THORN GTLED Pro Tunnel Light Instruction Manual
- June 8, 2024
- THORN
Table of Contents
- GTLED PRO
- TYPE : GP AL
- TYPE : GP PB
- TYPE : GP AB
- 1 GP AL S – IN
- 2 GP AL MS/M/L/XL – IN
- 3 GP AL S – IN
- 5 GP PB
- 6
- 7
- 8 GP PB
- 9 GP PB
- 10 GP PB
- 11 INSTALLATION GP PB
- 12 GP AB
- 13 GP AB
- 14 Installation GP AB
- 15 Connection GP AB
- 16
- 17 Quantity of luminaire / GP PB / GP AB
- 18 INSTALLATION
- 19 Maximum Circuit Breaker 135W & 200W
- 20 Luminaire functional data
- 21 CLEANING
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
- LED = X
- LED = 3 X
GTLED PRO
Installation instructions
The luminaire should be positioned so that prolonged staring into the luminaire at a distance <2m is not expected
WARNING :
Warranty is void if housing has been opened
TYPE : GP AL
MS-M-L-XL XL
GP AL
| A (mm)| B (mm)| C (mm)| |
---|---|---|---|---|---
S| 773| 168| 84| 12-48|
3,4 kg
MS
| 520| 313| 90| 12-48| 6,5 kg
M| 800| 72-108|
10,3 kg
L
| 952| 144| 12,4 kg
XL| 1320| 216|
17,5 kg
LED CLASS I CLASS II IK08 IP66
TYPE : GP PB
Caution, risk of electric shock
OUT1 DALI OUT2 DALI
OUT1 BPL OUT2 BPL
24, 36
GP PB
| L(m)|
---|---|---
1x200W| OUT1| 1,5 <-> 8|
6,6 <->7,6kg
2x135W
| OUT1| 1,5 <-> 8| 7,6 <->9,1kg
2x200W| OUT1| 1,5 <-> 8|
8,1 <->9,6kg
2x135W
| OUT2| 1,5 <-> 8| 7,8 <->9,7kg
2x200W| OUT2| 1,5 <-> 8|
8,2 <->10,1kg
3x200W
| OUT1| 1,5 <-> 8| 9,5 <->11,7kg
4x135W| OUT2| 1,5 <-> 8|
10,1 <->13,1kg
4x200W
| OUT2| 1,5 <-> 8|
11 <->14kg
CLASS I CLASS II IK08 IP66
TYPE : GP AB
Caution, risk of electric shock
OUT1 DALI OUT2 DALI
OUT1 BPL OUT2 BPL
33
5
GP AB
| L(m)|
---|---|---
1x200W| OUT1| 1,5 <-> 8|
6,9<->7,9kg
2x135W
| OUT1| 1,5 <-> 8| 7,8<->9,2 kg
2x200W| OUT1| 1,5 <-> 8|
8,2<->9,7kg
2x135W
| OUT2| 1,5 <-> 8| 8 <->9,8 kg
2x200W| OUT2| 1,5 <-> 8|
8,4<->10,3 kg
3x200W
| OUT1| 1,5 <-> 8| 9,6<->11,7 kg
4x135W| OUT2| 1,5 <-> 8|
10,1 <->13 kg
4x200W
| OUT2| 1,5 <-> 8|
11<->13,9 kg
CLASS I CLASS II IK08 IP66
1 GP AL S – IN
GP AL S – IN/OUT
2 GP AL MS/M/L/XL – IN
GP AL MS – IN/OUT
SWITCH OFF POWER BEFORE CONNECTING LUMINAIRE
3 GP AL S – IN
GP AL MS/M/L/XL – IN
4 GP AL S – IN/OUT
GP AL MS – IN/OUT
5 GP PB
6
7
DALI CL1
-
DALI IN
-
DALI OUT
-
Yellow/green
-
Blue
-
Brown
-
Power Supply
IN -
Power Supply
OUT
| BPL CL1
-
Yellow/green
-
Blue
-
Brown
-
Power Supply
IN -
Power Supply
OUT
---|---
DALI CL2
-
DALI IN
-
DALI OUT
-
Blue
-
Brown
-
Power Supply
IN -
Power Supply
OUT
|
BPL CL2
-
Blue
-
Brown
-
Power Supply
IN -
Power Supply
OUT
8 GP PB
Power Supply
- IN Power Supply
- OUT Power Supply
CLASS 1| CLASS 2
5G4mm² – 3G6mm²
Ø15 – 21mm|
4x6mm² – 2x10mm²
Ø15 – 21mm
9 GP PB
DALI|
230V D1 D2
=
50/60Hz ****
| ****
---|---|---
Maximum DALI units per DALI line: 60
Maximum length of DALI line: 300m with 1,5mm² cable
Number of repeater: 1 (extension to 600m)
DALI
10 GP PB
