Profibus DP Interface
User Guide
P2 Profibus DP Interface
This option module is specifically designed to be used with the P2 and V3
series of variable speed drive products and is intended for professional
incorporation into complete equipment or systems. If installed incorrectly it
may present a safety hazard. Before commencing installation and commissioning,
the user should ensure they are fully familiar with the P2, and in particular
have read the important safety information and warnings contained in the P2 /
V3 manual.
Note
This User Guide is intended to be used with P2 & V3 firmware version 1.20.
The firmware version of the drive can be displayed in parameter P0-28.
Overview
The Profibus DP Interface is intended to be installed in the drive option slot,
and allows the drive to be connected to a Profibus DP network. The interface
offers the following functionality:
- Automatic Baud Rate Detection from 9.6kpbs to 12mbps Cyclic Process Data Exchange
- 4 Input Words from the network master to the drive
- 4 Output Words from the drive to the network master
- Parameter Access via DPV-1 Read / Write Services
Installation
- Ensure the drive power is removed prior to installing the option module
- Remove the blanking cover from the option module slot
- Carefully slide the option module into the slot, ensuring that the locating tabs are correctly aligned. Do not use excessive force
- Tighten the 2 clamping screws to secure the module in place
Drive Setup
- Set the drive to Fieldbus control mode by setting parameter P1-12 = 4
- Ensure Advanced Parameter Access is enabled on the drive by setting P1-14 = 101
- Set the required node address for the drive in P5-01
- Further drive parameter setting options are possible, please read the drive P2/V3 User Guide for further information
Compatibility:
This Option is suitable for use on the following product ranges:
P2 (P2-… Drives)
V3 (V3-… Drives)
Part No:| 82-PROFB-CC
40 Log Canoe Circle Stevensville, MD 21666 USA|
| Item|
1| Operation Mode
2| Status
3| Profibus Network Connector
Operation Mode
State| Indication
Off| No Power / Not inserted
Green| Online, Data Exchange
Flashing Green| Network OK, No data exchange
Single Red Flash| Parameter Error
Double Red Flash| Network Error
Status
State| Indication
Off| No Power
Green| Initialised
Flashing Green| Initialised, self testing
Red| Error
Profibus DP Connector Pinnout
Pin| Function
1| N/C
2| N/C
3| B Line Positive RxD/TxD, RS485 level
4| RTS (Request to send)
5| GND Bus ground (isolated)
6| +5V Bus Output termination power (isolated, short-circuit protected)
7| N/C
8| A Line Negative RxD/TxD, RS485 level
9| N/C
82-PROFB -CC Profibus DP Interface User Guide
Data Mapping
P2 & V3 series drives support a 4 word cyclic data exchange format. The format
and data contained in each word is detailed below.
Input Data (PDI) Telegram
This part of the memory contains the real-time drive commands sent from the
network master to the drive, allowing the drive to be controlled. The function
of the first two data words (PDI 1 and PDI 2) is fixed, to allow basic control
over the drive operation and output frequency to be achieved. The configuration
of the remaining two words can be adjusted by the user.
A 16 Bit control word is used to control the behaviour of the drive when P1-12
= 4. The bits function as follows :
Bit| Name| Description|
---|---|---|---
0| Drive Run| 0 : Drive Stop
1 : Drive Run| For normal operation, Bit 3 has the highest priority, bit 0 has
the lowest priority
(bit 3>bit 1>bit 0). For normal run/stop control, Bit 0 only should be used.
Note that the start/stop (bit 0), fast stop (bit 1) and coast stop (bit 3) can
only be used to control the drive when P2-31= 0 to 3. If P2-37 > 3, the
start/stop function is controlled directly by the drive control terminals. The
Reset function (bit 2) will operate providing that the drive is set for
Fieldbus control
P1-12 = 4.
1| Fast Stop Select| 0 : No Function
1 : Drive Stop with Deceleration Ramp 2
2| Fault Reset| 0 : No Function
1 : Rising Edge fault reset request
3| Not Used| 0 : No Function
1 : Drive Coasts to stop. Overrides bit 0
15-Apr| Coast Stop| Not Used
PDI Word 2: Fixed Function : Frequency Setpoint
This word is used to transfer the frequency setpoint to the Optidrive. The
input data is a 16bit signed integer including one decimal place. For example,
a value of 500 represents a frequency setpoint to the drive of 50.0Hz, value
123 gives 12.3Hz. For a negative (reverse) speed reference, a negative value
can be transferred to the drive, where the MSB of the high byte must be 1. For
example, -1(0xFFFF) gives -0.1Hz. -234(0xFF16) gives -23.4Hz. The allowed
input value range is from -5000 to +5000; however the drive output speed will
be limited by the maximum speed set by P1-01. PDI Word 3 : User Defined
Function
The function of this data word can be selected by the user using drive
parameter P5-14. The possible setting options are shown below:
0: Torque limit/reference (P2 Only) – This option must be selected if the
drive output torque limit / setpoint is to be controlled from the fieldbus.
