FS COM M6200 Network Management Unit User Guide
- June 4, 2024
- FS COM
Table of Contents
M6200 Network Management Unit
User Guide
Introduction
FS M6200 Series Platform provides a managed, flexible, and scalable
architecture for fiber networks.
It can support EDFA, OEO, OLP, DCM, and other M6200 Series Infrastructure
Modules to construct a multi-service optical transmission network platform.
M6200 Series Platform Overview
M6200 Series Infrastructure Modules
- Slot Card Type
- Slot Card Type
NOTE:
- M6200 series modules are designed as 1-slot card types or 2-slot card types to match the managed chassis.
- 1-slot module: OEO, DWDM EDFA, OLP, DWDM Red/Blue Filter, DCM(40km), OSC, NMU, etc.
- 2-slot module: MUX, DEMUX, DCM(80km).
M6200 Series Managed Chassis
Chassis Type | Chassis Slot |
---|---|
M6200-CH2U | 7pcs |
M6200-CH5U | 15pcs |
Accessories
DWDM Mux Demux Module
Front Panel Port
Port | Port Type | Description |
---|---|---|
C21-C60 | LC/UPC | Mux/Demux Channel Port |
OUT | Optical Singal Output Port | |
IN | Optical Singal Input Port | |
MON | Input/Output Optical Power Monitoring Port |
DWDM EDFA (Erbium Doped Fiber Amplifier) Front Panel Port
Port | Port Type | Description |
---|---|---|
VOA Port | SFP | Optical Power Attenuation Adjusting Port for SFP VOA |
OUT | LC/UPC | Optical Signal Output Port |
IN | Optical Signal Input Port | |
OSCO | Optical Supervisory Channel Output Port | |
OSCI | Optical Supervisory Channel Input Port | |
MON | Optical Signal Monitoring Port | |
CONSOLE | Micro USB | Debugging & Upgrading Port |
Front Panel LED
LED | Alarm State | Normal State | Description |
---|---|---|---|
ALM | Always-ON: | ||
There is an alarm about the power supply, the fan, or the NMU module. | Light | ||
OFF | Module State Alarm |
Quick Flash:
The module type does not match.
RUN| Always OFF:
The module is not normally enabled.| Slow Flash| Module Run
IN| Always Red:
There is a LOS alarm at the port.| Always Green| Input Optical Power Alarm
OUT| Always OFF:
The port is not enabled.
10G OEO Transponder
Front Panel Port
Port | Port Type | Description |
---|---|---|
Port 1~10 | SFP/SFP+ | Optical Transceiver Signal Transmitting Port |
Front Panel LED
LED | Status | Description |
---|---|---|
SYS | Slow Flash of Green Light | There is no alarm in the module. |
Quick Flash of Red Light | The module type does not match. | |
Slow Flash of Red Light | There is an alarm in the module. | |
Always Red | The module is enabled. | |
1~10 | Always Green | There is no LOS alarm at the port. |
Always Red | There is a LOS alarm at the port. | |
Always OFF | The port is disabled. |
Signal Protocol
Service | Type | Rate |
---|---|---|
STM-1 | SDH Service | 155.52Mbit/s |
STM-4 | 622.08Mbit/s | |
STM-16 | 2.488Gbit/s | |
STM-64 | 9.95Gbit/s | |
ESCON | SAN Service | 200Mbit/s |
FC100 | 1.06Gbit/s | |
FC200 | 2.12Gbit/s | |
DVB-ASI. SDL | Digital TV Service | 270Mbit/s |
HD-SDI | HDTV Service | 1.485Gbit/s |
GE | Ethernet Service | 1.25Gbit/s |
FE | 125Mbit/s | |
CPRI Option1 | 0.6144Gbit/s | |
CPRI Option2 | 1.2288Gbit/s | |
CPRI Option3 | 2.4576Gbit/s | |
10GE LAN | 10.31Gbit/s | |
10GE WAN | 9.95Gbit/s | |
OTU2 | OTN Service | 10.71Gbit/s |
OTU2e | 11.1Gbit/s |
100G OEO Transponder
Front Panel Port
Port | Port Type | Description |
---|---|---|
Port 1~6 | QSFP+/QSFP28 | 40/100Gbps Optical Transceiver Signal |
Transmitting Port
Front Panel Port
LED | Status | Description |
---|---|---|
ALM | Always Red | There is an alarm for the Power, Fan, and NMU modules. |
Quick Flash of Red Light | The module type does not match. | |
