Bardac driVES P2 Series AC Vector Drive User Guide
- June 17, 2024
- Bardac drives
Table of Contents
- P2 Series AC Vector Drive
- Quick Start Up
- General Information and Ratings
- Mechanical Installation
- Electrical Installation
- Keypad and Display Operation
- Parameters
- Control Terminal Functions
- Extended Parameters
- Serial Communications
- Technical Data
- Troubleshooting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
P2 Series
AC Vector Drive
For Precision Industrial Motor Speed & Torque Control
0.75 – 160kW / 1HP – 250HP
200 – 480V 1 / 3 Phase Input
P2 Series AC Vector Drive
Declaration of Conformity
Bardac Corporation hereby states that the P2 Series product range conforms to
the relevant safety provisions of the following council directives: 2014/30/EU
(EMC) and 2014/35/EU (LVD)
Designed and manufacture is in accordance with the following harmonised
European standards:
EN 61800-5-1: 2007| Adjustable speed electrical power drive systems. Safety
requirements. Electrical, thermal and energy.
---|---
EN 61800-3: 2004 /A1 2012| Adjustable speed electrical power drive systems.
EMC requirements and specific test methods
EN 55011: 2007| Limits and Methods of measurement of radio disturbance
characteristics of industrial, scientific and medical (ISM) radio-frequency
equipment (EMC)
EN60529: 1992| Specifications for degrees of protection provided by enclosures
Safe Torque OFF (“STO”) Function
The P2 incorporates a hardware STO (Safe Torque Off) Function, designed in
accordance with the standards listed below.
Standard | Classification | Independent Approval |
---|---|---|
EN 61800-5-2:2007 | Type 2 | *TUV |
EN ISO 13849-1:2006 | PL “d” | |
EN 61508 (Part 1 to 7) | SIL 2 | |
EN60204-1 | Uncontrolled Stop “Category 0” | |
EN 62061 | SIL CL 2 |
Electromagnetic Compatibility
All P2 drives are designed with high standards of EMC in mind. All versions
suitable for operation on Single Phase 230 volt and Three Phase 400 volt
supplies and intended for use within the European Union are fitted with an
internal EMC filter. This EMC filter is designed to reduce the conducted
emissions back into the mains supply via the power cables for compliance with
the above harmonised European standards. It is the responsibility of the
installer to ensure that the equipment or system into which the product is
incorporated complies with the EMC legislation of the country of use, and the
relevant category. Within the European Union, equipment into which this
product is incorporated must comply with the EMC Directive 2004/108/EC. This
User Guide provides guidance to ensure that the applicable standards may be
achieved.
Copyright Bardac Corporation © 2018
All rights reserved. No part of this User Guide may be reproduced or
transmitted in any form or by any means, electrical or mechanical including
photocopying, recording or by any information storage or retrieval system
without permission in writing from the publisher.
2 Year Warranty
All P2 Series drives units carry a 2 year warranty against manufacturing
defects from the date of manufacture. The manufacturer accepts no liability
for any damage caused during or resulting from transport, receipt of delivery,
installation or commissioning. The
manufacturer also accepts no liability for damage or consequences resulting
from inappropriate, negligent or incorrect installation, incorrect adjustment
of the operating parameters of the drive, incorrect matching of the drive to
the motor, incorrect installation, unacceptable dust, moisture, corrosive
substances, excessive vibration or ambient temperatures outside of the design
specification.
The local distributor may offer different terms and conditions at their
discretion, and in all cases concerning warranty, the local distributor should
be contacted first.
This user guide is the “original instructions” document. All non-English
versions are translations of the “original instructions”.
The contents of this User Guide are believed to be correct at the time of
printing. In the interest of a commitment to a policy of continuous
improvement, the manufacturer reserves the right to change the specification
of the product or its performance or the contents of the User Guide without
notice.
This User Guide is for use with version 2.30 Firmware. User Guide Revision
3.01.
Bardac Corporation adopts a policy of continuous improvement and whilst every
effort has been made to provide accurate and up to date information, the
information contained in this User Guide should be used for guidance purposes
only and does not form the
part of any contract.
| This manual is intended as a guide for proper installation. Bardac cannot
assume responsibility for the compliance or the non-compliance to any code,
national, local or otherwise, for the proper installation of this drive or
associated equipment. A hazard of personal injury and/or equipment damage
exists if codes are ignored during installation.
---|---
| This drive contains high voltage capacitors that take time to discharge
after removal of the main supply. Before working on the drive, ensure
isolation of the main supply from line inputs. Wait ten (10) minutes for the
capacitors to discharge to safe voltage levels. Failure to observe this
precaution could result in severe bodily injury or loss of life.
| Only qualified electrical personnel familiar with the construction and
operation of this equipment and the hazards involved should install, adjust,
operate, or service this equipment. Read and understand this manual and other
applicable manuals in their entirety before proceeding. Failure to observe
this precaution could result in severe bodily injury or loss of life.
Quick Start Up
1.1. Important Safety Information
Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and
Caution information elsewhere.
Danger: Indicates a risk of electric shock, which, if not avoided, could
result in damage to the equipment and possible injury or death.
This variable speed drive product (drive) is intended for professional
incorporation into complete equipment or systems as part of a fixed
installation. If installed incorrectly it may present a safety hazard. The
drive uses high voltages and currents, carries a high level of stored
electrical energy, and is used to control mechanical plant that may cause
injury. Close attention is required to system design and electrical
installation to avoid hazards in either normal operation or in the event of
equipment malfunction. Only qualified electricians are allowed to install and
maintain this product.
System design, installation, commissioning and maintenance must be carried out
only by personnel who have the necessary training and experience. They must
carefully read this safety information and the instructions in this Guide and
follow all information
regarding transport, storage, installation and use of the drive, including the
specified environmental limitations.
Do not perform any flash test or voltage withstand test on the drive. Any
electrical measurements required should be carried out with the drive
disconnected.
Electric shock hazard! Disconnect and ISOLATE the drive before attempting any
work on it. High voltages are present at the terminals and within the drive
for up to 10 minutes after disconnection of the electrical supply. Always
ensure by using a suitable multimeter that no voltage is present on any drive
power terminals prior to commencing any work.
Where supply to the drive is through a plug and socket connector, do not
disconnect until 10 minutes have elapsed after turning off the supply.
Ensure correct earthing connections and cable selection as per defined by
local legislation or codes. The drive may have a leakage current of greater
than 3.5mA; furthermore the earth cable must be sufficient to carry the
maximum supply fault current which normally will be limited by the fuses or
MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the
drive, according to any local legislation or codes.
Do not carry out any work on the drive control cables whilst power is applied
to the drive or to the external control circuits. The “Safe Torque Off”
Function does not prevent high voltages from being present at the drives power
terminals.
Danger: Indicates a potentially hazardous situation other than
electrical, which if not avoided, could result in damage to property.
Within the European Union, all machinery in which this product is used must
comply with the Machinery Directive 2006/42/EC, Safety of Machinery. In
particular, the machine manufacturer is responsible for ensuring that the
electrical equipment complies with EN60204-1 and providing a disconnecting
device which must be one of the following types:
- A switch-disconnector, utilization category AC-23B (EN 60947-3).
- A circuit breaker suitable for isolation in accordance with EN 60947-2.
- A disconnector with an integrated auxiliary contact that ensures under all circumstances the switching devices break the load circuit prior to opening of the main contacts of the disconnector (EN 60947-3).
For installation in other regions, conformance with local electrical
regulations and codes of practice must be adhered to.
The level of integrity offered by the drive control input functions – for
example stop/start, forward/reverse and maximum speed, is not sufficient for
use in safety-critical applications without independent channels of
protection. All applications where malfunction could cause injury or loss of
life must be subject to a risk assessment and further protection provided
where needed.
The driven motor can start at power up if the enable input signal is present.
The STOP function does not remove potentially lethal high voltages.
ISOLATE the drive and wait 10 minutes before starting any work on it.
Never carry out any work on the Drive, Motor or Motor cable whilst the input
power is still applied.
The drive can be programmed to operate the driven motor at speeds above or
below the speed achieved when connecting the motor directly to the mains
supply. Obtain confirmation from the manufacturers of the motor and the driven
machine about suitability for operation over or under the intended speed range
prior to machine start up.
Do not activate the automatic fault reset function on any systems whereby this
may cause a potentially dangerous situation.
IP55 and IP66 drives provide their own pollution degree 2 environments. IP20
drives must be installed in a pollution degree 2 environment, mounted in a
cabinet with IP54 or better.
The drives are intended for indoor use only.
When mounting the drive, ensure that sufficient cooling is provided. Do not
carry out drilling operations with the drive in place, dust and swarf from
drilling may lead to damage.
The entry of conductive or flammable foreign bodies should be prevented.
Flammable material should not be placed close to the drive.
Relative humidity must be less than 95% (non-condensing). Ensure that the
supply voltage, frequency and no. of phases (1 or 3 phase) correspond to the
rating of the drive as delivered.
Never connect the mains power supply to the Output terminals U, V, W.
Do not install any type of automatic switchgear between the drive and the
motor.
Wherever control cabling is close to power cabling, maintain a minimum
separation of 100 mm and arrange crossings at 90 degrees.
Ensure that all terminals are tightened to the appropriate torque setting.
Do not attempt to carry out any repair of the drive. In the case of suspected
fault or malfunction, contact your local Bardac Sales Partner for further
assistance.
Do not operate the drive with any of the enclosure covers removed.
1.2. Quick Start Process
Step | Action | See Section | Page |
---|---|---|---|
1 | Identify the Model Type and ratings of your drive from the model code on |
the label. In particular:
– Check the voltage rating suits the incoming supply
– Check the output current capacity meets or exceeds the full load current for
the intended motor
– Check the enclosure type is suitable for the intended mounting location.|
2.1. Identifying the Drive by Model Number
2.3. Understanding the Rating Label
2.4. Drive Model Numbers – IP20
2.5. Drive Model Numbers – IP55
2.6. Drive Model Numbers – IP66
3.1. General| 6
7
7
9
10
11
2| Unpack and check the drive.
Notify the supplier and shipper immediately of any damage.| |
3| Ensure correct ambient and environmental conditions for the drive are met
by the proposed mounting location.| 10.1. Environmental| 68
4| Install the drive in a suitable cabinet (IP20 Units), ensuring suitable
cooling air is available.
Mount the drive to the wall or machine (IP55 & IP66).| 3.1. General
3.2. Before Installation
3.5. Mechanical Dimensions and Weight
3.6.Guidelines for Enclosure Mounting (IP20 Units)
3.7. Mounting the Drive – IP20 Units
3.8.Guidelines for Mounting (IP55 Units)
3.9.Guidelines for Mounting (IP66 Units)| 11
11
12
15
16
16
17
5| Select the correct power and motor cables according to local wiring
regulations or code, noting the maximum permissible sizes.| 10.2. Input/Output
Power and Current Ratings| 68
6| For IT Supply network, or any power supply type where the phase – earth
voltage may exceed the phase – phase voltage (such as ungrounded supplies),
disconnect the EMC filter before connecting the supply.| 10.5. Internal EMC
Filter and Varistors – Disconnection Procedure| 72
7| Check the supply cable and motor cable for faults or short circuits.| |
8| Route the cables| |
9| Check that the intended motor is suitable for use, noting any precautions
recommended by the supplier or manufacturer.| 4.6. Motor Connection
8.2.3. Parameter Group 4 – High Performance Motor Control| 23
50
10| Check the motor terminal box for correct Star or Delta configuration where
applicable.| 4.7. Motor Terminal Box Connections| 23
11| Ensure correct wiring protection is providing, by installing a suitable
circuit breaker or fuses in the incoming supply line.| 4.3.3. Fuse / Circuit
Breaker Selection| 22
12| Connect the power cables, especially ensuring the protective earth
connection is made.| 4.1. Connection Diagram| 20
13| Connect the control cables as required for the application.| 4.10. Control
Terminal Connections| 24
14| Thoroughly check the installation and wiring.| |
15| Commission the drive parameters.| 5.5. Changing Parameters
6. Parameters| 33
35
General Information and Ratings
2.1. Identifying the Drive by Model Number
The model number of each P2 drive is constructed according to the following
system:
2.2. Product Rating Label Location
All P2 models carry a rating label, which can be located as follows:
2.3. Understanding the Rating Label
The product rating label provides the following information.
| Key
---|---
1| Model Code
2| Enclosure Type and IP Rating
3| Firmware Version
4| Serial Number
5| Technical Data – Supply Voltage
6| Technical Data – Maximum continuous output current
2.4. Drive Model Numbers – IP20
Mechanical Dimensions and Mounting information are shown from section 3.5.1.
IP20 Units on page 12.
Electrical Specifications are shown in section 10.2. Input/Output Power and
Current Ratings on page 68.
200-240V ±10% – 1 Phase Input
kW Model| kW| HP Model| HP| Output Current (A)|
Frame Size
P2-22075-1KF42| 0.75| P2-22010-1HF42| 1| 4.3| 2
P2-22150-1KF42| 1.5| P2-22020-1HF42| 2| 7| 2
P2-22220-1KF42| 2.2| P-2-22030-1HF42| 3| 10.5| 2
200-240V ±10% – 3 Phase Input
kW Model| kW| HP Model| HP| Output Current (A)|
Frame Size
P2-22075-3KF42| 0.75| P2-22010-3HF42| 1| 4.3| 2
P2-22150-3KF42| 1.5| P2-22020-3HF42| 2| 7| 2
P2-22220-3KF42| 2.2| P2-22030-3HF42| 3| 10.5| 2
P2-32040-3KF42| 4| P2-32050-3HF42| 5| 18| 3
P2-32055-3KF42| 5.5| P2-32075-3HF42| 7.5| 24| 3
P2-42075-3KF42| 7.5| P2-42100-3HF42| 10| 30| 4
P2-42110-3KF42| 11| P2-42150-3HF42| 15| 46| 4
P2-52150-3KF42| 15| P2-52020-3HF42| 20| 61| 5
P2-52185-3KF42| 18.5| P2-52025-3HF42| 25| 72| 5
380-480V ±10% – 3 Phase Input
kW Model| kW| HP Model| HP| Output Current (A)|
Frame Size
P2-24075-3KF42| 0.75| P2-24010-3HF42| 1| 2.2| 2
P2-24150-3KF42| 1.5| P2-24020-3HF42| 2| 4.1| 2
P2-24220-3KF42| 2.2| P2-24030-3HF42| 3| 5.8| 2
P2-24400-3KF42| 4| P2-24050-3HF42| 5| 9.5| 2
P2-34055-3KF42| 5.5| P2-34075-3HF42| 7.5| 14| 3
P2-34075-3KF42| 7.5| P2-34100-3HF42| 10| 18| 3
P2-34110-3KF42| 11| P2-34150-3HF42| 15| 24| 3
P2-44150-3KF42| 15| P2-44200-3HF42| 20| 30| 4
P2-44185-3KF42| 18.5| P2-44250-3HF42| 25| 39| 4
P2-44220-3KF42| 22| P2-44300-3HF42| 30| 46| 4
P2-54300-3KF42| 30| P2-54040-3HF42| 40| 61| 5
P2-54370-3KF42| 37| P2-54050-3HF42| 50| 72| 5
P2-84200-3KF42| 200| P2-84300-3HF42| 300| 370| 8
P2-84250-3KF42| 250| P2-84350-3HF42| 350| 450| 8
500-600V ±10% – 3 Phase Input
kW Model| kW| HP Model| HP| Output Current (A)|
Frame Size
P2-26075-3K042| 0.75| P2-26010-3H042| 1| 2.1| 2
P2-26150-3K042| 1.5| P2-26020-3H042| 2| 3.1| 2
P2-26220-3K042| 2.2| P2-26030-3H042| 3| 4.1| 2
P2-26400-3K042| 4| P2-26050-3H042| 5| 6.5| 2
P2-26550-3K042| 5.5| P2-26075-3H042| 7.5| 9| 2
P2-36075-3K042| 7.5| P2-36100-3H042| 10| 12| 3
P2-36110-3K042| 11| P2-36150-3H042| 15| 17| 3
P2-36150-3K042| 15| P2-36200-3H042| 20| 22| 3
P2-46185-3K042| 18.5| P2-46250-3H042| 25| 28| 4
P2-46220-3K042| 22| P2-46300-3H042| 30| 34| 4
P2-46300-3K042| 30| P2-46400-3H042| 40| 43| 4
P2-56370-3K042| 37| P2-56050-3H042| 50| 54| 5
P2-56450-3K042| 45| P2-56060-3H042| 60| 65| 5
2.5. Drive Model Numbers – IP55
Mechanical dimensions and mounting information are shown from section 3.5.2.
IP55 Units on page 13.
Electrical specifications are shown in section 10.2. Input/Output Power and
Current Ratings on page 68.
200-240V ±10% – 3 Phase Input
kW Model Number| kW| HP Model Number| HP| Output
Current (A)| Frame Size
P2-42055-3KF4N| 5.5| P2-42075-3HF4N| 7.5| 24| 4
P2-42075-3KF4N| 7.5| P2-42100-3HF4N| 10| 39| 4
P2-42110-3KF4N| 11| P2-42150-3HF4N| 15| 46| 4
P2-52150-3KF4N| 15| P2-52020-3HF4N| 20| 61| 5
P2-52185-3KF4N| 18.5| P2-52025-3HF4N| 25| 72| 5
P2-62022-3KF#N| 22| P2-62030-3HF#N| 30| 90| 6
P2-62030-3KF#N| 30| P2-62040-3HF#N| 40| 110| 6
P2-62037-3KF#N| 37| P2-62050-3HF#N| 50| 150| 6
P2-62045-3KF#N| 45| P2-62060-3HF#N| 60| 180| 6
P2-72055-3KF#N| 55| P2-72075-3HF#N| 75| 202| 7
P2-72075-3KF#N| 75| P2-72100-3HF#N| 100| 248| 7
380-480V ±10% – 3 Phase Input
kW Model Number| kW| HP Model Number| HP| Output
Current (A)| Frame Size
P2-44110-3KF4N| 11| P2-44150-3HF4N| 15| 24| 4
P2-44150-3KF4N| 15| P2-44200-3HF4N| 20| 30| 4
P2-44185-3KF4N| 18.5| P2-44250-3HF4N| 25| 39| 4
P2-44220-3KF4N| 22| P2-44300-3HF4N| 30| 46| 4
P2-54300-3KF4N| 30| P2-54040-3HF4N| 40| 61| 5
P2-54370-3KF4N| 37| P2-54050-3HF4N| 50| 72| 5
P2-64045-3KF#N| 45| P2-64060-3HF#N| 60| 90| 6
P2-64055-3KF#N| 55| P2-64075-3HF#N| 75| 110| 6
P2-64075-3KF#N| 75| P2-64120-3HF#N| 120| 150| 6
P2-64090-3KF#N| 90| P2-64150-3HF#N| 150| 180| 6
P2-74110-3KF#N| 110| P2-74175-3HF#N| 175| 202| 7
P2-74132-3KF#N| 132| P2-74200-3HF#N| 200| 240| 7
P2-74160-3KF#N| 160| P2-74250-3HF#N| 250| 302| 7
500-600V ±10% – 3 Phase Input
kW Model Number| kW| HP Model Number| HP| Output
Current (A)| Frame Size
P2-46150-3K04N| 15| P2-46200-3H04N| 20| 22| 4
P2-46185-3K04N| 18.5| P2-46250-3H04N| 25| 28| 4
P2-46220-3K04N| 22| P2-46300-3H04N| 30| 34| 4
P2-46300-3K04N| 30| P2-46400-3H04N| 40| 43| 4
P2-56370-3K04N| 37| P2-56050-3H04N| 50| 54| 5
P2-56450-3K04N| 45| P2-56060-3H04N| 60| 65| 5
P2-66055-3K0#N| 55| P2-66075-3H0#N| 75| 78| 6
P2-66075-3K0#N| 75| P2-66100-3H0#N| 100| 105| 6
P2-66090-3K0#N| 90| P2-66125-3H0#N| 125| 130| 6
P2-66110-3K0#N| 110| P2-66150-3H0#N| 150| 150| 6
2.6. Drive Model Numbers – IP66
Mechanical dimensions and mounting information are shown from section 3.5.3.
IP66 Units on page 14.
Electrical specifications are shown in section 10.2. Input/Output Power and
Current Ratings on page 68.
200-240V ±10% – 1 Phase Input
kW Model| ****
kW
| HP Model| ****
HP
| Output Current (A)| Frame Size
Non Switched| Switched| Non Switched| Switched
P2-22075-1KF4X-TN| P2-22075-1KF4Y-TN| 0.75| P2-22010-1HF4X-TN| P2-22010-1HF4Y-
TN| 1| 4.3| 2
P2-22150-1KF4X-TN| P2-22150-1KF4Y-TN| 1.5| P2-22020-1HF4X-TN| P2-22020-1HF4Y-
TN| 2| 7| 2
P2-22220-1KF4X-TN| P2-22220-1KF4Y-TN| 2.2| P2-22030-1HF4X-TN| P2-22030-1HF4Y-
TN| 3| 10.5| 2
200-240V ±10% – 3 Phase Input
kW Model| ****
kW
| HP Model| ****
HP
| Output Current (A)| Frame Size
Non Switched| Switched| Non Switched| Switched
P2-22075-3KF4X-TN| P2-22075-3KF4Y-TN| 0.75| P2-12010-3HF4X-TN| P2-22010-3HF4Y-
TN| 1| 4.3| 2
P2-22150-3KF4X-TN| P2-22150-3KF4Y-TN| 1.5| P2-22020-3HF4X-TN| P2-22020-3HF4Y-
TN| 2| 7| 2
P2-22220-3KF4X-TN| P2-22220-3KF4Y-TN| 2.2| P2-22030-3HF4X-TN| P2-22030-3HF4Y-
TN| 3| 10.5| 2
P-32040-3KF4X-TN| P2-32040-3KF4Y- TN| 4| P2-32050-3HF4X-TN| P2-32050-3HF4Y-TN|
5| 18| 3
380-480V ±10% – 3 Phase Input
kW Model| ****
kW
| HP Model| ****
HP
| Output Current (A)| Frame Size
Non Switched| Switched| Non Switched| Switched
P2-24075-3KF4X-TN| P2-24075-3KF4Y-TN| 0.75| P2-24010-3HF4X-TN| P2-24010-3HF4Y-
TN| 1| 2.2| 2
P2-24150-3KF4X-TN| P2-24150-3KF4Y-TN| 1.5| P2-24020-3HF4X-TN| P2-24020-3HF4Y-
TN| 2| 4.1| 2
P2-24220-3KF4X-TN| P2-24220-3KF4Y-TN| 2.2| P2-24030-3HF4X-TN| P2-24030-3HF4Y-
TN| 3| 5.8| 2
P2-24400-3KF4X- TN| P2-24400-3KF4Y- TN| 4| P2-24050-3HF4X-TN| P2-24050-3HF4Y-
TN| 5| 9.5| 2
P2-34055-3KF4X- TN| P2-34055-3KF4Y- TN| 5.5| P2-34075-3HF4X-TN| P2-34075
-3HF4Y-TN| 7.5| 14| 3
P2-34075-3KF4X-TN| P2-34075-3KF4Y-TN| 7.5| P2-34100-3HF4X-TN| P2-34100-3HF4Y-
TN| 10| 18| 3
500-600V ±10% – 3 Phase Input
kW Model| ****
kW
| HP Model| ****
HP
| Output Current (A)| Frame Size
Non Switched| Switched| Non Switched| Switched
P2-26075-3K04X| P2-26075-3K04Y| 0.75| P2-26010-3H04X| P2-26010-3H04Y| 1| 2.1|
2
P2-26150-3K04X| P2-26150-3K04Y| 1.5| P2-26020-3H04X| P2-26020-3H04Y| 2| 3.1| 2
P2-26220-3K04X| P2-26220-3K04Y| 2.2| P2-26030-3H04X| P2-26030-3H04Y| 3| 4.1| 2
P2-26400-3K04X| P2-26400-3K04Y| 4| P2-26050-3H04X| P2-26050-3H04Y| 5| 6.5| 2
P2-26550-3K04X| P2-26550-3K04Y| 5.5| P2-26075-3H04X| P2-26075-3H04Y| 7.5| 9| 2
P2-36075-3K04X| P2-36075-3K04Y| 7.5| P2-36100-3H04X| P2-36100-3H04Y| 10| 12| 3
P2-36110-3K04X| P2-36110-3K04Y| 11| P2-36150-3H04X| P2-36150-3H04Y| 15| 17| 3
Mechanical Installation
3.1. General
- The drive should be mounted in a vertical position only, on a flat, flame resistant, vibration free mounting using the integral mounting holes or DIN Rail clip (Frame Size 2 only).
