novus N1040T Controller User Guide
- June 17, 2024
- Novus
Table of Contents
N1040T Controller
Specifications
-
Model: N1040T Controller
-
Inputs: Thermocouple J, Thermocouple K,
Thermocouple T, Pt100 -
Outputs: 2 or 4 output channels
-
Output Types: Voltage pulse output, SPST-NO
Relay, SPDT Relay -
Control Modes: ON/OFF Mode, PID Mode
Product Usage Instructions
Safety Alerts
CAUTION: Read the manual completely before
installing and operating the equipment. All safety recommendations
must be followed to ensure personal safety and prevent damage to
the system.
Risk of Electric Shock: Follow safety
precautions to prevent electric shock.
Installation/Connections
Ensure a firm hold is obtained during installation.
Electrical Connections
The layout of the features on the back panel of the controller
is shown in Figure 1.
Signal Input
The input type must be defined during equipment configuration.
Refer to Table 1 for available input options.
Outputs
The controller has multiple output channels that can be
configured as Control Output, Timer Outputs, or Alarm Outputs.
Refer to the manual for specific configurations of each output
channel.
Temperature Control Output
The process control output can operate in ON/OFF Mode or PID
Mode. Set parameters accordingly and utilize the Auto-tuning
function for PID mode.
Alarm Output
The controller has alarm functions that can be directed to any
output channel. Configure the alarms based on specific conditions
such as Absolute Minimum/Maximum Value Alarm, Differential Value
Alarm, or Open Sensor Alarms.
FAQ
How do I configure the alarm functions on the N1040T
Controller?
To configure alarm functions, refer to Table 2 in the manual for
different alarm trigger conditions such as Absolute Minimum/Maximum
Value Alarm, Differential Value Alarm, or Open Sensor Alarms. Each
alarm function has specific settings to be adjusted based on your
requirements.
What are the available input options for the N1040T
Controller?
The available input options for the N1040T Controller include
Thermocouple J, Thermocouple K, Thermocouple T, and Pt100. Ensure
the correct input type is defined during equipment
configuration.
N1040T Controller
TIME AND TEMPERATURE CONTROLLER USER GUIDE V2.1x N
SAFETY ALERTS
The following symbols are used on the equipment and throughout this manual to
draw the user’s attention to important information related to the safety and
use of the equipment.
CAUTION:
Read the manual completely before installing and operating
the equipment.
CAUTION OR HAZARD: Risk of electric shock.
All safety recommendations appearing in this manual must be followed to ensure personal safety and prevent damage to the instrument or system. If the instrument is used in a manner other than that specified in this manual, the device safety protections may not be effective.
INSTALLATION / CONNECTIONS
The controller should be attached to a panel, following the sequence of steps
below: · Make a panel cutout, as shown in the SPECIFICATIONS section. · Remove
the mounting clamp from the controller. · Insert the controller into the panel
cutout. · Reattach the mounting clamp on the controller, pressing until a
firm hold is obtained.
ELECTRICAL CONNECTIONS
The layout of the features on the back panel of the controller is shown in
Figure 1:
Figure 1 Electrical connections
INSTALLATION RECOMMENDATIONS
· Input signal conductors must run through the plant separately from the
supply and output conductors. If possible, in grounded conduits.
· The power supply for the electronic instruments must come from a proper
instrumentation network.
· It is essential to use RC FILTERS (noise suppressors) at contactor coils,
solenoids, etc.
· In control applications, it is essential to consider what can happen when
any part of the system fails. The internal devices of the equipment do not
guarantee full protection.
FEATURES
SIGNAL INPUT
The input type to be used must be defined during equipment configuration.
Table 1 shows the available input options:
TYPE Thermocouple J Thermocouple K Thermocouple T
Pt100
CODE
MEASUREMENT RANGE
Tc j Range: -110 to 950 °C (-166 to 1742 °F)
Tc k Range: -150 to 1370 °C (-238 to 2498 °F) Tc t Range: -160 to 400 °C (-256 to 752 °F)
Pt Range: -200 to 850 °C (-328 to 1562 °F)
Table 1 Input type
DIGITAL INPUT (DIG IN)
Available at terminals 15 and 16 on the back panel. It recognizes the closure
of Dry Contact switches. The A3 flag indicates the Digital Input condition:
On = DI enabled (closed). Off = DI disabled (open).
OUTPUTS
The controller has 2 or 4 output channels, according to the model ordered.
