is removed from a common venting system, the system is
likely too large for proper venting of appliances still connected to it. If
this occurs, follow this test procedure:
Figure 6-1 – Typical Masonry Chimney Requirements
At time of removal of an existing boiler, the following steps shall be
followed with each appliance remaining connected to the common venting system
placed in operation, while the other appliances remaining connected to the
common venting system are not in operation.
1. Seal an unused opening in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch
and determine there is no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all
doors between the space in which the appliances remaining connected to the
common venting system are located and other spaces of the building. Turn on
clothes dryers and any other appliance not connected to the common venting
system. Turn on any exhaust fans, such as range hoods and bathroom exhausts,
so they operate at maximum speed. Do not operate a summer exhaust fan. Close
fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting
instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. Minimum draft should be -.02″ w.c.
7. After it has been determined that each appliance remaining connected to a
common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and any other gas burning
appliances to their previous condition of use.
8. Any improper operation of the common venting system should be corrected so
the installation conforms with the National Fuel gas Code, ANSI Z223.1/NFPA
54, and/or the Natural Gas and Propane Installation Code, CAN/CSA B149.1. When
re-sizing any portion of the common venting system, the common venting system
should be re-sized to approach the minimum size determined using the
appropriate tables in Chapter 13 of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, and/or the Natural Gas and Propane Installation Code, CAN/CSA
B149.1.
9. Draft pressure must be negative under all conditions with all aplliances
operating.
See NFPA for Installation Specifications Type B Vent Masonry Chimney Requirements
20
PN 240013661 Rev. B [02/10/2023]
7 – VENT INSTALLATION
! WARNING
Boiler and venting installations shall be performed
3. Boiler series is classified as a Category I. Vent installation shall be in
accordance with “Venting of
Equipment,” of the National Fuel Gas Code, ANSI
by a qualified expert and in accordance with the appropriate manual.
Installing or venting boiler or other gas appliance with improper methods or
materials may result in serious injury or death due
to fire or to asphyxiation from poisonous gases such as carbon monoxide which
is odorless and invisible.
Z223.1/NFPA 54, or “Venting Systems and Air Supply for Appliances,” of the
Natural Fuel Gas and Propane Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes.
4. Inspect chimney. Chimney shall be lined per NFPA 54/ ANSI Z223.1 or as
required by local authority. Verify chimney is constructed according to NFPA
211 and ANSI
! WARNING
Z223.1/NFPA 54. Vent connector shall be Type B or metal pipe having resistance to heat and corrosion not
Do not connect boiler to any portion of mechanical draft system operating
under positive pressure.
7.1 Check Your Chimney It must be clean, the right size, properly constructed
and in good condition. A chimney shall be lined in a manner acceptable to the
authority having jurisdiction.
less than that of galvanized sheet steel or aluminum not less than 26 gauge
thick (24 gauge for 6 and 7 inch).
5. Connect flue pipe from draft hood to chimney. Bolt or screw joints
together to avoid sags. Flue pipe should not extend beyond inside wall of
chimney more than 1/4
inch. Do not install manual damper in flue pipe or reduce size of flue outlet
except as provided by the latest revision of National Fuel Gas Code, ANSI ANSI
Z223.1/
Chimney Sizing Chimney sizing, and vent installation must be in accordance with The National Fuel Gas Code, ANSI Z223.1/NFPA 54 or CAN/CSA B149.1, or applicable provisions of local building codes.
NFPA 54 or CAN/CSA B149.1. Protect combustible ceiling
and walls near flue pipe as required by National Fuel Gas Code. Where two or
more appliances vent into a
common flue, the area of the common flue must be at least equal to the area of
the largest flue plus 50 percent of the area of each additional flue.
This is a high efficiency boiler with low stack temperature. Following recommendations are in addition to requirements of the National Fuel Gas Code.
- Type B double wall vent pipe is recommended for vent
connector. Single wall vent connectors should not be used unless following conditions are true:
a. Except for basement, boiler is not installed in
7.3 Chimney Inspection
Chimney must be clean, right size, properly constructed and in good condition.
Installation must conform to requirements of the authority having jurisdiction
or, in absence of such requirements, to The National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
unheated space.
b. Total horizontal portion of vent connector, not including elbows is less
than 5 feet in length.
2. Outside chimneys (i.e. chimneys exposed to outdoors below roof line on one
or more sides) do not use unless they are:
a. enclosed in a chase, or
b. lined with type B vent pipe, or listed flexible vent liner, or other
certified chimney lining system.
3. Where possible it is recommended to common vent boiler and water heater.
4. For multiple Category I boiler installations, consult boiler manufacturer
for venting recommendations.
5. Minimize horizontal vent length.
7.4 Vent Pipe · Connect draft hood to boiler using 2 screws (provided)
onto flue collector. Connect two safety circuit wires (attached to vent damper
harness) to blocked vent switch. See Figure 13-1. · Fasten sections of vent
pipe with 3 sheet metal screws at each joint to make piping rigid. · Support
horizontal portions of vent system to prevent sagging. · Use stove pipe wires
or metal strapping every 5′ to support pipe from above. · Vent pipe through
crawl space, use double wall vent pipe. · Vent pipe passing through
combustible wall or partition, use ventilated metal thimble. Thimble should be
4″
larger in diameter than vent pipe.
