LCN 9130 Series Complete Door Closer Instruction Manual
- June 4, 2024
- LCN
Table of Contents
9130 Series Complete Door Closer
Instruction Manual
Benchmark III
General
The Benchmark is an automatic electromechanical swinging door operator for use on hinged, center pivoted and offset pivoted doors. When activated, the Benchmark drives the door to full open position, then electrical power is turned off and the door is closed by spring force. The activating circuit opens the door from any position in the closing swing. During a power failure, the Benchmark acts as a manual door closer (Size 3). Door opening and closing cycles, including opening speed, back check speed, hold open time delay, closing peed, and latch position, are adjustable.
WARNING
Always disconnect the main power to the operator prior to servicing or
cleaning.
CAUTION
This operator is for indoor use only.
Do not mount any accessories directly to the operator.
Replacement Parts & System Components
Part| 27” Header| Full-Length Header
Single| Full-Length Header Double
---|---|---|---
Premium Control Box| 9130-3462SC
9140-3462SC| 9130-3462SC
9130-3462SC| 9150-3462SC
Gear Box| 9130-3454S
9140-3554S| 9130-3454
9140-3454| 9150-3454S
End Caps| 9130-334| 9140-334| 9150-334
Part| Pull| Standard Push| Extended Reveal Push|
Finish
---|---|---|---|---
Arm Assembly| 9130-3077T| 9140-3077
9150-3077| 9140-3077L
9150-3077L| US28
DC13
Replacement Parts & System Components (Cont.)
Double Push System (Screw pack not shown)
1
Pre-Installation Site & Product Check
1a Check that the Product Model is correct for the required application.
1b Check that all parts listed on the Bill of Material are in the shipping
container.
1c Check the architectural drawings and final approved shop drawings for the
position of frame and structural openings.
1d Check header and frame dimensions and required clearances.
1e
Check Door Width:
a. 26” minimum for 27” Push Operator
b. 30” minimum for 27” Pull Operator
c. 36” minimum for Full-Length Push or Full Length Pull Operators
1f Check that Door Weight is 200 lbs. or less. For a heavier door, consult the
factory.
1g Check that a 115 volt, single phase, 60 Hz, fused 15 amp, the 3-wire power
supply is available at the side jamb with approximately 12” of wire available
to connect to the Operator. UL-approved flexible conduit is recommended for
the 115-volt power line.
The 115-volt power supply must be a dedicated circuit from the main circuit
breaker panel and must NOT be connected to any building
a lighting system that operates fluorescent lights.
Operator Installation
Remove Control Box from Operator Mounting Bracket, then remove Motor/Gearbox
from Bracket:
Control Box and Motor/Gearbox Removal
27” Pull, 27” Push, and Double Push Systems
Control Box and Motor/Gearbox Removal
Full-Length Pull and Full-Length Push Systems
2b
Prepare Header/Frame and Door:
a. 27” Pull System ………………………………………………………………………………………………………………………………….Page 6
b. Full-Length Pull System ………………………………………………………………………………………………………………………Page 6
c. 27” Push System………………………………………………………………………………………………………………………………..Page 7
d. Full Length Push System …………………………………………………………………………………………………………………….Page 7
e. Double Push System ………………………………………………………………………………………………………………………….Page 8
f. Low Ceiling Application ……………………………………………………………………………………………………………………….Page
8
NOTE
For Push Units with a Reveal greater than 6” refer to the installation sheet
included in the Extended Arm package.
2c Install Operator Mounting Bracket on Header/Frame. For Full-Length systems,
also install Switch Bracket on Header/ Frame.
2d Install Motor/Gearbox on Operator Mounting Bracket. Then install Control
Box on Bracket.
2e Proceed to Chapter 3: Wiring (Page 9).
27” Pull System Header/Frame and Door Preparation
Full-
Length Pull System Header/Frame and Door Preparation
Center Operator Cover (with End Caps removed) over the opening and mark a
vertical line at each end. Align ends of Operator Mounting Bracket and Switch
Bracket with vertical lines and adjust vertical position per the diagram
below. Mark and prepare mounting holes.
27”
Push System Header/Frame and Door Preparation
Full-
Length Push System Frame/Header and Door Preparation
Center operator cover (with end caps removed) over the opening and mark a
vertical line at each end. Align ends of operator mounting bracket and switch
bracket with vertical lines and adjust vertical position per the diagram
below. Mark and prepare mounting holes.