These channels must be configured to operate as Control Output, T1 Timer
Output, T2 Timer Output, or Alarm 4 Output.
OUTPUT 1 Voltage pulse output type, 5 Vdc / 50 mA max. Available at terminals
4 and 5.
OUTPUT 2 SPST-NO Relay. Available at terminals 6 and 7.
OUTPUT 3 SPST-NO Relay. Available at terminals 13 and 14.
OUTPUT 4 SPDT Relay. Available at terminals 10, 11, and 12.
NOVUS AUTOMATION
1/7
TEMPERATURE CONTROL OUTPUT
The process control output can operate in the following modes: 1) ON/OFF Mode
or 2) PID Mode.
To operate in ON/OFF Mode, you must set the PB parameter to 0.0. The values of
the PID parameters can be set automatically with the Auto-tuning function
(ATvN).
ALARM OUTPUT
The controller has an alarm, which can be directed to any output channel and
can operate with one of the functions described in Table 2:
off Alarm off.
Absolute Minimum Value Alarm.
lo It triggers when the PV (temperature) value is below the value set by the
Alarm Setpoint (SPA4).
PV SPA1
Absolute Maximum Value
Alarm.
PV
ki It triggers when the PV value SPA1 is above the value set by the
Alarm Setpoint.
Differential Value Alarm.
In this function, the SPA4 parameter represents a difference between PV and control SP.
dif
PV
PV
difl
SP SPA4 SP SP + SPA4
SV + SPA4 SP SV SPA4
Positive SPA4
Negative SPA4
Minimum Differential Value Alarm.
It triggers when the PV value is below the point set by SP-SPA4 (using alarm 1
as an example).
PV
PV
SP SPA4
SP
SP SP SPA4
difk
Positive SPA4
Negative SPA4
Maximum Differential Value Alarm.
It triggers when the PV value is above the point set by SP+SPA4.
SP SP + SPA4
PV
PV
SP + SPA4 SP
Positive SPA4
Negative SPA4
ierr
Open Sensor Alarms (Sensor Break Alarm).
It operates when the input presents problems such as a broken sensor, poorly
connected sensor, etc.
Table 2 Alarm functions
Important note: Alarms configured with functions ki, diff, and diffk will also trigger the related output when the controller identifies and signals a sensor failure. A relay type output configured to act as a Maximum Alarm (ki), for example, will act when the SPAL value is exceeded and when the sensor connected to the controller input is broken.
NOVUS AUTOMATION
N1040T Controller
ALARM INITIAL BLOCK
The Initial Block feature inhibits the alarm from being activated if an alarm
condition exists in the process when the controller goes into operation. The
alarm will only be enabled after the process has passed a non-alarm condition.
This function is useful, for example, at the beginning of the process control
operation. At this point, the PV value is still far from the value set with
SP. Thus, alarm situations are expected and often their signaling is unwanted.
The Initial Block is not valid for the ierr function (Open Sensor).
OFFSET
Feature that allows you to make small adjustments to the PV indication. It
allows you to correct measurement errors that appear, for example, when
replacing a temperature sensor.
LOOP BREAK DETECTION FUNCTION
The lbd.t parameter sets a maximum time interval, in minutes, for PV to react
to the command from the control output. If there is not a minimal and proper
reaction throughout this interval, the controller will signal the occurrence
of a LBD event on its display. This indicates problems in the control loop. If
you set the lbd.t parameter to 0 (zero), this function is disabled. This
function allows you to detect problems in the installation, such as a bad
actuator or a failure in the power supply process to the load.
SAFE OUTPUT FUNCTION DURING SENSOR FAILURE
Function that puts the control output into a safe condition for the process
when identifying an error in the sensor input. When identifying a sensor
failure, the controller will set the percentage value (set in 1E.ov parameter)
for the control output. The controller will remain in this condition until the
sensor failure disappears. When in ON/OFF Mode, the values for 1E.ov are only
0 and 100 %. When in PID Mode, any values between 0 and 100 % are accepted.
USB INTERFACE
The USB interface is used to CONFIGURE, MONITOR, or UPDATE the FIRMWARE. To do
this, you must use QuickTune software, which offers features to create, view,
save, and open configurations from the device or from files on your computer.