7.2 Requirements
1. Vent pipe must slope upward from the boiler not less
NOTICE
than ¼ inch for every 1 foot (21 mm/m) to verticle
Minimum Vent Pipe Clearance – Wood and other
vent terminal.
combustible materials must not be closer than 6″
2. Horizontal portions of venting system shall be supported rigidly every 5 feet and at the elbows. No
from any surface of single wall metal vent pipe. Listed Type B vent pipe or other listed venting
portion of vent pipe should have any dips or sags.
systems shall be installed in accordance with their
listing.
21
PN 240013661 Rev. B [02/10/2023]
8 – VENT DAMPER INSTALLATION & INSTRUCTIONS
8.1 Vent Damper Connecting The Vent Damper And Vent Connector Refer to page 4
for size and location of vent (flue opening).
NOTICE Damper blade on furnished vent damper has 1/2 square inch hole
(approximately 3/4″ diameter). Boilers equipped with intermittent ignition,
hole should be plugged by using plug supplied with vent damper.
Fasten sections of vent pipe with sheet metal screws to make piping rigid.
Support horizontal potions of vent system to prevent sagging. Use stovepipe
wires every 5′ to support pipe from above. Use double wall vent pipe if vent
pipe must go through crawl space. Where vent pipe passes through combustible
wall or partition, use ventilated metal thimble. Thimble should be 4 inches
larger in diameter than vent pipe.
Figure 8-1 – Vent Damper Installation
1. Follow damper installation instructions provided with damper.
2. Position furnished vent damper on top of flue outlet collar. Fasten damper
securely to flue outlet collar with sheet metal screws. Verify damper blade
has clearance to operate inside of diverter. Do not modify either draft
diverter or vent damper during installation.
As An Option
Damper may be installed in horizontal or vertical position, closer to flue
outlet collar preferred. See Figures 8-1, 8-2, 8-3 and enclosed vent damper
instructions.
3. Install vent damper to service only single boiler for which it is
intended. Damper position indicator shall be in visible location following
installation. Locate damper so it is accessible for servicing. See Figure 8-2
page 22.
4. Damper must be in the open position when appliance main burners are
operating.
5. Boiler is equipped with factory wired harness that plugs into vent damper.
6. Slope pipe up from boiler to chimney not less than 1/4″ per foot.
7. Run pipe as directly as possible with as few elbows as possible.
8. Do not connect to fireplace flue.
9. End of vent pipe must be flush with inside face of chimney flue. Use a
sealed-in thimble for chimney connection.
10. Clearance of not less than 6 inches (152mm) between Vent Damper and
combustible material must be maintained. Additional clearance should be
allowed for service of Vent Damper.
11. Vent Damper position indicator must be in visible location following
installation.
22
PN 240013661 Rev. B [02/10/2023]
8 – VENT DAMPER INSTALLATION & INSTRUCTIONS Figure 8-2 – Vent Damper Placement
Figure 8-3 – Vent Damper Position Indicator
23
PN 240013661 Rev. B [02/10/2023]
9 – CONNECTING GAS SERVICE
! DANGER
Fire Hazard. Do not use matches, candles, open flames, or other methods
providing ignition source. Failure to comply will result in death or serious
injury.
! CAUTION
Table 9-1 Min. Supply Pressure Max. Supply Pressure
Natural Gas 5″ w.c.
13.5″ w.c.
Manifold Pressure
3.5″ w.c.
Propane 11″ w.c.
13.5″ w.c.
10″ w.c. (4 sec. only)
10.5″ w.c.
WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance. · Do not touch any electrical switch; do
not use
any phone in your building. · Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s instructions. · If you cannot reach
your gas supplier, call the fire department.
! WARNING
Fire, explosion, asphyxiation and burn hazard. Boiler piping and gas
connections shall be leak tested before placing boiler in operation. Failure
to follow these instructions and or improper installation could result in
death or serious injury.
NOTICE Use of CSA approved corrugated, semi-rigid stainless steel tubing with
polyethylene jacketing is approved for use with boilers following tubing
manufacturer’s instructions. Use of flexible appliance gas tubing also known
as a “whip” is not allowed per NFPA 54.
9.2 Leak Check Gas Piping
Pressure test boiler and gas connection before placing boiler in operation. ·
Pressure test over 1/2 psig (3.5 kPa). Disconnect
boiler and its individual gas shutoff valve from gas supply system. · Pressure
test at 1/2 psig (3.5 kPa) or less. Isolate boiler from gas supply system by
closing manual gas
shutoff valve. · Locate leakage using gas detector, non-corrosive
detection fluid, or other leak detection method acceptable to authority having
jurisdiction. Do not
use matches, candles, open flames, or other methods providing ignition source.
· Correct leaks immediately and retest.
Figure 9-1 – Gas Piping
Union Recommended
for service
INSTALL MANUAL VALVE WITHIN 6 FT. (183 cm) OF BOILER AND 5 FT. (152 cm) ABOVE THE FLOOR WHERE REQUIRED BY LOCAL CODES
3″ (8 cm) Minimum Sediment Trap
9.1 General
To Gas Control Inlet
· Use piping materials and joining methods acceptable to authority having
jurisdiction. In absence of such requirements: USA – National Fuel gas Code,
ANSI Z223.1/NFPA 54
· Size and install gas piping system to provide sufficient gas supply to meet
maximum input at not less than minimum supply pressure. See Table 9-1.
· Support piping with hooks, straps, bands, brackets, hangers, or building
structure components to prevent or dampen excessive vibrations and prevent
strain on gas connection. Boiler will not support piping weight.
