THORN ALTIS G5 Powerful Light Controlled Instruction Manual
- May 15, 2024
- THORN
Table of Contents
THORN ALTIS G5 Powerful Light Controlled
Specifications
- Product Name: ALTIS G5
- Type: ALG5 – 144L – 168L
- IP Rating: IP66
- Impact Protection: IK08
Installation Instructions
For installation higher than 3m, secure the product with a retaining cable
attached to the frame (not included in the delivery). Refer to local
installation norms/regulations for guidance.
Brick Orientation
Ensure the luminaire is positioned correctly according to the brick
orientation specifications provided in the manual.
Electrical Connection
Exercise extreme caution when making electrical connections. Do not connect
any LED CONNECTION wire (high voltage) inside the NTC connector to prevent
critical failure and irreversible damage to the ALTIS luminaire.
Connection Box Setup
Follow the instructions provided in the manual for setting up the
connection box for ALTIS G5 2 x 1 Luminaire. Ensure proper wiring and
connections are made to avoid any issues.
FAQ
-
Q: What should I do if the product is not functioning correctly after installation?
A: If you encounter any issues with the product’s functionality post- installation, please check the electrical connections and ensure they are set up as per the provided instructions. If problems persist, contact customer support for further assistance. -
Q: Can the ALTIS G5 be used in outdoor environments?
A: Yes, the ALTIS G5 luminaire has an IP66 rating, making it suitable for outdoor use. Ensure proper installation and maintenance to maximize performance and longevity.
Installation instructions
- The luminaire with clear optic should be positioned so that prolonged staring intothe luminaire at a distance <2m is not expected
- Extreme caution : Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire
- Caution , risk of electric shock Danger, risque de chocs électriques
- The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
DIMENSIONS
ALG5 GB LE
CONNECTION BOX
Extreme caution : Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire
PINOUT
Number| Label| Description
| L1| AC LINE 1 INPUT
| L2| AC LINE 2 INPUT
| | PROTECTIVE EARTH
| DA+| DALI INPUT
| DA+| DALI RE-LAUNCH
| DA-| DALI INPUT
| DA-| DALI RE-LAUNCH
| | PROTECTIVE EARTH FOR LUMINAIRE
5| NTC| THERMAL MEASURE INPUT
1| +1| LED1+CONNECTION
2| -1| LED1-CONNECTION
3| +3| LED3+CONNECTION
4| -3| LED3-CONNECTION
SIGNALLING LED INDICATIONS ON THE GEAR BOX|
---|---
PERIOD| PULSES| FAULT DESCRIPTION| PRIORITY|
The encoded
| 1| One or more active outputs is not working| Maximum
Minimum
|
5| Undervoltage on one or more active outputs|
faults are|
based on pulses|
2| short circuit on one or more active outputs|
emitted every|
4 seconds|
3| One or more active outputs disconnection from load|
| 4| Overload on one or more active outputs|
CABLE GLAND
TYPE| ØMin| ØMax
M16| 5 mm| 10 mm
M25| 10 mm| 17 mm
M32| 13 mm| 21 mm
SEAL REDUCER
for GB and FLOOD
TYPE| ØMin| ØMax
M32| 10 mm| 16 mm
Extreme caution : Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire
PINOUT
Number| Label| Description
| L1| AC LINE 1 INPUT
| L2| AC LINE 2 INPUT
| | PROTECTIVE EARTH
| A| DMX INPUT DATA+
| A| DMX-RE-LAUNCH DATA+
| B| DMX INPUT DATA-
| B| DMX-RE-LAUNCH DATA-
| S| DMX COMMON / SHIELD
| S| DMX COMMON / SHIELD
| | PROTECTIVE EARTH FOR LED MODULE
7
| NTC| THERMAL MEASURE INPUT
1| +1| LED1+CONNECTION
2| -1| LED1-CONNECTION
3| +3| LED3+CONNECTION
4| -3| LED3-CONNECTION
SIGNALLING LED INDICATIONS ON THE GEAR BOX|
---|---
PERIOD| PULSES| FAULT DESCRIPTION| PRIORITY|
The encoded
| 1| One or more active outputs is not working| Maximum
Minimum
|
5| Undervoltage on one or more active outputs|
faults are|
based on pulses|
2| short circuit on one or more active outputs|
emitted every|
4 seconds|
3| One or more active outputs disconnection from load|
| 4| Overload on one or more active outputs|
CABLE GLAND
TYPE| ØMin| ØMax
M16| 5 mm| 10 mm
M25| 10 mm| 17 mm
M32| 13 mm| 21 mm
SEAL REDUCER
for GB and FLOOD
TYPE| ØMin| ØMax
M32| 10 mm| 16 mm
18 ALG5 GB 3CH / 200-250 Vac – ALG5 GB 3 CH /250-440 Vac
CIRCUIT BREAKER recommendation
It should mentioned in the notice that calculation has been done with a
Circuit Breaker Load Factor of 100%.
