THORN ALTIS G4 Floodlight Instruction Manual

June 8, 2024
THORN

ALTIS G4 Floodlight
Instruction ManualTHORN ALTIS G4 Floodlight

ALTIS G4 Floodlight

TYPE: ALG4 432L
IP66 / IK08
=30.9 kg
The luminaire with clear optic should be positioned so that prolonged staring into the luminaire at a distance <2m is not expected
Caution, risk of electric shock
Extreme caution: Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire
The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.THORN ALTIS
G4 Floodlight - icon 4

GEAR BOX : ALG4 GB LE 432L

THORN ALTIS G4 Floodlight - Figure 1 TaMIN = -40°C / TaMAX = +50°C
(up to 50°C with driving current derating)
IP66 / IK08
corrosion environment from C1 to C3 according to standard ISO9223
ALG4 GB 432LTHORN ALTIS G4 Floodlight - Figure 2 TaMIN = -40°C / TaMAX = +55°C
(up to 55°C with driving current derating)
IP66 / IK08

DIMENSIONS

THORN ALTIS G4 Floodlight - Figure 3

  ScXO° * ScX15′ * ScX45° * SX65′ * ScX90° *
ALG4 432L 0.14 0.26 0.48 0.55

THORN ALTIS G4 Floodlight - Figure 4 *** These data refer to the worst case at indicated angle
ALG4 GB LE 432L**THORN ALTIS G4 Floodlight - Figure
5THORN ALTIS G4 Floodlight - Figure 6

  1. 1xM20 with extra large washer (not provided)
    or

  2. 2xM20 with extra large washer (not provided)

For installation higher >3m
Secure product with retaining cable attached to the frame (not included in the delivery).
Please refer to local installation norms/regulations.THORN ALTIS G4
Floodlight - Figure 7THORN ALTIS G4 Floodlight - Figure
8THORN ALTIS G4 Floodlight - Figure 9THORN ALTIS
G4 Floodlight - Figure 10

CONNECTION BOX

THORN ALTIS G4 Floodlight - Figure 11

ELECTRICAL CONNECTION

THORN ALTIS G4 Floodlight - Figure 12 Extreme caution :
Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire (7*)  Optionnal : NTC connection (thermal monitoring).
Cable 9x cores or above is recommended (ex : H07 RN-F 9G1,5mm²)

PINOUT

Number| Label| Description
1| +1| LED1+Connection (TOP Brick
2| -1| LED1-Connection (TOP Brick
3| +3| LED3+Connection (BOT Brick
4| -3| LED3-Connection (BOT Brick
5| +2| LED2+Connection (MID Brick
6| -2| LED2-Connection (MID Brick
7| NTC option| Thermal Measure INPUT
| GND| PROTECTIVE EARTH
| GND| PROTECTIVE EARTH

THORN ALTIS G4 Floodlight - Figure 13 Recommended:
H07 RN-F 9G1,5 mm² with NTC connected or H07 RN-F 7G1,5 mm² if NTC not connected THORN ALTIS G4 Floodlight - Figure 14 Recommended:
H07 RN-F 7G1,5 mm² ( Without NTC )

ALG4 GB 432L / ELECTRICAL CONNECTION / DALI

THORN ALTIS G4 Floodlight - Figure 15

Extreme caution: Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire

PINOUT

Number| Label| Description
| L1| AC LINE 1 INPUT
| L2| AC LINE 2 INPUT
| | PROTECTIVE EARTH
| DA+| DALI INPUT
| DA+| DALI RE-LAUNCH
| DA-| DALI INPUT
| DA-| DALI RE-LAUNCH
| | PROTECTIVE EARTH FOR LED MODULE
7| NTC| THERMAL MEASURE INPUT
1| 1| LED1+CONNECTION (TOP Brick)
2| -1| LED1-CONNECTION (TOP Brick)
5| 2| LED2+CONNECTION (MID Brick)
6| -2| LED2-CONNECTION (MID Brick)
3| 3| LED3+CONNECTION (BOT Brick)
4| -3| LED3-CONNECTION (BOT Brick)