· Use thread (joint) compound (pipe dope) suitable for
liquefied petroleum gas. · Install field sourced manual main shutoff valve,
ground
joint union, and sediment trap upstream of gas valve. See Figure 9-1.
MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS/HOUR (Gas Pressure = 0.5 psig or less, Pressure Drop = 5 in. w/c)
Table 9-2
Length of Pipe (Feet)
½”
Nominal Iron Pipe Size
¾”
1″
1¼”
10
175
360
680
1400
20
120
250
465
950
30
97
200
375
770
40
82
170
320
660
60
66
138
260
530
80
57
118
220
460
100
50
103
195
400
For additional information refer to the National Fuel Gas Code Handbook.
24
PN 240013661 Rev. B [02/10/2023]
10 – ELECTRICAL
! WARNING
Electrical shock hazard. Turn OFF electrical power supply at service panel
before making electrical connections. Failure to do so could result in death
or serious injury.
! WARNING
Fire, electrical shock hazard. Verify all electrical connections are secure.
Failure to do so could result in death or serious injury.
8. There are two (2) options when using Zone 2 for an indirect tank or
heating zone using the IC control to power the Zone 2 pump:
a. A Zone 2 wiring kit is available see parts list. This plugs into the Molex
connector for the Zone 2 pump and provides power leads for the pump.
b. Cut off the end of the Molex connector and wire the Zone 2 pump leads
directly using wire nuts or other approved electrical connectors.
c. Refer to Zone 2 Settings section of Hydrostat IC instructions (enclosed
separately in literature package) for setting options.
10.1 Electrical Wiring
If an external electrical source is utilized, the boiler, when installed, must
be electrically bonded to ground in accordance with the requirements of the
authority having jurisdiction or, in the absence of such requirements, with
the National Electrical Code, ANSI/NFPA 70, and/or the See wiring diagrams on
the following pages for details.
· J-box and circulator harness are shipped in parts box, and may be wired on
either side of boiler as desired.
· Electrically bond boiler to ground in accordance with requirements of
authority having jurisdiction.
Refer to: USA – National Electrical Code, ANSI/NFPA 70. · Aluminum
wiring/conductors not permitted.
10.2 Thermostat Installation
1. Use a thermostat with dry contacts which does not pull any load from the
control. Use a separate transformer for zone valve wiring.
2. Thermostat should be installed on inside wall about four feet above floor.
3. NEVER install thermostat on outside wall.
4. Do not install thermostat where it will be affected by drafts, hot or cold
pipes, sunlight, lighting fixtures, televisions, fireplace, or chimney.
5. Check thermostat operation by raising and lowering thermostat setting as
required to start and stop burners.
6. Instructions for final adjustment of thermostat are packaged with
thermostat (adjusting heating anticipator, calibration, etc.)
7. Thermostat’s heat anticipator must be adjusted to match total current draw
of all controls associated with boiler during heating cycle.
25
PN 240013661 Rev. B [02/10/2023]
11 – WIRING DIAGRAMS
! WARNING
Modification, substitution or elimination of factory equipped, supplied or
specified components may result in personal injury or loss of life. Figure
11-1 – 4200 Fuel Smart Hydrostat IC Control
(REFER TO PARTS LIST)
26
PN 240013661 Rev. B [02/10/2023]
11 – WIRING DIAGRAM Figure 11-2 – 4200 Fuel Smart Hydrostat IC Control – ladder
27
PN 240013661 Rev. B [02/10/2023]
12 – LIGHTING INSTRUCTIONS
! WARNING
If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury or loss of life. · This
appliance is equipped with an ignition device
which automatically lights burner. Do NOT try to light this burner by hand.
· Before operating smell all around appliance area for gas. Be sure to smell
next to floor because some gas is heavier than air and will settle to the
floor.
· Use only your hand to turn the gas shutoff valve. Never use tools. If valve
will not turn by hand, do not try to repair it, call a qualified service
technician. Force or attempted repair may result in fire or explosion.
· Do not use this appliance if any part has been under water. Immediately call
a qualified service technician to inspect appliance and to replace any part of
control system and any gas control which has been under water.
12.2 Operating Instructions For Intermittent Pilot System
1. STOP! Read and follow all safety information. 2. Set the thermostat to
lowest setting. 3. Turn off all electric power to the appliance. 4. This
appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot by hand. 5. Lift
and remove front panel.
Figure 12-1 – Intermittent Pilot
NOTICE
Before lighting any type of pilot burner, verify the hot water boiler and
system are full of water to minimum pressure of 12 psi in the system, also
verify system is vented of air. Set operating control of thermostat to “below”
normal setting. Refer to following appropriate lighting instruction.
6. Turn gas control knob clockwise
to “OFF.”
7. Wait (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “What To Do If You Smell Gas” in the safety information to the left. If you don’t smell gas, go on to the next step.
8. Turn gas control knob counterclockwise
to “ON.”
12.1 Lighting Procedure For Boiler With Intermittent Pilot System This
appliance is equipped with an ignition device which automatically lights the
pilot. Do not try to light the appliance by hand.
! CAUTION
WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance.
· Do not touch any electrical switches; do not use any phone in your building.
· Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.
9. Turn on all electric power to the appliance.
10. Set thermostat to desired setting.
11. If the appliance will not operate, follow the instructions “To Turn Off
Gas To Appliance” , and call qualified service technician or your gas
supplier.