Always OFF | There is no alarm in the module. | |
RUN | Slow Flash of Green Light | The module is normal. |
Always OFF | The module does not work. | |
1~6 | Always Green | There is no LOS alarm at the port. |
Always Red | There is a LOS alarm at the port. | |
Quick Flash of Red Light | The transceiver does not match. | |
Always OFF | The port is disabled. |
DCM (Dispersion Compensation Module)
Front Panel Port
Port | Port Type | Description |
---|---|---|
IN | LC/UPC | Optical Signal Input Port |
OUT | Optical Signal Output Port |
OSC Module (Optical Supervisory Channel Module) Front Panel Port
Port | Port Type | Description |
---|---|---|
IN1/2 | LC/UPC | Transmission Line Side Optical Singal Input Port |
OUT1/2 | Transmission Line Side Optical Singal Output Port | |
OSCI1/OSCI2 | Optical Supervisory Channel Input Port | |
OSCO1/OSCO2 | Optical Supervisory Channel Output Port | |
TX1/2 | WDM Demultiplexing Optical Singal Input Port | |
RX1/2 | WDM Multiplexing Optical Singal Output Port |
1+1 OLP (Optical Line Protection) Front Panel Port
Port | Port Type | Description |
---|---|---|
TX/RX | LC/UPC | Input/Output Port Connected to the Transmission Equipment |
T1/R1 | Main Optical Signal Transmitting Port/Receiving Port | |
T2/R2 | Backup Optical Signal Transmitting Port/Receiving Port | |
CONSOLE | Micro USB | Debugging & Upgrading Port |
Panel Key Instruction
Key | Function | Description |
---|---|---|
AUTO/FORCE | Press for switching auto mode or manual mode | Switching |
Working Mode
PRI/SEC| Press for switching work channel of primary/second state|
Switching Working Channel
Front Panel LED
LED | Status | Description |
---|---|---|
ALM | Always-ON | There is an alarm in the sub-module. |
Quick Flash | The module type does not match. | |
Always OFF | The alarm does not exist. | |
RUN | Slow Flash | The module works normally. |
Always OFF | The module is not normally enabled. | |
A/F | Always-ON | The module is in automatic mode. |
Always OFF | The module is in manual mode. | |
P/S | Always-ON | The line is in the primary channel state. |
Always OFF | The line is in a secondary channel state. | |
TX/R1/R2 | Always-ON | The line power is normal. |
Always OFF | The line power is lower than the threshold. |
Managed Chassis Front Panel Port
Slots | Description |
---|---|
NMU Module | Network Management Unit(NMU), the main control module of the |
chassis
Blank Plate 1| Used for 1+1 NMU module backup or M6200 series business
module
Blank Plate 2~7| Used for 1-slot/2-slot M6200 series business module
Fan| Support field-replaceable and hot-swappable
AC Power| AC power supply, 90VAC~264VAC, 45Hz~65Hz, supports 1+1 backup
Front Panel Port
Slots | Description |
---|---|
NMU Module | Network Management Unit(NMU), the main control module of the |
chassis
Blank Plate 1| Only used for 1+1 NMU module backup
Blank Plate 2~15| Used for 1-slot/2-slot M6200 series business module
Fan| Support field-replaceable and hot-swappable
AC Power| AC power supply, 110VAC~260VAC, 45Hz~65Hz, supports 1+1 backup
Networking Management Unit Front Panel Port
Port | Port Type | Rate | Description |
---|---|---|---|
MGMT 1~4 | RJ45 ETH | 10/100M | |
Auto-negotiate | 1. Connect to the local network management computer |
2. Interface for NMS concatenation equipment
MGMT5~6| SFP| 100M| Out of band OSC management
CONSOLE| RJ45 ETH| /| Debugging & Upgrading port
Front Panel LED
LED | Status | Description |
---|---|---|
ALM | Always-ON | There is an alarm on the power supply, the fan, or the |
NMU Module.