V in
Nominal
| Inrush Current Data| # Drivers for each Circuit Breaker
---|---|---
I peak
(A)
| Half Value Time (µs)| Type B 10A| Type B 16A| Type B 20A| Type B 25A| Type C 10A| Type C 16A| Type C 20A| Type C 25A| Type D
10A
| Type D
16A
| Type D
20A
| Type D
25A
230Vac| 40| 2500| 0| 1| 1| 2| 0| 1| 1| 2| 0| 1| 1| 2
400Vac| 68| 2000| 0| 1| 1| 1| 1| 1| 2| 2| 1| 1| 2| 3
GUIDELINE FOR INTEGRATION OF GEAR BOX
If you cannot follow instructions included in previous section regarding gear box integration, you have to measure Tc reference point taking into consideration that measures must be down to Tc_max
Tc Reference at Max Ambient ALG5 GB LE / ELECTRICAL CONNECTION
The wiring should follow label marking instruction,
Otherwise the product could be damaged or the fonctions could be affected.
Each set of + or – are not potential identical, cross connection is
prohibited.
CABLE GLAND
TYPE| ØMin| ØMax
M20| 6.3 mm| 11.3 mm
M25| 10 mm| 16.3 mm
ALG5 GB LE / 200-250 Vac – ALG5 GB LE /250-440 Vac
Drivers for each circuit breaker Referring to the circuit breakers available
on the market, the maximum number on the driver connectable for each circuit
breaker is as the following table.
No| i| Inrush| | t| | | | | | | | | | #| | | cuit| e| | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
(A| T
10A
| T
16A
| T
20A
| T
25A
| T|
32A
| T
40A
| T| 63A| | T| 10A| T
16A
| T
20A
| T
25A
| 15 A| 2000| | 0| 1| 1| 1| | 2| 2| | 4| | | 0| 1| 1| 1
| 25 A| 2000| | 1| 1| 2| 2| | 3| 4| | 6| | | 1| 2| 2| 3
No|
i
| Inrush| | t|
(A| T
32A
| T
40A
| T
63A
|
| 15 A| 2000| | 2| 2| 4
| 25 A| 2000| | 4| 5| 8
If you cannot follow instructions included in previous section regarding gear box integration, you have to measure Tc reference point taking into consideration that measures must be down to Tc_max
Aiming Device
ALTIS LED AIMING DEVICE
96671487 | ALTIS G4/G5 AIMING DEVICE WITH VISOR |
---|---|
96671488 | ALTIS G4/G5 AIMING DEVICE BRACKET |
ALTIS LED AIMING DEVICE
Louvres / Bird Deterrent
96671492 | ALTIS G4/G5 1 BRICK LOUVRE A4 |
---|---|
96671493 | ALTIS G4/G5 1 BRICK LOUVRE A5 |
96671494 | ALTIS G4/G5 1 BRICK LOUVRE A6/A6I |
96671496 | ALTIS G4/G5 1 BRICK LOUVRE MB |
96671495 | ALTIS G4/G5 1 BRICK LOUVRE NB/EB |
96671497 | ALTIS G54/G 1 BRICK LOUVRE WB |
Visor
Power supply support
- Replace any cracked protective shield.
Class II luminaires must be installed so that exposed metal work of the luminaire is not in contact with any part of the electrical installation connected to a protective conductor.
WARNING: Class I luminaires must be earthed.
- This luminaire operates at mains voltage which must be switched off before intervention in control gear.
- Any modification to this luminaire is forbidden.
- Lighted objects nearer than the minimal distance in the is forbidden.
Thorn Lighting is constantly developing and improving its products. The right is reserved to change specifications without prior notification or public announcement. © Thorn Lighting
- To ensure maintaining the best system performances, we advice to switch on the system “At least one night hour per month”.
- corrosion environment from C1 to C5 according to standard ISO9223 except gear Box ALG4 GB LE corrosion environment from C1 to C3
Read User Manual Online (PDF format)