12. Replace front panel
12.3 TO TURN OFF GAS TO THE APPLIANCE
1. Set the thermostat to lowest setting. 2. Turn off all electric power to
the appliance if service is
to be performed. 3. Lift and remove front panel. 4. Push in gas control knob
slightly and turn clockwise
to “OFF.” DO NOT FORCE. 5. Call qualified service technician.
28
PN 240013661 Rev. B [02/10/2023]
13 – NORMAL SEQUENCE OF OPERATION
! WARNING
Burn Hazard. View port on burner door may be hot. Wear personal protection
when servicing this boiler.
! WARNING
Fire and Asphyxiation hazard. Do not attempt to place boiler in operation if
safety switches shut the main burner gas off. Contact a qualified service
agency. Failure to follow these instructions could result in death or serious
injury.
13.1 General
1. Thermostat actuates on call for heat, completing circuit to control. A.
Completed circuit to control will energize the vent damper. The circulator
will be energized if the boiler water temperature is above 125°F. B. When the
vent damper is fully open the damper end switch completes the circuit to
ignition system, ignition takes place.
2. In event the boiler water temperature exceeds high limit setting on the
boiler mounted high limit control, power is interrupted between control system
and ignition system.
Figure 13-1 Blocked Vent Safety Switch, Roll-out Safety Switch (Front Panel
Removed)
Integral Draft Hood
A. Power remains off until boiler water temperature drops below high limit
setting.
B. Circulator continues to operate under this condition until thermostat is
satisfied.
3. In event the flow of combustion products through the boiler venting system
becomes blocked: A. Blocked vent safety switch shuts main burner gas off.
B. If boiler flue-way becomes blocked: flame rollout safety switch shuts main
burner gas off. See Figure 13-1.
4. 2-Zone Capability: The Hydrostat IC is equipped with a second zone for use
with a 120-volt circulator. This zone is factory set to function with an
indirect water heater for domestic hot water (DHW). The control allows the
boiler to run up to high limit setting to satisfy calls from this zone. The
control will allow the Smart DHW Priority feature to prioritize domestic hot
water. The second zone can also be used for a heating zone in which case it
should not be prioritized. See Zone 2 settings in the Hydrolevel Manual
provided with your boiler.
If either of these condition A or B exist: Do not attempt to place boiler back
into operation. Contact certified service agency. Do Not jumper safety
switch(s).
For detailed sequence of control, see Appendix A.
Hydrolevel Control
Blocked Vent Safety Switch
Burner Door
Gas Valve
Igniter
View Port
Rollout Switch
Burners
Base 29
PN 240013661 Rev. B [02/10/2023]
14 – GENERAL MAINTENANCE AND CARE INSTRUCTIONS
! WARNING
Label all wires prior to disconnection when servicing controls. Wiring errors
could cause improper and dangerous operation.
14.1 Seasonal Startup · Before seasonal start-up, have a certified service
agency
check boiler for soot and scale in flues, clean burners and check gas input
rate to maintain high operating efficiency. · Verify proper operation after
servicing.
· Service agency will verify system is filled with water to minimum pressure
and open air vents, if used, to expel any air accumulated in the system. Check
entire piping system and, if any leaks appear, have them repaired.
· Circulators need to be checked and maintained. Refer to circulator
manufacturer’s instructions.
· Inspect venting system at the start of each heating season.
Check vent pipe from boiler to chimney for signs of deterioration by rust or
sagging joints. Repair if necessary.
Remove vent pipe at base of chimney or flue and using a mirror, check vent for
obstruction and verify vent is in good working order.
· Boiler flue gas passageways may be inspected by a light and mirror.
Remove burner door. See Figure 13-1 page 29.
Place trouble lamp in flue collector through draft relief opening or flue
inspection cover.
With mirror positioned above burners, flue gas passageways can be checked for
soot or scale
14.2 Clean Flue Gas Passageways
Follow this procedure to clean flue gas passageways:
1. Remove burner tray from heat exchanger by disconnecting the gas supply, by
removing two (2) nuts. Pull out the assembly. see Figure 14-1 page 31.
2. Remove top jacket panel.
3. Remove flue inspection cover.
4. Place sheet of heavy paper or similar material over bottom of base and
brush down flue passageways. Soot and scale will collect on paper and is
easily removed with the paper.
5. With paper still in place in base, clean top of boiler castings of boiler
putty or silicone used to seal between castings and flue collector. Verify
chips are not lodged in flue passageways.
When cleaning process is complete, restore boiler components to their original
position. Use IS-808 GE silicone (available from distributor) to seal around
flue collector, and inspection cover if required.
30
PN 240013661 Rev. B [02/10/2023]
14 – GENERAL MAINTENANCE AND CARE INSTRUCTIONS
14.3 General Maintenance
Figure 14-1 – Burner Tray
· Visually inspect main burner and pilot flames at start of heating season and
again in mid-season.
Main burner flame should have well defined inner blue mantel with lighter blue
outer mantel.
Check burner throats and burner orifices for lint or dust obstruction. Figures
14-1 and 14-3.
GAS VALVE
BURNERS
· Pilot flame should envelop to ½ inch of tip of ignition/sensing electrode. See Figure 14-2.
· To adjust pilot flame: remove pilot adjustment
cover screw and turn inner adjustment screw
counterclockwise
to increase or clockwise
to decrease pilot flame. Replace cover screw after
adjustment to prevent possible gas leakage. See
Figure 12-1, Page 28.