The feature to save and open configurations in files allows you to transfer
configurations between devices and create backups. For specific models,
QuickTune allows you to upgrade the firmware (internal software) of the
controller via USB interface. To MONITOR, you can use any supervisory (SCADA)
or laboratory software that supports Modbus RTU communication over a serial
communication port. When connected to the USB interface of a computer, the
controller will be recognized as a conventional serial port (COM x). You
should use QuickTune software or consult the Device Manager in the Windows
Control Panel to identify the COM port assigned to the device. Refer to the
Modbus memory mapping in the device communication manual and the supervisory
software documentation. To use the USB communication, follow the steps below:
1. Download QuickTune software, free of charge, from our website and install
it on the computer to be used. The USB drivers required for the operation of
the communication will be installed with the software.
2. Connect the USB cable between the device and the computer. The controller
does not need to be powered. The USB interface will provide enough power for
the
2/7
communication to operate (other device functions may not operate). 3. Run
QuickTune, configure the communication, and start the device recognition.
The USB interface IS NOT ISOLATED from the signal input (INPUT) and possible
digital inputs and outputs of the controller. Its purpose is temporary use
during CONFIGURATION and MONITORING periods. For the safety of people and
equipment, it should only be used when the equipment is fully disconnected
from the input/output signals. The USB interface can be used in any other
situation, but it requires careful consideration by the people performing the
installation. For MONITORING over long periods and with the inputs and outputs
connected, it is recommended to use the RS485 interface, available or optional
in most of our devices.
TIMERS
The controller has 2 timers, which can operate independently of the
temperature control.
T1 TIMER
T1 is the main timer. It has several features that provide different modes of
operation.
T1 TIMER – STARTUP MODES
T1 Timer has 4 trigger modes:
RUN Allows you to start time counting when activating control (RvN = YES).
SP Allows you to start time counting when the PV value reaches the SP value
set for the process.
F Allows you to start time counting by using the key. Once the timing has
started, pressing the key again will interrupt the process.
To start a new cycle, press the key again.
DI Allows you to start time counting via Digital Input. When you trigger the
DI (close contact), the time counting will start. If the DI is disabled (open
contact) before the end of the timer, it will be interrupted. Returning to DI
will start a new cycle.
Note: If you manually set the RvN parameter to NO (control disabled), the
triggering options via key and DI will not allow you to re-enable control (RvN
= YES).
T1 TIMER – OPERATION MODES
T1 Timer has 3 operation modes:
off T1 output turns off at the end of T1. In this mode, T1 output turns on at
the beginning of T1 and turns off at the end of T1. The A1 flag turns on at
the beginning of the timer and flashes after the end of the T1 interval.
On T1 output turns on at the end of T1. When T1 timer starts, the T1 output
remains off. At the end of the timer, T1 output is turned on and will remain
in this condition until a new cycle starts. The A1 flag flashes during the
timing of T1. After T1, it
NOVUS AUTOMATION
N1040T Controller
turns on permanently, signaling that the output is still on. On.x T1 output
remains on at the end of T1. The T1 output is switched on at the beginning of
T1 timer and remains in this condition even at the end of the timing. The A1
flag turns on during the timing of T1. After T1, it starts flashing, signaling
that the output is still on. The operation modes define the behavior of the
outputs linked to the timer. You can link to any available output: OUT1, OUT2,
OUT3, or OUT4. The A1 flag indicates the current stage of the timer.
T2 TIMER
Secondary timer. It starts its timing at the end of T1. It can also be linked
to any available output on the controller. The linked output always turns on
at the beginning of T2 and turns off at the end. The A2 flag indicates the
condition of timing T2:
T2 in progress A2 on. T2 not started or already finished A2 off.
TIMING DIRECTION
The time counting for the timers can occur in 2 modes: 1) Increasing Mode or
2) Decreasing Mode. In Increasing Mode (UP), counting starts at 0 and goes up
to the programmed time interval (T1, T2) In Decreasing Mode (DOWN), it starts
at the programmed time value and goes down to 0.
BEHAVIOR OF THE TEMPERATURE CONTROL AT THE END OF THE TIMER
During the timing intervals of T1 and T2, the temperature control has normal
operation. The output defined as Temperature Control acts to bring the PV
value to the value set in SP. However, at the end of the T1 + T2 interval, it
is possible to configure the controller to disable temperature control,
setting the RvN parameter to NO. See T.E.(.0 Parameter (Timer Cycle).
TIMER TIME BASE
The TBAS parameter (Timer Cycle) allows you to set the time base to be used.
