hakel HGS 100 EB Separating Lightning Rod Instruction Manual

June 4, 2024
hakel

hakel HGS 100 EB Separating Lightning Rod

hakel-HGS-100-EB-Separating-Lightning-Rod-PRODUCT

The length of the flexible connecting cable is 200 mm and it is ended with a loop GPH12 of cross section 13 mm.

DIMENSION

hakel-HGS-100-EB-Separating-Lightning-Rod-FIG-1

Type   HGS 100 HGS 100 EB HGS 100 ST
Class to EN 62561-3, IEC 62561-3     H (for high loading)
DC-Sparkover voltage   400 ÷ 750 V DC
Nominal discharge current (8/20) In   100 kA
Rated over power frequency withstand voltage UW AC 285 V
Rated DC withstand voltage UW DC   350 V
Rated impulse spark over voltage Ur imp < 1400 V
Max. lightning impulse current (10/350) Imp   100 kA
charge Q   50 As
specific energy W/R   2500 kJ/Ω
Insulation resistance at 100 V DC Ri > 1 GΩ
Capacitance at 1 MHz C   25 pF
Housing material   aluminum
Degree of protection of the enclosure     IP66
Operating temperature range -40 °C ÷ +70 °C
Lifetime     min. 100 000 h
Weight m 320 g
Article number   10 005 10 009 10 101

hakel-HGS-100-EB-Separating-Lightning-Rod-FIG-2

Safety instructions

The product may only be connected and installed by an electrician. Before installation, the product must be checked for physical damage. If any defect or deficiency is found during this inspection, the product must not be installed. Its permissible use is described in the installation instructions. Follow the installation instructions carefully and connect according to the connection diagram provided. This product and its linked equipment may be damaged by loads that exceed a given value. Interference with the device leads to the loss of the right to claim.

HAKEL spol. s r.o.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

hakel User Manuals

Related Manuals