THORN ALTIS G4 Floodlight - Figure 16

SIGNALLING LED INDICATIONS ON THE GEAR BOX

PERIOD| PULSES| FAULT DESCRIPTION| PRIORITY
The encoded faults are based on pulses emitted every 4 seconds| 1| One or more CCR module enabled by config are not communicating with logic board| Maximum
Minimum
5| Firmware version of one or more CCR module is not compatible with logic board firmware version
2| One or more CCR’s output is short-circuited
3| Load failure on one or more CCR’s output
4| Thermal derating active (output current reduction)

CABLE GLAND

TYPE ØMin ØMax
M16 5 mm 10 mm
M25 10 mm 17 mm
M32 13 mm 21 mm

ALG4 GB 432L / ELECTRICAL CONNECTION / RDM-DMX

THORN ALTIS G4 Floodlight - Figure 17 Extreme caution: Do not connect any LED CONNECTION wire (high voltage) inside NTC connector !! It could result in a critical failure and damage irreversibly the ALTIS luminaire

PINOUT

Number| Label| Description
| L1| AC LINE 1 INPUT
| L2| AC LINE 2 INPUT
| | PROTECTIVE EARTH
| A| DMX INPUT DATA+
| A| DMX-RE-LAUNCH DATA+
| B| DMX INPUT DATA-
| B| DMX-RE-LAUNCH DATA
| S| DMX COMMON / SHIELD
| S| DMX COMMON / SHIELD
| | PROTECTIVE EARTH FOR LED MODULE
7| NTC| THERMAL MEASURE INPUT
1| -1| LED1+CONNECTION (TOP Brick)
2| 1| LED1-CONNECTION (TOP Brick)
5| 2| LED2+CONNECTION (MID Brick)
6| -2| LED2-CONNECTION (MID Brick)
3| 3| LED3+CONNECTION (BOT Brick)
4| -3| LED3-CONNECTION (BOT Brick)

THORN ALTIS G4 Floodlight - Figure 18

SIGNALLING LED INDICATIONS ON THE GEAR BOX

PERIOD| PULSES| FAULT DESCRIPTION| PRIORITY
The encoded faults are based on pulses emitted every 4 seconds| 1| One or more CCR module enabled by config are not communicating with logic board| Maximum
Minimum
5| Firmware version of one or more CCR module is not compatible with logic board firmware version
2| One or more CCR’s output is short-circuited
3| Load failure on one or more CCR’s output
4| Thermal derating active (output current reduction)

CABLE GLAND

TYPE ØMin ØMax
M16 5 mm 10 mm
M25 10 mm 17 mm
M32 13 mm 21 mm

ALG4 GB 432L MOUNTING

THORN ALTIS G4 Floodlight - Figure 19

ALG4 GB 432L / 200-250 Vac – ALG4 GB 432L/250-440 Vac

CIRCUIT BREAKER recommendation
It should mentioned in the notice that calculation has been done with a Circuit Breaker Load Factor of 100%.

V in
Nominal| Inrush Current Data| # Drivers for each Circuit Breaker
---|---|---
I peak
(A)| Half Value
Time (ps)| Type B
10A| Type B
16A| Type B
20A| Type B
25A| Type C
10A| Type C
16A| Type C
20A| Type C
25A| Type D
10A| Type D
16A| Type D
20A| Type D
25A
230Vac| 40| 2500| 0| 1| 1| 2| 0| 1| 1| 2| 0| 1| 1| 2
400Vac| 68| 2000| 0| 1| 1| 1| 1| 1| 2| 2| 1| 1| 2| 3

GUIDELINE FOR INTEGRATION OF GEAR BOXTHORN ALTIS G4 Floodlight - Figure
20 If you cannot follow instructions included in previous section regarding gear box integration, you have to measure Tc reference point taking into consideration that measures must be down to Tc_max

Tc Reference at Max Ambient

Position| Horizontal| Vertical| Side
THORN ALTIS G4 Floodlight - Figure 21
230Vac| 81°C| 80°C| 82°C (Ref.)
400Vac| 69°C| 68°C| 70°C (Ref.)
Ambient Max| 55°C| 55°C| 55°C (Ref.)