- The drive must be installed in a pollution degree 1 or 2 environment only.
- Do not mount flammable material close to the drive.
- Ensure that the minimum cooling air gaps, as detailed in sections 3.6. Guidelines for Enclosure Mounting (IP20 Units), 3.8. Guidelines for Mounting (IP55 Units) and 3.9. Guidelines for Mounting (IP66 Units) are left clear.
- Ensure that the ambient temperature range does not exceed the permissible limits for the drive given in section 10.1. Environmental.
- Provide suitable clean, moisture and contaminant free cooling air sufficient to fulfil the cooling requirements of the drive.
3.2. Before Installation
- Carefully Unpack the drive and check for any signs of damage. Notify the shipper immediately if any exist.
- Check the drive rating label to ensure it is of the correct type and power requirements for the application.
- To prevent accidental damage always store the drive in its original box until required. Storage should be clean and dry and within the temperature range –40°C to +60°C.
3.3. UL Compliant Installation
Note the following for UL-compliant installation:
- For an up to date list of UL compliant products, please refer to UL listing NMMS.E226333.
- The drive can be operated within an ambient temperature range as stated in section 10.1. Environmental.
- For IP20 units, installation is required in a pollution degree 1 environment.
- For IP55 & IP66 units, installation in a pollution degree 2 environment is permissible.
- UL Listed ring terminals / lugs must be used for all bus bar and grounding connections. Refer to section 10.3. Additional Information for UL Approved Installations on page 71.
3.4. Installation Following a Period of Storage
Where the drive has been stored for some time prior to installation, or has
remained without the main power supply present for an extended period of time,
it is necessary to reform the DC capacitors within the drive according to the
following table before operation.
For drives which have not been connected to the main power supply for a period
of more than 2 years, this requires a reduced mains voltage mains voltage to
be applied for a time period, and gradually increased prior to operating the
drive. The voltage levels relative to the drive rated voltage, and the time
periods for which they must be applied are shown in the following table.
Following completion of the procedure, the drive may be operated as normal.
Storage Period /Power-OFF Period| Initial Input Voltage
Level| Time Period T1| Secondary Input Voltage Level| Time
Period T2| Third Input Voltage Level| Time Period T3| Final
Input Voltage Level| Time Period T4
---|---|---|---|---|---|---|---|---
Up to 1 Year| 100%| N/A
1 – 2 Years| 100%| 1 Hour| N/A
2 – 3 Years| 25%| 30 Minutes| 50%| 30 Minutes| 75%| 30 Minutes| 100%| 30
Minutes
More than 3 Years| 25%| 2 Hours| 50%| 2 Hours| 75%| 2 Hours| 100%| 2 Hours
3.5. Mechanical Dimensions and Weight
3.5.1. IP20 Units
Drive Size| A| B| C| D| E| F|
Weight
---|---|---|---|---|---|---|---
mm| in| mm| in| mm| in| mm| in|
mm| in| mm| in| Kg| Ib
2| 221| 8.70| 110| 4.33| 185| 7.28| 209| 8.23| 63| 2.48| 63| 2.48| 1.8| 4.0
3| 261| 10.28| 131| 5.16| 205| 8.07| 247| 9.72| 80| 3.15| 80| 3.15| 3.5| 7.7
4| 418| 16.46| 160| 6.30| 240| 9.45| 400| 15.75| 125| 4.92| 125| 4.92| 9.2|
20.3
5| 486| 19.13| 222| 8.74| 260| 10.24| 460| 18.11| 175| 6.89| 175| 6.89| 18.1|
39.9
Mounting Bolts
Frame Size| Metric| UNF
2| M4| #8
3| M4| #8
4| M8| 5/16
5| M8| 5/16
Tightening Torques
| Frame Size| Required Torque
Control Terminals| All| 0.5 Nm| 4.5 lb-in
Power Terminals
| 2 & 3| 1 Nm| 9 lb-in
4| 2 Nm| 18 lb-in
5| 4 Nm| 35.5 lb-in
NOTE
*The IP20 Frame Size 4 Chassis can obstruct the rotation (tightening) of a bolt or screw with a hex head, a fixing with a round head will be most suitable for the mounting of this unit.
3.5.2. IP55 Units
Drive Size| A| B| C| D| E| F| G|
H| I| Weight
---|---|---|---|---|---|---|---|---|---|---
mm| in| mm| in| mm| in| mm| in|
mm| in| mm| in| mm| in| mm| in|
mm| in| kg| Ib
4| 450| 17.72| 428| 16.85| 433| 17.05| 8| 0.31| 252| 9.92| 171| 6.73| 110|
4.33| 4.25| 0.17| 7.5| 0.30| 11.5| 25.4
5| 540| 21.26| 515| 20.28| 520| 20.47| 8| 0.31| 270| 10.63| 235| 9.25| 175|
6.89| 4.25| 0.17| 7.5| 0.30| 23| 50.7
6| 865| 34.06| 830| 32.68| 840| 33.07| 10| 0.39| 330| 12.99| 330| 12.99| 200|
7.87| 5.5| 0.22| 11| 0.43| 55| 121.2
7| 1280| 50.39| 1245| 49.02| 1255| 49.41| 10| 0.39| 360| 14.17| 330| 12.99|
200| 7.87| 5.5| 0.22| 11| 0.43| 89| 196.2
Mounting Bolts
Frame Size| Metric| UNF
4| M8| #8
5| M8| #8
6| M10| 5/16
7| M10| 5/16
Tightening Torques
| Frame Size| Required Torque
Control Terminals| All| 0.5 Nm| 4.5 lb-in
Power Terminals
| 4| 2 Nm| 18 lb-in
5| 4 Nm| 35.5 lb-in
6| 15 Nm| 11 lb-ft
7| 15 Nm| 11 lb-ft
Mechanical Installation
3.5.3. IP66 Units
Drive Size| A| B| D| E| F| G| H|
I| J| Weight
---|---|---|---|---|---|---|---|---|---|---
mm| in| mm| in| mm| in| mm| in|
mm| in| mm| in| mm| in| mm| in|
mm| in| kg| Ib
2| 257| 10.12| 220| 8.66| 200| 7.87| 29| 1.12| 239| 9.41| 188| 7.40| 178|
7.01| 4.2| 0.17| 8.5| 0.33| 4.8| 10.6
3| 310| 12.20| 277| 10.89| 252| 9.90| 33| 1.31| 266| 10.47| 211| 8.29| 200|
7.87| 4.2| 0.17| 8.5| 0.33| 7.7| 16.8
Mounting Bolts
Frame Size| Metric| UNF
2| M4| #8
3| M4| #8
Tightening Torques
| Frame Size| Required Torque
Control Terminals| All| 0.5 Nm| 4.5 lb-in
Power Terminals| 2 & 3| 1 Nm| 9 lb-in
3.6. Guidelines for Enclosure Mounting (IP20 Units)
- IP20 drives are suitable for use in pollution degree 1 environments, according to IEC-664-1. For pollution degree 2 or higher environments, drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution degree 1 environment around the drive.
- Enclosures should be made from a thermally conductive material.
- Ensure the minimum air gap clearances around the drive as shown below are observed when mounting the drive.
- Where ventilated enclosures are used, there should be venting above the drive and below the drive to ensure good air circulation. Air should be drawn in below the drive and expelled above the drive.
- In any environments where the conditions require it, the enclosure must be designed to protect the drive against ingress of airborne dust, corrosive gases or liquids, conductive contaminants (such as condensation, carbon dust, and metallic particles) and sprays or splashing water from all directions.
- High moisture, salt or chemical content environments should use a suitably sealed (non-vented) enclosure.
The enclosure design and layout should ensure that the adequate ventilation paths and clearances are left to allow air to circulate through the drive heatsink. Bardac recommend the following minimum sizes for drives mounted in non-ventilated metallic enclosures:
Drive Size| X
Above & Below| Y
Either Side| Z
Between| Recommended airflow
---|---|---|---|---
mm| in| mm| in| mm| in| m3/min CFM
2| 75| 2.95| 10| 0.39| 46| 1.81| 0.3| 11
3| 100| 3.94| 10| 0.39| 52| 2.05| 0.9| 31
4| 200| 7.87| 25| 0.98| 70| 2.76| 1.7| 62
5| 200| 7.87| 25| 0.98| 70| 2.76| 2.9| 104
8| 300| 11.81| 100| 3.94| | | 20| 705
NOTE
Dimension Z assumes that the drives are mounted side-by-side with no
clearance.
Typical drive heat losses are <3% of operating load conditions.
Above are guidelines only and the operating ambient temperature of the drive
MUST be maintained at all times.
3.7. Mounting the Drive – IP20 Units
- IP20 Units are intended for installation within a control cabinet.
- When mounting with screws:
- Using the drive as a template, or the dimensions shown above, mark the locations for drilling.
- Ensure that when mounting locations are drilled, the dust from drilling does not enter the drive.
- Mount the drive to the cabinet backplate using suitable M5 mounting screws.
- Position the drive, and tighten the mounting screws securely.
- When Din Rail Mounting (Frame Size 2 Only):
- Locate the DIN rail mounting slot on the rear of the drive onto the top of the DIN rail first.
- Press the bottom of the drive onto the DIN rail until the lower clip attaches to the DIN rail.
- If necessary, use a suitable flat blade screw driver to pull the DIN rail clip down to allow the drive to mount securely on the rail.
- To remove the drive from the DIN rail, use a suitable flat blade screwdriver to pull the release tab downwards, and lift the bottom of the drive away from the rail first.
3.8. Guidelines for Mounting (IP55 Units)
- Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in section 10.1. Environmental on page 68.
- The drive must be mounted vertically, on a suitable flat surface.
- The minimum mounting clearances as shown in the table below must be observed.
- The mounting site and chosen mountings should be sufficient to support the weight of the drives.
- IP55 units do not require mounting inside an electrical control cabinet; however they may be if desired.
- Using the drive as a template, or the dimensions shown above, mark the locations required for drilling.
- Suitable cable glands to maintain the IP protection of the drive are required. Gland sizes should be selected based on the number and size of the required connection cables. Drives are supplied with a plain, undrilled gland plate to allow the correct hole sizes to be cut as required. Remove the gland plate from the drive prior to drilling.
**** | X –Above & Below | Y –Either Side |
---|---|---|
Drive Size | mm | in |
4 | 200 | 7.87 |
5 | 200 | 7.87 |
6 | 200 | 7.87 |
7 | 200 | 7.87 |
NOTE
Typical drive heat losses are approximately 3% of operating load
conditions.
Above are guidelines only and the operating ambient temperature of the drive
MUST be maintained at all times.
3.9. Guidelines for Mounting (IP66 Units)
- Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in section 10.1. Environmental.
- The drive must be mounted vertically, on a suitable flat surface.
- The minimum mounting clearances as shown in the table below must be observed.
- The mounting site and chosen mountings should be sufficient to support the weight of the drives.
- Using the drive as a template, or the dimensions shown below, mark the locations required for drilling.
- Suitable cable glands to maintain the ingress protection of the drive are required. Gland holes for power and motor cables are pre-moulded into the drive enclosure, recommended gland sizes are shown above. Gland holes for control cables may be cut as
required.
Drive Size
| X
Above & Below| Y
Either Side
---|---|---
mm| in| mm| in
2| 200| 7.87| 10| 0.39
3| 200| 7.87| 10| 0.39
Cable Gland Sizes
Frame| Power Cable| Motor Cable| Control Cables
2| M25 (PG21)| M25 (PG21)| M20 (PG13.5)
3| M25 (PG21)| M25 (PG21)| M20 (PG13.5)
NOTE
Typical drive heat losses are approximately 3% of operating load conditions.
Above are guidelines only and the operating ambient temperature of the drive
MUST be maintained at all times.
3.10. Removing the Terminal Cover
3.10.1. Frame Sizes 2 & 3 Using a suitable flat blade screwdriver, rotate
the two retaining screws indicated until the screw slot is vertical.
3.10.2. Frame Size 4
Using a suitable flat blade screwdriver, rotate the two retaining screws indicated until the screw slot is vertical.
3.10.3. Frame Size 5 Using a suitable flat blade screwdriver, rotate
the four retaining screws indicated until the screw slot is vertical.
Terminal Cover Release Screws
3.10.4. Frame Sizes 6 & 7Using a suitable flat blade screwdriver, rotate the
six retaining screws indicated until the screw slot is vertical.
3.11. Routine Maintenance
The drive should be included within the scheduled maintenance program so that
the installation maintains a suitable operating environment, this should
include:
- Ambient temperature is at or below that set out in section 10.1. Environmental.
- Heat sink fans freely rotating and dust free.
- The Enclosure in which the drive is installed should be free from dust and condensation; furthermore ventilation fans and air filters should be checked for correct air flow.
Checks should also be made on all electrical connections, ensuring screw terminals are correctly torqued; and that power cables have no signs of heat damage.
Electrical Installation
4.1. Connection Diagram
All power terminal locations are marked directly on the product. IP20 Frame
Size 2 – 4 units have AC/DC power input located at the top with the motor and
brake resistor connections located at the bottom. All other units have power
terminals located at the bottom.
4.1.1. Electrical Power Connections
Key | Page |
---|---|
A | 4.2. Protective Earth (PE) (Ground) Connection |
B | 4.3. Incoming Power Connection |
C | 4.3. Incoming Power Connection |
D | External Isolator / Disconnect |
E | 4.3.3. Fuse / Circuit Breaker Selection |
F | 4.3.4. Optional Input Choke |
G | 4.13. EMC Compliant Installation |
H | 4.6. Motor Connection |
I | 4.8. Connecting a Brake Resistor |
J | 4.5. Operation with DC Power Supply or Common DC Bus |
4.1.2. Control Connections
Key | Sec. | Page |
---|---|---|
1 | +24V | 24 Volt DC Input / Output |
2 | DI1 | Digital Input 1 (Run Enable) |
3 | DI2 | Digital Input 2 |
4 | DI3 | Digital Input 3 |
5 | +10V | +10Volt DC Output |
6 | AI1 / DI4 | Analog Input 1 / Digital Input 4 |
7 | 0V | 0 Volt Common |
8 | AO1 | Analog Output 1 |
9 | 0V | 0 Volt Common |
10 | AI2 / DI5 | Analog Input 2 / Digital Input 5 |
11 | AO2 | Analog Output 2 |
12 | STO- | STO 0 Volt Connection |
13 | STO+ | STO + 24VDC Connection |
14 | RL1-C | Relay Output 1 Common |
15 | RL1-NO | Relay Output 1 Normally Open |
16 | RL1-NC | Relay Output 2 Normally Closed |
17 | RL2-A | Relay Output 2 |
18 | RL2-B | Relay Output 2 |
4.2. Protective Earth (PE) (Ground) Connection
4.2.1. Grounding Guidelines
Adequate safety earthing must be provided in accordance with local wiring
rules and codes of practice. The ground terminal of each drive should be
connected back to the common safety earth bar to maintain touch potentials
within safe limits. The ground terminal of each drive should be individually
connected DIRECTLY to the site ground bus bar (through the EMC filter if
installed). The drive ground connections should not loop from one drive to
another, or to, or from any other equipment. Ground impedance must conform to
local industrial safety regulations and/or electrical codes.
To meet UL regulations, UL approved ring crimp terminals should be used for
all ground wiring connections. The integrity of all ground connections should
be checked periodically.
4.2.2. Protective Earth Conductor
The Cross sectional area of the PE Conductor must be at least equal to that of
the incoming supply conductors.
4.2.3. Motor Ground
The driven motor must be locally connected to a suitable ground location to
maintain touch potentials within safe limits. In addition, the motor ground
must be connected to one of the ground terminals on the drive.
4.2.4. Ground Fault Monitoring
As with all inverters, a leakage current to earth can exist. The drive is
designed to produce the minimum possible leakage current whilst complying with
worldwide standards. The level of current is affected by motor cable length
and type, the effective switching
frequency, the earth connections used and the type of RFI filter installed. If
an ELCB (Earth Leakage Circuit Breaker) is to be used, the following
conditions apply:
- A Type B Device must be used.
- The device must be suitable for protecting equipment with a DC component in the leakage current.
- Individual ELCBs should be used for each drive.
4.2.5. Shield Termination (Cable Screen)
The safety ground terminal provides a grounding point for the motor cable
shield. The motor cable shield connected to this terminal (drive end) should
also be connected to the motor frame (motor end). Use a shield terminating or
EMI clamp to connect the shield to the safety ground terminal.
4.3. Incoming Power Connection
4.3.1. Suitability
All P2 models are designed for use on a single phase or balanced three phase
supply depending on the model.
For all models and ratings when working with an IT Supply network, or any
power supply type where the phase to earth voltage may exceed the phase to
phase voltage (such as ungrounded supplies), the internal EMC filter and surge
protection must be disconnected before connecting the supply. Refer to section
10.5. Internal EMC Filter and Varistors – Disconnection Procedure on page 72
for further information.
For three phase supply models, a maximum of 3% imbalance is allowed between
phases.
4.3.2. Cable Selection
- For 1 phase ac supply, power should be connected to L1/L, L2/N.
- For a DC Supply, the main power cables should be connected to L1/L, L2/N.
- For 3 phase ac supplies, the mains power cables should be connected to L1, L2, and L3. Phase sequence is not important. Neutral connection is not required.
For compliance with CE and C Tick EMC requirements, refer to section 4.10. Control Terminal Connections on page 24.
-
A fixed installation is required according to IEC61800-5-1 with a suitable disconnecting device installed between the drive and the main Power Source. The disconnecting device must conform to the local safety code / regulations (e.g. within Europe,
EN60204-1, Safety of machinery). -
The cables should be dimensioned according to any local codes or regulations. Maximum dimensions for each drive model are given in section 10.2. Input/Output Power and Current Ratings on page 68.
4.3.3. Fuse / Circuit Breaker Selection
- Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line, according to the data in section 10.2. Input/Output Power and Current Ratings on page 68.
- The fuses must comply with any local codes or regulations in place. In general, type gG (IEC 60269) or UL type J fuses are suitable; however in some cases type aR fuses may be required. The operating time of the fuses must be below 0.5 seconds.
- Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in place of fuses, providing that the clearing capacity is sufficient for the installation.
- The maximum permissible short circuit current at the drive power terminals as defined in IEC60439-1 is 100kA.
- The drive provides thermal and short circuit protection for the connected motor and motor cable.
4.3.4. Optional Input Choke
An optional Input Choke is recommended to be installed in the supply line for
drives where any of the following conditions occur:
- The incoming supply impedance is low or the fault level / short circuit current is high.
- The supply is prone to dips or brown outs.
- An unbalanced supply system is used (3 phase drives) where the voltage levels during on load operation exceed the designed 3% capacity of the drive.
- The power supply to the drive is via a busbar and brush gear system (typically overhead Cranes).
In all other installations, an input choke is recommended to ensure protection
of the drive against power supply faults.
4.4. Operation of 3 Phase drives from a Single Phase Supply
A special function of P2 allows all drives designed for operation on 3 phase
supplies to be operated on a single phase supply of the correct rated voltage
at up to 50% of the nominal capacity.
For Example, Model Number P2-64060-3HF4N can be operated on a single phase
supply, 380 – 480 volts, with the maximum output current limited to 45 Amps.
The supply must be connected to the L1 and L2 terminals of the drive.
4.5. Operation with DC Power Supply or Common DC Bus
P2 models provide terminals to directly connect to the DC Bus for applications
which require this. For further information on using the DC Bus connections,
please refer to your Bardac sales Partner.
4.6. Motor Connection
- The drive inherently produces fast switching of the output voltage (PWM) to the motor compared to the mains supply, for motors which have been wound for operation with a variable speed drive then there is no preventative measures required, however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative measures may be required.
- The motor should be connected to the drive U, V, and W terminals using a suitable 3 or 4 core cable. Where a 3 core cable is utilised, with the shield operating as an earth conductor, the shield must have a cross sectional area at least equal to the phase conductors when they are made from the same material. Where a 4 core cable is utilised, the earth conductor must be of at least equal cross sectional area and manufactured from the same material as the phase conductors.
- The motor earth must be connected to one of the drive earth terminals to provide a low impedance path for common mode leakage current to return to the drive. This is best achieved in practice by using a cable with suitable shielding which provides a low impedance path at high frequencies, and ensuring correct, low impedance earth bonding of the motor cable at both ends. For further information, refer to section 4.13. EMC Compliant Installation on page 26.
4.7. Motor Terminal Box Connections
Most general purpose motors are wound for operation on dual voltage supplies.
This is indicated on the nameplate of the motor. This operational voltage is
normally selected when installing the motor by selecting either WYE (STAR) or
DELTA connection. WYE (STAR) always gives the higher of the two voltage
ratings.
Incoming Supply Voltage | Motor Nameplate Voltages | Connection |
---|---|---|
230 | 230 / 400 | Delta |
19](https://manuals.plus/wp-content/uploads/2024/02/Bardac-driVES-P2-Series-
AC-Vector-Drive-fig-19.png)
400| 400 / 690
400| 230 / 400| WYE (Star)|
4.8. Connecting a Brake Resistor
P2 units feature an internal brake transistor, fitted as standard for all
models. The brake resistor should be connected to the DC+ and BR terminals of
the drive.
The brake transistor is enabled using P1-05 (Refer to section 8.1. Parameter
Group 2 – Extended Parameters on page 44 for further information).
Software protection against brake resistor overload is carried out within the
drive. For correct protection of the brake resistor, the following settings
are required:
- Set P1-14 = 201.
- Enter the resistance of the brake resistor in P6-19 (Ohms).
- Enter the power of the brake resistor in P6-20 (kW).
