MITSUBISHI ELECTRIC PUZ-A12NKA7 Ceiling Cassette Heat Pump System Owner’s Manual

June 17, 2024
Mitsubishi Electric

MITSUBISHI ELECTRIC PUZ-A12NKA7 Ceiling Cassette Heat Pump System

MITSUBISHI ELECTRIC PUZ-A12NKA7 Ceiling Cassette Heat Pump
System

INDOOR UNIT FEATURES

  • Space-efficient ductless installation
  • Equipped with 3D i-see Sensor® for enhanced comfort and energy efficiency
  • Airflow settings for high and low ceiling applications
  • Individual vane settings for direct/indirect airflow control or variable airflow patterns
  • Knockouts for outside-air intake and branch-duct run
  • Filter indicator signal
  • Easy-to-clean, washable filter (optional high-efficiency filter available – requires multi-function casement)
  • Built-in condensate lift mechanism
  • Ideal for retail shops, classrooms, office spaces, conference centers, building lobbies, and more
  • Multiple control options available:
    • kumo cloud® smart device app for remote access
    • Third-party interface options
    • Wired or wireless controllers

OUTDOOR UNIT FEATURES

  • Variable speed INVERTER-driven compressor
  • Pre-charged with refrigerant volume for piping length up to 70 ft
  • Low ambient cooling down to 0°F providing 100% capacity
  • 24-hour continuous operation (cooling mode)
  • High pressure protection
  • Fast restart
  • Superior energy and operational efficiency
  • Seacoast protection*
    • External Outer Panel: Phosphate coating + Acrylic-Enamel coating
    • Fan Motor Support: Epoxy resin coating (at edge face)
    • Separator Assembly Valve Bed: Epoxy resin coating (at edge face)
    • Blue Fin treatment is an anti-corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants.
    • Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing
    • Seacoast protection standard from 2022 production

SPECIFICATIONS

PLA-A12EA7 & PUZ-A12NKA7

Cooling at 95°F1

| Maximum Capacity| BTU/H| 12,000
---|---|---|---
Rated Capacity| BTU/H| 12,000
Minimum Capacity| BTU/H| 5,800
Maximum Power Input| W| 730
Rated Power Input| W| 730
Moisture Removal| Pints/h| 1.2
Sensible Heat Factor| 0.89
Power Factor [208V / 230V]| %| 93.4 / 93.4

Heating at 47°F2

| Maximum Capacity| BTU/H| 20,000
Rated Capacity| BTU/H| 14,000
Minimum Capacity| BTU/H| 5,500
Maximum Power Input| W| 1,500
Rated Power Input| W| 830
Power Factor [208V / 230V]| %| 95.0 / 95.0

Heating at 17°F3

| Maximum Capacity| BTU/H| 12,200
Rated Capacity| BTU/H| 10,100
Maximum Power Input| W| 1,200
Rated Power Input| W| 1,170

Efficiency

| SEER | SEER2| 27.0 | 26.9
EER1 | EER21| 16.4 | 16.4
HSPF [IV] | HSPF2 [IV]| 12.8 | 10.9
COP at 47°F2| 4.94
COP at 17°F at Maximum Capacity3| 2.98
ENERGY STAR® Certified| Yes

Electrical

| Voltage, Phase, Frequency| 208/230, 1, 60
Guaranteed Voltage Range| V AC| 198 – 253
Voltage: Indoor – Outdoor, S1-S2| V AC| 208/230
Voltage: Indoor – Outdoor, S2-S3| V DC| 24
Short-circuit Current Rating [SCCR]| kA| 5
Recommended Fuse/Breaker Size (Oudoor)| A| 15
Recommended Wire Size [Indoor – Outdoor]| AWG| 14
Power Supply| Indoor unit is powered by the outdoor unit

Indoor Unit

| MCA| A| 1.0
Fan Motor Full Load Amperage| A| 0.26
Fan Motor Type| DC Motor
Airflow Rate at Cooling, Dry| CFM| 420–460–490–530
Airflow Rate at Cooling, Wet| CFM| 380–420–450–490
Airflow Rate at Heating, Dry| CFM| 420–460–490–530
Sound Pressure Level [Cooling]| dB[A]| 27–28–29–30
Sound Pressure Level [Heating]| dB[A]| 27–28–29–30
Drain Pipe Size| In. [mm]| 1-1/4 [32]
Condensate Lift Mechanism, Maximum Distance| In. [mm]| 33-7/16 [849]
Coating on Heat Exchanger| —
External Finish Color| White Munsell 6.4Y 8.9/0.4
Unit Dimensions| W x D x H: In. [mm]| 33-1/16 // 37-13/32 x 33-1/16 // 37-13/32 x 10-5/32 // 1-9/16 [840 //

