Allen-Bradley 800G-ACGK1 Bulletin 800G Cable Gland Kits Instruction Manual
- June 17, 2024
- Allen Bradley
Table of Contents
- 800G-ACGK1 Bulletin 800G Cable Gland Kits
- Specifications
- Safety Instructions
- Assemble, Install, and Commission
- General Assembly
- Plastic Cable Gland Installation
- Metal Cable Gland Installation
- Maintenanc
- Repair and Replacement
- Approximate Dimensions
- Declaration of Conformity
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Installation Instructions
Original Instructions
Bulletin 800G Cable Gland Kits
Catalog Numbers 800G-ACGKx
800G-ACGK1 Bulletin 800G Cable Gland Kits
ATTENTION: To help prevent electrical shock, disconnect from power source
before installing or servicing. Follow NFPA 70E requirements or other
applicable installation standards. Install in suitable enclosure. Keep free
from contaminants.
Only suitably trained personnel can install, adjust, commission, use,
assemble, disassemble, and maintain the product in accordance with applicable
codes of practice. If a malfunction or damage occurs, do not attempt to repair
the product.
IMPORTANT When working in hazardous areas, the safety of personnel and
equipment depends on compliance with the relevant safety regulations. The
people in charge of installation and maintenance bear a special
responsibility. They must be knowledgeable of the applicable rules and
regulations.
These instructions provide a summary of the most important installation
measures. Everyone working with the product must read these instructions so
that they are familiar with the correct handling of the product.
Keep these instructions for future reference as they must be available
throughout the expected life of the product.
- Plastic Cable Gland Kits
These kits must be installed within Bulletin 800G *-EX” assembled stations. They cannot be used in Bulletin 800G c-UL-us stations for Class I Division 2 and Class I Zone 1 hazardous areas. They are not intended to be installed in third-party explosion-proof or flame-proof enclosures. Cable gland kit contents are as follows: Cat. No.| Description
---|---
800G-ACGK1| M20 plastic cable gland (1) with earth bracket (1)
800G-ACGK3| M25 plastic cable gland (1) with earth bracket (1) - Metal Cable Gland Kits
These kits must be installed within Bulletin 800G “*-EX” assembled stations or Bulletin 800G c-UL-us assembled stations for Class I Division 2 and Class I Zone 1 hazardous areas. They are not intended to be installed in chird-party explosion-proof or flame-proof enclosures. Cable gland kit contents are as follows: Cat. No.| Description
---|---
800G-ACGK5| M20 metal cable gland (1) with earth plate (1)
800G-ACGK6| M25 metal cable gland (1) with earth plate (1)
800G-ACGK7| M20S metal cable gland (2) with earth plate (1)
Specifications
| Plastic Cable Glands| Metal Cable Gland
---|---|---
Certifications and Ratings (Bulletin 800G Assembled Stations)
c-UL-us Stations | — | E10314 |
---|---|---|
ATEX (-EX Stations) | CML 15 ATEX 3024 | CML 15 ATEX 3024 |
IECEx (-EX Stations) | IECEx CML 15.0014 | IECEx CML 15.0014 |
INMETRO (-EX Stations) | UL-BR 17.0366 | UL-BR 17.0366 |
NEPSI (-EX Stations) | GYJ17.1200X | GYJ17.1200X |
Gas and Dust protection type | • II 2 G Ex db eb IIC T6 Gb | |
• II 2 D Ex tb IIIC T80C Db | • II 2 G Ex db eb IIC T6 Gb |
• II 2 D Ex tb IIIC T80C Db
Ambient Temperature Range| -55…+60 °C (-67…+140 °F)| -55…+60 °C (-67…+140 °F)
Degree of Protection| IP64, IP66| IP64, IP66
Miscellaneous Cable Gland Kit Product Information
Cable Gland Material| • Body/Cap: Polyamide
• Seal: Silicone| • Body/Cap: Nickel-plated brass
• Seal/O-ring: Silicone
---|---|---
Cable Gland Outer Thread Size and Pitch| M20 x 1.5, M25 x 1.5| M20 x 1.5, M25
x 1.5
Cable Gland Clamping Range (Inner Seal)| • M20: 7…13 mm (9/32…33/64 in.)
• M25: 12…17 mm (15/32…43/64 in.)| • M20S: 6…12 mmm (15/64…15/32 in.)
• M20: 8.5 14.5 mm (21/64…37/64 in.)
• M25: 12 20 mm (15/32…25/32 in.)
Cable Gland Clamping Range (Outer Seal)| —| • M20S: 8.5…16 mm (21/64…33/64
in.)
• M20: 12…20 mm (15/32…43/64 in.)
• M25: 16…26 mm (33/64…1-1/32 in.)