The options are:
Sec MM:SS. The time intervals T1 and T2 are shown in minutes and seconds.
Min HH:MM. The time intervals T1 and T2 are shown in hours and minutes.
3/7
OPERATION
The front panel of the controller can be seen in Figure 2:
Figure 2 Front panel identification Display: Displays the measured variable,
configuration parameter symbols, and their respective values/conditions. TUNE
flag: Remains on while the controller is in the tuning process. RUN flag:
Indicates that the controller is in operation. OUT flag: Indicates the status
of the temperature control output. A1 flag: Indicates the status of the output
linked to T1. A2 flag: Indicates the status of the output linked to T2. A3
flag: Indicates the Digital Input condition. A4 flag: Indicates the Alarm 4
condition.
Key: Key used to advance to successive parameters and parameter cycles.
Increment Key and Decrement Key: Keys used to change parameter values.
Key: Key used to move back parameters during configuration.
STARTUP
When powered up, the controller displays its software version number for the
first 3 seconds. After that, it will show the measured process variable (PV)
value (temperature) in the upper display and the SP value in the lower
display. This is the Indication Screen. To be used in a process, you need to
configure the controller. To configure it, you must define each of its
parameters. The configuration parameters are gathered into affinity groups,
called parameter cycles:
Operation / Tuning / Timer / Alarms / Input / Calibration The key gives access
to the cycles and their parameters. By holding down the key, the controller
jumps from one cycle to another every 2 seconds, displaying the first
parameter of each cycle: PV >> atvn >> t1 >> fva4 >> type >> pass >> PV … To
enter the desired cycle, simply release the key when its first parameter is
displayed. To advance through the parameters of this cycle, press the key with
short touches. At the end of each cycle, the controller will return to the
Indication Screen. The symbol for each parameter will be shown in the upper
display while its respective value/condition will be shown in the lower
display.
N1040T Controller
PARAMETER DESCRIPTION
OPERATION CYCLE
PV + SP
PV Indication Screen.
The value of the measured variable (PV) temperature is shown in the upper
display (red).
The control Setpoint value (SP) is shown in the lower display (green).
PV + TM
PV Indication screen and elapsed time. The upper display (red) shows the
measured temperature value (PV).
The lower display (green) shows the countdown of the time interval set for T1
Time.
You cannot adjust this screen.
T1
Timer 1
Allows you to set the T1 Time interval.
Adjustable between 00:00 and 99:59 (HH:MM or MM:SS).
This parameter will be displayed in this cycle when defined in T.en parameter.
SP.A4
Alarm SP. Allows you to define the actuation point of the alarm outputs.
For alarms programmed with Differential type functions, these parameters set
deviations.
This parameter will be displayed in this cycle when defined in sp4 parameter.
Rvn Allows you to enable or disable the controller’s Run action on the
process. It acts as a switch, turning the
controller on or off.
YES Enabled outputs.
NO Disabled outputs.
This parameter will be displayed in this cycle when defined in rvn.e parameter.
TUNING CYCLE
Atvn AUTO-TUNING. Allows you to enable the automatic Auto-tuning tuning of the PID parameters (pb, ir, dt).
off Auto-tuning is off.
Fast Perform tuning in Fast Mode.
Fv11 Perform tuning in Accurate Mode.
See SETTING THE PID PARAMETERS chapter.
PB
Proportional Band
Proportional Band. Value of the P term of the PID control mode. In percent of
the maximum range of the input type.
Adjustable between 0 and 500.0 %.
When set to 0.0 (zero), it defines ON/OFF control mode.
ir Integral Rate. Value of the I term of the PID control Integral Rate mode.
In repetitions per minute (Reset).
Adjustable between 0 and 24.00.
Displayed only if proportional band 0.
dt
Derivative Time
Derivative Time. Value of the D term of the PID control mode. In seconds.
Adjustable between 0 and 250 seconds.
Displayed only if proportional band 0.
(t PWM Cycle Time. Value of the PWM Cycle period of Cycle Time the PID
control. In seconds.
Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band 0.
NOVUS AUTOMATION
4/7
kyst
Hysteresis
A(t
Action
sfst
Soft Start
0vt1 0vt2 0vt3 0vt4
Control hysteresis. Hysteresis value for ON/OFF control. Adjustable between 0
and the measurement range width of the selected input type. Displayed if
proportional band Pb = 0.
Allows you to set the control logic:
Reverse Action control. Suitable for re heating. Turns on the control output
when
PV is below SP.