The voltage level at these terminals may exceed 800VDC.
Stored charge may be present after disconnecting the mains power.
Allow a minimum of 10 minutes discharge after power off before attempting any
connection to these terminals.
4.9. Control Terminal Wiring
- All analog signal cables should be suitably shielded. Twisted pair cables are recommended.
- Power and Control Signal cables should be routed separately where possible, and must not be routed parallel to each other.
- Signal levels of different voltages e.g. 24 Volt DC and 110 Volt AC, should not be routed in the same cable.
- Maximum control terminal tightening torque is 0.5Nm.
- Control Cable entry conductor size: 0.05 – 2.5mm 2/ 30 – 12 AWG.
4.10. Control Terminal Connections
Example connection schematics are provided in section 7.3. Example Connection
Schematics on page 41.
4.10.1. +24VDC Input / Output
When the mains power is applied to the drive, terminal 1 provides a +24VDC
output, maximum load 100mA. This may be used to activate digital inputs or
provide power to sensors.
When no mains power is applied to the drive, the drive control electronics may
be powered from an external +24VDC source. When powered in this way, all
analog and digital I/O and communication functions remain operative, however
the motor may not be
operated, which allows safe testing and commissioning of the installation
without risk of high voltage being present. When powered in this way, the
drive requires up to 100mA.
4.10.2. Digital Inputs
Up to five digital inputs are available. The function of the inputs is defined
by parameters P1-12 and P1-13, which are explained in section 7. Control
Terminal Functions on page 38.
4.10.3. Analog Inputs
Two analog inputs are available, which may also be used as digital Inputs if
required. The signal formats are selected by parameters as follows:
- Analog Input 1 Format Selection Parameter P2-30.
- Analog Input 2 Format Selection Parameter P2-33.
These parameters are described more fully in section 8.1. Parameter Group 2 –
Extended Parameters on page 44.
The function of the analog input, e.g. for speed reference or PID feedback for
example is defined by parameters P1-12 and P1-13.
The function of these parameters and available options are described in
section 7. Control Terminal Functions on page 38.
4.10.4. Analog Outputs
Two analog outputs are available, and may be used for 0 – 10 Volt Signal (max
load 20mA), 0 – 20mA, 4 – 20mA or a digital +24Volt DC, 20mA output. The
parameters to select function and format are as follows.
Analog Input | Function selected by | Format selected by |
---|---|---|
Analog Input 1 | P2-11 | P2-12 |
Analog Input 2 | P2-13 | P2-14 |
These parameters are described more fully in section 8.1. Parameter Group 2 –
Extended Parameters on page 44.
4.10.5. Relay Outputs
Two relay outputs are available, which may be used to switch external loads up
to 5A at 230 VAC or 6A at 30VDC.
Relay 1 has both normally open and normally closed contacts available. Relay 2
provides a simple open or closed contact.
The relay output function may be configured using parameters P2-15 and P2-18,
which are described in section 8.1. Parameter Group 2 – Extended Parameters on
page 44.
4.11. IP66 Switched Version Integrated Control Switch and Potentiometer
Wiring
The P2 is optionally available with an integrated mains disconnect / isolator
and front mounted control switch and potentiometer. This allows the drive to
be operated directly from the front control panel, whilst also providing for
options such as Hand / Auto or Local / Remote Control etc.
The built in switch and pot are wired inside the terminal cover directly to
the user control terminals as shown in the diagram below.
These connections may be disconnected by the user if they are not required.
The control switch activates the first two digital inputs as follows:
4.12. Motor Thermal Overload Protection
4.12.1. Internal Thermal Overload Protection
The drive has an in-built motor thermal overload function; this is in the form
of an “I.t-trP” trip after delivering >100% of the value set in P-08 for a
sustained period of time (e.g. 150% for 60 seconds).
4.12.2. Motor Thermistor Connection
Where a motor thermistor is to be used, it should be connected as follows:
Control Motor Strip | Additional Information |
---|
|
Compatible Thermistor: PTC Type, 2.5kΩ trip level.
Use a setting of P1-13 that has Input 5 function as E-TRIP “External Trip”,
e.g. P1-13 = 6. Refer to section 7.2. Digital Input Configuration Parameter
P1-13 on page 39 for further details.
Enable the Motor PTC Thermistor Input function in parameter P2-33.
4.13. EMC Compliant Installation
4.13.1. Recommended Installation for EMC Compliance
4.13.2. Recommended Cable Types by EMC Category
Category| Supply Cable Type| Motor Cable Type| Control
Cables| Maximum Permissible Motor Cable Length
---|---|---|---|---
C1678| Shielded1| Shielded1,5| __
Shielded4
| 1M / 5M9
C28| Shielded²| Shielded1, 5| 5M / 25M9
C38| Unshielded3| Shielded2| 25M / 100M9
- A screened (shielded) cable suitable for fixed installation with the relevant mains voltage in use. Braided or twisted type screened cable where the screen covers at least 85% of the cable surface area, designed with low impedance to HF signals. Installation of a standard cable within a suitable steel or copper tube is also acceptable.
- A cable suitable for fixed installation with relevant mains voltage with a concentric protection wire. Installation of a standard cable within a suitable steel or copper tube is also acceptable.
- A cable suitable for fixed installation with relevant mains voltage. A shielded type cable is not necessary.
- A shielded cable with low impedance shield. Twisted pair cable is recommended for analog signals.
- The cable shield should be terminated at the motor end using an EMC type gland allowing connection to the motor body through the largest possible surface area. The shield must also be terminated at the drive end, as close as practically possible to the drive output terminals. Where drives are mounted in a steel control panel enclosure, the cable screen may be terminated directly to the control panel backplate using a suitable EMC clamp or gland fitted as close to the drive as possible. The drive earth terminal must also be connected directly to this point, using a suitable cable which provides low impedance to high frequency currents. For IP55 and IP66 drives, connect the motor cable shield to the gland plate or internal ground clamp.
- 230 Volt, 1 phase input drives using internal EMC filter. Other models require external EMC filter.
- Compliance with category C1 conducted emissions only is achieved. For compliance with category C1 radiated emissions, additional measures may be required, contact your Sales Partner for further assistance.
- EMC categories for drives with internal filter EMC filter and rated voltage less than 480 Volts. For other drives, additional EMC filtering is required.
- Permissible cable length with additional external EMC filter.
4.13.3. Enclosed Drives Recommended Cable Connections
4.14. Safe Torque Off
Safe Torque OFF will be referred to as “STO” through the remainder of this
section.
4.14.1. Responsibilities
The overall system designer is responsible for defining the requirements of
the overall “Safety Control System” within which the drive will be
incorporated; furthermore the system designer is responsible for ensuring that
the complete system is risk assessed and that the “Safety control System”
requirements have been entirely met and that the function is fully verified,
this must include confirmation testing of the “STO” function before drive
commissioning.
The system designer shall determine the possible risks and hazards within the
system by carrying out a thorough risk and hazard analysis, the outcome of the
analysis should provide an estimate of the possible hazards, furthermore
determine the risk levels and identify any needs for risk reduction. The “STO”
function should be evaluated to ensure it can sufficiently meet the risk level
required.
4.14.2. What STO Provides
The purpose of the “STO“ function is to provide a method of preventing the
drive from creating torque in the motor in the absence of the “STO“ input
signals (Terminal 12 with respect to Terminal 13), this allows the drive to be
incorporated into a complete safety
control system where “STO“ requirements need to be fulfilled.
- The “STO“ function can typically eliminate the need for electro-mechanical contactors with cross-checking auxiliary contacts as per normally required to provide safety functions.
- The drive has the “STO“ function built-in as standard and complies with the definition of “Safe torque off“ as defined by IEC 61800-52:2007.
The “STO“ function also corresponds to an uncontrolled stop in accordance with
category 0 (Emergency Off), of IEC 60204-1. This means that the motor will
coast to a stop when the “STO” function is activated, this method of stopping
should be confirmed as being acceptable to the system the motor is driving.
The “STO“ function is recognised as a fail-safe method even in the case where
the “STO“ signal is absent and a single fault within the drive has occurred,
the drive has been proven in respect of this by meeting the following safety
standards:
| SIL
(Safety Integrity Level)| PFHD
(Probability of dangerous
Failures per Hour)| SFF
(Safe failure fraction %)| Lifetime assumed
---|---|---|---|---
EN 61800-5-2| 2| 1.23E-09 1/h (0.12 % of SIL 2)| 50| 20 Yrs
| PL
(Performance Level)| CCF (%)
(Common Cause Failure)| MTTFd| Category
---|---|---|---|---
EN ISO 13849-1| PL d| 1| 4525a| 3
| SILCL
---|---
EN 62061| SILCL 2
NOTE The values achieved above maybe jeopardised if the drive is
installed outside of the Environmental limits detailed in section 10.1.
Environmental.
4.14.3. What STO Does Not Provide
__
__
__
__
__
| Disconnect and ISOLATE the drive before attempting any work on it. The
“STO“ function does not prevent high voltages from being present at the drive
power terminals.
---|---
1 NOTE The “STO“ function does not prevent the drive from an unexpected
re-start. As soon as the “STO“inputs receive the relevant signal it is
possible (subject to parameter settings) to restart automatically, Based on
this, the function should not be used for carrying out short-term non-
electrical machinery operations (such as cleaning or maintenance work).
2 NOTE In some applications additional measures may be required to fulfil
the systems safety function needs: the “STO“ function does not provide motor
braking. In the case where motor braking is required a time delay safety relay
and/or a mechanical brake arrangement or similar method should be adopted,
consideration should be made over the required safety function when braking as
the drive braking circuit alone cannot be relied upon as a fail safe method.
When using permanent magnet motors and in the unlikely event of a multiple
output power devices failing then the motor could effectively rotate the motor
shaft by 180/p degrees (Where p denotes number of motor pole pairs).
4.14.4. “STO“ Operation
When the “STO” inputs are energised, the “STO” function is in a standby state,
if the drive is then given a “Start signal/command” (as per the start source
method selected in P1-13) then the drive will start and operate normally.
When the “STO” inputs are de-energised then the STO Function is activated and
stops the drive (Motor will coast), the drive is now in “Safe Torque Off”
mode.
To get the drive out of “Safe Torque Off” mode then any “Fault messages” need
to be reset and the drive “STO” input needs to be re-energised.
4.14.5. “STO” Status and Monitoring
There are a number of methods for monitoring the status of the “STO” input,
these are detailed below:
Drive Display
In Normal drive operation (Mains AC power applied), when the drives “STO”
input is de-energised (“STO” Function activated) the drive will highlight this
by displaying “InHibit”, (NOTE If the drive is in a tripped condition then the
relevant trip will be displayed and not “InHibit”).
Drive Output Relay
- Drive relay 1: Setting P2-15 to a value of “13” will result in relay opening when the “STO” function is activated.
- Drive relay 2: Setting P2-18 to a value of “13” will result in relay opening when the “STO” function is activated.
“STO” Fault Codes
Fault Code | Code Number | Description | Corrective Action |
---|---|---|---|
“Sto-F” | 29 | A fault has been detected within either of the internal channels | |
of the “STO” circuit. | Refer to your Bardac Sales Partner |
4.14.6. “STO” Function Response Time
The total response time is the time from a safety related event occurring to
the components (sum of) within the system responding and becoming safe. (Stop
Category 0 in accordance with IEC 60204-1).
- The response time from the “STO” inputs being de-energised to the output of the drive being in a state that will not produce torque in the motor (“STO” active) is less than 1ms.
- The response time from the “STO” inputs being de-energised to the “STO” monitoring status changing state is less than 20ms.
- The response time from the drive sensing a fault in the STO circuit to the drive displaying the fault on the display/Digital output showing drive not healthy is less than 20ms.
4.14.7. “STO“ Electrical Installation
The “STO” wiring shall be protected from inadvertent short circuits or
tampering which could lead to failure of the “STO” input signal, further
guidance is given in the diagrams below.
In addition to the wiring guidelines for the “STO” circuit below, section
4.13.1. Recommended Installation for EMC Compliance on page 26 should also be
followed.
The drive should be wired as illustrated below; the 24Vdc signal source
applied to the “STO” input can be either from the 24Vdc on the drive or from
an External 24Vdc power supply.
4.14.8. Recommended “STO” Wiring NOTE The Maximum cable length from
Voltage source to the drive terminals should not exceed 25 mtrs.
4.14.9. External Power Supply Specification
4.14.10. Safety Relay Specification
The safety relay should be chosen so that at minimum it meets the safety
standards in which the drive meets.
Voltage Rating (Nominal) | 24Vdc |
---|---|
STO Logic High | 18-30Vdc (Safe torque off in standby) |
Current Consumption (Maximum) | 100mA |
4.14.11. Enabling the “STO” Function
The “STO” function is always enabled in the drive regardless of operating mode
or parameter changes made by the user.
Standard Requirements| SIL2 or PLd SC3 or better (With Forcibly guided
Contacts)
---|---
Number of Output Contacts| 2 independent
Switching Voltage Rating| 30Vdc
Switching Current| 100mA
4.14.12. Testing the “STO” Function
Before commissioning the system the “STO” function should always be tested for
correct operation, this should include the following tests:
- With the motor at standstill, and a stop command given to the drive (as per the start source method selected in P1-13):
- De-energise the “STO” inputs (Drive will display ““InHibit”).
- Give a start command (as per the start source method selected in P1-13) and check that the drive still displays “Inhibit” and that the operation is in line with the section 4.14.4. “STO“ Operation and section 4.14.5. “STO” Status and Monitoring.
- With the motor running normally (from the drive):
- De-energise the “STO” inputs.
- Check that the drive displays “Inhibt” and that the motor stops and that the operation is in line with the section and section 4.14.4. “STO“ Operation and section 4.14.5. “STO” Status and Monitoring.
4.14.13. “STO” Function Maintenance
The “STO” function should be included within the control systems scheduled
maintenance program so that the function is regularly tested for integrity
(Minimum once per Year), furthermore the function should be integrity tested
following any safety system
modifications or maintenance work. If drive fault messages are observed refer
to section 11.1. Fault Messages on page 74 for further guidance.
Keypad and Display Operation
The drive is configured and its operation monitored via the keypad and
display.
5.1. OLED Keypad and Display Layout
| NAVIGATE| Used to display real-time information, to access and exit
parameter edit mode and to store parameter changes.|
---|---|---|---
| UP| Used to increase speed in real-time mode or to increase parameter
values in parameter edit mode.
| DOWN| Used to decrease speed in real-time mode or to decrease
parameter values in parameter edit mode.
| RESET / STOP| Used to reset a tripped drive.
When in Keypad mode is used to Stop a running drive.
| **** START| When in keypad mode, used to Start a stopped drive or to
reverse the direction of rotation if bi-directional keypad mode is enabled.
5.3. Selecting the Language on the OLED Display
5.3.1. Operating Displays
5.4. Additional Display Messages
5.5. Changing Parameters
5.6. Parameter Factory Reset / User Reset
The P2 provides a feature to allow the user to define their own default
parameter set. After commissioning all required parameters, the user can save
these as the defaul parameters by setting P6-29 = 1. If required, the User
Default Parameters may be cleared by setting P6-29 = 2.
If the user wishes to relaod the User Default Parameters from the drive
memory, the following procedure is used.
5.7. Resetting the Drive Following a Trip
The P2 has many protection features, designed to protect both the drive and
motor from accidental damage. When any of these protection features are
activated, the drive will trip, and display a fault message. The fault
messages are listed in section 11.1. Fault
Messages on page 74.
When a trip occurs, after the cause of the trip has been investigated and
rectified, the user can reset the trip in one of the following ways:
- Press the keypad Stop key.
- Power off the drive completely, then power on again.
- If P1-13 > 0, switch off digital input 1, then back on again.
- If P1-12 = 4, reset via the fieldbus interface.
- If P1-12 = 6, reset via CAN.
5.8. Keypad Short Cuts
The following short cuts can be used to speed up selecting and changing
parameters when using the keypad.
5.8.1. Selecting the Parameter Groups
When extended or advanced parameter access is enabled (see section 8. Extended
Parameters on page 44), additional parameter groups are visible, and may be
selected quickly by the following method.
Whilst in the parameter selection menu, press the Navigate and Up or Navigate and Down keys simultaneously.| The next highest or lowest accessible parameter group will be selected.
5.8.2. Selecting the Lowest Parameter in a Group
Whilst in the parameter selection menu, press the Up and Down keys simultaneously.| The next highest or lowest accessible parameter group will be selected.
5.8.3. Setting a Parameter to the Minimum Value
Whilst editing a parameter value, press the Up and Down keys simultaneously.| The parameter will be set to the lowest possible value.
5.8.4. Adjusting Individual Digits
When editing parameter values and making large changes, e.g. setting the motor
rated speed from 0 to 1500RPM, it is possible to directly select the parameter
digits using the following method.
Whilst editing a parameter value, press the Stop and Navigate keys
simultaneously.| The cursor will step one digit to the left. Repeating the key
press will move
another digit to the left.| The individual digit value may be adjusted using
the up and down keys.| Adjust the value using
the Up and Down keys.| When the cursor reaches
the highest accessible
digit, pressing Stop and
Navigate will return the
cursor to the right most
digit.| Press the Navigate key to return to the parameter selection menu.
Parameters
6.1. Parameter Set Overview
The P2 Parameter set consists of 10 groups as follows:
- Group 0 – Read Only Monitoring Parameters
- Group 1 – Basic Configuration Parameters
- Group 2 – Extended Parameters
- Group 3 – PID Control Parameters
- Group 4 – High Performance Motor Control Parameters
- Group 5 – Field Bus Parameters
- Group 6 – Advanced Options
- Group 7 – Advanced Motor Control
- Group 8 – Application Parameters
- Group 9 – Advanced I/O Selection
When the drive is reset to factory defaults, or is in its factory supplied
state, only Group 1 Parameters can be accessed. In order to allow access to
parameters from the higher level groups, the access code must be changed as
follows.
P1-14 = P2-40 (Default setting = 101). With this setting, parameter groups 1 –
5 can be accessed, along with the first 50 parameters in Group 0.
P1-14 = P6-30 (Default setting = 201). With this setting, all parameters are
accessible.
6.2. Parameter Group 1 – Basic Parameters
The basic parameter group allows the user to:
-
Enter the motor nameplate information
o P1-07 = Motor Rated Voltage
o P1-08 = Motor Rated Current
o P1-09 = Motor Rated Frequency
o P1-10 = (Optionally) Motor Rated Speed -
Define the operating speed limits
o P1-01 = Maximum Frequency or Speed
o P1-02 = Minimum Frequency or Speed -
Define the acceleration and deceleration times used when starting and stopping the motor, or changing speed
o P1-03 = Acceleration Time
o P1-04 = Deceleration Time -
Select where the drive should receive it’s command signals from, and determine what functions are associated with the drive control terminal inputs
o P1-12 Selects the control source
o P1-13 Assigns the functions to the digital inputs
These parameters will often provide enough functions to allow the user to complete basic commissioning in simple applications. The parameters are described more fully below.
Par.| Description| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P1-01| Maximum Frequency / Speed Limit| P1-02| 500.0|
50.0 (60.0)| Hz / Rpm
Maximum output frequency or motor speed limit – Hz or rpm. If P1-10 >0, the
value entered / displayed is in Rpm.
P1-02| Minimum Frequency / Speed Limit| 0.0| P1-01|
20.0| Hz / Rpm
Minimum speed limit – Hz or rpm.
If P1-10 >0, the value entered / displayed is in Rpm.
P1-03| Acceleration Ramp Time| See Below| 5.0 / 10.0|
Seconds
Acceleration ramp time from 0 to base speed (P-1-09) in seconds.
FS2 & FS3 : 5.0 Seconds Default Setting, 0.01 Seconds Resolution, 600.0
Seconds Maximum. FS4 – FS7 : 10.0 Seconds Default Setting, 0.1 Seconds
Resolution, 6000 Seconds Maximum.
Par.| Description| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P1-04| Deceleration Ramp Time| See Below| 5.0 / 10.0|
Seconds
Deceleration ramp time from base speed (P1-09) to standstill in seconds. When
set to zero, fastest possible ramp time without trip is activated.
FS2 & FS3 : 5.0 Seconds Default Setting, 0.01 Seconds Resolution, 600.0
Seconds Maximum. FS4 – FS7 : 10.0 Seconds Default Setting, 0.1 Seconds
Resolution, 6000.0 Seconds Maximum.
P1-05| Stop Mode| 0| 3| 0| –
0| Ramp To Stop| When the enable signal is removed, the drive will
ramp to stop, with the rate controlled by P1-04 as described above. In this
mode, the drive brake transistor (where fitted) is disabled.
1| Coast to Stop| When the enable signal is removed, the drive
output is immediately disabled, and the motor will coast (freewheel) to stop.
If the load can continue to rotate due to inertia, and the drive may possibly
be re-enabled whilst the motor is still rotating, the spin start function
(P2-26) should be enabled. In this mode, the drive brake transistor (where
fitted) is disabled.
2| Ramp To Stop| When the enable signal is removed, the drive will
ramp to stop, with the rate controlled by P1-04 as described above. The drive
brake chopper is also enabled in this mode.
3| Coast to Stop| When the enable signal is removed, the drive
output is immediately disabled, and the motor will coast (freewheel) to stop.
If the load can continue to rotate due to inertia, and the drive may possibly
be re-enabled whilst the motor is still rotating, the spin start function (P2-
26) should be enabled. The drive brake chopper is enabled in this mode,
however it will only activate when required during a change in the drive
frequency setpoint, and will not activate when stopping.
4| AC Flux Braking| As Option 0, but additionally, AC Flux
braking is used to increase the available braking torque.
P1-06| Energy Optimiser| 0| 1| 0| –
0| Disabled|
1| Enabled| When enabled, the Energy Optimiser attempts to reduce
the overall energy consumed by the drive and motor when operating at constant
speeds and light loads. The output voltage applied to the motor is reduced.
The Energy Optimiser is intended for applications where the drive may operate
for some periods of time with constant speed and light motor load, whether
constant or variable torque.
P1-07| Motor Rated Voltage| Drive Rating Dependent| Volts
This parameter should be set to the rated (nameplate) voltage of the motor
(Volts).
P1-08| Motor Rated Current| Drive Rating Dependent| Amps
This parameter should be set to the rated (nameplate) current of the motor.
P1-09| Motor Rated Frequency| 10| 500| 50 (60)|
Hz
This parameter should be set to the rated (nameplate) current of the motor.
P1-10| Motor Rated Speed| 0| 30000| 0| RPM
This parameter can optionally be set to the rated (nameplate) rpm of the
motor. When set to the default value of zero, all speed related parameters are
displayed in Hz, and the slip compensation for the motor is disabled. Entering
the value from the motor nameplate enables the slip compensation function, and
the drive display will now show motor speed in estimated rpm. All speed
related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will
also be displayed in Rpm.
NOTE When the drive is operated with the optional Encoder Feedback
Interface, this parameter must be set to the correct nameplate Rpm of the
connected motor.
P1-11| V/F Mode Voltage Boost| 0.0| Drive Rating
Dependent| %
Voltage boost is used to increase the applied motor voltage at low output
frequencies, in order to improve low speed and starting torque. Excessive
voltage boost levels may result in increased motor current and temperature,
and force ventilation of the motor may be required.
