THORN GTLED Pro Tunnel Light Instruction Manual

June 8, 2024
THORN

GTLED PRO

Installation instructions

The luminaire should be positioned so that prolonged staring into the luminaire at a distance <2m is not expected

WARNING :
Warranty is void if housing has been opened

TYPE : GP AL

THORN GTLED Pro - GP AL 1

MS-M-L-XL XL

THORN GTLED Pro - GP AL 2

THORN GTLED Pro - GP AL 3

GP AL

| A (mm)| B (mm)| C (mm)| |
---|---|---|---|---|---
S| 773| 168| 84| 12-48|

3,4 kg

MS

| 520| 313| 90| 12-48| 6,5 kg
M| 800| 72-108|

10,3 kg

L

| 952| 144| 12,4 kg
XL| 1320| 216|

17,5 kg

LED    CLASS I     CLASS II    IK08  IP66

TYPE : GP PB

Caution, risk of electric shock

OUT1 DALI                             OUT2 DALI

OUT1 BPL                              OUT2 BPL

THORN GTLED Pro - GP PB 5

24, 36

GP PB

| L(m)|
---|---|---
1x200W| OUT1| 1,5 <-> 8|

6,6 <->7,6kg

2x135W

| OUT1| 1,5 <-> 8| 7,6 <->9,1kg
2x200W| OUT1| 1,5 <-> 8|

8,1 <->9,6kg

2x135W

| OUT2| 1,5 <-> 8| 7,8 <->9,7kg
2x200W| OUT2| 1,5 <-> 8|

8,2 <->10,1kg

3x200W

| OUT1| 1,5 <-> 8| 9,5 <->11,7kg
4x135W| OUT2| 1,5 <-> 8|

10,1 <->13,1kg

4x200W

| OUT2| 1,5 <-> 8|

11 <->14kg

CLASS I     CLASS II    IK08  IP66

TYPE : GP AB

Caution, risk of electric shock

OUT1 DALI                                    OUT2 DALI
OUT1 BPL                                      OUT2 BPL
THORN GTLED Pro - GP AB 1  THORN GTLED Pro - GP AB
2

THORN GTLED Pro - GP AB 3

33

5

GP AB

| L(m)|
---|---|---
1x200W| OUT1| 1,5 <-> 8|

6,9<->7,9kg

2x135W

| OUT1| 1,5 <-> 8| 7,8<->9,2 kg
2x200W| OUT1| 1,5 <-> 8|

8,2<->9,7kg

2x135W

| OUT2| 1,5 <-> 8| 8 <->9,8 kg
2x200W| OUT2| 1,5 <-> 8|

8,4<->10,3 kg

3x200W

| OUT1| 1,5 <-> 8| 9,6<->11,7 kg
4x135W| OUT2| 1,5 <-> 8|

10,1 <->13 kg

4x200W

| OUT2| 1,5 <-> 8|

11<->13,9 kg

CLASS I     CLASS II    IK08  IP66

1 GP AL S – IN

GP AL S – IN/OUT

THORN GTLED Pro - Step 1

2 GP AL MS/M/L/XL – IN

GP AL MS – IN/OUT

THORN GTLED Pro - Step 2

THORN GTLED Pro - Step 3a SWITCH OFF POWER BEFORE CONNECTING LUMINAIRE

3 GP AL S – IN

GP AL MS/M/L/XL – IN

THORN GTLED Pro - Step 3 4 GP AL S – IN/OUT
GP AL MS – IN/OUT

THORN GTLED Pro - Step 4

5 GP PB

THORN GTLED Pro - Step 5

6

THORN GTLED Pro - Step 6

7

DALI CL1

THORN GTLED Pro - Step 7a

  1. DALI IN

  2. DALI OUT

  3. Yellow/green

  4. Blue

  5. Brown

  6. Power Supply
    IN

  7. Power Supply
    OUT

| BPL CL1

THORN GTLED Pro - Step 7b

  1. Yellow/green

  2. Blue

  3. Brown

  4. Power Supply
    IN

  5. Power Supply
    OUT

---|---
DALI CL2

THORN GTLED Pro - Step 7c

  1. DALI IN

  2. DALI OUT

  3. Blue

  4. Brown

  5. Power Supply
    IN

  6. Power Supply
    OUT

|

BPL CL2

THORN GTLED Pro - Step 7d

  1. Blue

  2. Brown

  3. Power Supply
    IN

  4. Power Supply
    OUT

8 GP PB

Power Supply
THORN GTLED Pro - Step 8a

  1. IN Power Supply
  2. OUT Power Supply

THORN GTLED Pro - Step 8a

CLASS 1| CLASS 2
5G4mm² – 3G6mm²

Ø15 – 21mm|

4x6mm² – 2x10mm²

Ø15 – 21mm

9 GP PB

DALI|

230V   D1 D2

=

50/60Hz ****

| ****
---|---|---

Maximum DALI units per DALI line: 60
Maximum length of DALI line: 300m with 1,5mm² cable
Number of repeater: 1 (extension to 600m)