Armor™ Wire Clamping Range| —| • M20S: 0.7…1.25 mm (1/32…3/64 in.)
• M20: 0.9…1.3 mm (1/32…3/64 in.)
• M25: 1.0…1.6 mm (3/64…1/16 in.)
Safety Instructions
Improper installation can cause malfunctioning and the loss of explosion
protection.
Cable glands can only be used within the specified ambient temperature range
and must be installed in a manner that maintains the specified ingress
protection rating.
Use in areas other than those areas specified or the modification of the
product by anyone other than the manufacturer is not permitted and exempts
Rockwell Automation from liability for defects and any further liability.
The applicable statutory rules and other binding directives that relate to
workplace safety, accident prevention, and environmental protection must be
observed.
Before you commission or restart operator, check compliance with all
applicable laws and directives.
All cable gland kits can only be used if they are in a clean and undamaged
condition. Do not modify these components in any way.
Special Conditions for Safe Use
The cable glands must be mounted at the electrical apparatus in a way that
helps prevent accidental rotation and loosening. The cable glands are only
suitable for fixed installations. Cables must be effectively clamped to help
prevent pulling or twisting.
WARNING: For gas and dust installations: Potential electrostaticcharging
hazard. Clean only with anti-static cloths
The certificate does not cover hazards that come from environmental conditions
different from the hazards clearly and precisely indicated in EN 60079-0
Clause 1.
Standards Certified To (800G “-EX” Assembled Station)
• EN 60079-0 • EN 60079-1 • EN 60079-7 • EN 60079-31
• IEC 60079-0 • IEC 60079-1 • IEC 60079-7 • IEC 60079-31
Assemble, Install, and Commission
ATTENTION: Risk of serious injury due to incorrect assembly, installation, and commissioning
- Only qualified personnel are allowed to assemble, disassemble, install, and commission the device.
- Protect devices against mechanical damage or electrostatic discharge.
- Use suitable tools and install cable firmly.
- Use cable that is rated with an appropriate temperature range suitable for the application.
General Assembly
In hazardous areas, the cable glands must be used in the following ways:
- In appropriate enclosures with “Ex e” increased safety type of protection. The clearance and creepage distances under IEC/ EN 60079-7 Clauses 4.3 and 4.4 must be observed.
- In an enclosure that corresponds to another approved type of protection that is specified in IEC/EN 60079-0 Clause 1.
- Within an 800G “-EX” assembled station that has been drilled/tapped at the manufacturing facility. Field modification of 800G “-EX” enclosures is not permitted and voids all certifications and hazardous location ratings.
Plastic Cable Gland Installation
Follow these steps to install the plastic cable gland:
-
Verify that the cable gland and earth bracket are intact with no physical damage.
-
Thread the cable gland onto the appropriately sized opening on the top or bottom of the Bulletin 800G “-EX” enclosure, verifying that the red sealing washer is between the cable gland body and the 800G “-EX” enclosure.
-
Tighten the gland to the following torque range:
• M20 cable glands — 1.5…2.5 N•m (13.3…22.1 lb•in)
• M25 cable glands — 2.0…3.0 N•m (17.7…26.6 lb•in) -
Remove the red dust plug and route the field cable through the seal of the cable gland. Adjust the free length of the cable so it can connect to all back-of-panel components inside of the enclosure.
-
Position the earth bracket where the cable gland is installed (top or bottom) and push the earth bracket between the rib and inside wall of the enclosure.
-
Open the terminal cages of the earth bracket and insert the conductors that must be grounded.
-
Tighten the earth bracket terminals to a torque range of 0.7…1.0 N•m (6…9 lb•in).
-
Tighten the cable gland cap to the following torque range:
• M20 cable glands — 5.5…6.5 N•m (48.7…57.5 lb•in)
• M25 cable glands — 8.0…10.0 N•m (70.8…88.5 lb•in)
Metal Cable Gland Installation
Figure 1 – Metal Cable Gland Parts
Middle Body Assembly
Item | Description |
---|---|
A | Cap |
B | Upper sealing ring |
C | Middle body |
D | O-ring |
E | Swivel braid retainer |
Lower Body Assembly
Item | Description |
---|---|
F | Grounding cone |
G | O-ring |
H | Lower sealing ring |
I | Lower Body |
Follow these steps to install the metal cable gland:
IMPORTANT When completing steps 4, 5, 9, 10, and 13 for the two M20S metal cable glands configuration, verify that the first cable gland is oriented as shown before installing the second cable gland. This orientation allows for both the proper threading and installation of the cable glands.
-
Verify that the cable gland and earth plate are intact with no physical damage.