An automatic setting ( ) is also possible, whereby the drive will
automatically adjust this parameter based on the motor parameters measured
during an autotune.
Par.| Description| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P1-12| Primary Command Source| 0| 6| 0| –
0| Terminal Control| The drive responds directly to signals applied
to the control terminals.
1| Uni-directional Keypad Control| The drive can be
controlled in the forward direction only using an external or remote Keypad.
2| Bi-directional Keypad Control| The drive can be controlled
in the forward and reverse directions using an external or remote Keypad.
Pressing the keypad START button toggles between forward and reverse.
3| PID Control| The output frequency is controlled by the
internal PID controller.
4| Fieldbus Control| Control via Modbus RTU if no fieldbus
interface option is present, otherwise control is from the fieldbus option
module interface.
5| Slave Mode| The drive acts as a Slave to a connected drive
operating in Master Mode.
6| CAN bus Control| Control via CAN bus connected to the RJ45
serial interface connector.
P1-13| Digital Input Source Select| 0| 21| 1| –
Defines the function of the digital inputs depending on the control mode
setting in P1-12. See section 7.1. Control Source Selection for more
information.
P1-14| Extended Menu Access Code| 0| 30000| 0| –
Parameter Access Control. The following settings are applicable:
P1-14 = P2-40 = 101 : Allows access to Extended Parameter Groups 0 – 5
P1-14 = P6-30 = 201 = Allows access to all parameter groups (Intended for
experienced users only, usage is not described in this User Guide).
Control Terminal Functions
For standard applications and operation, the basic control of the drive and
functions of all drive input terminals can be configured using just two
parameters, P1-12 and P1-13. P1-12 is used to define the source of all control
commands and the primary speed
reference source. P1-13 then allows fast selection of Analog and Digital Input
functions based on a selection table.
7.1. Control Source Selection
7.1.1. P1-12 Function
P1-12 is used to select the main control source of the drive and the main
speed reference according to the following table:
P1-12| Function| Control Source| Main Speed Reference|
Notes
---|---|---|---|---
0| Terminal Control| Terminals| Analog Input 1| All control signals are
applied to the control terminals. Functions are determined by P-15 Macro
setting.
1| Keypad Control| Keypad / Terminals| Motorised Pot / Keypad| When keypad
mode is selected, the default operation of the drive requires the keypad Start
& Stop buttons are used to control the drive. This can be changed using P-31
to allow the drive to be started from Digital Input 1 directly.
2| Keypad Control| Keypad / Terminals| Motorised Pot / Keypad
3| PID Control| Terminals| PID Output| Enable / Disable control of the drive
is through the drive control terminal strip.
Output frequency is set by the output of the PI Controller.
4| Fieldbus / Modbus RTU| Modbus RTU| Fieldbus / Modbus RTU| Control of the
drive operation is through a fieldbus option module mounted in the drive
option slot. If no option module is fitted, control is through the Modbus RTU
interface.
Digital Input 1 must be closed to allow operation.
5| Slave Mode| Master Drive| From Master| The P2 provides an inbuilt Master /
Slave function. A single drive acts as the Master, and connected Slave drives
will mimic the starting and stopping, along with the following the output
frequency, with any scaling applied.
Digital Input 1 must be closed to allow operation.
6| CAN Open| CAN Open| CAN| Control of the drive operation is through the CAN
Open Interface. Digital Input 1 must be closed to allow operation.
7.1.2. Overview
The P2 uses a Macro approach to simplify the configuration of the Analog and
Digital Inputs. There are two key parameters which determine the input
functions and drive behaviour:
-
P1-12 – Selects the main drive control source and determines how the output frequency of the drive is primarily controlled.
-
P1-13 – Assigns the Macro function to the analog and digital inputs.
Additional parameters can then be used to further adapt the settings, e.g. -
P2-30 – Used to select the format of the analog signal to be connected to analog input 1, e.g. 0 – 10 Volt, 4 – 20mA.
-
P2-33 – Used to select the format of the analog signal to be connected to analog input 2, e.g. 0 – 10 Volt, 4 – 20mA.
-
P2-36 – Determines whether the drive should automatically start following a power on if the Enable Input is present.
-
P2-37 – When Keypad Mode is selected, determines at what output frequency / speed the drive should start following the enable command, and also whether the keypad start key must be pressed or if the Enable input alone should start the drive.
The diagrams opposite provide an overview of the functions of each terminal macro function, and a simplified connection diagram for each.
7.1.3. Macro Function Guide
Function | Explanation |
---|---|
STOP | Latched Input, Open the contact to STOP the drive. |
RUN | Latched input, Close the contact to Start, the drive will operate as long |
as the input is maintained.
FWD⭮| Latched Input, selects the direction of motor rotation FORWARD.
REV⭯| Latched Input, selects the direction of motor rotation REVERSE.
RUN FWD⭮| Latched Input, Close to Run in the FORWARD direction, Open to STOP.
RUN REV⭯| Latched Input, Close to Run in the REVERSE direction, Open to STOP.
ENABLE| Hardware Enable Input.
In Keypad Mode, P-31 determines whether the drive immediately starts, or the
keypad start key must be pressed. In other modes, this input must be present
before the start command is applied via the fieldbus interface.
START⮥| Normally Open, Rising Edge, Close momentarily to START the drive (NC
STOP Input must be maintained).
^- START -^| Simultaneously applying both inputs momentarily will START the
drive (NC STOP Input must be maintained).
STOP⮧| Normally Closed, Falling Edge, Open momentarily to STOP the drive.
START⮥FWD⭮| Normally Open, Rising Edge, Close momentarily to START the drive
in the forward direction (NC STOP Input must be maintained).
START⮥REV⭮| Normally Open, Rising Edge, Close momentarily to START the drive
in the reverse direction (NC STOP Input must be maintained).
^-FAST STOP (P2-25)-^| When both inputs are momentarily active simultaneously,
the drive stops using Fast Stop Ramp Time P-24.
FAST STOP⮧ (P2-25)| Normally Closed, Falling Edge, Open momentarily to FAST
STOP the drive using Fast Stop Ramp Time P-24.
E-TRIP| Normally Closed, External Trip input. When the input opens
momentarily, the drive trips showing or
depending on P2-33 setting. See section 4.12.2. Motor Thermistor Connection on page 25 for further information.
Analog Input AI1| Analog Input 1, signal format selected using P-16.
Analog Input AI2| Analog Input 2, signal format selected using P-47.
AI1 REF| Analog Input 1 provides the speed reference.
AI2 REF| Analog Input 2 provides the speed reference.
P-xx REF| Speed reference from the selected preset speed.
PR-REF| Preset speeds P-20 – P-23 are used for the speed reference, selected
according to other digital input status.
PI-REF| PI Control Speed Reference.
PI FB| Analog Input used to provide a Feedback signal to the internal PI
controller.
KPD REF| Keypad Speed Reference selected.
INC SPD?| Normally Open, Close the input to Increase the motor speed.
DEC SPD?| Normally Open, Close input to Decrease motor speed.
FB REF| Selected speed reference from Fieldbus (Modbus RTU / CAN Open / Master
depending on P-12 setting).
(NO)| Input is Normally Open, Close momentarily to activate the function.
(NC)| Input is Normally Closed, Open momentarily to activate the function.
DECEL P1-04| During deceleration and stopping, Deceleration Ramp 1 (P1-04) is
used.
DECEL P8-11| During deceleration and stopping, Deceleration Ramp 2 (P8-11) is
used (Requires Advanced Parameter Access, see section 6.1. Parameter Set
Overview on page 35.
7.2. Digital Input Configuration Parameter P1-13
P1-13 | DI1 | DI2 | DI3 | AI1 / DI4 | AI2 / DI5 |
---|---|---|---|---|---|
State | 0 | 1 | 0 | 1 | 0 |
0 | 1 | ||||
0 | User defined | ||||
1 | STOP | RUN | FWD ⭮ | REV ⭯ | P1-12 REF |
P2-02
2| STOP| RUN| FWD ⭮| REV ⭯| DI3| DI4| DI5| Preset
Speed
0| 0| 0| P2-01 REF
1| 0| 0| P2-02 REF
0| 1| 0| P2-03 REF
1| 1| 0| P2-04 REF
0| 0| 1| P2-05 REF
1| 0| 1| P2-06 REF
0| 1| 1| P2-07 REF
1| 1| 1| P2-08 REF
3| STOP| RUN| FWD ⭮| REV ⭯| P1-12 REF| P2-01 REF| Analog Input AI1|
Analog Input AI2
4| STOP| RUN| FWD ⭮| REV ⭯| P1-12 REF| P2-01 REF| Analog Input AI1|
DECEL P1-04| DECEL P8-11
5| STOP| RUN| FWD ⭮| REV ⭯| P1-12 REF| AI2 REF| Analog Input AI1| Analog
Input AI2
6| STOP| RUN| FWD ⭮| REV ⭯| P1-12 REF| P2-01 REF| Analog Input AI1|
E-TRIP| OK
7| STOP| RUN| FWD ⭮| REV ⭯| DI3| DI4| Preset Speed|
E-TRIP| OK
Off| Off| P2-01 REF
On| Off| P2-02 REF
Off| On| P2-03 REF
On| On| P2-04 REF
8| STOP| RUN| FWD ⭮| REV ⭯| DI3| DI4| Preset Speed|
DECEL P1-04| DECEL P8-11
Off| Off| P2-01 REF
On| Off| P2-02 REF
Off| On| P2-03 REF
On| On| P2-04 REF
8| STOP| RUN| FWD ⭮| REV ⭯| DI3| DI4| Preset Speed|
P1-12 REF| PR-REF
Off| Off| P2-01 REF
On| Off| P2-02 REF
Off| On| P2-03 REF
On| On| P2-04 REF
10| STOP| RUN| FWD ⭮| REV ⭯| (NO)| INC SPD ?| (NO)| DEC SPD ?| P1-12
REF1| P2-01-REF
11| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| P1-12 REF| PR-REF| Analog Input
AI1| P2-01 REF| P2-02 REF
12| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| DI3| DI4| DI5|
Preset Speed
Off| Off| Off| P2-01 REF
On| Off| Off| P2-02 REF
Off| On| Off| P2-03 REF
On| On| Off| P2-04 REF
Off| Off| On| P2-05 REF
On| Off| On| P2-06 REF
Off| On| On| P2-07 REF
On| On| On| P2-08 REF
13| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| P1-12 REF| P2-01 REF| Analog Input
AI1| Analog Input AI2
14| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| P1-12 REF| P2-01 REF| Analog Input
AI1| DECEL P1-04| DECEL P8-11
15| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| P1-12 REF| AI2-REF| Analog Input
AI1| Analog Input AI2
16| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| P1-12 REF| P2-01 REF| Analog Input
AI1| E-TRIP| OK
P1-13| DI1| DI2| DI3| AI1 / DI4| AI2 / DI5
---|---|---|---|---|---
State| 0| 1| 0| 1| 0| 1| 0| 1|
0| 1
17| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| DI3| DI4| Preset
Speed| E-TRIP| OK
Off| Off| P2-01 REF
On| Off| P2-02 REF
Off| On| P2-03 REF
On| On| P2-04 REF
18| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| DI3| DI4| Preset
Speed| DECEL P1-04| DECEL P8-11
Off| Off| P2-01 REF
On| Off| P2-02 REF
Off| On| P2-03 REF
On| On| P2-04 REF
19| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| DI3| DI4| Preset
Speed| P1-12 REF| PR-REF
Off| Off| P2-01 REF
On| Off| P2-02 REF
Off| On| P2-03 REF
On| On| P2-04 REF
20| STOP| RUN FWD ⭮| STOP| RUN REV ⭯| (NO)| INC SPD ⭡| (NO)| DEC SPD ?|
P1-12 REF1| P2-01-EF
21| (NO)| START ⮥
FWD ⭮
| STOP ⮧| (NC)| (NO)| START ⮥
REV ⭯
| Analog Input AI1| P1-12 REF| P2-01-EF
7.3. Example Connection Schematics
P1-13 Setting : | 1 | 4 | 11 | 14 |
---|---|---|---|---|
+24VDC | +24VDC | +24VDC | +24VDC | |
Enable / Disable | Enable / Disable | Run Forward | Run Forward | |
Reverse / Forward | Reverse / Forward | Run Reverse | Run Reverse | |
P1-12 REF / | P1-12 REF / | P1-12 REF / | P1-12 REF / | |
PR REF | PR REF | PR REF | PR REF | |
+10 VDC | +10 VDC | +10 VDC | +10 VDC | |
AIN 1 | AIN 1 | AIN 1 | AIN 1 | |
0 V | 0 V | 0 V | 0 V | |
AOUT 1 | AOUT 1 | AOUT 1 | AOUT 1 | |
0 V | 0 V | 0 V | 0 V | |
P2-01 / | DECEL P1-04 / | P2-01 / | DECEL P1-04 / | |
P2-02 REF | DECEL P8-11 | P2-02 REF | DECEL P8-11 | |
AOUT 2 | AOUT 2 | AOUT 2 | AOUT 2 | |
STO + | STO + | STO + | STO + | |
STO – | STO – | STO – | STO – | |
2 | 8 | 9 | 1218 | |
--- | --- | --- | --- | --- |
+24VDC | +24VDC | +24VDC | +24VDC | +24VDC |
Enable / Disable | Enable / Disable | Enable / Disable | Run Forward | Run Forward |
Reverse / Forward | Reverse / Forward | Reverse / Forward | Run Reverse | Run |
Reverse
PR SEL BIT 0| PR SEL BIT 0| PR SEL BIT 0| PR SEL BIT 0| PR SEL BIT 0
+10 VDC| +10 VDC| +10 VDC| +10 VDC| +10 VDC
PR SEL BIT 1| PR SEL BIT 1| PR SEL BIT 1| PR SEL BIT 1| PR SEL BIT 1
0V| 0V| 0V| 0V| 0V
AOUT 1| AOUT 1| AOUT 1| AOUT 1| AOUT 1
0 V| 0V| 0V| 0 V| 0 V
PR SEL BIT 2| DECEL P1-04 /
DECEL P8-11| P1-12 REF /
PR REF| PR SEL BIT 2| DECEL P1-04 /
DECEL P8-11
AOUT 2| AOUT 2| AOUT 2| AOUT 2| AOUT 2
STO +| STO +| STO +| STO +| STO +
STO –| STO –| STO –| STO –| STO –
P1-13 Setting :
+24VDC | +24VDC | +24VDC | +24VDC |
---|---|---|---|
Enable / Disable | Enable / Disable | Run Forward | Run Forward |
Reverse / Forward | Reverse / Forward | Run Reverse | Run Reverse |
P1-12 REF / P2-01 REF | P1-12 REF / AI2 REF | P1-12 REF / P2-01 REF | P1-12 REF / |
I2 REF
+10 VDC| +10 VDC| +10 VDC| +10 VDC
AIN 1| AIN 1| AIN 1| AIN 1
0 V| 0 V| 0 V| 0 V
AOUT 1| AOUT 1| AOUT 1| AOUT 1
0 V| 0 V| 0 V| 0 V
AIN 2| AIN 2| AIN 2| AIN 2
AOUT 2| AOUT 2| AOUT 2| AOUT 2
STO +| STO +| STO +| STO +
STO –| STO –| STO –| STO –
P1-13 Setting :
6 | 16 |
---|---|
+24VDC | +24VDC |
Enable / Disable | Run Forward |
Reverse / Forward | Run Reverse |
P1-12 REF / P2-01 REF | P1-12 REF / P2-01 REF |
+10 VDC | +10 VDC |
AIN 1 | AIN 1 |
0 V | 0 V |
AOUT 1 | AOUT 1 |
0 V | 0 V |
E-TRIP | E-TRIP |
AOUT 2 | AOUT 2 |
STO + | STO + |
STO – | STO – |
P1-13 Setting : | 10 |
--- | --- |
+24VDC | +24VDC |
Enable / Disable | Run Forward |
Reverse / Forward | Run Reverse |
INC SPEED | INC SPEED |
+10 VDC | +10 VDC |
DEC SPEED | DEC SPEED |
0 V | 0 V |
AOUT 1 | AOUT 1 |
0 V | 0 V |
P1-12 REF / P2-01 REF | P1-12 REF / P2-01 REF |
AOUT 2 | AOUT 2 |
STO + | STO + |
STO – | STO – |
P1-13 Setting : | 21 |
+24 VDC |
NO Push Start Forward
NC Push Stop
NO Push Start Reverse
+10VDC
AIN 1
0V
AOUT 1
0V
P1-12 REF / P2-01 REF
AOUT 2
STO +
STO –
Extended Parameters
8.1. Parameter Group 2 – Extended Parameters
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P2-01| Preset / Jog Frequency / Speed 1| P1-02| P1-01|
5.0| Hz / Rpm
P2-02| Preset / Jog Frequency / Speed 2| P1-02| P1-01|
10.0| Hz / Rpm
P2-03| Preset / Jog Frequency / Speed 3| P1-02| P1-01|
25.0| Hz / Rpm
P2-04| Preset / Jog Frequency / Speed 4| P1-02| P1-01|
50.0 (60.0)| Hz / Rpm
P2-05| Preset / Jog Frequency / Speed 5| P1-02| P1-01|
0.0| Hz / Rpm
P2-06| Preset / Jog Frequency / Speed 6| P1-02| P1-01|
0.0| Hz / Rpm
P2-07| Preset / Jog Frequency / Speed 7| P1-02| P1-01|
0.0| Hz / Rpm
P2-08| Preset / Jog Frequency / Speed 8| P1-02| P1-01|
0.0| Hz / Rpm
Preset Speeds / Frequencies selected by digital inputs depending on the
setting of P1-13. If P1-10 = 0, the values are entered as Hz. If P1-10 > 0,
the values are entered as Rpm. Setting a negative value will reverse the
direction of motor rotation.
P2-09| Skip Frequency Centre Point| P1-02| P1-01|
0.0| Hz / Rpm
P2-10| Skip Frequency Band Width| 0.0| P1-01| 0.0|
Hz / Rpm
The Skip Frequency function is used to avoid the drive operating at a certain
output frequency, for example at a frequency which causes mechanical resonance
in a particular machine. Parameter P2-09 defines the centre point of the skip
frequency band, and is used conjunction with P2-10. The drive output frequency
will ramp through the defined band at the rates set in P1-03 and P1-04
respectively, and will not hold any output frequency within the defined band.
If the frequency reference applied to the drive is within the band, the drive
output frequency will remain at the upper or lower limit of the band.
P2-11| Analog Output 1 (Terminal 8) Function Select| 0|
11| 8| –
Digital Output Mode. Logic 1 = +24V DC
0| Drive Enabled (Running)| Logic 1 when the drive is enabled
(Running).
1| Drive Healthy| Logic 1 When no Fault condition exists on the
drive.
2| At Target Frequency (Speed)| Logic 1 when the output
frequency matches the setpoint frequency.
3| Output Frequency > 0.0| Logic 1 when the motor runs above zero
speed.
4| Output Frequency >= Limit| Logic 1 when the motor speed exceeds
the adjustable limit.
5| Output Current >= Limit| Logic 1 when the motor current exceeds
the adjustable limit.
6| Motor Torque >= Limit| Logic when the motor torque exceeds the
adjustable limit.
7| Analog Input 2 Signal Level >= Limit| Logic when the signal
applied to the Analog Input 2 exceeds the adjustable limit.
NOTE When using settings 4 – 7, parameters P2-16 and P2-17 must be used
together to control the behaviour. The output will switch to Logic 1 when the
selected signal exceeds the value programmed in P2-16, and return to Logic 0
when the signal falls below the value programmed in P2-17.
Analog Output Mode
8| Output Frequency (Motor Speed)| 0 to P-01.
9| Output (Motor) Current| 0 to 200% of P1-08.
10| Motor Torque| 0 to 200% of motor rated torque.
11| Output (Motor) Power| 0 to 150% of drive rated power.
12| PID Output| Output from the internal PID Controller, 0 – 100%.
P2-12| Analog Output 1 (Terminal 8) Format| See Below| | –
| 0 to10V
| 0 to 20mA
| 4 to 20mA
| 10 to 0V
| 20 to 0mA
| 20 to 4mA
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P2-13| Analog Output 2 (Terminal 11) Function Select| 0|
12| 9| –
Digital Output Mode. Logic 1 = +24V DC
0| Drive Enabled (Running)| Logic 1 when the drive is enabled
(Running).
1| Drive Healthy| Logic 1 When no Fault condition exists on the
drive.
2| At Target Frequency (Speed)| Logic 1 when the output frequency
matches the setpoint frequency.
3| Output Frequency > 0.0| Logic 1 when the motor runs above zero
speed.
4| Output Frequency >= Limit| Logic 1 when the motor speed exceeds
the adjustable limit.
5| Output Current >= Limit| Logic 1 when the motor current exceeds
the adjustable limit.
6| Motor Torque >= Limit| Logic when the motor torque exceeds the
adjustable limit.
7| Analog Input 2 Signal Level >= Limit| Logic when the signal
applied to the Analog Input 2 exceeds the adjustable limit.
NOTE When using settings 4 – 7, parameters P2-16 and P2-17 must be used
together to control the behaviour. The output will switch to Logic 1 when the
selected signal exceeds the value programmed in P2-16, and return to Logic 0
when the signal falls below the value programmed in P2-17.
Analog Output Mode
8| Output Frequency (Motor Speed)| 0 to P-01.
9| Output (Motor) Current| 0 to 200% of P1-08.
10| Motor Torque| 0 to 200% of motor rated torque.
11| Output (Motor) Power| 0 to 150% of drive rated power.
12| PID Output| Output from the internal PID Controller, 0 – 100%.
P2-14| Analog Output 2 (Terminal 11) Format| See Below| | –
| 0 to10V
| 0 to 20mA
| 4 to 20mA
| 10 to 0V
| 20 to 0mA
| 20 to 4mA
P2-15| User Relay 1 Output (Terminals 14, 15 & 16) Function
**Select| 0| 14| 1| –
Setting| Function| Logic 1 when
0| Drive Enabled (Running)| The drive is enabled (Running).
1| Drive Healthy| No fault or trip condition exists on the
drive.
2| At Target Frequency (Speed)| Output frequency matches the
setpoint frequency.
3| Output Frequency > 0.0| The motor runs above zero speed.
4| Output Frequency >= Limit| The motor speed exceeds the adjustable
limit.
5| Output Current >= Limit| The motor current exceeds the adjustable
limit.
6| Motor Torque >= Limit| The motor torque exceeds the adjustable
limit.
7| Analog Input 2 Signal Level >= Limit| The signal applied to
the Analog Input 2 exceeds the adjustable limit.
8| Reserved| No Function.
9| Reserved| No Function.
10| Maintenance Due| The internally programmable maintenance timer
has elapsed.
11| Drive Ready| 0 to 150% of drive rated power.
12| Drive Tripped| The drive is not tripped, the STO circuit is
closed, the mains supply is present and the hardware enable input present
(Digital Input 1 unless changed by the user).
13| STO Status| When both STO inputs are present and the drive is
able to be operated.
