Touch Controls SP SmartPack Commercial Lighting Controller Installation Guide
- June 17, 2024
- Touch Controls
Table of Contents
SMARTPACK
PART # SP
SYMBOLS AS SHOWN
ON SUBMITTAL AND
CONSTRUCTION
DOCUMENTS
INSTALLATION INSTRUCTIONS
FRONT (LOW VOLTAGE CONNECTIVITY)
TIPS / NOTES
- SMARTNET CABLING – CAT 5 (MINIMUM) CABLE – CONNECT TO SMART PORTS OF CONNECTABLE DEVICES (MAXIUMUM OF 10 DEVICES).
- 0-10v DIMMING CABLE – SIZE PER BALLAST MFG – RECOMMEND 22GU-16GU
- STATUS LED INDICATION:
- MANUAL OVERRIDE BUTTON
- STANDARD 4″ SQUARE ELECTRICAL BOX – NOT INCLUDED
- SMARTPACK
SMARTPACK DEVICE CONNECTIVITY
CABLE TYPES
LINE ID| DESCRIPTION| TYPE| NOTES
| BRANCH| CAT 5 (MIN)| TOTAL BRANCH LENGTH NOT TO EXCEED 400′