11 INSTALLATION GP PB
-
THROUGH WIRING with DALI (example)
-
Accessory
GP IO 2xSOCKETS JUNCTION CABLE W… -
N product in line
=>Quantity of
luminaire / GP PB -
Imax = 20A
-
Power Supply
12 GP AB
5
13 GP AB
14 Installation GP AB
15 Connection GP AB
DALI|
230V D1 D2
=
50/60Hz ****
| ****
---|---|---
Maximum DALI units per DALI line: 60
Maximum length of DALI line: 300m with 1,5mm² cable
Number of repeater: 1 (extension to 600m)
DALI CL1
- Brown
- Yellow/Green
- Blue
- Grey
- Black
- Power Supply
| DALI CL2
- Brown
- Blue
- Grey
- Black
- Power Supply
---|---
BPL CL1
- Brown
- Yellow/Green
- Blue
- Black
- Power Supply
|
BPL CL2
- Brown
- Blue
- Black
- Power Supply
16
17 Quantity of luminaire / GP PB / GP AB
Example
| 12L
---|---
GP PB 1×200 HV-OUT1-50| 7 – 8 – 9 – 10
1 OUTPUT of 7 luminaires 12L
to
1 OUTPUT of 10 luminaires 12L
| 12L
---|---
GP PB 2×135 HV-OUT2-105| 2×3
2 OUTPUTS of 3 luminaires 12L
18 INSTALLATION
Maximum cable distance
GP PB 1×200 DA LV-OUT1-70
-
LED = X
- 1,5mm² copper
GP PB 1×200 DA LV-OUT1-70
Maximum cable voltage loss: 2% of total led output voltage (typ. @25°C)
Cable 1,5mm² copper (0,023ohm.mm²/m)
-
LED = 3 X
- 1,5mm² copper
Example for the same operating point
- GP PB 1×200 DA LV-OUT1-70
- GP AL M 72L IN ≤850mA
- 1,5mm² copper
- L < 200m
172 LED 324 LED
- GP PB 1×200 DA LV-OUT1-70
- GP AL S 24L IO
- GP AL S 24L IN
- 1,5mm² copper
- L < 200m
- GP PB 2×200 DA LV-OUT2-70
- 1,5mm² copper
- GP AL S 24L IO
- GP AL S 24L IN
- L < 200m
19 Maximum Circuit Breaker 135W & 200W
135W
Maximum loading of automatic circuit breaker
Calculation uses typical values from ABB series S200 as a reference.
Actual values may differ due to used circuit breaker types and installation
environement.
200W
Maximum loading of automatic circuit breaker
Calculation uses typical values from ABB series S200 as a reference.
Actual values may differ due to used circuit breaker types and installation
environement.
20 Luminaire functional data
Wiring type A
luminaire with 1 channel
Wiring type B
luminaire with 2 channels
Wiring type C
luminaire with 3 channels
21 CLEANING
EVERY 6 MONTHS
-Replace any cracked protective shield.
-Class II luminaires must be installed so that exposed metal work of the luminaire is not in contact with any part of the electrical installation connected to a protective conductor.
WARNING: Class I luminaires must be earthed.
-This luminaire operates at mains voltage which must be switched off before intervention in control gear.
-Any modification to this luminaire is forbidden.
-Lighted objects nearer than the minimal distance in the is forbidden.
Thorn Lighting is constantly developing and improving its products. The right
is reserved to change specifications without prior notification or public
announcement.
© Thorn Lighting
96670083 02 01/2022