· Check burners and pilot for signs of corrosion, rust or scale buildup.
· Area around boiler shall be clear and free of
combustible materials, gasoline and other flammable vapors and liquids.
ORIFICES
Figure 14-2 – Gas Burner Pilot Assembly Proper Flame Adjustment
Shown
(9.53/t8o”1to2.17/m2m” )
PILOT LINT SCREEN
· Free flow of combustion and ventilating air to boiler and boiler room shall not be restricted or blocked.
· Inspect factory supplied and field sourced low water cutoffs annually, or as recommended by low water cutoff manufacturer. Flush float type low water cutoffs per manufacturer’s instructions.
· Contact a Qualified Service Agency to make annual inspection of boiler and
heating system. This should include:
1. Check casting and vent for signs of corrosion from condensate.
2. Examine pilot lint screen and clean if needed.
3. Check venting for any signs of corrosion, rust, damage or deterioration.
Contact a Qualified Service Agency immediately if you observe any of these
conditions.
4. Clean oxidation on the igniter/flame sensor with an abrasive cloth.
Figure 14-3 – Gas Burner Flame
INNER BLUE MANTEL
LIGHT BLUE OUTER MANTEL
31
PN 240013661 Rev. B [02/10/2023]
14 – GENERAL MAINTENANCE AND CARE INSTRUCTIONS
14.4 Adjusting Gas Input
1. Adjust gas input to boiler by removing protective cap on
pressure regulator, and turning screw clockwise
to
increase input and counterclockwise
to decrease
input. See Figure 12-1 page 28.
2. Manifold pressures are taken at outlet side of gas valve. See Pg 24 for proper pressure recommendations.
3. To check for proper flow of natural gas to boiler, divide input rate shown on rating plate by heating value of gas obtained from local gas company. This determines number of cubic feet of gas required per hour.
4. Determine flow of gas through meter for two minutes and multiply by 30 to
get hourly rate with all other gas
appliances off.
5. Make minor adjustments to gas input as described above. See Figure 12-1 page 28.
6. Change burner orifices if final manifold pressure varies more than plus or
minus 0.3 inches water column from
specified pressure listed on boiler rating plate.
7. Primary air adjustment is not necessary, therefore air shutters are not furnished.
CHECK SAFETY CONTROL CIRCUIT. Test ignition
system safety shutoff device after placing boiler in operation. Blocked vent
switch and rollout switch. can be tested by removing one of the wires. See
Figure 12-1 page 28.
8. Intermittent Pilot: With main burner operating, turn
pilot gas adjusting screw clockwise
until pilot
gas is turned off. Within 90 seconds main gas control
closes, shutting off gas to main burner.
9. High Limit Control: Remove front cover and note temperature setting. Refer to appendix A for adjustment procedure. Decrease setting to minimum and operate boiler. When boiler water temperature exceeds control temperature setting, control will open circuit, closing automatic main gas valve.
32
PN 240013661 Rev. B [02/10/2023]
15 – RATINGS AND CAPACITIES
Table 15-1 – Ratings and Capacities
Boiler Model 15B-060K UH15B-060K 15B-095K UH15B-095K 15B-120K UH15B-120K 15B- 150K UH15B-150K 15B-175K UH15B-175K 15B-205K UH15B-205K 15B-235K UH15B-235K
Number of
Sections 3
4
5
6
7
8
9
(1)
Input Btu/hr 59,000
92,500
120,000
149,000
175,000
205,000
235,000
(1)
Heating Capacity Btu/hr 50,000
78,000
101,000
125,000
147,000
172,000
197,000
(2)
Net AHRI Rating Water
Btu/hr 43,000
68,000
88,000
109,000
128,000
150,000
171,000
AFUE
84.0 84.0 84.0 84.0 84.0 84.0 84.0
Flue Diameter
Inches
4 5 6 6 7 7 7
(1)
High Altitude Input
Btu/hr
53,100
(3)
Recommended Air Cushion Tank
15
83,200
30
108,000
30
134,100
30
157,500
30
184,500
30
211,500
30
EXPLANATORY NOTES — All boilers are design certified for installation on
noncombustible floor. — Recommended chimney height 20 feet. In special cases
where conditions permit, chimney height may be
reduced to 10 feet. Refer to the latest revision of National Fuel Gas Code
ANSI Z223.13/NFPA 54 part 11. — Electric service to be 120 Volts, 15 Amps, 60
Hz. — The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level. United
States, over 2000 ft (610m) above sea level. Reduce input rate 4% for every
1000 ft (304m) above sea level.
(2) Net AHRI Water Ratings shown based on piping and pickup allowance of 1.15.
Consult manufacturer before selecting boiler for installations having unusual
piping and pickup requirements, such as intermittent system operation,
extensive piping systems, etc. For forced hot water systems where boiler and
all piping within area to be heated, boiler may be selected on basis of its
heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase
size for cast iron baseboard and radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, High Limit
Control, Intermittent Electric Ignition Pilot System, Vent Damper Relay, Main
Gas Burners, Gas Control (Includes Automatic Gas Valve, Intermittent Pilot,
Safety Shutoff, Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve,
Drain Valve, Spill Switch, Rollout Switch, Automatic Vent Damper, Wiring
Harness, Safety Pilot.
33
PN 240013661 Rev. B [02/10/2023]
APPENDIX A – CONTROL FUNCTION
! WARNING
Burn and scald hazard. Do not add water until boiler has fully cooled. Failure
to follow these instructions could result in death or serious injury.
