Whirlpool WGT4027E Gas Washer Dryer User Guide
- June 17, 2024
- Whirlpool
Table of Contents
Whirlpool WGT4027E Gas Washer Dryer
Specifications
- Product Model Numbers: WGT4027E, WGTLV27F
Dimensions
- 27 Model:
- Width: 58 7/8″ (1495 mm)
- Depth: 26″ (660 mm)
- Height: 65 3/4″ (1670 mm)
- 24 Model:
- Width: 35 7/8″ (911 mm)
- Depth: 20 1/2″ (521 mm)
- Height: 65 3/4″ (1670 mm)
Installation Clearances
For each arrangement, consider allowing more space for ease of installation
and servicing, spacing for companion appliances, and clearances for walls,
doors, and floor moldings. Space must be large enough to allow the door to
fully open. Add spacing on all sides of the dryer to reduce noise transfer. If
a closet door or louvered door is installed, top and bottom air openings in
the door are required.
DIMENSIONS
For each arrangement, consider allowing more space for ease of installation and servicing, spacing for companion appliances and clearances for walls, doors, and floor moldings. Space must be large enough to allow door to fully open. Add spacing on all sides of dryer to reduce noise transfer. If a closet door or louvered door is installed, top and bottom air openings in door are required.
Recommended installation clearances
Companion appliance spacing should also be considered.
27″ Model
Recommended/Minimum spacing
NOTE: Most installations require a minimum of 6″ (152 mm) clearance behind
dryer for the exhaust vent with an elbow. See “Venting Requirements.”
24″ Model
Recommended installation clearances
Companion appliance spacing should also be considered.
Recommended/Minimum spacing
NOTE: Most installations require a minimum of 6″ (152 mm) clearance behind the
dryer for the exhaust vent with an elbow. See “Venting Requirements.”
Drain System
A drain system can be installed using a floor drain, wall standpipe, floor standpipe, or laundry tub. Select the method you need.
Floor standpipe drain system
Minimum diameter for a standpipe drain: 2″ (51 mm). Minimum carry-away
capacity: 17 gal. (64 L) per minute. Top of standpipe must be at least 39″
(991 mm) high; install no higher than 96″ (2.4 m) from the bottom of
washer/dryer. If you must install higher than 96″ (2.4 m), you will need a
sump pump system.
Wall standpipe drain system
See requirements for floor standpipe drain system.
Floor drain system
Floor drain system requires a Siphon Break Kit (Part Number 285834), 2
Connector Kits (Part Number 285385), and an Extension Drain Hose (Part Number
285863) that may be purchased separately. To order, please see toll-free phone
numbers in your Use and Care Guide. Minimum siphon break: 28″ (710 mm) from
bottom of washer/dryer. (Additional hoses may be needed.)
Laundry tub drain system
Minimum capacity: 20 gal. (76 L). Top of the laundry tub must be at least 39″
(991 mm) above floor on 27″ models, or 34″ (864 mm) above floor on 24″ models;
install no higher than 96″ (2.4 m) from the bottom of the washer/dryer.
IMPORTANT: To avoid siphoning, no more than 4.5″ (114 mm) of drain hose should
be inside standpipe or below the top of the wash tub. Secure drain hose with a
shipping strap or plastic strap.
INSTALLATION REQUIREMENTS GAS SUPPLY REQUIREMENTS
Gas supply: This dryer is equipped for use with Natural gas. Dryer can be converted to L.P. gas. When rigid pipe is used it should be 1/2″ IPS. When acceptable to the gas supplier and local codes, 3/8″ approved tubing may be used for lengths under 20 ft (6.1 m). For lengths over 20 ft (6.1 m), larger tubing should be used. Pipe-joint compounds resistant to the action of L.P. gas must be used. Must include 1/8″ NPT minimum plugged tapping accessible for test gauge connection, immediately upstream of the gas connection to the washer/dryer. An individual manual shutoff valve must be installed within 6 ft (1.8 m) of the dryer in accordance with the National Fuel Gas Code ANSI Z223.1.
ELECTRICAL REQUIREMENTS
- 120 Volt, 60 Hz, AC only, 15- or 20- amp fused electrical supply is required. A time-delay fuse or circuit breaker is recommended. It is also recommended that a separate circuit serving only this dryer be provided.
- It is your responsibility to supply the required 3- or 4-wire, single phase, 120/240 volt, 60 Hz, AC only electrical supply (or 3- or 4-wire, 120/208 volt electrical supply, if specified on the serial/rating plate) on a separate 30-amp circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. Connect to an individual branch circuit. Do not have a fuse in the neutral or grounding circuit.
- Do not use an extension cord.
WATER (STEAM MODELS ONLY) REQUIREMENTS
The dryer must be connected to the cold water faucet using new inlet hoses. Do not use old hoses. Do not over tighten. Damage to the coupling can result.
VENTING REQUIREMENTS
Exhaust venting: Exhaust your dryer to the outside. 4″ (102 mm) diameter vent
is required. Rigid or flexible metal exhaust vent must be used. Do not use
plastic or metal foil vet. Exhaust hood must be at least 12″ (305 mm) from the
ground or any object that may be in the path of the exhaust.
WARNING : To reduce the risk of fire, this dryer MUST BE EXHAUSTED OUTDOORS.
- Only a 4″ (102 mm) heavy metal exhaust vent and clamps
- Reduced performance, resulting in longer drying times may be used.
- Do not use plastic or metal foil vents.
Exhaust hoods: Recommended Styles:
- Must be at least 12″ (305 mm) from the ground or any object that may obstruct exhaust (such as flowers, rocks, bushes, or snow).
Determine vent path
- Select route that will provide the straightest and most direct path outdoors.
- Plan installation to use fewest number of elbows and turns.
- When using elbows or making turns, allow as much room as possible.
- Bend vent gradually to avoid kinking.
- Use as few 90° turns as possible.
Determine vent length and elbows needed for best drying performance
- Use following Vent System Chart to determine type of vent material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified in Vent System Chart. Exhaust systems longer than those specified will:
- Shorten life of dryer.
- Reduce performance, resulting in longer drying times and increased energy usage.
- The Vent System Charts provide venting requirements that will help achieve best drying performance.
NOTE : Bottom exhaust installations have a 90° turn inside the dryer. To determine maximum exhaust length, add one 90° turn to the charts.
- Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to change materials and specifications without notice.
- Dimensions are for planning purposes only. For complete details, see Installation Instructions packed with product. Specifications subject to change without notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>