Air King AK200LS Exhaust Fan Instruction Manual
- June 17, 2024
- Air King
Table of Contents
IMPORTANT INSTRUCTIONS OPERATING
MANUAL
Exhaust Fan
Models: AK200LS, AK280LS,
AK300LS
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE
PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should always be followed
to reduce the risk of fire, electric shock and injury to person, including the
following:
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have
questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service panel
and lock the service disconnecting means to prevent power from being switched
on accidentally. When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag, to the service
panel.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified person(s)
in accordance with all applicable codes and standards, including fire-related
construction.
b) Sufficient air is needed for proper combustion and exhausting of gases
through the flue (chimney) of fuel burning equipment to prevent back drafting.
Follow the heating equipment manufacturer’s guideline and safety standards
such as those published by the National Fire Protection Association (NFPA) and
the American Society for Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE), and the local code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS.
d) Ducted fans must always be vented to the outdoors.
e) This unit must be grounded.
f) To avoid motor bearing damage and noisy and/or unbalanced impellers, keep
drywall spray, construction dust, etc. off power unit.
g) Read all instructions before installing or using exhaust fan.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, DO NOT USE THIS FAN
WITH ANY SOLID-STATE SPEED CONTROL DEVICE.
a) If this unit is to be installed over a tub or shower, it must be marked as
appropriate for the application and be connected to a GFCI (Ground Fault
Circuit Interrupter) – protected branch circuit.
WARNING: DO NOT USE IN KITCHENS.
WARNING: THE DUCTING FROM THIS FAN TO THE OUTSIDE OF THE BUILDING HAS A
STRONG EFFECT ON THE AIR FLOW, NOISE AND ENERGY USE OF THE FAN. USE THE
SHORTEST, STRAIGHTEST DUCT ROUTING POSSIBLE FOR BEST PERFORMANCE, AND AVOID
INSTALLING THE FAN WITH SMALLER DUCTS THAN RECOMMENDED. INSULATION AROUND THE
DUCTS CAN REDUCE ENERGY LOSS AND INHIBIT MOLD GROWTH. FANS INSTALLED WITH
EXISTING DUCTS MAY NOT ACHIEVE THEIR RATED AIRFLOW.
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE STARTING
INSTALLATION.
SECTION 1
Preparing the Exhaust Fan
-
Unpack fan from the carton and confirm that all pieces are present. In addition to the exhaust fan you should have:
1 – Grill
1 – Damper Assembly (attached)
4 – Mounting Rails
1 – Mounting Flange
1 – Instruction/Safety Sheet -
Choose the location for your fan. To ensure the best air and sound performance, it is recommended that the length of ducting and the number of elbows be kept to a minimum, the radius of each elbow be as large as possible for the installation, and that insulated hard ducting be used. Larger duct sizes will reduce noise and airflow restrictions. This fan will require at least 10” of clearance in the ceiling or wall, and will mount through drywall up to 3/4” thick.
-
No additional vibration deadening materials are needed for this fan.
SECTION 2
New Construction
- Install the rails into the mounting channel on the housing. Center the mounting channel in the slots on the housing, then from inside the housing tighten the mounting channel nuts so the channel is securely in place. Position the housing next to the joist. Line up housing so that it will be flush with the finished ceiling. Secure the ends of the rails with screws or nails (not included) to the joists and slide the housing into the final position (Figure 1).
SECTION 3
Existing Construction
- Set housing in position between the joist and trace an outline onto the ceiling material (Figure 2). Set housing aside and cut opening, being careful not to cut or damage any electrical or other hidden utilities. Install the rails into the mounting channel on the
housing. Center the mounting channel in the slots on the housing, then from inside the housing tighten the mounting channel nuts so the channel is securely in place. Position the housing in the previously cut hole so that it is flush with the finished ceiling. Secure the ends of the rails to the joists (Figure 1).
SECTION 4
Ducting
NOTE: 6″ OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL BUILDING CODES.
NOTE: The ducting from this fan to the outside of the building has a
strong effect on the air flow, noise and energy use of the fan. Use the
shortest, straightest duct routing possible for best performance, and avoid
installing the fan with smaller ducts than recommended.
Insulation around the ducts can reduce energy loss and inhibit mold growth.
Fans installed with existing ducts may not achieve their rated air flow.
- Connect the ducting to the fan’s duct collar (Figure 3). Secure in place using tape or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is recommended that low restriction termination fittings be used.
- Ensure duct joints and exterior penetrations are sealed with caulk or other similar material to create an air-tight path to minimize building heat loss or gain and to reduce the potential for condensation. Place/wrap insulation around duct and/or fan in order to minimize possible condensation buildup within the duct, as well as building heat loss or gain (Figure 4).