Always OFF| There is no alarm.
RUN| Quick Flash| The module works normally.
Always OFF| The module is not normally enabled.
ACT| Always-ON| The module is the primary module.
Always OFF| The module is the second module.
Site Environment
Keep the equipment indoors. If it is in the rainy season or in a humid
environment, dehumidification measures must be taken.
Ensure there is no water on the storage floor and no leakage to the packing box
of the equipment.
Avoid automatic fire fighting facilities, heating systems,s and other places
where leakage may occur.
Installing
Wearing ESD Wrist Strap
- Before touching any device or module, wear an ESD wrist strap or ESD gloves to protect sensitive components against electrostatic discharge from the human body.
- Connect another end of the ESD wrist strap to the PGND point on the chassis.
Installing Business Module
- Hold the ejector levers on the front panel of the module and raise them.
- Push the module gently along the guide rail until the module cannot go any further. Then lower the two ejector levers of the module.
Installing Mounting Brackets
- Secure the mounting brackets to the two sides of the M6200 series managed chassis with 8x M4 screws.
Rack Mounting
- Put the M6200 series managed chassis on the shelf in the cabinet.
- Install and tighten the panel with 4 sets of M6 screws.
- The cable manager can be installed together with mounting brackets to the cabinet.
Grounding the M6200 Series Managed Chassis
- Secure the grounding lug to the grounding point on the chassis front panel with the washers and screws.
- Connect the other end of the cable to a proper earth ground, such as the rack in which M6200 series is mounted.
**CAUTION:** The earth connection must not be removed unless all supply connections have been disconnected.
Connecting Power Cord
- Plug the AC power cord into the power port on the front panel of the AC power module.
- Connect the other end of the power cord to an AC power source.
WARNING: Do not install power cables while the power is on.
Connecting to the Management Ports
SFP Management Port
- Plug the compatible SFP transceiver into the SFP port on the front of the NMU module.
- Connect a fiber optic cable to the transceiver. Then connect the other end of the cable to another fiber device, such as a switch.
RJ45 Management port
- Connect one end of the standard RJ45 Ethernet cable to the MGMT1&2 port on the front of the NMU module.
- Connect the other end of the cable to a computer.
NOTE:
- SFP management port is designed for long-haul management of more than 100m.
- The RJ45 management port is designed for short-haul management of less than 100m.
- You can start your management by selecting one of the above six management ports.
Configuring the M Series Platform
Configuring the M Series Platform Using the Web-based interface
Step 1: Connect your computer with the network cable to any Ethernet MGMT
port of the NMU module.
Step 2: Get the NMS software from the CD of chassis accessories or
download the file “NMS software” online, and then install it. Step 3:
Double Click “NMS Server” icon on the desktop and the dialogue box of license
validation will pop up. Enter the license key (included in the CD) to finish
validation. (If you can’t find the license key, please contact the FS sales
manager for help.)
Step 4: Then the NMS server interface pops up. Double-click “Start NMS Server” to run the server, when it prompts “Please connect your client to the web server on port: 9090”, it means that you have successfully started the NMS server. And then you can close the NMS Server window, the server is still running in the background. Step 5: Open a browser window. (Recommend IE11.0 and above version or Google Chrome browser).
- If you log in from the local NMS host, enter localhost:9090 in the address bar to open the login interface.
- If you log in from another remote host, enter the server IP address XXX.XXX.XXX.XXX:9090 (IP address of NMS server) to open the login interface.