14| PID Error >= Limit| The PID Error (difference between setpoint
and feedback) is greater than or equal to the programmed limit.
NOTE When using settings 4 – 7 and 14, parameters P2-16 and P2-17 must be
used together to control the behaviour. The output will switch to Logic 1 when
the selected signal exceeds the value programmed in P2-16, and return to Logic
0 when the signal falls below the value programmed in P2-17.
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P2-16| Adjustable Threshold 1 Upper Limit (Analog Output 1 / Relay
Output 1)| P2-17| 200.0| 100.0| %
P2-17| Adjustable Threshold 1 Lower Limit (Analog Output 1 / Relay
Output 1)| 0.0| P2-16| 0.0| %
Used in conjunction with some settings of Parameters P2-11 & P2-15.
P2-18| User Relay 2 Output (Terminals 17 & 18) Function **select|
0| 14| 0| –
Setting| Function| Logic 1 when
0| Drive Enabled (Running)| The drive is enabled (Running).
1| Drive Healthy| No fault or trip condition exists on the
drive.
2| At Target Frequency (Speed)| Output frequency matches the
setpoint frequency.
3| Output Frequency > 0.0| The motor runs above zero speed.
4| Output Frequency >= Limit| The motor speed exceeds the adjustable
limit.
5| Output Current >= Limit| The motor current exceeds the adjustable
limit.
6| Motor Torque >= Limit| The motor torque exceeds the adjustable
limit.
7| Analog Input 2 Signal Level >= Limit| The signal applied to
the Analog Input 2 exceeds the adjustable limit.
8| Hoist Brake Control| Enables Hoist Mode. The Output relay may be
used to control the motor holding brake. Refer to your Bardac Sales Partner
for further information.
9| Reserved| No Function.
10| Maintenance Due| The internally programmable maintenance timer
has elapsed.
11| Drive Ready| 0 to 150% of drive rated power.
12| Drive Tripped| The drive is not tripped, the STO circuit is
closed, the mains supply is present and the hardware enable input present
(Digital Input 1 unless changed by the user).
13| STO Status| When both STO inputs are present and the drive is
able to be operated.
14| PID Error >= Limit| The PID Error (difference between setpoint
and feedback) is greater than or equal to the programmed limit.
NOTE When using settings 4 – 7 and 14, parameters P2-16 and P2-17 must be
used together to control the behaviour. The output will switch to Logic 1 when
the selected signal exceeds the value programmed in P2-16, and return to Logic
0 when the signal falls below the value programmed in P2-17.
P2-19| Adjustable Threshold 1 Upper Limit (Analog Output 2 / Relay
Output 2)| P2-20| 200.0| 100.0| %
P2-20| Adjustable Threshold 1 Lower Limit (Analog Output 2 / Relay
Output 2)| 0.0| P2-19| 0.0| %
Used in conjunction with some settings of Parameters P2-13 & P2-18.
P2-21| Display Scaling Factor| -30.000| 30.000|
0.000| –
P2-22| Display Scaling Source| 0| 2| 0| –
P2-21 & P2-22 allow the user to program the drive to display an alternative
output unit scaled from an existing parameter, e.g. to display conveyer speed
in metres per second based on the output frequency. This function is disabled
if P2-21 is set to 0.
If P2-21 is set >0, the variable selected in P2-22 is multiplied by the factor
entered in P2-21, and displayed whilst the drive is running, with a ‘c’ to
indicate the customer scaled units.
P2-22 Options| Scaled Value is
0| Motor Speed| If P-10 = 0, Output Frequency (Hz) x Scaling Factor
If P-10 > 0, Motor RPM x Scaling Factor
1| Motor Current| Motor Amps x Scaling Factor
2| Analog Input 2| Analog Input 2 % (P0-02) x Scaling Factor
3| P0-80 Value| P0-80 Value x Scaling Factor
P2-23| Zero Speed Holding Time| 0.0| 60.0| 0.2|
Seconds
Determines the time for which the drive output frequency is held at zero when
stopping, before the drive output is disabled.
P2-24| Effective Switching Frequency| Drive Rating Dependent|
kHz
Effective power stage switching frequency. The range of settings available and
factory default parameter setting depend on the drive power and voltage
rating. Higher frequencies reduce the audible ‘ringing’ noise from the motor,
and improve the output current waveform, at the expense of increased drive
losses. Refer to section 0 for further information regarding operation at
higher switching frequency.
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P2-25| 2nd Deceleration Ramp Time| 0.00| 240.0| 0.00|
Seconds
This parameter allows an alternative deceleration ramp down time to be
programmed into the drive, which can be selected by digital inputs (dependent
on the setting of P1-13) or selected automatically in the case of a mains
power loss if P2-38 = 2.
When set to 0.0, the drive will coast to stop.
P2-26| Spin Start Enable| 0| 1| 0| –
0| Disabled| Spin Start is not active. This setting should be used
for all applications where the motor is always stationary before the drive is
enabled.
1| Enabled| When enabled, on start up the drive will attempt to
determine if the motor is already rotating, and will begin to control the
motor from its current speed. A short delay may be observed when starting
motors which are not turning.
2| Enabled for Coast, Trip or after Mains Loss| Spin start is
active only following the listed conditions, otherwise spin start is disabled.
P2-27| Standby Mode Timer| 0.0| 250.0| 0.0|
Seconds
This parameter defines the time period, whereby if the drive operates at the
frequency / speed set in P3-14 (Standby speed threshold) for greater than the
set time period, the drive output will be disabled, and the display will show
. The function is disabled if
P2-27 = 0.0.
P2-28| Slave Speed Scaling Control| 0| 3| 0| –
Active in Keypad mode (P1-12 = 1 or 2) and Slave mode (P1-12=5) only. The
keypad reference can be multiplied by a preset scaling factor or adjusted
using an analog trim or offset.
0| Disabled (No Scaling)
1| Actual Speed = Digital Speed x P2-29
2| Actual Speed = (Digital Speed x P2-29) + Analog Input 1 Reference
3| Actual Speed = (Digital Speed x P2-29) x Analog Input 1 Reference
P2-29| Slave Speed Scaling Factor| -500.0| 500.0|
100.0| %
Used in conjunction with P2-28.
P2-30| Analog Input 1 (Terminal 6) Format| See Below| | –
Setting| Signal Format
| 0 to 10 Volt Signal (Uni-polar)
| 10 to 0 Volt Signal (Uni-polar)
| -10 to +10 Volt Signal (Bi-polar)
| 0 to 20mA Signal
| 4 to 20mA Signal, the drive will trip and show the fault code if the
signal level falls below 3mA
| 4 to 20mA Signal, the drive will ramp to stop if the signal level falls
below 3mA
| 20 to 4mA Signal, the drive will trip and show the fault code if the
signal level falls below 3mA
| 20 to 4mA Signal, the drive will ramp to stop if the signal level falls
below 3mA
P2-31| Analog Input 1 Scaling| 0.0| 2000.0| 100.0|
%
Scales the analog input by this factor, e.g. if P2-30 is set for 0 – 10V, and
the scaling factor is set to 200.0%, a 5 volt input will result in the drive
running at maximum speed (P1-01).
P2-32| Analog Input 1 Offset| -500.0| 500.0| 0.0|
%
Sets an offset, as a percentage of the full scale range of the input, which is
applied to the analog input signal.
P2-33| Analog Input 2 (Terminal 10) Format| See Below| | –
Setting| Signal Format
| 0 to 10 Volt Signal (Uni-polar)
| 10 to 0 Volt Signal (Uni-polar)
| Motor PTC Thermistor Input
| 0 to 20mA Signal
| 4 to 20mA Signal, the drive will trip and show the fault code if the signal
level falls below 3mA
| 4 to 20mA Signal, the drive will ramp to stop if the signal level falls
below 3mA
| 20 to 4mA Signal, the drive will trip and show the fault code if the signal
level falls below 3mA
| 20 to 4mA Signal, the drive will ramp to stop if the signal level falls
below 3mA
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P2-34| Analog Input 2 Scaling| 0.0| 2000.0| 100.0|
%
Scales the analog input by this factor, e.g. if P2-30 is set for 0 – 10V, and
the scaling factor is set to 200.0%, a 5 volt input will result in the drive
running at maximum speed (P1-01).
P2-35| Analog Input 2 Offset| -500.0| 500.0| 0.0|
%
Sets an offset, as a percentage of the full scale range of the input, which is
applied to the analog input signal.
P2-36| Start Mode Select / Automatic Restart| See Below| |
%
Defines the behaviour of the drive relating to the enable digital input and
also configures the Automatic Restart function.
| Following Power on or reset, the drive will not start if Digital Input 1
remains closed. The Input must be closed after a power on or reset to start
the drive.
| Following a Power On or Reset, the drive will automatically start if Digital
Input 1 is closed.
| Following a trip, the drive will make up to 5 attempts to restart at 20
second intervals. The drive must be powered down to reset the counter. The
numbers of restart attempts are counted, and if the drive fails to start on
the final attempt, the drive will fault with, and will require the user to
manually reset the fault.
D ANGER! “ modes allow th e driv
e to Auto-star t, th erefore th e impac
t on sy stem/Personnel safety needs to be considered.
P2-37| Keypad Mode Restart Speed| 0| 3| 1| –
This parameter is only active when P1-12 = 1 or 2. When settings 0 to 3 are
used, the drive must be started by pressing the Start key on the keypad. When
settings 4 – 7 are used, the drive starting is controlled by the enable
digital input.
0| Minimum Speed| Following a stop and restart, the drive will
always initially run at the minimum speed P1-02.
1| Previous Operating Speed| Following a stop and restart, the
drive will return to the last keypad setpoint speed used prior to stopping.
2| Current Running Speed| Where the drive is configured for
multiple speed references (typically Hand / Auto control or Local / Remote
control), when switched to keypad mode by a digital input, the drive will
continue to operate at the last operating speed.
3| Preset Speed 8| Following a stop and restart, the drive will
always initially run at Preset Speed 8 (P2-08).
4| Minimum Speed (Terminal Enable)| Following a stop and
restart, the drive will always initially run at the minimum speed P1-02.
5| Previous Operating Speed (Terminal Enable)| Following a stop
and restart, the drive will return to the last keypad setpoint speed used
prior to stopping.
6| Current Running Speed (Terminal Enable)| Where the drive is
configured for multiple speed references (typically Hand / Auto control or
Local / Remote control), when switched to keypad mode by a digital input, the
drive will continue to operate at the last operating speed.
7| Preset Speed 8 (Terminal Enable)| Following a stop and restart,
the drive will always initially run at Preset Speed 8 (P2-08).
P2-38| Mains Loss Ride Through / Stop Control| 0| 2|
0| –
0| Mains Loss Ride Through| The drive will attempt to continue
operating by recovering energy from the load motor. Providing that the mains
loss period is short, and sufficient energy can be recovered before the drive
control electronics power off, the drive will automatically restart on return
of mains power.
1| Coast To Stop| The drive will immediately disable the output to
the motor, allowing the load to coast or free wheel. When using this setting
with high inertia loads, the Spin Start function (P2-26) may need to be
enabled.
2| Fast Ramp To Stop| The drive will ramp to stop at the rate
programmed in the 2nd deceleration time P2-25.
3| DC Bus Power Supply Mode| This mode is intended to be used
when the drive is powered directly via the +DC and –DC Bus connections. Refer
to your Bardac Sales Partner for further details.
P2-39| Parameter Access Lock| 0| 1| 0| –
0| Unlocked| All parameters can be accessed and changed.
1| Locked| Parameter values can be displayed, but cannot be
changed.
P2-40| Extended Parameter Access Code Definition| 0| 9999|
101| –
Defines the access code which must be entered in P1-14 to access parameter
groups above Group 1.
8.2. Parameter Group 3 – PID Control
8.2.1. Overview
The P2 provides an internal PID controller. Parameters for configuration of
the PID controller are located together in Group 3. For simple applications,
the user needs to only define the setpoint source (P3-05 to select the source
or P3-06 for a fixed setpoint),
feedback source (P3-10) and adjust the P Gain (P3-01), I time (P3-02) and
optionally the differential time (P3-03).
The PID operation is uni-directional, and all signals are treated as 0 – 100%
to provide a simple, intuitive operating format.
8.2.2. Parameter List
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P3-01| PID Proportional Gain| 0.1| 30.0| 1.0| –
PID Controller Proportional Gain. Higher values provide a greater change in
the drive output frequency in response to small changes in the feedback
signal. Too high a value can cause instability.
P3-02| PID Integral Time Constant| 0.0| 30.0| 1.0|
s
PID Controller Integral Time. Larger values provide a more damped response for
systems where the overall process responds slowly.
P3-03| PID Differential Time Constant| 0.00| 1.00|
0.00| s
PID Differential Time Constant.
P3-04| PID Operating Mode| 0| 1| 1| –
0| Direct Operation| Use this mode if an increase in the motor
speed should result in an increase in the feedback signal.
1| Inverse Operation| Use this mode if an increase in the motor
speed should result in a decrease in the feedback signal.
P3-05| PID Reference (Setpoint) Source Select| 0| 2|
0| –
0| PID Reference (Setpoint) Source Select| P3-06 is used.
1| Analog Input 1 Setpoint| Analog Input 1 as displayed in P0-01 is
used.
2| Analog Input 2 Setpoint| Analog Input 2 as displayed in P0-02 is
used.
P3-06| PID Digital Reference (Setpoint)| 0.0| 100.0|
0.0| %
When P3-05 = 0, this parameter sets the preset digital reference (setpoint)
used for the PID Controller. Where the feedback is provided from a transducer
such as a pressure transducer or level measurement, this represents the
percentage of the pressure range (e.g. for a 0 – 10 Bar transducer, 4 bar =
40%) or the level.
P3-07| PID Controller Output Upper Limit| P3-08| 100.0|
100.0| %
Limits the maximum value output from the PID controller.
P3-08| PID Controller Output Lower Limit| 0.0| P3-07|
0.0| %
Limits the minimum output from the PID controller.
P3-09| PID Output Limit Control| 0| 3| 0| –
0| Digital Output Limits| The output range of the PID controller is
limited by the values of P3-07 & P3-08.
1| Analog Input 1 Provides a Variable Upper Limit| The output
range of the PID controller is limited by the values of P3-08 & the signal
applied to Analog Input 1.
2| Analog Input 1 Provides a Variable Lower Limit| The output range
of the PID controller is limited by the signal applied to Analog Input 1 & the
value of P3-07.
3| PID output Added to Analog Input 1 Value| The output value from
the PID Controller is added to the speed reference applied to the Analog Input
- P3-10| PID Feedback Signal Source Select| 0| 1| 0|
–
0| Analog Input 2
1| Analog Input 1
2| Output Current
3| DC Bus Voltage
4| Differential : Analog Input 1 – Analog Input 2
5| Largest Value : Analog Input 1 or Analog Input 2
Par| Parameter Name| Minimum| Maximum| Default| Units
---|---|---|---|---|---
P3-11| Maximum PID Error to Enable Ramps| 0.0| 25.0| 0.0| %
Defines a threshold PID error level, whereby if the difference between the setpoint and feedback values is less than the set threshold, the internal ramp times of the drive are disabled. Where a greater PID error exists, the ramp times are enabled to limit the rate of change of motor speed on large PID errors, and react quickly to small errors.
Setting to 0.0 means that the drive ramps are always enabled. This parameter is intended to allow the user to disable the drive internal ramps where a fast reaction to the PID control is required, however by only disabling the ramps when a small PID error exists, the risk of possible over current or over voltage trips being generated are reduced.
P3-12| PID Feedback Value Display Scaling Factor| 0.000| 50.000| 0.000| –
Applies a scaling factor to the displayed PID feedback, allowing the user to display the actual signal level from a transducer, e.g. 0 – 10 Bar etc.
P3-13| PID Error Wake Up Level| 0.0| 100.0| 5.0| %
Sets a programmable level whereby if the drive enters standby motor whilst operating under PID control, the selected feedback signal must fall below this threshold before the drive will return to normal operation.
P3-18| PID Operation Control| 0| 1| 1| –
0| Continuous PID Operation| In this operating mode, the PID controller operates continuously, regardless of whether the drive is enabled or disabled. This can result in the output of the PID controller reaching the maximum level prior to the drive enable signal being applied.
1| PID operation on Drive Enable| In this operating mode, the PID controller only operates when the drive is enabled, and hence will always start from zero when the drive is enabled.
8.2.3. Parameter Group 4 – High Performance Motor Control Overview
Parameters relating to the motor control are located together in Group 4.
These parameters allow the user to:
- Select the motor type to match the connected motor.
- Carry out an autotune.
- Define the torque limits and setpoint source for control methods that support this (vector control methods only).
The P2 can operate with both Asynchronous Induction Motors, the type most commonly seen today, and also some synchronous motors. The sections below provide basic guidance on how to adjust the parameters to operate with the required motor type.
8.2.4. Asynchronous IM Motors
IM Motor Control Methods
IM Motors may be operated in the following modes:
-
V/F Speed Control (Default Mode)
o This mode provides the simplest control, and is suitable for a wide range of applications. -
Sensorless Vector Torque Control
o This method is suitable for specific applications only, which require the motor torque to be the primary control function, rather than speed, and should be used with extreme care only in specific applications. -
Sensorless Vector Speed Control
o This method provides increased starting torque compared to V/F mode, along with improved motor speed regulation with changing load conditions. This method is suitable for more demanding applications.
Operating in Sensorless Vector Speed Control Mode
The P2 can be programmed by the user to operate in Sensorless Vector mode,
which provides enhanced low speed torque, optimum motor speed regulation
regardless of load and accurate control of the motor torque. In most
applications, the default Voltage Vector control mode will provide adequate
performance, however if Sensorless Vector operation is required, use the
following procedure.
-
Ensure advanced parameter access is enabled by setting P1-14 = 101.
-
Enter the motor nameplate details into the relevant parameters as follows:
o P1-07 Motor Rated Voltage
o P1-08 Motor Rated Current
o P1-09 Motor Rated Frequency
o (Optional) P1-10 Motor Rated Speed (Rpm)
o P4-05 Motor Power Factor. -
Select Sensorless Vector Speed Control mode by setting P4-01 = 0.
-
Ensure that the motor is correctly connected to the drive.
-
Carry out a motor data Autotune by setting P4-02 = 1.
The Autotune will begin immediately when P4-02 is set regardless of the status
of the drive enable signal. Whilst the autotune procedure does not drive or
spin the motor, the motor shaft may still turn slightly. It is not normally
necessary to uncouple the load from the motor; however the user should ensure
that no risk arises from the possible movement of the motor shaft.
It is essential that the correct motor data is entered into the relevant drive
parameters. Incorrect parameter settings can result in poor or even dangerous
performance.
8.2.5. Synchronous Motors
Overview
The P2 provides open loop vector control of the following synchronous motor
types.
PM AC Permanent Magnet AC Motors and BLDC Brushless DC Motors
The P2 can be used to control Permanent Magnet AC or Brushless DC motors
without a feedback encoder or resolver. These motors operate synchronously,
and a vector control strategy is used to maintain correct operation. In
general, the motor can be operated
between 10% – 100% of rated speed with a correctly selected and configured
drive. Optimum control is achieved when the motor back EMF / Rated speed ratio
is >= 1V/Hz. Motors with Back EMF / Rated frequency ratio below this level may
not operate correctly, or may operate only with reduced speed range.
PM AC and BLDC motor control employs the same strategy, and the same
commissioning method is applied.
Permanent Magnet motors (including BLDC) produce an output voltage known as
the Back EMF when the shaft is rotated.
The user must ensure that the motor shaft cannot rotate at a speed where this
Back EMF exceeds the voltage limit for the drive, otherwise damage can occur.
The following parameter settings are necessary before attempting to operate the motor.
-
Ensure advanced parameter access is enabled by setting P1-14 = 101.
-
Enter the motor nameplate details into the relevant parameters as follows:
o P1-07 Back EMF at Rated Frequency / Speed (kE)
This is the voltage imposed by the magnets at the drive output terminals when the motor operates at rated frequency or speed.
Some motors may provide a value for volts per thousand RPM, and it may be necessary to calculate the correct value for P1-07.
o P1-08 Motor Rated Current.
o P1-09 Motor Rated Frequency.
o (Optional) P1-10 Motor Rated Speed (Rpm). -
Select PM Motor Speed control mode by setting P4-01 = 3 or BLDC Motor Speed Control by setting P4-01 = 5.
-
Ensure that the motor is correctly connected to the drive.
-
Carry out a motor data Autotune by setting P4-02 = 1.
o The autotune measures the electrical data required from the motor to ensure good control. -
To improve motor starting and low speed operation, the following parameters may require adjustment:
o P7-14: Low Frequency Torque Boost Current: Injects additional current into the motor to help rotor alignment at low output frequency. Set as % of P1-08.
o P7-15: Low Frequency Torque Boost Frequency Limit: Defines the frequency range where the torque boost is applied. Set as % of P1-09.
Following the steps above, it should be possible to operate the motor. Further parameter settings are possible to enhance the performance if required, please refer to your Bardac Sales Partner for more information.
8.2.6. Syn RM Synchronous Reluctance Motors
When operating with Synchronous Reluctance motors, carry out the following
steps:
-
Ensure advanced parameter access is enabled by setting P1-14 = 101.
-
Enter the motor nameplate details into the relevant parameters as follows:
o P1-07 Motor Rated Voltage.
o P1-08 Motor Rated Current.
o P1-09 Motor Rated Frequency.
o (Optional) P1-10 Motor Rated Speed (Rpm).
o P4-05 Motor Power Factor. -
Select Synchronous Reluctance Motor Control mode by setting P4-01 = 6.
-
Ensure that the motor is correctly connected to the drive.
-
Carry out a motor data Autotune by setting P4-02 = 1.
8.2.7. Group 4 Parameter Listing
Incorrect adjustment of parameters in menu group 4 can cause unexpected
behaviour of the motor and any connected machinery. It is recommended that
these parameters are only adjusted by experienced users.
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P4-01| Motor Control Mode| 0| 6| 2| –
Setting| Motor Type| Primary Control| Control
Method| Additional Information
0| IM| Speed| Vector| Speed control with Torque Limit. Torque Limit
Source selected by P4-06.
1| IM| Torque| Vector| Torque Control with Speed Limit. Torque reference
selected by P4-06. Speed Limit defined by the Speed Reference.
2| IM| Speed| V/F| V/F control for simple applications with standard IM
Motors.
3| AC PM| Speed| Vector| For speed control of AC PM motors with
Sinusoidal back EMF.
4| AC PM| Torque| Vector| For torque control of AC PM motors with
Sinusoidal back EMF.
5| BLDC| Speed| Vector| For speed control of BLDC motors with
Trapezoidal back EMF.
6| Syn RM| Speed| Vector| For speed control of Synchronous Reluctance
motors.
P4-02| Motor Parameter Auto-tune Enable| 0| 1| 0|
–
When set to 1, the drive immediately carries out a non-rotating autotune to
measure the motor parameters for optimum control and efficiency. Following
completion of the autotune, the parameter automatically returns to 0.