Control – LED legend
6 ECONOMY TARGET When the Economy feature is active, the Fuel Smart HydroStat
continually sets target temperatures below the high limit setting
to maximize fuel efficiency. When the boiler water reaches the target
temperature, the LED illuminates and the burner will shut down. The boiler
water will continue to circulate and heat the house as long as the thermostat
call continues. The LED will stay lit until
the boiler temperature drops below the differential set point at which point
the boiler will be allowed to
fire again. See Differential explanation on page 6 of Hydrolevel Manual. NOTE:
This LED illuminates regularly during normal boiler operation
1 TEMP ACTIVE Indicates the Fuel Smart HydroStat control is powered and the
temperature function is active.
2 TEMP HI TEMP Illuminates when the boiler water temperature reaches the high
limit setting. It will remain lit until the water temperature falls 10°. The
Fuel SmartHydroStat prevents burner operation while this LED is on. See
Differential explanation on page 6 of Hydrolevel Manual.
3 LWCO ACTIVE Indicates the low water cut-off (LWCO) function of the Fuel
Smart HydroStat is active. When the control is installed with a Hydrolevel
Electro-Well, this LED will be on at all times when the control is powered.
IMPORTANT: If the control is installed with a well other than the Electro-
Well, this LED will not illuminate indicating the control is not providing low
water cut-off functionality.
4 LWCO LOW WATER Indicates the boiler is in a low water condition. The
HydroStat control will prevent burner operation during this condition. If the
LOW WATER light is blinking, the control has been programmed to provide
lockout protection in the event a low water condition is detected. (see Manual
Reset Low Water Cut-Off on page 8 of Hydrolevel manual). Pressing the
TEST/SETTINGS button will reset the control.
IMPORTANT: The system must be checked by a qualified heating professional
prior to resuming operation.
7 TEST/SETTINGS Button
To Test Low Water Cut-Off: Press and hold the Test/ Settings button for 5 seconds. The display will read
LCO.
LWCO TEST LCO
The red Low Water light should illuminate and the
burner circuit should de-energize. NOTE: The control
must be installed with a Hydrolevel Electro-Well for
low water cut-off functionality (SEE Hydrolevel manual for more details).
To View Current Settings: Press and release the Test/Settings Button in short
intervals to sequentially
display the following settings:
HIGH LIMIT SETTING HL
LOW LIMIT SETTING LL
ECONOMY SETTING ECO
CURRENT TARGET TEMPERATURE ooo
FLAME CURRENT FLA
The display will return to boiler temperature (default) if Test/Settings
Button in not pressed for 5 seconds.
NOTE: flame current reading will remain in the display for 30 seconds to allow for pilot adjustment.
5 ECONOMY ACTIVE Indicates the Thermal Targeting function is active and the
Fuel Smart HydroStat will reduce boiler temperature to conserve fuel. The
Economy feature is activated using the ECONOMY dial.
34
PN 240013661 Rev. B [02/10/2023]
Ignition – LED Legend
APPENDIX A – CONTROL FUNCTION
A-1. Intermittent Pilot Ignition System Checks
1 LIMITS illuminates on a call for heat to indicate the external limits are
satisfied. (External limits may include flame rollout, spill switch, secondary
low water cut-off etc.). If the external limits are open, the LIMITS light
will blink.
2 V-PWR Indicates power has been sent to the vent damper.
3 V-SW Illuminates when the vent damper switch an has made. If the damper end
switch fail to make in 30 seconds, the V-SW light will blink.
4 FLAME Illuminates when the pilot flame is lit. If the pilot flame is not
sensed within 75 seconds or if flame is lost, the FLAME light will blink.
! DANGER
Carbon Monoxide Hazard: If the burner fires when the vent damper is not fully
opened or there is any other blockage in the flue, dangerous flue products,
such as carbon monoxide, will escape into the living space causing severe
personal injury or death. The flue as well as the vent damper must be checked
for proper operation before allowing the system to operate.
STEP 1: Check ignition cable. a. Verify ignition cable does not make contact
with metal surfaces. b. Verify only factory supplied Ignition cable (or
approved replacement) is used. c. Verify connections to ignition module and
igniter or igniter-sensor are clean and tight. d. Verify ignition cable
provides good electrical continuity.
STEP 2: Verify ignition system grounding. Nuisance shutdowns are often caused
by poor or erratic grounding. Common ground is required for module and pilot
burner/ igniter sensor.
Check for good metal-to-metal contact between pilot burner bracket and the
main burner.
Check ground lead from GND (BURNER) terminal on module to pilot burner. Verify
connections are clean and tight. If wire is damaged or deteriorated, replace
with No. 14-18 gauge, moisture-resistant, thermoplastic insulated wire with
105°C [221°F] minimum rating.
Check ceramic flame rod insulator for cracks or evidence of exposure to
extreme heat, which can permit leakage to ground. Replace pilot burner/
igniter sensor and provide shield if necessary.
If flame rod or bracket is bent out of position, restore to correct position.
35
PN 240013661 Rev. B [02/10/2023]
APPENDIX A – CONTROL FUNCTION
STEP 3: Check spark ignition circuit.
! WARNING
Electrical shock hazard. Ignition circuit generates over 10,000 volts. Turn
OFF electrical power supply at service panel before making electrical
connections. Failure to do so could result in death or serious injury.