Direct Action control. Suitable for dir refrigeration. Turns on the control
output
when PV is above SP.
Soft Start Function. Allows you to set the time interval during which the
controller will limit the control output (MV) rise speed. Adjustable between 0
and 9999 s. The value zero (0) disables the Soft Start function.
Allows you to set the operation mode of the OUT1, OUT2, OUT3, and OUT4 output
channels:
Off Not used.
(trl It acts as temperature control.
a4 It acts as an Alarm 4 output.
Lbd It acts as a LBD function output.
t1 It acts as a T1 Timer output.
t2 It acts as a T2 Timer output.
TIMER CYCLE
T1
Timer 1
Allows you to set the T1 Time interval.
Adjustable between 00:00 and 99:59 (HH:MM or MM:SS).
T.en Allows you to display the T1 Time parameter (T1) also Timer Enable in the Operation Cycle.
Enables T1 to be displayed in the Operation Yes Cycle.
DOES NOT enable T1 to be displayed in the no Operation Cycle.
T.dir
T.str
Timer Start
Allows you to set the timing direction of T1. up Progressive counting,
starting from 0. Dn Countdown.
Allows you to set the T1 timer startup mode. di The DI starts and resets the
timer.
f key starts, stops, and resets the timer.
sP It starts when PV reaches SP. It starts when you enable control (Rvn =
rvn YES).
T.end Allows you to set the behavior of the T1 output at the Timer End end of T1 timer.
T.e.(.0
Timer End Control Off
off T1 output turns off at the end of T1. On T1 output turns on at the end of
T1.
On.x T1 output remains on at the end of T1. Allows you to set the temperature
control behavior at the end of the T1 + T2 timers.
Finishes control at the end of the timer (RvN yes = no).
The temperature control continues to no operate.
NOVUS AUTOMATION
N1040T Controller
T2
Timer 2
tbas
time base
Allows you to set the T2 Time interval. Adjustable between 00:00 and 99:59
(HH:MM or MM:SS). Time interval where the T2 output will remain on after the
end of T1 timer.
Allows you to set the time base for T1 and T2 timers.
Min Hours and minutes (HH:MM). Sec Minutes and seconds (MM:SS).
ALARM CYCLE
Fva4 Allows you to set the alarm functions according to the
Function Alarm
options in Table 2.
Sp.a4
Alarm SP. Value that defines the actuation point of the alarm output.
For Differential type functions, this parameter defines the deviations between
PV and SP.
This parameter is not used for the ierr alarm function.
Sp4.e SP Enable. Allows you to display the SP.A4 parameter in the Operation Cycle.
YES Displays the SP.A4 parameter in the Operation Cycle.
NO
DOES NOT display the SP.A4 parameter in the Operation Cycle.
Bla4
Blocking Alarm
Alarm 4 – Initial Block. YES Enables the Initial Block. NO DOES NOT enable the Initial Block.
Xya4 Alarm hysteresis. Allows you to set the difference
Hysteresis of between the PV value at which the alarm is turned on Alarm and
the value at which it is turned off.
flsh Allows you to indicate the occurrence of alarm Flash conditions by
flashing the PV indication on the
indication screen.
YES Enables the alarm signaling by PV flashing.
NO
DOES NOT enable the alarm signaling by PV flashing.
INPUT CYCLE
Type Allows you to define the input type to be used.
Type
J Tc J -110 to 950 °C / -166 to 1742 °F
K Tc k -150 to 1370 °C / -238 to 2498 °F
T Tc t -160 to 400 °C / -256 to 752 °F
Pt100 Pt -200 to 850 °C / -328 to 1562 °F
fltr
Filter
Input digital filter.
Used to improve the stability of the measured signal (PV).
Adjustable between 0 and 20. At 0, it means the filter is off. At 20, it means
the filter is at maximum.
The higher the filter value, the slower the response of the measured value.
Dp.po Allows you to set the display mode of the decimal Decimal Point point.
Vni t Allows you to set the temperature unit to be used:
Unit
°f Fahrenheit.
°( Celsius.
0ffs Allows you to make corrections to the indicated PV Offset value.
Spll Allows you to set the lower limit to adjust SP.
SP Low Limit
5/7
Spxl Allows you to set the upper limit to adjust SP.
SP High Limit
Lbd.t Time interval for the LBD function. Loop break Maximum time interval for
the PV to react to control detection time output commands. In minutes.