ALG4 GB LE 432L / ELECTRICAL CONNECTION

THORN ALTIS G4 Floodlight - Figure 22

PINOUT

Number Label Description
L AC INPUT
N AC INPUT
PE PROTECTIVE EARTH
PE PE FOR LED MODULE
NTC THERMAL PROTECTION FOR LED FIXTURE
3 V3+ OUTPUT CHANNEL 3+ (BOT Brick)
1 V3- OUTPUT CHANNEL 3- (BOT Brick)
2 V2+ OUTPUT CHANNEL 2+ (MID Brick)
4 V2- OUTPUT CHANNEL 2- (MID Brick)
5 V1+ OUTPUT CHANNEL 1+ (TOP Brick)
6 V1- OUTPUT CHANNEL 1- (TOP Brick)

THORN ALTIS G4 Floodlight - Figure 23 The wiring should be strictly followed by the marking label instruction, Otherwise the product could be damaged or the fonctions could be affected.
Each set of + or – are not potential identical, cross connection is prohibited.

CABLE GLAND

TYPE| ØMin| ØMax
M20| 6.3 mm| 11.3 mm
M25| 10 mm| 16.3 mm

ALG4 GB LE 432L MOUNTING

THORN ALTIS G4 Floodlight - Figure 24

ALG4 GB LE 432L / 200-250 Vac – ALG4 GB LE 432L/250-440 Vac

Drivers for each circuit breaker
Referring to the circuit breakers available on the market, the maximum number on the driver connectable for each circuit breaker is as the following table.

Circuit Breaker Type| MCB B/C 10A| MCB B/C 16A| MCB B/C 20A| MCB B/C 25A| MCB B/C 32A
---|---|---|---|---|---
Input: 220~240Vac| 1| 1| 2| 2| 3
Input: 380~400Vac| 1| 2| 2| 3| 4

GUIDELINE FOR INTEGRATION OF GEAR BOXTHORN ALTIS G4 Floodlight - Figure
25 If you cannot follow instructions included in previous section regarding gear box integration, you have to measure Tc reference point taking into consideration that measures must be down to Tc_max

Tc Reference at Max Ambient

Position| Horizontal| Vertical| Side
220Vac| 85°C| 84°C| 85°C (Ref.)
400Vac| 80°C| 77°C| 80°C (Ref.)
Ambient Max| 50°C| 50°C| 50°C (Ref.)

Aiming Device

ALTIS LED AIMING DEVICE
Installation instructionsTHORN ALTIS G4 Floodlight - Figure
27

96671487 ALTIS G5 AIMING DEVICE WITH VISOR
96671488 ALTIS G5 AIMING DEVICE BRACKET

Louvres / Bird Deterrent
ALTIS LED
Installation instructions
TYPE : ALTIS LED G4/G5 ACCESSORIESTHORN ALTIS G4 Floodlight - Figure
30

96671492 ALTIS G5 1 BRICK LOUVRE A4
96671493 ALTIS G5 1 BRICK LOUVRE A5
96671494 ALTIS G5 1 BRICK LOUVRE A6/A6I
96671496 ALTIS G5 1 BRICK LOUVRE MB
96671495 ALTIS G5 1 BRICK LOUVRE NB/EB
96671497 ALTIS G5 1 BRICK LOUVRE WB

96671489 ALTIS G5 BIRD DETERRENT
Visor
ALTIS LED
Installation instructions
TYPE: ALTIS G4/G5 ACCESSORIES
96671498 ALTIS G5 1 BRICK AJ VISORTHORN ALTIS G4 Floodlight - Figure
32 Power supply support
ALTIS LED
Installation instructions
TYPE: ALTIS G4/G5 ACCESSORIES 96671490 ALTIS G5 GB BRACKET 3 BRICK STIRRUPTHORN ALTIS G4 Floodlight - Figure 34

  • Replace any cracked protective shield.

  • Class II luminaires must be installed so that exposed metal work of the luminaire is not in contact with any part of the electrical installation connected to a protective conductor.
    WARNING: Class I luminaires must be earthed.

  • This luminaire operates at mains voltage which must be switched off before intervention in control gear.

  • Any modification to this luminaire is forbidden.

  • Lighted objects nearer than the minimal distance in the is forbidden.

Thorn Lighting is constantly developing and improving its products. The right is reserved to change specifications without prior notification or public announcement.

© Thorn Lighting

  • To ensure maintaining the best system performances, we advice to switch on the system “At least one night hour per month”.
  • corrosion environment from C1 to C5 according to standard ISO9223 except gear box ALG4 GB LE 432L corrosion environment from C1 to C3

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>