Energize module and listen for audible sparking noise. When operating
normally, there should be a buzzing noise that turns on and off twice per
second for duration of 17 seconds depending on model. Reconnect ignition
cable.
4. Recheck ignition sequence as follows: a. Adjust thermostat above room temperature. b. Verify ignition sequence at burner.
Figure A-1 – Troubleshooting Pilot Flame
APPEARANCE
SMALL BLUE FLAME
CAUSE
CHECK FOR LACK OF GAS FROM: · CLOGGED ORIFICE FILTER · CLOGGED PILOT FILTER ·
LOW GAS SUPPLY PRESSURE · PILOT ADJUSTMENT AT MINIMUM
STEP 4: Verify pilot and main burner light-off. 1. Initiate call for heat.
Turn thermostat above room
temperature. Ignition sequence may be delayed by thermal purge up to 2
minutes.
2. Watch pilot burner during ignition sequence.
Verify ignition spark stops within a few seconds after pilot is lit.
Verify Main burner lights within a few seconds of pilot lighting
a. Check pilot flame. Verify it is blue, steady and envelops 3/8 to 1/2 in.
[10 to 13 mm] of flame rod. See Figure A-1 for possible flame problems and
causes.
b. If necessary, adjust pilot flame by turning pilot adjustment screw on gas
control clockwise to decrease or counterclockwise to increase pilot flame.
Following adjustment, always replace pilot adjustment cover screw and tighten
firmly to assure proper gas control operation. Figure 12-1, page 28.
3. If pilot does not stay lit, ensure adequate flame current as follows.
Turn off boiler at circuit breaker or fuse box.
Clean flame rod with emery cloth.
Verify electrical connections are clean and tight. Replace damaged wire.
Check for cracked ceramic insulator, which can cause short to ground, and
replace pilot if necessary.
Set temperature below room set-point to end call for heat.
LAZY YELLOW FLAME
CHECK FOR LACK OF AIR FROM: · DIRTY ORIFICE · DIRTY LINT SCREEN, IF USED · DIRTY PRIMARY AIR OPENING IF THERE IS ONE · PILOT ADJUSTMENT AT MINIMUM
WAVY BLUE FLAME
CHECK FOR: · EXCESSIVE DRAFT AT PILOT LOCATION
· RECIRCULATING PRODUCTS OF COMBUSTION
NOISY LIFTING BLOWING FLAME
CHECK FOR: · HIGH GAS PRESSURE
HARD SHARP FLAME
THIS FLAME IS CHARACTERISTIC OF MANUFACTURED GAS CHECK FOR:
· HIGH GAS PRESSURE
· ORIFICE TOO SMALL
Correct Pilot Flame: 3/8 to 1/2 inch in flame
36
PN 240013661 Rev. B [02/10/2023]
APPENDIX B – VENT DAMPER INSTALLATION
! WARNING
Asphyxiation, burn hazard. Improper operation of vent damper may result in
serious injury or death due to fire or to asphyxiation from poisonous gases
such as carbon monoxide which is odorless and invisible.
B.1 Damper Installation Follow Damper installation instructions provided with
damper. See Figure 1a & 1b.
1. Verify only boiler is serviced by Vent Damper. Figure 2.
2. Clearance of 6 inches (152 mm) between Vent Damper and combustible
material shall be maintained. Allow additional clearance for service of Vent
Damper.
3. Vent Damper shall be in the open position when appliance main burners are
operating.
4. Vent Damper position indicator must be in visible location following
installation.
Figure 1a – Horizontal Installations
Flow
NO
To Boiler
YES
YES
Vent Damper To Chimney
NO
Install vent damper with actuator to sides of vent only. Do not mount above or below vent
Figure B-1b – Vertical Installations
To Chimney
Flow To Boiler
Vent Damper
Actuator may be installed in any
position
Figure 2 – Alternate Vent Damper Installation
B.2 Vent Damper
Check vent damper and all flue product carrying areas of boiler annually for
deterioration from corrosion or other sources. Contact your service agent for
repairs.
Check Vent Damper Operation as follows:
1. When boiler is off, check vent damper position indicator points to closed
position. See Figure 3.
2. Turn thermostat or controller up to call for heat and check vent damper
indicator points to open position See Figure 3.
3. Turn thermostat or controller down again and check damper position
indicator returns to closed position.
4. Return thermostat to desired position. 5. Place vent damper in open
position to permit burner
operation by using “HOLD DAMPER OPEN” switch, located on damper controller. 6.
Thermostat controls burner firing as before, while damper remains open. 7. DO
NOT turn damper open manually, motor damage will result. 8. Set switch to
“AUTOMATIC OPERATION” to close vent damper during burner off cycle. 9. For
further information, and for vent damper troubleshooting guide, refer to
manual packaged with vent damper.
Do not install Vent Damper within 6″ (152mm) of combustible material
Do Not Install Here
Install Damper Here
Boiler
Water Heater
Chimney
Figure 3 – Vent Damper Position Indicator
ROTATION OPEN
CLOSED Flue Gas Flow
ROTATION OPEN
CLOSED Flue Gas
Damper Closed
Damper Open
Open and Closed Positions Shown
37
PN 240013661 Rev. B [02/10/2023]
APPENDIX B – VENT DAMPER INSTALLATION
B.3 Vent Damper Harness – Molex Plugs
! WARNING
Follow all instructions regarding safety operational controls in this manual.
Failure to follow these instructions could result in death or serious injury.