P4-03| Vector Speed Controller Proportional Gain| 0.1|
400.0| 25.0| %
Sets the proportional gain value for the speed controller when operating in
Vector Speed or Vector Torque motor control modes (P4-01 = 0 or 1). Higher
values provide better output frequency regulation and response. Too high a
value can cause instability or even over current trips. For applications
requiring best possible performance, the value should be adjusted to suit the
connected load by gradually increasing the value and monitoring the actual
output speed of the load until the required dynamic behaviour is achieved with
little or no overshoot where the output speed exceeds the setpoint.
In general, higher friction loads can tolerate higher values of proportional
gain, and high inertia, low friction loads may require the gain to be reduced.
P4-04| Vector Speed Controller Integral Time Constant| 0.000|
2.000| 0.050| s
Sets the integral time for the speed controller. Smaller values provide a
faster response in reaction to motor load changes, at the risk of introducing
instability. For best dynamic performance, the value should be adjusted to
suit the connected load.
P4-05| Motor Power Factor Cos Ø| 0.50| 0.99| –|
–
When operating in Vector Speed motor control modes, this parameter must be set
to the motor nameplate power factor.
Par| Parameter Name| Minimum| Maximum| Default|
Units
---|---|---|---|---|---
P4-06| Torque Control Reference / Limit Source| 0| 5|
0| –
0| Fixed Digital| The torque controller reference / limit is set in
P4-07.
1| Analog Input 1| The output torque is controlled based on the
signal applied to Analog Input 1, whereby 100% input signal level will result
in the drive output torque being limited by the value set in P4-07.
2| Analog Input 2| The output torque is controlled based on the
signal applied to Analog Input 2, whereby 100% input signal level will result
in the drive output torque being limited by the value set in P4-07.
3| Fieldbus| The output torque is controlled based on the signal
from the communications Fieldbus, whereby 100% input signal level will result
in the drive output torque being limited by the value set in P4-07.
4| Master / Slave| The output torque is controlled based on the
signal from the Master / Slave, whereby 100% input signal level will result in
the drive output torque being limited by the value set in P4-07.
5| PID Controller Output| The output torque is controlled
based on the output of the PID controller, whereby 100% input signal level
will result in the drive output torque being limited by the value set in
P4-07.
P4-07| Maximum Motoring Current Limit| P4-08| 500.0|
150.0| %
When operating in Vector Speed or Vector Torque motor control modes (P4-01 = 0
or 1), this parameter defines the maximum torque limit or reference used by
the drive in conjunction with P4-06.
When operating in V/F Mode (P4-01 = 2), this parameter defines the maximum
output current the drive will provide to the motor before reducing the output
frequency to attempt to limit the current.
P4-08| Minimum Motoring Torque Limit| P4-08| 500.0|
150.0| %
Active only in Vector Speed or Vector Torque motor control modes (P4-01 = 0 or
1). Sets a minimum torque limit, whereby the when the drive is enabled, it
will always attempt to maintain this torque on the motor at all times whilst
operating.
NOTE This parameter should be used with extreme care, as the drive output
frequency will increase to achieve the torque level, and may exceed the
selected speed reference.
P4-09| Generator Mode Max. Torque Limit (Maximum Regenerative
Torque)| 0.0| 200.0| 100.0| %
Active only in Vector Speed or Vector Torque motor control modes (P4-01 = 0 or
1). Sets the maximum regenerating torque allowed by the drive.
P4-10| V/F Characteristic Adjustment Frequency| 0.0|
P1-09| 0.0| Hz
When operating in V/F mode (P4-01 = 2), this parameter in conjunction with
P4-11 sets a frequency point at which the voltage set in P4-11 is applied to
the motor. Care must be taken to avoid overheating and damaging the motor when
using this feature.
P4-11| V/F Characteristic Adjustment Voltage| 0| P1-07|
0| V
Used in conjunction with parameter P4-10.
P4-12| Thermal Overload Value Retention| 0| 1| 0|
–
0| Disabled|
1| Enabled| All drives feature electronic thermal overload
protection for the connected motor, designed to protect the motor against
damage. An internal overload accumulator monitors the motor output current
over time, and will trip the drive if the usage exceeds the thermal limit.
When P4-12 is disabled, removing the power supply from the drive and re-
applying will reset the value of the accumulator. When P4-12 is enabled, the
value is retained during power off.
P4-13| Output Phase Sequence| 0| 1| 0| –
0| U,V,W| Stand motor phase sequence. Typically, this provides
clockwise rotation of the motor.
1| U,W,V| Reverse motor phase sequence. Typically this provides
counter-clockwise rotation of the motor.
8.3. Parameter Group 5 – Communication Parameters
8.3.1. Overview
The P2 provides many methods to allow the user to connect to a variety of
fieldbus networks. In addition, connection to options such as external
keypads, drive.web programmable conrollers, PC and Optistick are possible.
Parameter Group 5 provides the parameters required to configure the various
fieldbus interfaces and connection points.
8.3.2. Connecting Bardac drive.web Options
All Bardac drive.web options which require communication with the drive,
connect to the P2 using the built in RJ45 connection point.
The pin connections on these options are already matched, such that a simple
pin to pin plug in cable can be used to connect these options without any
special requirements.
For further information on connecting and using these optional items, refer to
the specific option User guide.
8.3.3. Connecting to a PC or Mac via Ethernet or USB
A low cost, plug-in drive.web speedy interface controller can be used to
connect a drive or drive system to a PC running the savvy tools on currently
supported versions of either Microsoft Windows or Mac OSX operating systems
with Java. The savvy tools can be used to configure connect and control a
drive or complete drive control system.
Get savvy
Download – get the free basic savvy tools from https://driveweb.com/get-
savvy/ for easy programming & networking via a speedy (model dw224) interface
to your computer USB or Ethernet port.
- Import/export configurations – edit programs – monitor – control – create trend charts – export operational data to a .csv file
- create savvyPanel operator stations for touch screens for PCs, Macs, iPad, iPhone
- network drives peer to peer over Ethernet – build complete integrated drive systems without using a PLC or SCADA
- Add smarty automation controllers for full featured featured programmable control and remote i/o
- Upgrade savvy to the savvy-SFD, Signal Flow Diagram version for easy systems design with drag and drop connections
- Add smart function blocks for advanced control, winders, encoder position, motion, indexing, registration, solar tracking & more
Get Training
Get free online training for drive configuration and drive system design –
contact training@bardac.com
8.3.4. Modbus RTU Connection
The P2 supports Modbus RTU communication. Connection is made through the RJ45
connector. For further information refer to section
9.2. Modbus RTU Communications on page 61.
8.3.5. CAN Open Connection
The P2 supports CAN Open communication. Connection is made through the RJ45
connector. For further information refer to section
9.3. CAN Open Communication on page 63.
8.3.6. Other Fieldbus Networks
Additional fieldbus network protocols are supported using optional interfaces.
Call Bardac (USA 410-604-3400) or refer
to the Bardac.com website for a list of supported protocols and the required
interface option modules.
8.3.7. Communication Parameters
Par | Name | Minimum | Maximum | Default | Units |
---|---|---|---|---|---|
P5-01 | Drive Fieldbus Address | 0 | 63 | 1 | – |
Sets the Fieldbus address for the drive.
P5-02| CAN Baud Rate| 125| 1000| 500| kbps
Sets the baud rate when CAN Open communications are used.
P5-03| Modbus RTU Baud rate| 9.6| 115.2| 115.2|
kbps
Sets the baud rate when Modbus RTU communications are used.
P5-04| Modbus RTU| –| –| –| –
Sets the expected Modbus telegram data format as follows:
| No Parity, 1 stop bit
| No parity, 2 stop bits
| Odd parity, 1 stop bit
| Even parity, 1 stop bit
Par| Name| Minimum| Maximum| Default| Units
---|---|---|---|---|---
P5-05| Communications Loss Timeout| 0.0| 5.0| 2.0|
Seconds
Sets the watchdog time period for the communications channel. If a valid
telegram is not received by the drive within this time period, the drive will
assume a loss of communications has occurred and react as selected below.
Setting to zero disables the function.
P5-06| Communications Loss Action| 0| 3| 0| –
0| Trip & Coast To Stop
1| Ramp to Stop Then Trip
2| Ramp to Stop Only (No Trip)
3| Run at Preset Speed 8
P5-07| Fieldbus Ramp Control| 0| 1| 0| –
0| Disabled| Ramps are control from internal drive parameters P1-03
and P1-04.
1| Enabled| Ramps are controlled directly by the Fieldbus PDI4 Data
Word.
P5-08| Fieldbus Process Data Output Word 4 Select| 0| 4|
0| –
0| Output Torque| 0 to 2000 = 0 to 200.0%
1| Output Power| Output power in kW to two decimal places, e.g.
400 = 4.00kW
2| Digital Input Status| Bit 0 indicates digital input 1 status,
bit 1 indicates digital input 2 status etc
3| Analog Input 2 Signal Level| 0 to 1000 = 0 to 100.0%
4| Drive Heatsink Temperature| 0 to 100 = 0 to 100°C
P5-12| Fieldbus Process Data Output Word 3 Select| 0| 7|
0| –
0| Motor current| Output current to 1 decimal place, e.g. 100 =
10.0 Amps
1| Power (x.xx kW)| Output power in kW to two decimal places, e.g.
400 = 4.00kW
2| Digital input status| Bit 0 indicates digital input 1 status,
bit 1 indicates digital input 2 status etc
3| Analog Input 2 Signal Level| 0 to 1000 = 0 to 100.0%
4| Drive Heatsink Temperature| 0 to 100 = 0 to 100°C
5| User register 1| User Defined Register 1 Value
6| User register 2| User Defined Register 1 Value
7| P0-80 value| User Selected data value
P5-13| Fieldbus Ramp Control| 0| 1| 0| –
0| Fieldbus PDI 4 Function| This option must be selected if the
drive acceleration and deceleration ramps are to be controlled from the
fieldbus. P5-07 must also be set to 1 to enable this function.
1| User register 4| The value received by the drive in PDI 4 is
transferred to User Register 4. This option allows the function of the process
data word to be defined in Parameter Group 9. In this case, User Register 4
should not be written to within any PLC function code, although the value can
be read.
P5-14| Fieldbus Process Data Input Word 3 Select| 0| 2|
0| –
0| Torque limit/reference| This option must be selected if the
drive output torque limit / setpoint is to be controlled from the fieldbus.
This also requires setting P4-06 = 3.
1| User PID reference register| This option allows the setpoint to
the PID controller to be received from the Fieldbus. In order for this option
to be used, P9-38 must be set to 1, and the PID User setpoint must not be
utilised within the PLC function.
2| User register 3| The value received by the drive in PDI 3 is
transferred to User Register 3. This option allows the function of the process
data word to be defined in Parameter Group 9. In this case, User Register 3
should not be written to within any PLC function code, although the value can
be read.
P5-15| Modbus Response Delay| 0| 16| 0| Chr
Allows the user to configure an additional delay between the drive receiving a
request via the Modbus RTU interface, and transmitting a reply. The value
entered represents the delay in addition to the minimum delay permissible
according to the Modbus RTU specification, and is expressed as the number of
additional characters.
8.4. Advanced Parameters
For Advanced Parameters, basic information only is provided in this guide.
Contact Bardac at USA 410-604-3400 for
further information.
8.4.1. Parameter Group 6 – Advanced Configuration
Par. | Function | Setting Range | Default | Notes |
---|---|---|---|---|
P6-01 | Enable Firmware Upgrade | 0 | Disabled | 0 |
not be adjusted by the user.
1| I/O and DSP Upgrade
2| I/O Upgrade
3| DSP Upgrade
P6-02| Minimum Effective Switching Frequency| 4 – 32kHz (Model
Dependent)| 4 kHz|
P6-03| Auto Reset Time Delay| 1 – 60 Seconds| 20s|
P6-04| Relay Output Hysteresis| 0.0 – 25.0%| 0.3%|
P6-05| Encoder Feedback Enable| 0| Disabled| 0|
1| Enabled
P6-06| Encoder PPR| 0 – 65535| 0|
P6-07| Speed Error Trip Threshold| 0.0 – 100.0%| 5.0%|
P6-08| Maximum Speed Reference Frequency| 0 – 20kHz| 0 kHz|
P6-09| Speed Droop Control| 0.0 – 25.0%| 0.0%|
P6-10| Function Block Program Enable| 0| Disabled| 0|
1| Enabled
P6-11| Speed Hold Time on Enable| 0 – 250s| 0s|
P6-12| Speed Hold / DC Injection Time on Disable| 0 – 250s| 0s|
P6-13| Hoist Mode : Brake Release Time| 0.0 – 5.0s| 0.2s|
P6-14| Hoist Mode : Brake Apply Time| 0.0 – 5.0s| 0.3s|
P6-15| Hoist Mode : Pre-Torque Level| 0.0 – 200.0%| 8.0%|
P6-16| Hoist Mode : Pre-Torque Timeout| 0.0 – 25.0s| 5.0s|
P6-17| Torque Limit Trip Time| 0.0 – 25.0s| 0.0s|
P6-18| DC Injection Current| 0.0 – 100.0%| 0.0%|
P6-19| Brake Resistor Resistance| Model Dependent|
P6-20| Brake Resistor Power| Model Dependent|
P6-21| Brake Chopper Under Temperature Duty Cycle| 0.0 – 20.0%| 2.0%|
P6-22| Reset Fan Run Time| 0| No Reset| 0|
1| Reset
P6-23| Reset Energy Meters| 0| No Reset| 0|
1| Reset
P6-24| Maintenance Time Interval| 0 – 60000 Hours| 0 Hours|
P6-25| Reset Maintenance Time| 0| No Reset| 0|
1| Reset
P6-26| Analog Output 1 Scaling| 0.0 – 500.0%| 100.0%|
P6-27| Analog Output 1 Offset| -500.0 – 500.0%| 0.0%|
P6-28| P0-80 Display Value| 0 – 255| 0|
P6-29| Save User Parameters| 0| No Function| 0|
1| Save Parameters
2| Clear Parameters
P6-30| Advanced Access Code| 0 – 9999| 201|
8.4.2. Parameter Group 7 – Motor Control
Par. | Function | Setting Range | Default | Notes |
---|---|---|---|---|
P7-01 | MeasuredMotor Stator Resistance | 0.000 – 65.535 | Drive Dependent |
Motor date, measured or calculated curing the autotune.
P7-04 is not used for PM & BLDC Motors. P7-06 is used only for PM motors.
P7-02| Motor Rotor Resistance| 0.000 – 65.535
P7-03| Motor Stator Inductance| 0.0000 – 1.0000
P7-04| Motor Magnetising Current| Drive Dependent
P7-05| Motor Leakage Coefficient (Sigma)| 0.000 – 0.250
P7-06| Motor Q Axis Inuctance (Lsq)| 0.0000 – 1.0000
P7-07| Enhanced Generator Mode| 0| Disable| 0| Improves motor control in
applications with high regenerative power requirement.
1| Enable
P7-08| Motor Parameter Adaptation| 0| Disabled| 0| Enables motor
parameter adaptation, intended to compensate for changes in the motor
temperature during operation.
1| Enable
P7-09| Over Voltage Current Limit| 0.0 – 100.0%| 5.0%|
P7-10| System Inertia Constant| 0 – 600| 10|
P7-11| Pulse Width Minimum Limit| 0 – 500| |
P7-12| Magnetising Period| 0 – 5000ms| Drive Dependent| Sets the motor
magnetising period in V/F Mode. Sets the motor alignment time in PM modes.
P7-13| Vector Mode Derivative| 0.00 – 1.00| 0.00| Derivative speed loop
gain applied in Vector control modes.
P7-14| Low Frequency Torque Boost Current| 0.0 – 100.0%| 0.0%| For PM
Motors, applies a torque boost current at low frequency, % x P1-08.
P7-15| Low Frequency Torque Boost Frequency Limit| 0.0 – 50.0%| 0.0%|
For PM motors, determines the frequency, % x P1-09 when the boost current is
removed.
8.4.3. Parameter Group 8 – Additional Ramps and Functions
Par. | Function | Setting Range | Default | Notes |
---|---|---|---|---|
P8-01 | Acceleration Ramp 2 | 0.00 – 600.0 / 0.0 – 6000.0s | 5.0s | |
P8-02 | Speed Boundary Ramp 1 ⭢ Ramp 2 | 0.0 – P1-01 Hz / Rpm | 0.0 | |
P8-03 | Acceleration Ramp 3 | 0.00 – 600.0 / 0.0 – 6000.0s | 5.0s | |
P8-04 | Speed Boundary Ramp 2 ⭢ Ramp 3 | 0.0 – P1-01 Hz / Rpm | 0.0 | |
P8-05 | Acceleration Ramp 4 | 0.00 – 600.0 / 0.0 – 6000.0s | 5.0s | |
P8-06 | Speed Boundary Ramp 3 ⭢ Ramp 4 | 0.0 – P1-01 Hz / Rpm | 0.0 | |
P8-07 | Deceleration Ramp 4 | 0.00 – 600.0 / 0.0 – 6000.0s | 5.0s | |
P8-08 | Speed Boundary Ramp 4 ⭢ Ramp 3 | 0.0 – P1-01 Hz / Rpm | 0.0 | |
P8-09 | Deceleration Ramp 3 | 0.00 – 600.0 / 0.0 – 6000.0s | 5.0s | |
P8-10 | Speed Boundary Ramp 3 ⭢ Ramp 2 | 0.0 – P1-01 Hz / Rpm | 0.0 | |
P8-11 | Deceleration Ramp 2 | 0.00 – 600.0 / 0.0 – 6000.0s | 5.0s | |
P8-12 | Speed Boundary Ramp 2 ⭢ Ramp 1 | 0.0 – P1-01 Hz / Rpm | 0.0 | |
P8-13 | Ramp Select Control | 0 | Digital Inputs | 0 |
1 | Speed Dependent |
8.4.4. Parameter Group 9 – User Inputs and Output Programming
Par. | Function | Setting Range | Default | Notes |
---|---|---|---|---|
P9-01 | Enable Input Source | These parameters allow the user to directly |
select the source of the various command points. Parameters are only
adjustable if P1-13 = 0. This allows complete fiexibility over the drive
control functions, and interaction with the internal Function Block
programming environment.
P9-02| Fast Stop Source
P9-03| Run Forward Source
P9-04| Run Reverse Source
P9-05| Latch Enable| 0| Disabled| 0|
1| Enabled
P9-06| Reverse Input Source| See above
P9-07| Reset Source
P9-08| External Trip Source
P9-09| Terminal Control Override Source
P9-10| Speed Setpoint 1| In combination with P9-18 – P9-20, allow
selection of several speed reference sources for common applications.
P9-11| Speed Setpoint 2
P9-12| Speed Setpoint 3
P9-13| Speed Setpoint 4
P9-14| Speed Setpoint 5
P9-15| Speed setpoint 6
P9-16| Speed Setpoint 7
P9-17| Speed Setpoint 8
P9-18| Reference Select Bit 0| See above
P9-19| Reference Select Bit 1
P9-20| Reference Select Bit 2
P9-21| Preset Speed Select Bit 0
P9-22| Preset Speed Select Bit 1
P9-23| Preset Speed Select Bit 2
P9-24| Acceleration Ramp Select Bit 0
P9-25| Acceleration Ramp Select Bit 1
P9-26| Deceleration Ramp Bit 0
P9-27| Deceleration Ramp Bit 1
P9-28| MOP Up Source
P9-29| MOP Down Source
P9-30| Speed Limit Switch Forward
P9-31| Speed Limit Switch Reverse
P9-33| Analog Output 1 Control| 0| P2-11| 0| These parameters allow the
user to overdide the normal parameter control source for the associated
function, allowing interaction with the internal Function Block programming
environment.
1| Function Block Digital
2| Function Block Analog
P9-34| Analog Output 2 Control| 0| P2-13| 0
1| Function Block Digital
2| Function Block Analog
P9-35| Relay 1 Control| 0| P2-15| 0
1| Function Block Digital
P9-36| Relay 2 Control| 0| P2-18| 0
1| Function Block Digital
P9-37| Display Scaling Control| 0| P2-21| 0
1| Function Block Digital
P9-38| PID Setpoint Control| 0| P3-05| 0
1| Function Block Digital
P9-39| PID Feedback Control| 0| P3-10| 0
1| Function Block Digital
P9-40| Torque Reference Control| 0| P4-06| 0
1| Function Block Digital
P9-41| Relay 3, 4 and 5 Control| 0| Default Settings| 0
1| Function Block Digital
8.5. Parameter Group 0 – Monitoring Parameters (Read Only)
Par. | Function | Units |
---|---|---|
P0-01 | Analog Input 1 Scaled Signal Level | % |
P0-02 | Analog Input 2 Scaled Signal Level | % |
P0-03 | Digital Input Status – Bit representation (0 or 1) where the left | |
most digit indicates the status of Digital Input 1 | N/A | |
P0-04 | Pre-Ramp Speed Reference | Hz / RPM |
P0-05 | Torque Reference / Limit | % |
P0-06 | Digital (Keypad) Speed Reference | Hz / RPM |
P0-07 | Fieldbus Speed Reference | Hz / RPM |
P0-08 | PID Reference (Setpoint) | % |
P0-09 | PID Feedback | % |
P0-10 | PID Output | % |
P0-11 | Applied Motor Voltage | V |
P0-12 | Output Torque | % |
P0-13 | Trip Log – Last 4 Trips | N/A |
P0-14 | Motor Magnetising Current Id | A |
P0-15 | Motor Rotor Current Iq | A |
P0-16 | DC Voltage Ripple | V |
P0-17 | Motor Stator Resistance Rs | Ω |
P0-18 | Motor Stator Inductance Ls | H |
P0-19 | Motor Rotor Resistance Rr | Ω |
P0-20 | DC Bus Voltage | V |
P0-21 | Drive Temperature | °C |
P0-22 | Remaining Service Time | Hours |
P0-23 | Operating Time Heatsink > 85°C | HH:MM:SS |
P0-24 | Operating Time High Ambient Temperature | HH:MM:SS |
P0-25 | Rotor Speed | Hz / RPM |
P0-26 | Energy consumption kWh | kWh |
P0-27 | Energy Consumption MWh | MWh |
P0-28 | Drive firmware version | N/A |
P0-29 | Drive Type | N/A |
P0-30 | Drive serial number | N/A |
P0-31 | Total Run Time | HH:MM:SS |
P0-32 | Run time since last trip 1 | HH:MM:SS |
P0-33 | Run time since last trip | HH:MM:SS |
P0-34 | Last operating time | HH:MM:SS |
P0-35 | Cooling fan operating time | Hours |
P0-36 | DC Bus Voltage Log: 8 samples, 256ms | V |
P0-37 | DC Bus Ripple Log: 8 samples 20ms | V |
P0-38 | Heatsink Temperature Log: 8 samples, 30s | °C |
P0-39 | Ambient temperature log: 8 samples, 30s | °C |
P0-40 | Motor Current Log: 8 samples 256ms | A |
P0-41 | Over current trip count | N/A |
P0-42 | Over voltage trip count | N/A |
P0-43 | Under voltage trip count | N/A |
P0-44 | Over temperature trip count | N/A |
P0-45 | Brake resistor over current trip count | N/A |
Par. | Function | Units |
--- | --- | --- |
P0-46 | Ambient over temperature trip count | N/A |
P0-47 | I/O processor error count | N/A |
P0-48 | DSP error count | N/A |
P0-49 | Modbus RTU error count | N/A |
P0-50 | CAN error count | N/A |
P0-51 | PDI cyclic data | N/A |
P0-52 | PDO cyclic data | N/A |
P0-53 | U phase offset and reference | N/A |
P0-54 | V phase offset and reference | N/A |
P0-55 | Reserved | N/A |
P0-56 | Brake transistor maximum on time and duty | N/A |
P0-57 | Ud / Uq | N/A |
P0-58 | Encoder speed value | Hz / RPM |
P0-59 | Frequency input reference | Hz / RPM |
P0-60 | Calculated slip | Hz / RPM |
P0-61 | Relay Hysteresis value | Hz / RPM |
P0-62 | Droop speed | Hz / RPM |
P0-63 | Post ramp speed reference | Hz / RPM |
P0-64 | Effective switching frequency | kHz |
P0-65 | Drive life time | HH:MM:SS |
P0-66 | Function block program ID | N/A |
P0-67 | Fieldbus torque reference | % |
P0-68 | User ramp value | S |
P0-69 | I2C error count | N/A |
P0-70 | Option module type | N/A |
P0-71 | Fieldbus interface type | N/A |
P0-72 | Ambient temperature | C |
P0-73 | 24 hour timer | Minute |
P0-74 | L1 – L2 input voltage | V |
P0-75 | L2 – L3 input voltage | V |
P0-76 | L3 – L1 input voltage | V |
P0-77 | Test parameter | N/A |
P0-78 | Test parameter | N/A |
P0-79 | Motor control & DSP version | N/A |
P0-80 | User specified internal value (P6-28) | N/A |
Serial Communications
9.1. RJ45 Connector Pin Assignment
The P2 drive has an RJ45 connector on the front of the control panel. This
connector allows the user to set up a drive network via a
wired connection. The connector contains multiple interfaces for different
communication protocols:
- Optibus Protocol – Used for PC and peripheral connection only
- Modbus RTU
- CANBus
The Optibus connection is always available, and can be used simultaneously
with other interfaces, however only one other interface may be used, e.g. If
Modbus RTU is in use, CAN is disabled. If a Fieldbus Option Module (E.g.