950 x 840 // 950 x 258 // 40]

Package Dimensions| W x D x H: In. [mm]| 35-9/16 // 39-6/16 x 34-5/16 // 38-3/16 x 15 // 4-12/16 [903 // 1,000

x 871 // 970 x 381 // 121]

Unit Weight| Lbs. [kg]| 46 // 11 [21 // 5]
Package Weight| Lbs. [kg]| 68 [31]
Indoor Unit Operating Temperature Range| Cooling Intake Air Temp [Maximum / Minimum]*| °F| 90 DB, 72 WB / 66 DB, 61 WB
Heating Intake Air Temp [Maximum / Minimum]| °F| 77 DB / 59 DB

  1. Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
  2. Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
  3. Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB

Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):

  • Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
  • Wind baffles required to operate below 23°F DB in cooling mode.
  • Heat pump system with wind baffle: 0°F – 115°F.
  • Refer to wind baffle documentation for further information.

Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re- start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

Blue Fin Coating Standard from 2022 production:
• PU(Y/Z)-A(12/18)NKA7 – Beginning with serial number 12U
• PU(Y/Z)-A(24/30/36/42)NKA7 – Beginning with serial number 1ZU

PLA-A12EA7 & PUZ-A12NKA7

Outdoor Unit

| MCA| A| 11.0
---|---|---|---
MOCP| A| 28
Fan Motor Full Load Amperage| A| 0.5
Fan Motor Output| W| 46
Airflow Rate [Cooling / Heating]| CFM| 1590 / 1590
Refrigerant Control| LEV
Defrost Method| Reverse Cycle
Coating on Heat Exchanger| Blue Fin Coating***
Sound Pressure Level, Cooling1| dB(A)| 44
Sound Pressure Level, Heating2| dB(A)| 46
Compressor Type| INVERTER-driven twin rotary
Compressor Model| SNB092FQCMC
Compressor Rated Load Amps| A| 7
Compressor Locked Rotor Amps| A| 12.0
Compressor Oil [Type // Charge]| oz.| FV50S // 12
External Finish Color| Ivory Munsell 3Y 7.8/1.1
Base Pan Heater| N/A
Unit Dimensions| W x D x H: In. [mm]| 31-13/16 (2+7/16) x 11-13/16 x 24-13/16 [809 (+62) x 300 x 630]
Package Dimensions| W x D x H: In. [mm]| 37-1/16 x 16-3/16 x 27-7/16 [941 x 411 x 697]
Unit Weight| Lbs. [kg]| 93 [42]
Package Weight| Lbs. [kg]| 104 [47]

Outdoor Unit Operating Temperature Range

| Cooling Air Temp [Maximum / Minimum]*| °F| 115 DB / 0 DB
Heating Air Temp [Maximum / Minimum]| °F| 70 DB, 59 WB / 12 DB, 14 WB
Heating Thermal Lock-out / Re-start Temperatures**| °F| 8 / 12

Refrigerant

| Type| R410A
Pre-Charged Refrigerant Amount| Lbs, oz| 4.0, 7.0
Maximum Pre-Charged Piping Length| Ft. [m]| 70.0 [21.0]
Additional Refrigerant Charge Per Additional Piping Length| oz./Ft. [g/m]| 0.2 [19]

Piping

| Gas Pipe Size O.D. [Flared]| In.[mm]| 1/2 [12.7]
Liquid Pipe Size O.D. [Flared]| In.[mm]| 1/4 [6.35]
Maximum Piping Length| Ft. [m]| 100 [30]
Maximum Height Difference| Ft. [m]| 100 [30]
Maximum Number of Bends| 15

NOTES:
AHRI Rated Conditions
(Rated data is determined at a fixed compressor speed)

  1. Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
  2. Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
  3. Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB

Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):

  • Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
  • Wind baffles required to operate below 23°F DB in cooling mode.
  • Heat pump system with wind baffle: 0°F – 115°F.
  • Refer to wind baffle documentation for further information.

Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re- start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
• System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

Blue Fin Coating Standard from 2022 production:
• PU(Y/Z)-A(12/18)NKA7 – Beginning with serial number 12U
• PU(Y/Z)-A(24/30/36/42)NKA7 – Beginning with serial number 1ZU

INDOOR UNIT ACCESSORIES

PLA-A12EA7

Control Interface

| 3-Pin Connector| □ PAC-715AD
---|---|---
Airzone ZBS Wired Blueface Principal Controller White| □ AZZBSBLUEFACECB
Airzone ZBS Wired Blueface Principal Controller White| □ AZZBSBLUEZEROCB
Airzone ZBS Wired Lite Controller White| □ AZZBSLITECB
Airzone ZBS Wireless Lite Controller White| □ AZZBSLITERB
Airzone ZBS Wireless Think Controller White| □ AZZBSTHINKRB
BACnet® and Modbus® Interface| □ PAC-UKPRC001-CN-1
CN24 Relay Kit| □ CN24RELAY-KIT-CM3
IT Extender| □ PAC-WHS01IE-E
kumo station® for kumo cloud®| □ PAC-WHS01HC-E
Remote Operation Adapter‡| □ PAC-SF40RM-E
Thermostat Interface| □ PAC-US444CN-1
Thermostat Interface| □ PAC-US445CN-1
USNAP Adapter| □ PAC-WHS01UP-E
Wireless Interface for kumo cloud®| □ PAC-USWHS002-WF-2

Remote Sensor

| Flush Mount Remote Temperature Sensor| □ PAC-USSEN002-FM-1
Flush Mount Temperature Sensor| □ PAC-USSEN001-FM-1
Remote Temperature Sensor| □ PAC-SE41TS-E
Wireless temperature and humitity sensor for kumo cloud®| □ PAC-USWHS003-TH-1

Wired Remote Controller

| Deluxe Wired MA Remote Controller†| □ PAR-40MAAU
Simple Ductless Wired Remote Controller| □ PAC-SDW01RC-1
Simple MA Remote Controller†| □ PAC-YT53CRAU-J
Touch MA Controller†| □ PAR-CT01MAU-SB

Wireless Remote Controller

| kumo touch™ RedLINK™ Wireless Controller| □ MHK2
Lockdown bracket for remote controller| □ RCMKP1CB
Wireless MA Receiver| □ PAR-FA32MA-W
Wireless MA Remote Controller| □ PAR-FL32MA-E
Wireless Remote Contoller| □ PAR-SL101A-E
Wireless Signal Receiver Panel| □ PAR-SR4LU-E
Casement| Multi-function Casement| □ PAC-SJ41TM-E

Condensate

| Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended]| □ X87-721
Blue Diamond (MicroBlue) Mini Condensate Pump (110/208/230V) up to 18,000 BTU/H| □ X86-003
Blue Diamond Sensor Extension Cable — 15 Ft.| □ C13-103
Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H| □ COMBI

Disconnect Switch

| (30A/600V/UL) [fits 2” X 4” utility box] – Black| □ TAZ-MS303
(30A/600V/UL) [fits 2” X 4” utility box] – White| □ TAZ-MS303W
Filter| High Efficiency Filter Element**| □ PAC-SH59KF-E
i-see Sensor® Panel| Grille with 3D i-see Sensor® (required)| □ PLP-41EAEU

Lineset

| 100’ x 1/4” x 100’ / 1/2” Lineset (Twin-Tube Insulation)| □ MLS141212T-100
15’ x 1/4” x 15’ / 1/2” Lineset (Twin-Tube Insulation)| □ MLS141212T-15
30’ x 1/4” x 30’ / 1/2” Lineset (Twin-Tube Insulation)| □ MLS141212T-30
50’ x 1/4” x 50’ / 1/2” Lineset (Twin-Tube Insulation)| □ MLS141212T-50
65’ x 1/4” x 65’ / 1/2” Lineset (Twin-Tube Insulation)| □ MLS141212T-65
Shutter Plate| Shutter Plate| □ PAC-SJ37SP-E
Space Panel| Space Panel| □ PAC-SJ38AS-E

NOTES: ‡PAC-SF40RM-E (Unable to use with wireless remote controller)

