hakel HGS 100 EB Separating Lightning Rod Instruction Manual
- June 4, 2024
- hakel
Table of Contents
hakel HGS 100 EB Separating Lightning Rod
The length of the flexible connecting cable is 200 mm and it is ended with a loop GPH12 of cross section 13 mm.
DIMENSION
Type | HGS 100 | HGS 100 EB | HGS 100 ST | |
---|---|---|---|---|
Class to EN 62561-3, IEC 62561-3 | H (for high loading) | |||
DC-Sparkover voltage | 400 ÷ 750 V DC | |||
Nominal discharge current (8/20) | In | 100 kA | ||
Rated over power frequency withstand voltage | UW AC | 285 V | ||
Rated DC withstand voltage | UW DC | 350 V | ||
Rated impulse spark over voltage | Ur imp | < 1400 V | ||
Max. lightning impulse current (10/350) | Imp | 100 kA | ||
charge | Q | 50 As | ||
specific energy | W/R | 2500 kJ/Ω | ||
Insulation resistance at 100 V DC | Ri | > 1 GΩ | ||
Capacitance at 1 MHz | C | 25 pF | ||
Housing material | aluminum | |||
Degree of protection of the enclosure | IP66 | |||
Operating temperature range | -40 °C ÷ +70 °C | |||
Lifetime | min. 100 000 h | |||
Weight | m | 320 g | ||
Article number | 10 005 | 10 009 | 10 101 |
Safety instructions
The product may only be connected and installed by an electrician. Before installation, the product must be checked for physical damage. If any defect or deficiency is found during this inspection, the product must not be installed. Its permissible use is described in the installation instructions. Follow the installation instructions carefully and connect according to the connection diagram provided. This product and its linked equipment may be damaged by loads that exceed a given value. Interference with the device leads to the loss of the right to claim.
HAKEL spol. s r.o.
- ADDRESS: Bratri Stefanu 980 500 03 Hradec Kralove Czech Republic
- Phone: +420 494 942 300
- info@hakel.com
- www.hakel.com