DALI
THORN GTLED Pro - Step 9

THORN GTLED Pro - Step 9e

10 GP PB

THORN GTLED Pro - Step 10

11 INSTALLATION GP PB

THORN GTLED Pro - Step 11

  1. THROUGH WIRING with DALI (example)

  2. Accessory
    GP IO 2xSOCKETS JUNCTION CABLE W…

  3. N product in line
    =>Quantity of
    luminaire / GP PB

  4. Imax = 20A

  5. Power Supply

12 GP AB

5

THORN GTLED Pro - Step 12

13 GP AB

THORN GTLED Pro - Step 13

14 Installation GP AB

THORN GTLED Pro - Step 14

15 Connection GP AB

DALI|

230V   D1 D2

=

50/60Hz ****

| ****
---|---|---

Maximum DALI units per DALI line: 60
Maximum length of DALI line: 300m with 1,5mm² cable
Number of repeater: 1 (extension to 600m)

THORN GTLED Pro - Step 15a

DALI CL1

THORN GTLED Pro - Step 15b

  1. Brown
  2. Yellow/Green
  3. Blue
  4. Grey
  5. Black
  6. Power Supply

| DALI CL2

  1. Brown
  2. Blue
  3. Grey
  4. Black
  5. Power Supply

---|---
BPL CL1

  1. Brown
  2. Yellow/Green
  3. Blue
  4. Black
  5. Power Supply

|

BPL CL2

  1. Brown
  2. Blue
  3. Black
  4. Power Supply
16

THORN GTLED Pro - Step 16

17 Quantity of luminaire / GP PB / GP AB

THORN GTLED Pro - Step 17

Example

| 12L
---|---
GP PB 1×200 HV-OUT1-50| 7 – 8 – 9 – 10

1 OUTPUT of 7 luminaires 12L
to
1 OUTPUT of 10 luminaires 12L

THORN GTLED Pro - Step 17a

| 12L
---|---
GP PB 2×135 HV-OUT2-105| 2×3

2 OUTPUTS of 3 luminaires 12L

THORN GTLED Pro - Step 17b

18 INSTALLATION

Maximum cable distance

GP PB 1×200 DA LV-OUT1-70

THORN GTLED Pro - Step 18a

  1. LED = X

  2. 1,5mm² copper

GP PB 1×200 DA LV-OUT1-70

THORN GTLED Pro - Step 18b

Maximum cable voltage loss: 2% of total led output voltage (typ. @25°C)
Cable 1,5mm² copper (0,023ohm.mm²/m)

  1. LED = 3 X

  2. 1,5mm² copper

THORN GTLED Pro - Step 18c

Example for the same operating point

THORN GTLED Pro - Step 18d

  1. GP PB 1×200 DA LV-OUT1-70
  2. GP AL M 72L IN ≤850mA
  3. 1,5mm² copper
  4. L < 200m

172 LED 324 LED

THORN GTLED Pro - Step 18f

  1. GP PB 1×200 DA LV-OUT1-70
  2. GP AL S 24L IO
  3. GP AL S 24L IN
  4. 1,5mm² copper
  5. L < 200m

THORN GTLED Pro - Step 18g

  1. GP PB 2×200 DA LV-OUT2-70
  2. 1,5mm² copper
  3. GP AL S 24L IO
  4. GP AL S 24L IN
  5. L < 200m
19 Maximum Circuit Breaker 135W & 200W

135W
Maximum loading of automatic circuit breaker

THORN GTLED Pro - Step 19a

Calculation uses typical values from ABB series S200 as a reference.
Actual values may differ due to used circuit breaker types and installation environement.

200W
Maximum loading of automatic circuit breaker

THORN GTLED Pro - Step 19b

Calculation uses typical values from ABB series S200 as a reference.
Actual values may differ due to used circuit breaker types and installation environement.

20 Luminaire functional data

THORN GTLED Pro - Step 20a

Wiring type A
luminaire with 1 channel

Wiring type B
luminaire with 2 channels

Wiring type C
luminaire with 3 channels

THORN GTLED Pro - Step 20d

21 CLEANING

EVERY 6 MONTHS

THORN GTLED Pro - Step 21c

-Replace any cracked protective shield.
-Class II luminaires must be installed so that exposed metal work of the luminaire is not in contact with any part of the electrical installation connected to a protective conductor.
WARNING: Class I luminaires must be earthed.
-This luminaire operates at mains voltage which must be switched off before intervention in control gear.
-Any modification to this luminaire is forbidden.
-Lighted objects nearer than the minimal distance in the is forbidden.

Thorn Lighting is constantly developing and improving its products. The right is reserved to change specifications without prior notification or public announcement.
© Thorn Lighting

96670083 02 01/2022