OUTDOOR UNIT ACCESSORIES

PUZ-A12NKA7

Air Outlet Guide Air Outlet Guide □ PAC-SJ07SG-E

Centralized Drain Pan

| Centralized Drain Pan| □ PAC-SG63DP-E
Drain Pan| □ PAC-SG64DP-E

Control/Service Tool

| Control/Service Tool| □ PAC-SK52ST
M- & P-Series Maintenance Tool Cable Set| □ M21EC0397
USB/UART Conversion Cable (Required for all laptop connection)| □ M21EC1397
Drain Socket| Drain Socket| □ MAC-871DS
Hail Guards| Hail Guard| □ HG-A5
M-NET Converter| M-NET Converter| □ PAC-SJ96MA-E

Mini-Split Wire

| 14 Gauge, 4 wire MiniSplit Cable—250 ft. roll| □ S144-250
14 Gauge, 4 wire MiniSplit Cable—50 ft. roll| □ S144-50
16 Gauge, 4 wire MiniSplit Cable—250 ft. roll| □ S164-250
16 Gauge, 4 wire MiniSplit Cable—50 ft. roll| □ S164-50
Mounting Pad| Condensing Unit Mounting Pad: 16” x 36” x 3”| □ ULTRILITE1

Stand

| 18” Single Fan Stand| □ QSMS1801M
24” Single Fan Stand| □ QSMS2401M
Condenser Wall Bracket| □ QSWB2000M-1
Condenser Wall Bracket – Stainless Steel Finish| □ QSWBSS
Outdoor Unit Stand — 12” High| □ QSMS1201M

Wind Baffle

| Front Wind Baffle| □ WB-PA4
Rear Wind Baffle| □ WB-RE4
Side Advanced Wind Baffle| □ WB-SD4

INDOOR UNIT DIMENSIONS

PLA-A12EA7 NOTE

  1. CHOOSE THE GRILLE AMONG THE DEDICATED GRILLES.
  2. REINFORCE THE SUSPENSION BOLT FOR EARTHQUAKE RESISTANCE AS NEEDED.
  3. FOR THE SUSPENSION BOLT, USE M10 OR W3/8. (PROCURED AT THE LOCAL SITE.)
  4. FOR DRAIN PIPE, USE VP-25(O.D. n1-1/4″(( 32) PVC TUBE). DRAIN PUMP INCLUSION. RAISE IS MAX 33-7/16″(850mm) FROM THE CEILING.
  5. ELECTRICAL BOX MAY BE REMOVED FOR THE SERVICE PURPOSE. MAKE SURE TO SLACK THE ELECTRICAL WIRE LITTLE BIT FOR CONTROL/POWER WIRES CONNECTION.
  6. THE HEIGHT OF THE INDOOR UNIT IS ABLE TO BE ADJUSTED WITH THE GRILLE ATTACHED
  7. REQUIRES “E” OR MORE SPACE BETWEEN TRANSOM AND CEILING FOR THE INSTALLATION.
  8. WHEN INSTALLING THE BRANCH DUCTS, BE SURE TO INSULATE ADEQUATELY. OTHERWISE CONDENSATION AND DRIPPING MAY OCCUR. (IT BECOMES THE CAUSE OF DROPLET OR DROPLET DRIPPING.)
  9. AS FOR NECESSARY INSTALLATION/SERVICE SPACE, PLEASE REFER TO THE RIGHT AT FIGURE.
  10. FOR THE INSTALLATION OF THE OPTIONAL HIGH EFFICIENCY FILTER OR MULTI-FUNCTIONAL CASEMENT, REFER TO SPECIAL DRAWING.

MITSUBISHI ELECTRIC PUZ-A12NKA7 Ceiling Cassette Heat Pump System
1

OUTDOOR UNIT DIMENSIONS

PUZ-A12NKA7

MITSUBISHI ELECTRIC PUZ-A12NKA7 Ceiling Cassette Heat Pump System
2

Free space around the outdoor unit
(basic example)

MITSUBISHI ELECTRIC PUZ-A12NKA7 Ceiling Cassette Heat Pump System
3

FOUNDATION BOLTS
Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts.
(Bolts, washers and nut must be purchased locally).

< Foundation bolt height>

MITSUBISHI ELECTRIC PUZ-A12NKA7 Ceiling Cassette Heat Pump System
4

PIPING-WIRING DIRECTION
Piping and wiring connection can be made from the rear direction only.

1340 Satellite Boulevard Suwanee, GA 30024
Toll Free: 800-433-4822 www.mehvac.com