1e.ov Percentage value to be applied to the output when occurs a failure in
the sensor connected to the controller input.
CALIBRATION CYCLE
All input types are factory calibrated. When a recalibration is necessary, it
must be performed by a specialized professional.
If you access this cycle by accident, do not change its parameters.
Pass Password field. This parameter is displayed before Password the protected
cycles.
See CONFIGURATION PROTECTION chapter.
(alib Allows you to enable the controller calibration. Calibration When not
enabled, the corresponding parameters are
hidden.
inL( Declaration of the range start calibration signal
Input Low Calibration
applied to the analog input.
ink( Declaration of the range end calibration signal applied
Input High Calibration
to the analog input.
Rstr Allows you to restore the factory calibrations.
Restore
(j Cold junction temperature.
Cold Junction
Pas.( Allows you to set a new password, which must not be
Password Change
Prot Allows you to set the Protection Level. See Table 3.
Protection
Rvn.e Allows you to display the RUN (rvn) parameter also RUN Enable in the Operation Cycle.
Yes Displays RUN in the Operation Cycle.
no DOES NOT display RUN in the Operation Cycle.
Rvn Allows you to enable or disable the controller’s Run action on the
process. It acts as a switch, turning the
controller on or off.
Yes Enables outputs.
no Disables outputs.
Snk
Serial Number
It displays the last 4 digits of the electronic serial number of the controller.
Snl
Serial Number
It displays the last 4 digits of the electronic serial number of the controller.
CONFIGURATION PROTECTION
The controller allows you to protect your configuration and prevent undue
changes.
In the Calibration Cycle, the Protection parameter (PROt) defines the
protection level to be adopted, limiting access to the cycles, as shown in
Table 3:
NOVUS AUTOMATION
N1040T Controller
PROTECTION LEVEL
PROTECTED CYCLES
1
Only the Calibration cycle is protected.
2
The Input and Calibration cycles are protected.
3
The Alarm, Input, and Calibration cycles are protected.
4
The Timer, Alarm, Input, and Calibration cycles are protected.
5
The Tuning, Timer, Alarm, Input, and Calibration cycles are protected.
6
All cycles, except the SP screen in the Operation Cycle, are protected.
7
All cycles are protected.
Table 3 Configuration Protection Levels
PASSWORD
When accessing the protected cycles, you will need to enter the password to be
able to change they configuration.
You must enter the password in the PASS parameter, the first parameter of the
protected cycles. Without it, the parameters of the protected cycles can only
be viewed.
The password is set in the Password Change parameter (PAS.(), presented in the
Calibration Cycle.
The controller is supplied with the Access Password set to 1111.
PASSWORD PROTECTION
The controller has a safety system. It helps prevent the input of several
passwords in an attempt to get the correct password right. Once 5 consecutive
invalid passwords are identified, the controller will stop accepting passwords
for 10 minutes.
MASTER PASSWORD
If you forget your password, you can use the Master Password feature. When
inserted, this password allows you to change the Password Change parameter
(PAS.() and set a new password for the controller.
The master password is composed of the last three digits of the controller’s
serial number plus the number 9000.
For a device with serial number 07154321, for example, the master password is
9 3 2 1.
You can obtain the serial number of the controller by pressing for 5 seconds.
SETTING THE PID PARAMETERS
During automatic tuning, the process is controlled in ON/OFF mode at the
programmed Setpoint (SP).
In some processes, automatic tuning can take many minutes to complete.
The recommended procedure for running it is:
· Set the desired SP value for the process.
· In the Atvn screen, enable automatic tuning by selecting between FAST or
FULL options.
The FAST option performs the tuning in the shortest possible time. The FULL
option prioritizes more precise tuning.
During automatic tuning, the TUNE flag will remain lit on the front of the
controller. You must wait until the tuning process is finished before you can
use the controller.
During the Auto-tuning, PV oscillations can be induced in the process around
the Setpoint.
If the tuning does not result in satisfactory control, Table 5 gives
guidelines for correcting the process behavior:
6/7
PARAMETER PROBLEM DISCOVERED SOLUTION
Proportional Band
Slow response Great oscillation
Decrease Increase
Integration Rate
Slow response Great oscillation
Increase Decrease
Derivative Time
Slow response or instability Great oscillation
Decrease Increase
Table 4 Manual adjustment of the PID parameters
For more details, check www.novusautomation.com.