Profibus) is inserted into the drive, both Modbus and CAN are disabled.
The electrical signal arrangement of the RJ45 connector is shown as follows:
9.2. Modbus RTU Communications
9.2.1. Modbus Telegram Structure
The P2 drive supports Master / Slave Modbus RTU communications, using the 03
Read Holding Registers and 06 Write Single Holding Register commands. Many
Master devices treat the first Register address as Register 0; therefore it
may be necessary to convert the Register Numbers detail in section 0 by
subtracting 1 to obtain the correct Register address. The telegram structure
is as follows:
Command 03 – Read Holding Registers
Master Telegram| Length| | Slave Response| Length
Slave Address| 1| Byte| Slave Address| 1| Byte
Function Code (03)| 1| Byte| Function Code (03)| 1| Byte
1st Register Address| 2| Bytes| Byte Count| 1| Byte
No. Of Registers| 2| Bytes| 1st Register Value| 2| Bytes
CRC Checksum| 2| Bytes| 2nd Register Value| 2| Bytes
| Etc…| |
CRC Checksum| 2| Bytes
Command 06 – Write Single Holding Register
Master Telegram| Length| | Slave Response| Length
Slave Address| 1| Byte| Slave Address| 1| Byte
Function Code (06)| 1| Byte| Function Code (06)| 1| Byte
Register Address| 2| Bytes| Register Address| 2| Bytes
Value| 2| Bytes| Register Value| 2| Bytes
CRC Checksum| 2| Bytes| CRC Checksum| 2| Bytes
9.2.2. Modbus Control & Monitoring Registers
The following is a list of accessible Modbus Registers available in the P2
drive.
-
When Modbus RTU is configured as the Fieldbus option, all of the listed registers can be accessed.
-
Registers 1 and 2 can be used to control the drive providing that Modbus RTU is selected as the primary command source (P1-12 = 4) and no Fieldbus Option Module is installed in the drive Option Slot.
-
Register 3 can be used to control the output torque level providing that:
o The drive is operating in Vector Speed or Vector Torque motor control modes (P4-01 = 1 or 2).
o The torque controller reference / limit is set for ‘Fieldbus’ (P4-06 = 3). -
Register 4 can be used to control the acceleration and deceleration rate of the drive providing that Fieldbus Ramp Control is enabled (P5-07 = 1).
-
Registers 6 to 24 can be read regardless of the setting of P1-12.
Register Number| Upper Byte| Lower Byte| Read
Write| Notes
---|---|---|---|---
1| Command Control Word| R/W| Command control word used to control the drive
when operating with Modbus RTU. The Control Word bit functions are as follows:
Bit 0 : Run/Stop command. Set to 1 to enable the drive. Set to 0 to stop the
drive. Bit 1 : Fast stop request. Set to 1 to enable drive to stop with 2nd
deceleration ramp. Bit 2 : Reset request. Set to 1 in order to reset any
active faults or trips on the drive. This bit must be reset to zero once the
fault has been cleared.
Bit 3 : Coast stop request. Set to 1 to issue a coast stop command.
2| Command Speed Reference| R/W| Setpoint must be sent to the drive in Hz to
one decimal place, e.g. 500 = 50.0Hz.
3| Command Torque Reference| R/W| Setpoint must be sent to the drive in % to
one decimal place, e.g. 2000 = 200.0%.
4| Command Ramp times| R/W| This register specifies the drive acceleration and
deceleration ramp times used when Fieldbus Ramp Control is selected (P5-08 =
- irrespective of the setting of P1-12. The input data range is from 0 to
60000 (0.00s to 600.00s).
6| Error code| Drive status| R| This register contains 2 bytes.
The Lower Byte contains an 8 bit drive status word as follows:
Bit 0 : 0 = Drive Disabled (Stopped), 1 = Drive Enabled (Running). Bit 1 : 0 = Drive Healthy, 1 = Drive Tripped.
Bit 2 : No Function.
Bit 3 : Drive Ready, 1 = Drive Inhibit.
Bit 4 : Maintenance Time Not Reached, 1 = Maintenance Time Reached. Bit 5 : 0 = Not In Standby (Sleep), 1 = Standby (Sleep) mode active.
Bit 6 : No function.
Bit 7 : 0 = Normal condition, 1 = Low or High Load condition detected.
The Upper Byte will contain the relevant fault number in the event of a drive trip.
Refer to section 11.1. Fault Messages for a list of fault codes and diagnostic information.
Bit 8 : No Function.
The Upper Byte will contain the relevant fault number in the event of a drive trip.
Refer to section 11.1. Fault Messages for a list of fault codes and diagnostic information.
7| Output Frequency| R| Output frequency of the drive to one decimal place, e.g.123 = 12.3 Hz.
8| Output Current| R| Output current of the drive to one decimal place, e.g.105 = 10.5 Amps.
9| Output Torque| R| Motor output torque level to one decimal place, e.g. 474 = 47.4 %.
10| Output Power| R| Output power of the drive to two decimal places, e.g.1100 = 11.00 kW.
11| Digital Input Status| R| Represents the status of the drive inputs where Bit 0 = Digital Input 1 etc.
20| Analog 1 Level| R| Analog Input 1 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0%.
21| Analog 2 Level| R| Analog Input 2 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0%.
22| Pre Ramp Speed Reference| R| Internal drive frequency setpoint.
23| DC bus voltages| R| Measured DC Bus Voltage in Volts.
24| Drive temperature| R| Measured Heatsink Temperature in °C.
9.2.3. Modbus Parameter Access
All User Adjustable parameters (Groups 1 to 5) are accessible by Modbus,
except those that would directly affect the Modbus communications, e.g.
- P5-01 Drive Fieldbus Address
- P5-03 Modbus RTU Baud Rate
- P5-04 Modbus RTU Data Format.
All parameter values can be read from the drive and written to, depending on
the operating mode of the drive – some parameters cannot be changed whilst the
drive is enabled for example.
When accessing a drive parameter via Modbus, the Register number for the
parameter is the same as the parameter number. Some parameters are internally
scaled, for further information refer to the P2 drive Modbus Register Map
Application Note, or Advanced User Guide.
E.g. Parameter P1-03 = Modbus Holding Register 103.
Since Modbus RTU supports sixteen bit integer values only, and the parameter
is adjustable to one decimal place, the register value will be multiplied by a
factor of ten, E.g. Read Value of P1-03 = 50, therefore this is 5.0 seconds.
9.3. CAN Open Communication
9.3.1. Overview
The CANopen communication profile in the P2 drive is implemented according to
the specification DS301 version 4.02 of CAN in automation (www.can-
cia.de). Specific device profiles such as DS402 are
not supported.
9.3.2. Basic Operation Setup
The CANopen communication function is enabled by default after power up
however in order to use any control functions through CANopen, Parameter P1-12
must be set to 6.
The CAN communication baud rate can is selected by parameter P5-02. Available
baud rates are 125kbps, 250kbps, 500kbps, 1Mbps. Default settings is 500kbps.
The Node ID is set up through drive address parameter P5-01 with a default
value of 1.
9.3.3. COB ID and Functions
The P2 drive provides the following default COB-ID and functions:
Table 1 : Messages and COB-IDs
Type| COB-ID| Function
NMT| 000h| Network management.
Sync| 080h| Synchronous message.
COB-ID can be configured to other value.
Emergency| 080h + Node address| Emergency message.
COB-ID can be configured to other value.
PDO1 (TX)| 180h + Node address| Process data object.
PDO1 is pre-mapped and enabled by default. PDO2 is pre-mapped and disabled by
default.
Transmission mode, COB-ID and mapping can be configured.
PDO1 (RX)| 200h + Node address
PDO2 (TX)| 280h + Node address
PDO2 (RX)| 300h + Node address
SDO (TX)| 580h + Node address| SDO channel can be used for drive parameter
access.
SDO (RX)| 600h + Node address
Error Control| 700h + Node address| Guarding and Heartbeat function are
supported. COB-ID can be configured to other value.
NOTE
-
The P2 SDO channel only supports expedited transmission.
-
The P2 can only support up to 2 Process Data Objects (PDO). All PDOs are pre-mapped, however PDO2 is disabled by default.
Table 2 gives the default PDO mapping information. -
Customer configuration (mapping) will NOT be saved during power down. This means that the CANopen configuration will restore to its default condition each time the drive is powered up.
9.3.4. Default PDO Mapping
Table 2: PDO Default Mapping
Type| Objects No.| Mapped Object| Length| Mapped
Function| Transmission
RX PDO 1| 1| 2000h| Unsigned 16| Control command register| 254 Valid
immediately
2| 2001h| Integer 16| Speed reference
3| 2002h| Integer 16| Torque reference
4| 2003h| Unsigned 16| User ramp reference
TX PDO1| 1| 200Ah| Unsigned 16| Drive status register| 254 Send after
receiving RX PDO1
2| 200Bh| Integer 16| Motor speed Hz
3| 200Dh| Unsigned 16| Motor current
4| 200Eh| Integer 16| Motor torque
SDO (RX) Error Control| 1| 0006h| Unsigned 16| Dummy| 254
2| 0006h| Unsigned 16| Dummy
3| 0006h| Unsigned 16| Dummy
4| 0006h| Unsigned 16| Dummy
TX PDO2| 1| 200Fh| Unsigned 16| Motor power| 254
2| 2010h| Integer 16| Drive temperature
3| 2011h| Unsigned 16| DC bus value
4| 200Ch| Integer 16| Motor speed (Internal data format)
- Drive control can only be achieved when P1-12=6
9.3.5. Supported PDO Transmission Types
Various transmission modes can be selected for each PDO.
For RX PDO, the following modes are supported:
Table 3: RX PDO Transmission Mode
Transmission Type| Mode| Description
0 – 240| Synchronous| The received data will be transferred to the drive
active control register when the next sync message is received.
254, 255| Asynchronous| The received data will be transferred to the drive
active control register immediately without delay.
For TX PDO, the following modes are supported:
Table 4: TX PDO Transmission Mode
Transmission Type| Mode| Description
0| Acyclic synchronous| TX PDO will only be sent out if the PDO data has
changed and PDO will be transmitted on reception of SYNC object.
1 – 240| Cyclic synchronous| TX PDO will be transmitted synchronously and
cyclically. The transmission type indicates the number of SYNC object that are
necessary to trigger TX PDO.
254| Asynchronous| TX PDO will only be transferred once corresponding RX PDO
has been received.
255| Asynchronous| TX PDO will only be transferred anytime if PDO data value
has changed.
9.3.6. CAN Open Specific Object Table
Index| Sub index| Function| Access| Type| PDO
Map| Default value
---|---|---|---|---|---|---
1000h| 0| Device type| RO| Unsigned 32| N| 0
1001h| 0| Error register| RO| Unsigned 8| N| 0
1002h| 0| Manufacturer status register| RO| Unsigned 16| N| 0
1005h| 0| COB-ID Sync| RW| Unsigned 32| N| 00000080h
1008h| 0| Manufacturer device name| RO| String| N| ODP2
1009h| 0| Manufacturer hardware version| RO| String| N| x.xx
100Ah| 0| Manufacturer software version| RO| String| N| x.xx
100Ch| 0| Guard time [1ms]| RW| Unsigned 16| N| 0
100Dh| 0| Life time factor| RW| Unsigned 8| N| 0
1014h| 0| COB-ID EMCY| RW| Unsigned 32| N| 00000080h+Node ID
1015h| 0| Inhibit time emergency [100us]| RW| Unsigned 16| N| 0
1017h| 0| Producer heart beat time [1ms]| RW| Unsigned 16| N| 0
1018h| 0| Identity object No. of entries| RO| Unsigned 8| N| 4
1| Vendor ID| RO| Unsigned 32| N| 0x0000031A
2| Product code| RO| Unsigned 32| N| Drive depended
3| Revision number| RO| Unsigned 32| N| x.xx
4| Serial number| RO| Unsigned 32| N| e.g. 1234/56/789
1200h| 0| SDO parameter No. of entries| RO| Unsigned 8| N| 2
1| COB-ID client -> server (RX)| RO| Unsigned 32| N| 00000600h+Node ID
2| COB-ID server -> client (TX)| RO| Unsigned 32| N| 00000580h+Node ID
1400h| 0| RX PDO1 comms param No. of entries| RO| Unsigned 8| N| 2
1| RX PDO1 COB-ID| RW| Unsigned 32| N| 40000200h+Node ID
2| RX PDO1 transmission type| RW| Unsigned 8| N| 254
1401h| 0| RX PDO2 comms param No. of entries| RO| Unsigned 8| N| 2
1| RX PDO2 COB-ID| RW| Unsigned 32| N| C0000300h+Node ID
2| RX PDO2 transmission type| RW| Unsigned 8| N| 0
1600h| 0| RX PDO1 mapping / No. of entries| RW| Unsigned 8| N| 4
1| RX PDO1 1st mapped object| RW| Unsigned 32| N| 20000010h
2| RX PDO1 2nd mapped object| RW| Unsigned 32| N| 20010010h
3| RX PDO1 3rd mapped object| RW| Unsigned 32| N| 20020010h
4| RX PDO1 4th mapped object| RW| Unsigned 32| N| 20030010h
1601h| 0| RX PDO2 mapping / No. of entries| RW| Unsigned 8| N| 4
1| RX PDO2 1st mapped object| RW| Unsigned 32| N| 00060010h
2| RX PDO2 2nd mapped object| RW| Unsigned 32| N| 00060010h
3| RX PDO2 3rd mapped object| RW| Unsigned 32| N| 00060010h
4| RX PDO2 4th mapped object| RW| Unsigned 32| N| 00060010h
1800h| 0| TX PDO1 comms param No. of entries| RO| Unsigned 8| N| 3
1| TX PDO1 COB-ID| RW| Unsigned 32| N| 40000180h+Node ID
2| TX PDO1 transmission type| RW| Unsigned 8| N| 254
3| TX PDO1 Inhibit time [100us]| RW| Unsigned 16| N| 0
1801h| 0| TX PDO2 comms param No. of entries| RO| Unsigned 8| N| 3
1| TX PDO2 COB-ID| RW| Unsigned 32| N| C0000280h+Node ID
2| TX PDO2 transmission type| RW| Unsigned 8| N| 0
3| TX PDO2 Inhibit time [100us]| RW| Unsigned 16| N| 0
Index| Sub index| Function| Access| Type| PDO
Map| Default value
---|---|---|---|---|---|---
1A00h| 0| TX PDO1 mapping / No. of entries| RW| Unsigned 8| N| 4
1| TX PDO1 1st mapped object| RW| Unsigned 32| N| 200A0010h
2| TX PDO1 2nd mapped object| RW| Unsigned 32| N| 200B0010h
3| TX PDO1 3rd mapped object| RW| Unsigned 32| N| 200D0010h
4| TX PDO1 4th mapped object| RW| Unsigned 32| N| 200E0010h
1A01h| 0| TX PDO2 mapping / No. of entries| RW| Unsigned 8| N| 4
1| TX PDO2 1st mapped object| RW| Unsigned 32| N| 200F0010h
2| TX PDO2 2nd mapped object| RW| Unsigned 32| N| 20100010h
3| TX PDO2 3rd mapped object| RW| Unsigned 32| N| 20110010h
4| TX PDO2 4th mapped object| RW| Unsigned 32| N| 200C0010h
9.3.7. Manufacturer Specific Object Table
The following table shows some of the manufacturer specific object dictionary
for the P2. For a complete list, refer to the P2 CAN Open Application Note.
Index| Sub index| Function| Access| Type| PDO
Map| Remark
---|---|---|---|---|---|---
2000h| 0| Control command register| RW| Unsigned 16| Y| See Note Below
2001h| 0| Speed reference| RW| Integer 16| Y| 500 = 50.0Hz
2002h| 0| Torque reference| RW| Integer 16| Y| 1000 = 100.0%
2003h| 0| User ramp reference| RW| Unsigned 16| Y| 500 = 5.00s
200Ah| 0| Drive status register| RO| Unsigned 16| Y| See Note Below
200Bh| 0| Motor speed Hz| RO| Unsigned 16| Y| 500 = 50.0Hz
200Dh| 0| Motor current| RO| Unsigned 16| Y| 123 = 12.3A
200Eh| 0| Motor torque| RO| Integer 16| Y| 4096 = 100.0%
200Fh| 0| Motor power| RO| Unsigned 16| Y| 1234 = 12.34kW
2010h| 0| Drive temperature| RO| Integer 16| Y| 30 = 30°C
2011h| 0| DC bus value| RO| Unsigned 16| Y|
2012h| 0| Digital input status| RO| Unsigned 16| Y|
2013h| 0| Analog input 1 (percentage)| RO| Unsigned 16| Y|
2014h| 0| Analog input 2 (percentage)| RO| Unsigned 16| Y|
2015h| 0| Analog output 1| RO| Unsigned 16| Y|
2016h| 0| Analog output 2| RO| Unsigned 16| Y|
2017h| 0| relay output 1| RO| Unsigned 16| Y|
2018h| 0| relay output 2| RO| Unsigned 16| Y|
2019h| 0| relay output 3 (extension card)| RO| Unsigned 16| Y|
201Ah| 0| relay output 4 (extension card)| RO| Unsigned 16| Y|
201Bh| 0| relay output 5 (extension card)| RO| Unsigned 16| Y|
203Ah| 0| Kilowatt hours (Can be reset by user)| RO| Unsigned 16| Y|
203Bh| 0| Megawatt hours (Can be reset by user)| RO| Unsigned 16| Y|
203Ch| 0| KWh meter| RO| Unsigned 16| Y|
203Dh| 0| MWh meter| RO| Unsigned 16| Y|
203Eh| 0| Total run hours| RO| Unsigned 16| Y|
203Fh| 0| Total run minute/second| RO| Unsigned 16| Y|
2040h| 0| Current run hours (Since last enable)| RO| Unsigned 16| Y|
2041h| 0| Current run minute/second| RO| Unsigned 16| Y|
2042h| 0| Time to next service| RO| Unsigned 16| Y|
2043h| 0| Room Temperature| RO| Unsigned 16| Y|
2044h| 0| Speed controller reference| RO| Unsigned 16| Y|
2045h| 0| Torque controller reference| RO| Unsigned 16| Y|
2046h| 0| Digital pot speed reference| RO| Unsigned 16| Y|
Object 2000h : Control Command Register
Object 200Ah : Drive Status Register
Technical Data
10.1. Environmental
Ambient Temperature| Storage and Transportation| All Units| -40 … 60°C / -40 …
140°F|
---|---|---|---|---
Operating| IP20 Units| -10 … 50°C / 14 … 122°F|
IP55 Units| – 10 … 40°C / 14 … 104°F| UL Approved
40 … 50°C / 104 … 122°F| With derating (refer to section 10.4.1. Derating for
Ambient Temperature on page 72)
IP66 Units| – 10 … 40°C / 14 … 104°F| UL Approved
40 … 50°C / 104 … 122°F| With derating (refer to section 10.4.1. Derating for
Ambient Temperature on page 72)
Altitude| Operating| All Units| =<1000m| With UL approval
=<4000m| With derating (refer to section 10.4.2. Derating for Altitude on page
72)
Relative Humidity| Operating| All Units| < 95%| Non-condensing, frost and
moisture free
10.2. Input/Output Power and Current Ratings
The following tables provide the output current rating information for the
various P2 models. Bardac always recommends that selection of the correct
drive is based upon the motor full load current at the incoming supply
voltage.
10.2.1. 200 – 240 Volt (+/- 10%),1 Phase Input, 3 Phase Output
Frame Size| Power Rating| Input Current| Fuse or
MCB (Type B)| Maximum Cable Size| Rated Output Current|
Maximum Motor Cable Length| Recommended Brake Resistance
---|---|---|---|---|---|---|---
kW| HP| A| Non UL| UL| mm| AWG/kcmil|
A| m| ft| Ω
2| 0.75| 1| 8.5| 10| 15| 8| 8| 4.3| 100| 330| 100
2| 1.5| 1.5| 15.2| 25| 20| 8| 8| 7| 100| 330| 50
2| 2.2| 3| 19.5| 25| 25| 8| 8| 10.5| 100| 330| 35
NOTE
- Ratings shown above apply to 40°C Ambient temperature. For derating information, refer to section 10.4.1. Derating for Ambient Temperature.
- The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length limit may be increased by 50%. When using the Bardac recommended output choke, the maximum cable length may be increased by 100%.
- The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor. Bardac recommends using an output choke for motor cable lengths of 50m or more to ensure good motor service life.
- For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses.