-
Position the earth plate where the cable gland will be installed (top or bottom of enclosure) and push the earth plate between the rib and inside wall of the enclosure.
-
Separate the lower body assembly and middle body assembly from one another, verifying that the lower sealing ring and grounding cone are on the lower body assembly of the cable gland.
-
Thread the lower body assembly of the cable gland onto the opening at the top or bottom of the 800G “-EX” or 800G c-UL-us enclosure, verifying that the O-ring is between the cable gland and the enclosure.
-
Tighten the lower body of the cable gland to the following torque:
• M20 cable glands — 16.2…19.8 N•m (143…175 lb•in)
• M25 and M20S cable glands — 18…22 N•m (159…195 lb•in) -
Insert the field cable through the middle body assembly of the cable gland. Adjust the free length of the cable so it can connect to all back-of-panel components inside of the enclosure.
-
If the field cable has armor or shielding, the length of the armor or shielding must be no more than the height of the grounding cone plus 2 mm (0.08 in.).
-
If the field cable has armor, distribute it evenly along the outer conical circumference of the grounding cone.
-
Insert the field cable through the lower body assembly of the cable gland. Begin to thread the middle body assembly onto the lower body assembly.
-
Tighten the middle body to the following torque ranges:
• M20 cable glands — 13.5…16.5 N•m (119…146 lb•in)
• M25 and M20S cable glands — 16.2…19.8 N•m (143…175 lb•in) -
Open the terminal cages of the earth plate and insert the conductors that must be grounded.
-
Tighten the earth plate terminals to a torque range of 0.7…1.0 N•m (6…9 lb•in).
-
Tighten the cable gland cap to the following torque:
• M20 cable glands — 13.5…16.5 N•m (119…146 lb•in)
• M25 and M20S cable glands — 16.2…19.8 N•m (143…175 lb•in)
Maintenanc
ATTENTION: Risk of serious injury due to incorrect maintenance.
-
Only qualified personnel are allowed to do any maintenance.
-
IEC/EN 60079-17 must be observed.
You must keep all cable gland kit components in good condition, operate them properly, monitor them, and clean them regularly. -
Check all cable glands, grounding components, and cables regularly for cracks, damage, or physical anomalies. Verify that they are properly installed.
IMPORTANT Potential electrostatic charging hazard. Clean only with wet, anti-static cloth.
Repair and Replacement
ATTENTION: Defective cable glands cannot be repaired; they must be replaced
- Cable gland kits are defective if the integrity of the device or seal has been compromised.
- Devices must be replaced with an equivalent catalog number from the manufacturer.
For more accessories and replacement parts that Rockwell Automationm offers, see https://ab.rockwellautomation.com/Push-Buttons/Hazardous-Location/800G.
Approximate Dimensions
Dimensions are shown in millimeters (inches). Disposal
At the end of its life, this equipment must be collected separately from any
unsorted municipal waste. Follow all local and national requirements for
disposal of this product.
Declaration of Conformity
Rockwell Automation, Inc., declares that plastic cable gland kits (800G-ACGK1, 800G-ACGK3) and metal cable gland kits (800G-ACGK5, 800G-ACGK6, 800G-ACGK7), when installed within Bulletin 800G “-EX” assembled stations, are in compliance with Essential Health and Safety Requirements of Directive 2014/34/EU (ATEX) as follows:
- Equipment Group II, Equipment Category 2
- Type of Protection “Ex db eb IIC Gb / Ex tb IIIC T80C Db”
- Compliance to standards EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-7:2015, and EN 60079-31:2014 per ATEX Examination Certificate CML 15ATEX3024
The full text of the EU declaration of conformity is available at
rok.auto/certifications.
Rockwell Automation Support
For technical support, visit
http://www.rockwellautomation.com/support/overview.page
See product label for manufacturer name and address. Importer for contact is
Rockwell Automation, Pegasus Park, DE Kleetlaan 12a, 1831 Diegem, Belgium
Rockwell Automation maintains current product environmental information on its
website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-
ethics/product-environmental-compliance.page.
Allen-Bradley, Armor, Rockwell Automation, and Rockwell Software are
trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their
respective companies.
EEE Yönetmeligine Uygundur.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752
İçerenköy, İstanbul, Tel: +90 (216) 5698400
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201
South Second Street, Milwaukee, W1 53204-2496 USA,
Tel: (1) 414.382.2000,
Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV,
Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium,
Tel: (32) 2 663 0600,
Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F,
Cyberport 3, 100 Cyberport Road, Hong Kong,
Tel: (852) 2887 4788,
Fax: (852) 2508 1846
Publication 800G-INOOG6A-EN-P – May 2019
PN-534159
10004603657 Ver 00
Copyright © 2019 Rockwell Automation, Inc.