SECTION 5
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE STARTING
INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE IN ACCORDANCE WITH LOCAL
CODES, ORDINANCES, OR NATIONAL ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH
METHODS OF INSTALLING ELECTRICAL WIRING, SECURE THE SERVICES OF A QUALIFIED
ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not
require the removal of the fan’s blower assembly. If you choose to wire the
unit from the inside, you will need to remove the blower assembly and internal
wiring compartment. Both methods are equally effective.
-
1a. External Wire Compartment: Remove the wire compartment cover screw and place cover in a secure place (Figure 5). 1b. Internal Wire Compartment: If the motor is already installed in the housing, remove the two screws holding the blower assembly in place. Lift up on the assembly and slide it out of the tabs on the housing (Figure 6). Remove the wire compartment cover screw and place the cover in a secure place (Figure 7). NOTE: If the fan motor plug is connected to the fan housing receptacle, unplug so the blower assembly can be completely removed.
-
Run wiring from an approved wall switch (not included) carrying the appropriate rating. One neutral (white), one ground (green or bare copper), and one hot (black lead connected to the switch). Secure the electrical wires to the housing with an approved electrical connector. Make sure you leave enough wiring in the box to make the connection to the fan’s receptacle.
-
From where you have chosen to access the fan’s junction box, connect the white wire from the house to the white wire from the fan’s receptacle. Connect the black wire from the wall switch to the black wire from the fan’s receptacle. Connect the ground wire from the house to the green wire from the fan housing (Figure 8). Use approved methods for all connections. NOTE: The fan’s receptacle wires might need to be pulled outside the compartment for connection.
Only pull the three loose wires outside of compartment. Additional wires will be present.
NOTE: Unit must be grounded according to all local and national codes. -
Carefully tuck wire back inside wire compartment and replace wire compartment cover securing with the screw that was removed earlier.
SECTION 6
Completing the Installation
-
Use a sealant appropriate for contact with the building materials present and for the temperature requirements of the installation to prevent air leakage from unconditioned spaces is recommended. If gaps between unit housing and ceiling are great, additional material (backing rod, ceiling material) may be required.
NOTE: This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan be completely covered by insulation in order to reduce heat loss or gain to unconditioned space. -
If the fan’s blower assembly was removed during the wiring process, reinstall the blower by reversing the directions in Section 5 (Wiring), Step 1b.
-
Plug the fan’s quick connect motor cord into the receptacle. This cord will only fit one way into the receptacle (Figure 9).
-
Install the ceiling mounting flange to cover any gaps which exist between the housing and the finished ceiling. Remove the two screws that connect the ceiling mounting flange to the housing. Put sealant (not provided) on inside edge of the ceiling mounting flange to ensure that the flange is sealed to the ceiling. Line up the screw holes in the ceiling mounting flange with the screw holes on the inside of the housing and press flange in place so it is tight against the ceiling. Reinstall ceiling flange mounting screws inside the housing (Figure 10). NOTE: If the housing is mounted too far or not far enough into the ceiling for the flange to make a solid connection, loosen the mounting channel and adjust the housing up or down on the rails. Once in place, fully tighten the mounting channel nuts.
-
Install the grill by squeezing the two ends of the springs together and installing them up into the slots on the fan’s housing. Push the grill up into position (Figure 11).
-
Restore power and test your installation.
SECTION 7
Use and Care
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE
SERVICING THE UNIT.
-
Cleaning the Grill: Remove grill and use a mild detergent, such as dishwashing liquid, and dry with a soft cloth. NEVER USE ANY ABRASIVE PADS OR SCOURING POWDERS.
Completely dry grill before reinstalling. Refer to instructions in Section 5 Finishing the Installation, to reinstall grill. -
Cleaning the Fan Assembly: Wipe all parts with a dry cloth or gently vacuum the fan.
NEVER IMMERSE ELECTRICAL PARTS IN WATER.
CALIFORNIA RESIDENTS ONLY:
WARNING: THIS PRODUCT CAN EXPOSE YOU TO A CHEMICAL [OR CHEMICALS] KNOWN
TO THE STATE OF CALIFORNIA TO CAUSE CANCER.
WARNING: THIS PRODUCT CAN EXPOSE YOU TO A CHEMICAL [OR CHEMICALS] KNOWN
TO THE STATE OF CALIFORNIA TO CAUSE REPRODUCTIVE TOXICITY.
Troubleshooting Guide
Trouble | Probable Cause | Suggested Remedy |
---|---|---|
1. Fan does not operate when the switch is on. | 1a. A fuse may be blown or a circuit tripped. |
1b. Connector plug from motor is not plugged in.
1c. Wiring is not connected properly.
1d Motor has stopped operating.| 1a. Replace fuse or reset circuit breaker.
1b. Turn off power to unit. Remove Grill and plug motor into receptacle in
housing. Restore power to unit.