This also requires setting P4-06 = 3. The input data is a 16bit unsigned
integer including one decimal place. For example, a value of 500 represents a
torque setpoint to the drive of 50.0%, value 123 gives 12.3%.
The allowed input value range is from 0 to +2000; however the drive output
torque will be limited by the maximum limit set by P4-07.
- User PID reference register – This option allows the setpoint to the PID controller to be received from the Fieldbus. In order for this option to be used, P9-38 must be set to 1, and the PID User setpoint must not be utilised within the drive PLC function.
- User register 3 – The value received by the drive in PDI 3 is transferred to User Register
- This option allows the function of the process data word to be defined in Parameter Group 9. In this case, User Register 3 should not be written to within any PLC function code, although the value can be read. PDI Word 4: User
Defined Function
The function of this data word can be selected by the user using drive
parameter P5-13. The possible setting options are shown below:
0: Fieldbus Ramp Control – This option must be selected if the drive
acceleration and deceleration ramps are to be controlled from the fieldbus.
P5-07 must also be set to 1 to enable this function.
- User register 4 – The value received by the drive in PDI 4 is transferred to User Register 4. This option allows the function of the process data word to be defined in Parameter Group 9. In this case, User Register 3 should not be written to within any PLC function code, although the value can be read.
Output Data
This part of the memory contains the real-time drive data returned from the
drive to the network master. The function of the first two data words (PDO 1
and PDO 2) is fixed. The configuration of the remaining two words can be
adjusted by the user.
PDO Word 1: Fixed Function : Drive Status & Error Code:
This word contains 2 bytes with information as follows:
High byte : Gives the drive error (fault) code. (Valid when the drive is
tripped)
Low byte : Gives the drive status information, 8 bits which function as
follows :
Bit | Logic 0 | Logic 1 | Notes |
---|---|---|---|
0 | Drive Stopped | Drive Running | |
1 | Drive Healthy | Drive Fault (Tripped) | |
2 | Maintenance Indication (V3 Only) | STO Inhibit | Logic 1 indicates that the |
Safe Torque Off hardware circuit connections required for drive operation are
not present. For further information, refer to the P2/V3 drive user guide.
3| | |
4-7| Not used| |
PDO Word 2 : Fixed Function : Output Frequency
This word gives the real time drive output frequency information. The data is
a 16bit signed integer with one decimal place. E.g. value 123 means 12.3Hz.
Value – 234 (0xFF16) means -23.4Hz.
PDO Word 3 : Output Current
Data to be transferred in this word can be selected by the User in drive
parameter P5-12. The possible settings are as follows:
0: Motor current – Output current to 1 decimal place, e.g. 100 = 10.0 Amps
- Power (x.xx kW) Output power in kW to two decimal places, e.g. 400 = 4.00kW
- Digital input status – Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
- Analog Input 2 Signal Level – 0 to 1000 = 0 to 100.0%
- Drive Heatsink Temperature – 0 to 100 = 0 to 100°C
- User register 1 – User Defined Register 1 Value
- User register 2– User Defined Register 1 Value
- P0-80 value – User Selected data value.
PDO Word 4 : User Defined
Data to be transferred in this word can be selected by the User in drive
parameter P5-08. The possible settings are as follows:
0 : Output Torque (Optidrive P2 Only) – 0 to 2000 = 0 to 200.0%
- Output Power – Output power in kW to two decimal places, e.g. 400 = 4.00kW
- Digital Input Status – Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc.
- Analog Input 2 Signal Level – 0 to 1000 = 0 to 100.0%
- Drive Heatsink Temperature – 0 to 100 = 0 to 100°C
Bardac Corporation 40 Log Canoe Circle, Stevensville, MD 21666 USA
Phone# +410-604-3400 Fax#
+410-604-3500
bardac.com
driveweb.com
automationthings.com
References
- Automation Things - AC Drives, DC Drives & Automation Controllers
- AC Drives, DC Drives, Motors & Control Technology | Bardac Drives
- Internet-Accessible Distributed Control Technology | drive.web
Read User Manual Online (PDF format)