MAINTENANCE
PROBLEMS WITH THE CONTROLLER
Connection errors and improper programming are the most common errors during
controller operation. A final review can avoid wasted time and damage. The
controller displays some messages that are intended to help you identify
problems:
MESSAGE
PROBLEM DESCRIPTION
—- Open Input. No sensor or signal.
Err1 Err6
Connection and/or configuration problems. Review the connections and the configuration.
Table 5 Error messages
Other error messages shown by the controller represent internal damage that necessarily implies sending the equipment for maintenance.
INPUT CALIBRATION
All controller input types leave the factory already calibrated, and
recalibration is not recommended for inexperienced operators. If you need to
recalibrate an input, proceed as described below: a) In the type parameter,
set the input type to be calibrated. b) Configure the lower and upper SP
limits for the maximum span of
the input type. c) Access the Calibration Cycle. d) Enter the password. e)
Enable the calibration when setting the parameter (alib to
YES. f) Using an electrical signal simulator, apply to the input terminals a
signal level close to the lower limit of the configured input range.
g) In the inL( parameter, use the and keys to adjust the display reading such
as to match the applied signal. Then press .
h) Apply a signal near the upper limit of the configured input’s measurement
range to the input terminals.
i) In the ink( parameter, use the and keys to adjust the display reading such
as to match the applied signal. Then press until you return to the PV
Indication Screen.
j) Confirm the calibration done. Note: When checking the controller, make sure
that the Pt100 excitation current required by the calibrator used is
compatible with the Pt100 excitation current used in this instrument: 0.170
mA.
N1040T Controller
SPECIFICATIONS
DIMENSIONS:…………………………………… 48 x 48 x 80 mm (1/16 DIN) Panel cut-out:
………………………….45.5 x 45.5 mm (+0.5 -0.0 mm) Approximated weight:
……………………………………………………..75 g
POWER SUPPLY: …………………. 100 to 240 Vac (50/60 Hz) / 48 to 240 Vcc / ±10 %
Optional 24 V…………………12 to 24 Vdc / 24 Vac (-10 % / +20 %) Maximum consumption:
……………………………………………….. 6 VA
ENVIRONMENTAL CONDITIONS: Operating temperature: ………………………………………… 0 to 50 °C
Relative humidity: …………………………………………… 80 % @ 30 °C (For temperatures above 30
°C (86 °F), reduce by 3 % for each °C) Installation category II, Installation
degree 2; Altitude < 2000 m
INPUT: Accepted types: ………………………………………………..J, K, T, Pt100 Internal resolution:
………………………………… 32767 levels (15 bits) Display resolution: ………………………………………… 0.1
/ 1 (°C / °F) Input reading rate: ………………………………up to 10 per second ().
Accuracy: …. J, K, T Thermocouples: 0.25 % of the span ±0.1 °C
………………………………………….. Pt100: 0.2 % of the span ±0.1 °C Input impedance:
……………………………………………………… 4.5 m Pt100 measurement: ……………………….. 3-wire type,
(=0.00385) With cable length compensation, excitation current of 0.170 mA. ()
Value adopted when the Digital Filter parameter is set to 0. For Digital
Filter values other than 0, the Input Reading Rate value is 5 samples per
second.
DIGITAL INPUT (DIG IN)……………..Dry contact / NPN collector-open OUTPUT
1:………………………………….Voltage pulse, 5 V / 50 mA max. OUTPUT 2:………………………….SPST
Relay; 1.5 A / 240 Vac / 30 Vdc OUTPUT 3:………………………….SPST Relay; 1.5 A / 240
Vac / 30 Vdc OUTPUT 4:……………………………SPDT Relay / 3 A / 240 Vac / 30 Vdc FRONT
PANEL: ……………………. IP65, Polycarbonate (PC) UL94 V-2 HOUSING:…………………………………………….
IP30, ABS+PC UL94 V-0 CONNECTIONS SUITABLE FOR PIN TYPE TERMINALS.
PROGRAMMABLE PWM CYCLE FROM 0.5 TO 100 SECONDS. IT STARTS OPERATION 3 SECONDS
AFTER BEING CONNECTED TO THE POWER SUPPLY. CERTIFICATIONS: CE, UKCA, and UL.
IDENTIFICATION
N1040T-PRRR N1040T-PRRR-24V
Standard model. Power Supply 100~240 Vac / 48~240 Vdc
Model with power supply 12~24 Vdc / 24 Vac
WARRANTY