1c. Turn off power to unit. Check that all wires are connected.
1d. Replace motor.
2. Fan is operating, but air moves slower than normal.| 2. Obstruction in the exhaust ducting.| 2. Check for any obstructions in the ducting. The most common are bird
nests in the roof cap or wall cap where the fan exhausts to the outside.
3. Fan is operating louder than normal| 3a. Motor is loose.
3b. Fan blade is hitting housing of unit.| 3a. Turn off power to unit. Remove
grill and check that all screws are fully tightened. Restore power to unit.
3b. Call your dealer for service.
LIMITED WARRANTY
WHAT THIS WARRANTY COVERS: This product is warranted against defects in
workmanship and/or materials.
HOW LONG THIS WARRANTY LASTS: This warranty extends only to the original
purchaser of the product and lasts for five (5) years from the date of
original purchase or until the original purchaser of the product sells or
transfers the product, whichever first occurs.
WHAT AIR KING WILL DO: During the warranty period, Air King will, at its sole
option, repair or replace any part or parts that prove to be defective or
replace the whole product with the same or comparable model.
WHAT THIS WARRANTY DOES NOT COVER: This warranty does not apply if the product
was damaged or failed because of accident, improper handling or operation,
shipping damage, abuse, misuse, unauthorized repairs made or attempted. This
warranty does not cover shipping costs for the return of products to Air King
for repair or replacement. Air King will pay return shipping charges from Air
King following warranty repairs or replacement
ANY AND ALL WARRANTIES, EXPRESSED OR IMPLIED (INCLUDING, WITHOUT LIMITATION,
ANY IMPLIED WARRANTY OF MERCHANTABILITY), LAST ONE YEAR FROM THE DATE OF
ORIGINAL PURCHASE OR UNTIL THE ORIGINAL PURCHASER OF THE PRODUCT SELLS OR
TRANSFERS THE PRODUCT, WHICHEVER FIRST OCCURS AND IN NO EVENT SHALL AIR KING’S
LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY INCLUDE (I) INCIDENTAL OR
CONSEQUENTIAL DAMAGES FROM ANY CAUSE WHATSOEVER, OR (II) REPLACMENT OR REPAIR
OF ANY HOUSE FUSES, CIRCUIT BREAKERS OR RECEPTACLES. NOTWITHSTANDING ANYTHING
TO THE CONTRARY, IN NO EVENT SHALL AIR KING’S LIABILITY UNDER ANY EXPRESS OR
IMPLIED WARRANTY EXCEED THE PURCHASE PRICE OF THE PRODUCT AND ANY SUCH
LIABILITY SHALL TERMINATE UPON THE EXPIRATION OF THE WARRANTY PERIOD.
Some states and provinces do not allow limitations on how long an implied
warranty lasts, or the exclusion or limitation of incidental or consequential
damages, so these exclusions or limitations may not apply to you. This
warranty gives you specific legal rights. You may also have other rights which
vary from state to state and province to province. Proof of purchase is
required before a warranty claim will be accepted.
CUSTOMER SERVICE:
Toll-Free 800-465-7300
Our Customer Service team is available to assist you with product questions,
service center locations, and replacement parts. They can be reached Monday
through Friday, 8am-4pm Eastern. Please have your model number available, as
well as the type and style (located on the label inside of your product).
Please do not return product to place of purchase.
www.airkinglimited.com
PARTS FOR DISCONTINUED, OBSOLETE AND CERTAIN OTHER PRODUCTS MAY NOT BE
AVAILABLE. DUE TO SAFETY REASONS, MANY ELECTRONIC COMPONENTS AND MOST HEATER
COMPONENTS ARE NOT AVAILABLE TO CONSUMERS FOR INSTALLATION OR REPLACEMENT.
# | Qty. | Description | Replacement Part # |
---|---|---|---|
1 | 2 | Mounting Rails | 551299002 |
2 | 4 | Mounting Channel | 551202123 |
3 | 1 | Blower Assembly – AK200LS | 5S2202201 |
1 | Blower Assembly – AK280LS | 552202311 | |
1 | Blower Assembly – AK300LS | 5S2202301 | |
4 | 1 | 6″ Metal Collar Assembly | 555299100 |
5 | 2 | Grill Springs | 551202046 |
6 | 1 | Grill | 551202048 |
7 | 1 | Ceiling Flange | 551202050 |
8 | 1 | Wire Compartment Assembly – AK200LS | 551202615 |
1 | Wire Compartment Assembly – AK280LS/ AK300LS | 551202052 | |
9 | 1 | Outlet Gasket | 551202053 |
Installer:………………
Installation Date:………………..
Place of Purchase:………………
Model Number:………………
www.airkinglimited.com
A210572051 Rev. H 1-16
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>