Step 6: Enter the correct user name and password (For the administrator,
the default login user name is “root”, and the default password is “public”),
as shown in the figure below: Step 7: Click login, you are now ready to
configure M series platform
NOTE: Refer to the M SERIES NETWORK MANAGEMENT USER MANUAL online for
further information
Troubleshooting
Module LEDs Working Abnormally
- Check the power cable connections at the M6200 series managed chassis and the power source.
- Make sure that all cables are used correctly and comply with the power specifications.
- Make sure that business modules are in the right position in the M6200 series managed chassis.
Accessing the Web-based Configuration Page Unsuccessfully
- Check the MGMT ports LED on the NMU module and make sure the Ethernet cable is connected properly.
- Try another port on the NMU module and make sure the Ethernet cable is suitable and works normally.
- Power off the M6200 series managed chassis. After a while, power it on again.
- Make sure the IP address of your NMS server is correctly configured.
- If you still cannot access the configuration page, please reinitialize the NMS server to its factory defaults.
Business Module Cannot Be Added
- Enter through CMD.
- Ping business module IP to check whether it can communicate.
- Check whether normal communication can be made between the business module and the NMU module.
- Change another business module.
Online Resources
Download: https://www.fs.com/download.html
Help Center: https://www.fs.com/service/help_center.html
Contact Us: https://www.fs.com/contact_us.html
Product Warranty
FS ensures our customers that for any damaged or faulty items due to our
workmanship, will o er a free return within 30 Days from the day you receive
your goods. This excludes any custom-made items or tailored solutions.
Warranty: M6200 series enjoy 2 years limited warranty against defect in
materials or workmanship. For more details about the warranty, please check at
:
https://www.fs.com/policies/warranty.html
Return: If you want to return the item(s), information on how to return
can be found at: https://www.fs.com/policies/day_return_policy.html
Compliance Information
FCC
Note: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and the receiver.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
CAUTION:
Any changes or modifications not expressly approved by the grantee of this
device could void the user’s authority to operate the equipment.
Responsible party (only for FCC matters)
FS.COM Inc.
380 Centerpoint Blvd, New Castle, DE 19720, United States
https://www.fs.com
CE
FS.COM GmbH hereby declares that this device is in compliance with Directive
2014/30/EU. A copy of the EU Declaration of Conformity is available at
www.fs.com/company/quality_control.html
FS.COM LIMITED
24F, Infore Center, No.19, Haitian 2nd Rd,
Binhai Community, Yuehai Street,Nanshan
District, Shenzhen City
FS.COM GmbH
NOVA Gewerbepark Building 7, Am
Gfild 7, 85375 Neufahrn bei Munich, Germany
Q.C. PASSED
Copyright © 2021 FS.COM All Rights Reserved.
Documents / Resources
| FS
COM M6200 Network Management
Unit
[pdf] User Guide
M6200, Network Management Unit, Management Unit, Network Management,
Management
---|---
References
- FS.com - HPC, Data Center, Enterprise, Telecom
- HPC, Data Centre, Enterprise, Telecom - FS.com United Kingdom
- HPC, Rechenzentrum, Unternehmen, Telekom - FS.com Deutschland
- FS.com - Data Center, Enterprise, Telecom
- Contact Us - FS.com
- Kontakt - FS.com Deutschland
- Technische Dokumente - FS.com Deutschland
- Rückgaberecht - FS.com Deutschland
- HPC, Rechenzentrum, Unternehmen, Telekom - FS.com Deutschland
- Hilfezentrum - FS.com Deutschland
- Technical Documents - FS.com
- HPC, Datacenter, Enterprise, Télécom - FS.com France
- Comment Nous Contacter - FS.com France
- Documents techniques - FS.com France
- Politique de retour - FS.com France
- HPC, Datacenter, Enterprise, Télécom - FS.com France
- Centre d'aide - FS.com France
- Return Policy - FS.com
- Products Warranty - FS.com