10.2.2. 200 – 240 Volt (+/- 10%), 3 Phase Input, 3 Phase Output
Frame Size| Power Rating| Input Current| Fuse or
MCB (Type B)| Maximum Cable Size| Rated Output Current|
Maximum Motor Cable Length| Recommended Brake Resistance
---|---|---|---|---|---|---|---
kW| HP| A| Non UL| UL| mm| AWG/kcmil|
A| m| ft| Ω
2| 0.75| 1| 5.1| 10| 10| 8| 8| 4.3| 100| 330| 100
2| 1.5| 2| 8.3| 10| 15| 8| 8| 7| 100| 330| 50
2| 2.2| 3| 12.6| 16| 17.5| 8| 8| 10.5| 100| 330| 35
3| 4| 5| 21.6| 25| 30| 8| 8| 18| 100| 330| 20
3| 5.5| 7.5| 29.1| 40| 40| 8| 8| 24| 100| 330| 20
4| 7.5| 10| 36.4| 50| 50| 16| 5| 30| 100| 330| 22
4| 11| 15| 55.8| 63| 70| 16| 5| 46| 100| 330| 22
5| 15| 20| 70.2| 80| 90| 35| 2| 61| 100| 330| 12
5| 18.5| 25| 82.9| 100| 110| 35| 2| 72| 100| 330| 12
6| 22| 30| 103.6| 125| 150| 150| 300MCM| 90| 100| 330| 6
6| 30| 40| 126.7| 160| 175| 150| 300MCM| 110| 100| 330| 6
6| 37| 50| 172.7| 200| 225| 150| 300MCM| 150| 100| 330| 6
6| 45| 50| 183.3| 250| 250| 150| 300MCM| 180| 100| 330| 6
7| 55| 50| 205.7| 250| 300| 150| 300MCM| 202| 100| 330| 6
7| 75| 50| 255.5| 315| 350| 150| 300MCM| 248| 100| 330| 6
NOTE
- Ratings shown above apply to 40°C Ambient temperature. For derating information, refer to section 10.4.1. Derating for Ambient Temperature.
- Operation with single phase supply is possible, with 50% derating of the output current capacity.
- The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length limit may be increased by 50%. When using the Bardac recommended output choke, the maximum cable length may be increased by 100%.
- The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor. Bardac recommends using an output choke for motor cable lengths of 50m or more to ensure good motor service life.
- For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses.
10.2.3. 380 – 480 Volt (+ / – 10%), 3 Phase Input, 3 Phase Output
Frame Size| Power Rating| Input Current| Fuse or
MCB (Type B)| Maximum Cable Size| Rated Output Current|
Maximum Motor Cable Length| Recommended Brake Resistance
---|---|---|---|---|---|---|---
kW| HP| A| Non UL| UL| mm| AWG/kcmil|
A| m| ft| Ω
2| 0.75| 1| 2.4| 10| 6| 8| 8| 2.2| 100| 330| 400
2| 1.5| 2| 5.1| 10| 10| 8| 8| 4.1| 100| 330| 200
2| 2.2| 3| 7.5| 10| 10| 8| 8| 5.8| 100| 330| 150
2| 4| 5| 11.2| 16| 15| 8| 8| 9.5| 100| 330| 100
3| 5.5| 7.5| 19| 25| 25| 8| 8| 14| 100| 330| 75
3| 7.5| 10| 21| 25| 30| 8| 8| 18| 100| 330| 50
3| 11| 15| 28.9| 40| 40| 8| 8| 24| 100| 330| 40
4| 15| 20| 37.2| 50| 50| 16| 5| 30| 100| 330| 22
4| 18.5| 25| 47| 63| 60| 16| 5| 39| 100| 330| 22
4| 22| 30| 52.4| 63| 70| 16| 5| 46| 100| 330| 22
5| 30| 40| 63.8| 80| 80| 35| 2| 61| 100| 330| 12
5| 37| 50| 76.4| 100| 100| 35| 2| 72| 100| 330| 12
6| 45| 60| 92.2| 125| 125| 150| 300MCM| 90| 100| 330| 6
6| 55| 75| 112.5| 125| 150| 150| 300MCM| 110| 100| 330| 6
6| 75| 100| 153.2| 200| 200| 150| 300MCM| 150| 100| 330| 6
6| 90| 150| 183.7| 250| 250| 150| 300MCM| 180| 100| 330| 6
7| 110| 175| 205.9| 250| 300| 150| 300MCM| 202| 100| 330| 6
7| 132| 200| 244.5| 315| 350| 150| 300MCM| 240| 100| 330| 6
7| 160| 250| 307.8| 400| 400| 150| 300MCM| 302| 100| 330| 6
8| 200| 300| 370| 500| 500| 240| 450MCM| 370| 100| 330| 2
8| 250| 350| 450| 500| 600| 240| 450MCM| 450| 100| 330| 2
NOTE
- Ratings shown above apply to 40°C Ambient temperature. For derating information, refer to section 10.4.1. Derating for Ambient Temperature.
- Operation with single phase supply is possible, with 50% derating of the output current capacity.
- The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length limit may be increased by 50%. When using the Bardac recommended output choke, the maximum cable length may be increased by 100%.
- The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor. Bardac recommends using an output choke for motor cable lengths of 50m or more to ensure good motor service life.
- For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses.
- Data values shown in Italics are provisional.
10.2.4. 500 – 600 Volt (+ / – 10%), 3 Phase Input, 3 Phase Output
Frame Size| Power Rating| Input Current| Fuse or
MCB (Type B)| Maximum Cable Size| Rated Output Current|
Maximum Motor Cable Length| Recommended Brake Resistance
---|---|---|---|---|---|---|---
kW| HP| A| Non UL| UL| mm| AWG/kcmil|
A| m| ft| Ω
2| 0.75| 1| 2.5| 10| 6| 8| 8| 2.1| 100| 330| 600
2| 1.5| 2| 3.7| 10| 6| 8| 8| 3.1| 100| 330| 300
2| 2.2| 3| 4.9| 10| 10| 8| 8| 4.1| 100| 330| 200
2| 4| 5| 7.8| 10| 10| 8| 8| 6.5| 100| 330| 150
2| 5.5| 7.5| 10.8| 16| 15| 8| 8| 9| 100| 330| 100
3| 7.5| 10| 14.4| 16| 20| 8| 8| 12| 100| 330| 80
3| 11| 15| 20.6| 25| 30| 8| 8| 17| 100| 330| 50
3| 15| 20| 26.7| 32| 35| 8| 8| 22| 100| 330| 33
4| 18.5| 25| 34| 40| 45| 16| 5| 28| 100| 330| 33
4| 22| 30| 41.2| 50| 60| 16| 5| 34| 100| 330| 22
4| 30| 40| 49.5| 63| 70| 16| 5| 43| 100| 330| 16
5| 37| 50| 62.2| 80| 80| 35| 2| 54| 100| 330| 16
5| 45| 60| 75.8| 100| 100| 35| 2| 65| 100| 330| 12
6| 55| 75| 90.9| 125| 125| 150| 300MCM| 78| 100| 330| 12
6| 75| 100| 108.2| 125| 150| 150| 300MCM| 105| 100| 330| 8
6| 90| 125| 127.7| 160| 175| 150| 300MCM| 130| 100| 330| 8
6| 110| 175| 160| 200| 200| 150| 300MCM| 150| 100| 330| 8
10.3. Additional Information for UL Approved Installations
The P2 is designed to meet the UL requirements. In order to ensure full
compliance, the following must be fully observed.
Input Power Supply Requirements
Supply Voltage| 200 – 240 RMS Volts for 230 Volt rated units, + /- 10%
variation allowed. 240 Volt RMS Maximum.
380 – 480 Volts for 400 Volt rated units, + / – 10% variation allowed, Maximum
500 Volts RMS.
500 – 600 Volts for 600 Volt rated units, + / – 10% variation allowed, Maximum
600 Volts RMS.
Imbalance| Maximum 3% voltage variation between phase – phase voltages
allowed.
All P2 units have phase imbalance monitoring. A phase imbalance of > 3% will
result in the drive tripping. For input supplies which have supply imbalance
greater than 3% (typically the Indian sub- continent & parts of Asia Pacific
including China) Bardac recommends the installation of input line reactors.
Alternatively, the drives can be operated as a single phase supply drive with
50% derating.
Frequency| 50 – 60Hz + / – 5% Variation.
Short Circuit Capacity| Voltage Rating| Min kW (HP)| Max kW (HP)| Maximum
supply short-circuit current
All| All| All| 100kA rms (AC)
All the drives in the above table are suitable for use on a circuit capable of
delivering not more than the above specified maximum short-circuit Amperes
symmetrical with the specified maximum supply voltage.
Incoming power supply connection must be according to section 4.3. Incoming
Power Connection.
All P2 units are intended for indoor installation within controlled
environments which meet the condition limits shown in section 10.1.
Environmental.
Branch circuit protection must be installed according to the relevant national
codes. Fuse ratings and types are shown in section 10.2. Input/ Output Power
and Current Ratings.
Suitable Power and motor cables should be selected according to the data shown
in section 10.2. Input/Output Power and Current Ratings.
Power cable connections and tightening torques are shown in section 3.4.
Installation Following a Period of Storage.
The P2 provides motor overload protection in accordance with the National
Electrical Code (US).
Where a motor thermistor is not fitted, or not utilised, Thermal Overload
Memory Retention must be enabled by setting P4-12 = 1.
Where a motor thermistor is fitted and connected to the drive, connection must
be carried out according to the information shown in section
4.7. Motor Terminal Box Connections.
10.4. Derating Information
Derating of the drive maximum continuous output current capacity is require
when:
- Operating at ambient temperature in excess of 40°C / 104°F for enclosed drives (non UL approved).
- Operating at Altitude in excess of 1000m/ 3281 ft.
- Operation with Effective Switching Frequency higher than the minimum setting.
The following derating factors should be applied when operating drives outside of these conditions.
10.4.1. Derating for Ambient Temperature
Enclosure Type| Maximum Temperature Without Derating (UL
Approved)| Derate by| Maximum Permissible Operating Ambient
Temperature with Derating (Non UL Approved)
---|---|---|---
IP20| 50°C / 122°F| N/A| 50°C
IP55| 40°C / 104°F| 1.5% per °C (1.8°F)| 50°C
IP66| 40°C / 104°F| 2.5% per °C (1.8°F)| 50°C
10.4.2. Derating for Altitude
Enclosure Type| Maximum Altitude Without Derating| Derate
by| Maximum Permssable (UL Approved)| Maximum Permssable (Non-UL
Approved)
---|---|---|---|---
IP20| 1000m / 3281ft| 1% per 100m / 328 ft| 2000m / 6562 ft| 4000m / 13123 ft
IP55| 1000m / 3281ft| 1% per 100m / 328 ft| 2000m / 6562 ft| 4000m / 13123 ft
IP66| 1000m / 3281ft| 1% per 100m / 328 ft| 2000m / 6562 ft| 4000m / 13123 ft
10.4.3. Derating for Swicthing Frequency
Enclosure Type | Switching Frequency (Where available) |
---|---|
4kHz | 8kHz |
IP20 | N/A |
IP55 | N/A |
IP66 | N/A |
10.4.4. Example of applying Derating Factors
A 4kW, IP66 drive is to be used at an altitude of 2000 metres above sea level,
with 12kHz switching frequency and 45°C ambient temperature.
From the table above, we can see that the rated current of the drive is 9.5
Amps at 40°C,
Firstly, apply the switching frequency derating, 12kHz, 25% derating
9.5 Amps x 75% = 7.1 Amps
Now, apply the derating for higher ambient temperature, 2.5% per °C above 40°C
= 5 x 2.5% = 12.5%
7.1 Amps x 87.5% = 6.2 Amps
Now apply the derating for altitude above 1000 metres, 1% per 100m above 1000m
= 10 x 1% = 10%
7.9 Amps x 90% = 5.5 Amps continuous current available.
If the required motor current exceeds this level, it will be necessary to
either:
- Reduce the switching frequency selected.
- Use a higher power rated drive and repeat the calculation to ensure sufficient output current is available.
10.5. Internal EMC Filter and Varistors – Disconnection Procedure
10.5.1. IP20 Drive Models
All P2 drive models provide a simple method to disconnect the internal EMC
filter and surge protection varistors by fully removing the screws shown
below. This should only be carried out where necessary, for example in cases
such as IT or ungrounded supplies, where the phase to ground voltage can
exceed the phase to phase voltage.
The EMC filter disconnect screw is labelled “EMC“.
The surge protection varistors disconnect screw is clearly labelled “VAR”.
Frame Sizes 2 & 3
The EMC Filter and Varistor disconnect screws are located on the left side of
the product when viewed from the front. Remove both screws completely
Frame Sizes 4
Frame Size 4 units have EMC Filter disconnection points only located on the
front face of the unit as shown.
Frame Size 5
Frame Size 5 units have EMC Filter disconnection points only located on the
front face of the unit as shown.
10.5.2. IP55 & IP66 Models
These models require disassembly in order to disconnect the EMC filter.
Disconnection should be carried out only by Bardac Approved Service Partners.
Troubleshooting
11.1. Fault Messages
Fault Code| No.| OLED Message Description|
Corrective Action
---|---|---|---
| 00| No Fault| Displayed in P0-13 if no faults are recorded in the log.
| 01| Brake channel over current| Ensure the connected brake resistor is above
the minimum permissible level for the drive – refer to the ratings shown in
section 10.2. Input/Output Power and Current Ratings.
Check the brake resistor and wiring for possible short circuits.
| 02| Brake resistor overload| The drive software has determined that the
brake resistor is overloaded, and trips to protect the resistor. Always ensure
the brake resistor is being operated within its designed parameter before
making any parameter or system changes.
To reduce the load on the resistor, increase deceleration the time, reduce the
load inertia or add further brake resistors in parallel, observing the minimum
resistance value for the drive in use.
| 03| Over current trip| Fault Occurs on Drive Enable
Check the motor and motor connection cable for phase – phase and phase –
earth short circuits. Check the load mechanically for a jam, blockage or
stalled condition.
Ensure the motor nameplate parameters are correctly entered, P1-07, P1-08,
P1-09.
If operating in Vector mode (P4-01 – 0 or 1), also check the motor power
factor in P4-05 and ensure an autotune has been successfully completed for the
connected motor.
Reduced the Boost voltage setting in P1-11. Increase the ramp up time in
P1-03.
If the connected motor has a holding brake, ensure the brake is correctly
connected and controlled, and is releasing correctly.
Fault Occurs When Running
If operating in Vector mode (P4-01 – 0 or 1), reduce the speed loop gain in
P4-03.
| 04| Drive has tripped on overload after delivering >100% of value in P1-08
for a period of time.| Check to see when the decimal points are fiashing
(drive in overload) and either increase acceleration rate or reduce the load.
Check motor cable length is within the limit specified for the relevant drive
in section 10.2. Ensure the motor nameplate parameters are correctly entered
in P1-07, P1-08, and P1-09.
If operating in Vector mode (P4-01 – 0 or 1), also check the motor power
factor in P4-05 and ensure an autotune has been successfully completed for the
connected motor.
Check the load mechanically to ensure it is free, and that no jams, blockages
or other mechanical faults exist.
| 05| Hardware Over Current| Check the wiring to motor and the motor for phase
to phase and phase to earth short circuits. Disconnect the motor and motor
cable and retest. If the drive trips with no motor connected, it must be
replaced and the system fully checked and retested before a replacement unit
is installed.
| 06| Over voltage on DC bus| The value of the DC Bus Voltage can be displayed
in P0-20.
A historical log is stored at 256ms intervals prior to a trip in parameter
P0-36.
This fault is generally caused by excessive regenerative energy being
transferred from the load back to the drive. When a high inertia or over
hauling type load is connected.
If the fault occurs on stopping or during deceleration, increase the
deceleration ramp time P1-04 or connect a suitable brake resistor to the
drive.
If operating in Vector Mode, reduce the speed loop gain P4-03.
If operating in PID control, ensure that ramps are active by reducing P3-11.
| 07| Under voltage on DC bus| This occurs routinely when power is switched
off.
If it occurs during running, check the incoming supply voltage, and all
connections into the drive, fuses, contactors etc.
| 08| Heatsink over temperature| The heatsink temperature can be displayed in
P0-21.
A historical log is stored at 30 second intervals prior to a trip in parameter
P0-38. Check the drive ambient temperature.
Ensure the drive internal cooling fan is operating.
Ensure that the required space around the drive as shown in sections 3.5.
Mechanical Dimensions and Weight to 3.9. Guidelines for Mounting (IP66 Units)
has been observed, and that the cooling airfiow path to and from the drive is
not restricted.
Reduce the effective switching frequency setting in parameter P2-24. Reduce
the load on the motor / drive.
| 09| Under temperature| Trip occurs when ambient temperature is less than
-10°C. The temperature must be raised over
-10°C in order to start the drive.
| 10| Factory Default parameters have been loaded| Press STOP key, the drive
is now ready to be configured for the required application.
| 11| External trip| E-trip requested on control input terminals. Some
settings of P1-13 require a normally closed contact to provide an external
means of tripping the drive in the event that an external device develops a
fault. If a motor thermistor is connected check if the motor is too hot.
Fault Code| No.| OLED Message Description|
Corrective Action
---|---|---|---
| 12| Communications Fault| Communications lost with PC or remote keypad.
Check the cables and connections to external devices.
| 13| Excessive DC ripple| The DC Bus Ripple Voltage level can be displayed in
parameter P0-16.
A historical log is stored at 20ms intervals prior to a trip in parameter
P0-37.
Check all three supply phases are present and within the 3% supply voltage
level imbalance tolerance.
Reduce the motor load.
If the fault persists, contact your local Bardac Sales Partner.
| 14| Input phase loss| Drive intended for use with a 3 phase supply, one
input phase has been disconnected or lost.
| 15| Instantaneous over current on drive output| Refer to fault 3 above.
| 16| Faulty thermistor on heatsink| Refer to your Bardac Sales Partner.
| 17| Internal memory fault| Parameters not saved, defaults reloaded.
Try again. If problem recurs, refer to your Bardac Authorised Distributor.
| 18| 4-20mA Signal Lost| The reference signal on Analog Input 1 or 2
(Terminals 6 or 10) has dropped below the minimum threshold of 3mA. Check the
signal source and wiring to the drive terminals.
| 19| Internal memory fault| Parameters not saved, defaults reloaded.
Try again. If problem recurs, refer to your Bardac Authorised Distributor.
| 20| User Parameter Default| User Parameter defaults have been loaded. Press
the Stop key.
| 21| Motor PTC Over Temperature| The connected motor PTC device has caused
the drive to trip.
| 22| Cooling Fan Fault| Check and if necessary, replace the drive internal
cooling fan.
| 23| Ambient Temperature High| The measured temperature around the drive is
above the operating limit of the drive. Ensure the drive internal cooling fan
is operating.
Ensure that the required space around the drive as shown in sections 3.5.
Mechanical Dimensions and Weight to 3.9. Guidelines for Mounting (IP66 Units)
has been observed, and that the cooling airfiow path to and from the drive is
not restricted.
Increase the cooling airfiow to the drive.
Reduce the effective switching frequency setting in parameter P2-24. Reduce
the load on the motor / drive.
| 24| Maximum Torque Limit Exceeded| The output torque limit has exceeded the
drive capacity or trip threshold. Reduce the motor load, or increase the
acceleration time.
| 25| Output Torque Too Low| Active only when hoist brake control is enabled
P2-18 = 8. The torque developed prior to releasing the motor holding brake is
below the preset threshold. Contact your local Bardac Sales Partner for
further information on using the P2 drive in hoist applications.
| 26| Drive output fault| Drive output fault.
| 29| Internal STO circuit Error| Refer to your Bardac Sales Partner.
| 30| Encoder Feedback Fault| Encoder communication /data loss.
| 31| Speed Error| Speed Error. The error between the measured encoder
feedback speed or the estimated rotor speed is greater than the pre-set limit
allowed.
| 32| Encoder Feedback Fault| Incorrect Encoder PPR count set in parameters.
| 33| Encoder Feedback Fault| Encoder Channel A Fault.
| 34| Encoder Feedback Fault| Encoder Channel B Fault.
| 35| Encoder Feedback Fault| Encoder Channels A & B Fault.
| 40| Autotune Failed| Measured motor stator resistance varies between phases.
Ensure the motor is correctly connected and free from faults. Check the
windings for correct resistance and balance.
| 41| Measured motor stator resistance is too large. Ensure the motor is
correctly connected and free from faults. Check that the power rating
corresponds to the power rating of the connected drive.
| 42| Measured motor inductance is too low. Ensure the motor is correctly
connected and free from faults.
| 43| Measured motor inductance is too large. Ensure the motor is correctly
connected and free from faults. Check that the power rating corresponds to the
power rating of the connected drive.
| 44| Measured motor parameters are not convergent. Ensure the motor is
correctly connected and free from faults. Check that the power rating
corresponds to the power rating of the connected drive.
| 45| Incorrect Supply Phase Sequence| Applies to Frame Size 8 drives only,
indicates that the incoming power supply phase sequence is incorrect. Any 2
phases may be swapped.
Fault Code| No.| OLED Message Description|
Corrective Action
---|---|---|---
| 49| Output Phase Loss| One of the motor output phases is not connected to
the drive.
| 50| Modbus Comms fault| A valid Modbus telegram has not been received within
the watchdog time limit set in P5-06. Check the network master / PLC is still
operating.
Check the connection cables.
Increase the value of P5-05 to a suitable level.
| 51| CAN Open comms trip| A valid CAN open telegram has not been received
within the watchdog time limit set in P5-06. Check the network master / PLC is
still operating.
Check the connection cables.
Increase the value of P5-06 to a suitable level.
| 52| Communications Option Module Fault| Internal communication to the
inserted Communication Option Module has been lost. Check the module is
correctly inserted.
| 53| IO card comms trip| Internal communication to the inserted Option Module
has been lost. Check the module is correctly inserted.
drive.web distributed Control Over Ethernet
Use a drive.web speedy embeddable, plug in controller on any Bardac drive to
provide:
- Unlimited, peer to peer, Ethernet connections (without a PLC) between all Bardac drives, programmable controllers, industrial touch screens
- Full featured programmable control functions for winders, indexing, shaft lock, registration, motion control, solar tracking and more
- Complete configuration of all devices in a system from any device USB port
- Total Internet access for programming, monitoring & control
Add a drive.web smarty programmable controller to provide:
- All the features of the speedy controller plus …
- Unlimited, distributed i/o – precision analog, logic, temperature, encoders, position.
- Stepper drive & frequency i/o
- DIN rail mount with plug-in termnals
- Communications port options
drive.web savvy tools
Configure, connect & control everything from anywhere via Internet, LAN or any device
- Runs on Windows, Mac OSX, Linux
- Easy drag and drop connections
- Easy system wide navigation
- Easy, complete device & system documentation
- Easy system trend charting & data logging
- Easy interface to old world devices via field bus options
- Provides the universal connectivity needed for the Industrial Internet of Things future (See section 8 or go to driveweb.com for more information, downloads & training)
Bardac Corporation 40 Log Canoe Circle, Stevensville, MD 21666 USA
Tel: +410-604-3400 Fax:
+410-604-3500
bardac.com driveweb.com
References
- AC Drives, DC Drives, Motors & Control Technology | Bardac Drives
- Internet-Accessible Distributed Control Technology | drive.web
- Manual-Hub.com - Free PDF manuals!
- AC Drives, DC Drives, Motors & Control Technology | Bardac Drives
- Get savvy | drive.web
- Manual-Hub.com – Free PDF manuals!
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>