Figure 4
Note
When servicing controls, all wires must be labeled prior to disconnection. Wiring errors can cause improper and dangerous operation. Do not turn damper open manually or motor damage will result.
Do not cut plug off of damper motor assembly this will affect warranty coverage.
Verify Molex pins are fully seated in both ends of Molex plugs
Figure 5
Check Molex Plugs on Vent Damper Harness:
Note
Damper wiring harness is made up of 4 individual colored wires, Brown, Black, Yellow, and Orange. See Figure 4.
1. Disconnect thermostat wires. 2. Confirm the Molex plugs on each end of the
damper
harness are wired and operating properly. See Figures 4 and 5. Damper end of
wiring harness: A. Hold plug in hand with wiring harness behind Molex
with “V” slot on top. Verify wire colors are in proper position.
B. Take reading across brown and black wires in Molex plug, using test meter
set for AC volts. 24 volts should be present.
i. IF NOT, source of the problem is not in damper; check line voltage and 24
volt supply.
ii. If 24 volts is present across brown and black, continue to step iii.
iii. Reconnect thermostat wires and turn up heat setting.
iv. Check voltage across black and orange wires in Molex plug. 24 volts AC
should be present: · IF NOT, source problem is not the damper.
· If 24 volts is present continue on to step v.
v. Place jumper wire across orange and yellow wires in Molex plug (see Figure
4). This will create bypass of the damper, boiler should then ignite. · If
boiler ignites: Go to section B.4 “Vent Damper Troubleshooting Guide”.
· If boiler does not ignite: Problem is not the damper. Go to Damper harness
Molex on Aquastat, Step C.
NOTE: Prior to replacing the damper, be sure the problem is not with wire
connections between damper and wiring harness.
Control End of wiring harness Hold plug in hand with wiring harness behind
Molex with
“V” slot on top. Verify wires colors are in proper position
“V” Slot
Yellow
Black
Brown
OPEN
Orange
Black
Check Molex Plugs on Vent Damper Harness:
C. Remove damper harness from control. Jump Molex connector on control board
between two center holes using ~ 18 ga. thermostat wire. See Figure 6 i. If
boiler ignites, replace damper harness
ii. If boiler does not light, check for 24 volts at B1-B2 on aquastat. If no
replace control.
iii. If 24 Volts are present Damper and Control are ok. Check ignition module,
rollout switch, spill switch or gas valve.
Figure 6
Jumper two center pins
38
PN 240013661 Rev. B [02/10/2023]
APPENDIX B – VENT DAMPER INSTALLATION
B.4 Vent Damper Troubleshooting Guide
! WARNING
Follow all instructions regarding safety operational controls in this manual.
Failure to follow these instructions could result in death or serious injury.
Note
When servicing controls, all wires must be labeled prior to disconnection.
Wiring errors can cause improper and dangerous operation. Do not turn damper
open manually or motor
damage will result and affect warranty coverage, use the service switch.
Normal Sequence of Operation
24 VAC Power
4 & 1
4 & 2
4 & 3
Power ON
All times Calling for Heat During combustion
Damper Position
Open or Closed Open or Opening Damper Open
Brown
Orange
Do not cut plug off of damper motor assembly this will affect warranty
coverage.
Vent Damper Troubleshooting
Yellow
Black
Problem
NO POWER Between 4 & 1
NO POWER Between 4 & 2 POWER Between 4 & 1 When calling for heat POWER Between
4 & 1 Between 4 & 2 DAMPER OPEN
Possible Cause
1. Off on limit (120VAC) 2. Bad transformer 3. Loose or broken connections 4.
Blown fuse or circuit breaker 5. Disconnect switch off 6. Harness not plugged
into receptacle on aquastat
Recommended Solution
1. turn limit on 2. Replace transformer 3. Tighten, repair, or replace
connection 4. Replace fuse or reset circuit breaker 5. Turn switch on 6. Plug
harness in
1. Thermostat not calling for heat 2. Burned out heat anticipator 3. Loose or broken connections 4. Off/On operating limit, pressure control or low water cut off 5. Off/On blocked vent switch or flame roll out
1. Turn thermostat up to call for heat 2. Replace thermostat 3. Tighten, repair, or replace connection 4. Turn operating limit, pressure control, or low water cutoff ON 5. Reset or replace switch
1. Loose or broken connection 2. Defective damper motor
1. Tighten, repair, or replace connection 2. Replace damper motor assembly
39
PN 240013661 Rev. B [02/10/2023]
IMPORTANT
In accordance with Section 325 (f) (3) of the Energy Policy and Conservation
Act, this boiler is equipped with a feature that saves energy by reducing the
boiler water temperature as the heating load decreases. This feature is
equipped with an override which is provided primarily to permit the use of an
external energy management system that serves the
same function.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS
IS TRUE:
· An external energy management system is installed that reduces the boiler
water temperature as the heating load decreases.
· This boiler is not used for any space heating · This boiler is part of a
modular or multiple boiler system having a total input of
300,000 BTU/hr or greater. · This boiler is equipped with a tankless coil.
2201 Dwyer Avenue, Utica, NY 13501 Tel. 800 325 5479 www.ecrinternational.com
All specifications subject to change without notice. ©2023 ECR International, Inc.
References
- A Family of Heating and Cooling Brands - ECR International / Granby
- National Institute for Occupational Safety & Health | NIOSH | CDC
- Workplace Safety and Health Topics | NIOSH | CDC
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>