Double Push System Header/Frame and Door Preparation
Center operator cover (with End Caps removed) over the opening and mark a
vertical line at each end. Align ends of Operator Mounting Bracket and Switch
Bracket with vertical lines and adjust vertical position per the diagram
below. Mark and prepare mounting holes.
Low
Ceiling Application (27” Push System Only) Header/Frame and Door Preparation
Wiring
CAUTION
Make sure all wires are properly dressed and secured to prevent interference.
Route all wiring away from moving parts, sharp edges, and heat sources. Use
copper conductors only. Do not modify the factory wiring or connect to
existing electrical circuits or devices.
3a Refer to the appropriate wiring diagram for the Control Box (Page 19) or
the diagram supplied for custom applications.
Connect the following cables:
- Ground Cable (Ground the Operator properly with the earth from main supply)
- Hall Effect Cable (Do not wrap the Hall Effect Cable around the Motor Power Cable)
- Motor Power Cable (Do not wrap the Motor Power Cable around the Hall Effect Cable)
- Control Box Power Cable
3b Connect Activate, Safety, Key Switch, and lock accessories, as needed.
Refer to the accessory instructions for any accessories used. Do not connect
any remote activating device to the door unless it is located within line of
sight of the door.
3c When wiring is complete, proceed to Chapter 4: Arm and Cover Installation
(page 10).
Arm & Cover Installation
CAUTION
Keep hands, clothing, wires, tools, etc., AWAY FROM Operator Motor when the
Operator Motor is turned on.
4a Make sure the Operator Powers are turned Off.
4b Install a jumper across the control box Main Act and Main Act.
4c Turn the operator power switch to On.
The operator motor will activate and drive to the Full Open position.
4d Attach the arm to the operator spindle loosely with the 8mm socket head
screw.
For push systems, ensure that the adjusting boss is inserted correctly.
4e
Attach the arm to the door.
1. For push systems, attach the push arm shoe to the door:
2.
For pull systems, slide the pull arm roller into the track, then insert a
track cap on each end of the track and attach the track to the door:
4f
Adjust arm:
1. For pull systems, remove the locking screw from the arm.
2. For the push system, remove the locking screw from the arm.
3.
Keep the door in the fully open position and adjust the arm length as
necessary to align the door at 90 degrees from closed.
When the arm is adjusted to the correct length, tighten the 8mm socket head
screw that secures the arm to the operator spindle.
4. Ensure this screw is secure, then tighten the arm locking screw.
4g Turn Off the power operator switch. The door should close.
4h Remove the jumper from the control box Main Act and Main Act.
4i Test the operator (see Chapter 5: Operational Check on page 13).
4j Adjust the operator as required (see Chapter 6: Operator Adjustment on page
15).
4k Snap the optional end cap insert (in a bag of screws) into the end cap
opposite the On/Off switch.
4l Install the cover assembly onto the operator.
4m Release the operator for service (see Chapter7: Release for Service on page
17).
Operational Check
5a Set the key switch to Auto (if used) and turn on the operator power switch.
5b Activate the operator using the activation device.
The operator will perform one sizing cycle.
Sizing cycle: Occurs after power is turned on and a legitimate activation
signal is received. During the sizing cycle, the door opens and closes one
time.
5c If the Door does NOT OPEN AT ALL during the sizing cycle:
- Check the door for binding.
- If an electromechanical lock is being used, check that the lock disengages before the operator opens the door.
- Check fuses, circuit breakers, and connections.
- Adjust the operator and check the door operation (see Chapter 6: Operator Adjustment on page 15).
Below are default settings:
Opening Speed ………………………………………………………………………………………………… 9:00
Back Check Speed …………………………………………………………………………………………… 3:00
Hold Open Time Delay ………………………………………………………………………………………. 10:00
Latch Position ………………………………………………………………………………………………….. 12:00
Closing Speed………………………………………………………………………………………………….. 12:00
SW1 1, 2, 3, 4 ………………………………………………………………………………………………….. OFF
Back Check Position …………………………………………………………………………………………. 4:00 (fully clockwise)
5d If the door does NOT OPEN FULLY during the sizing cycle:
- Check the door for binding.
- Increase the back check speed slightly and re-check the door operation. Repeat until the door opens fully.
5e If the door SLAMS OPEN during the sizing cycle, decrease the back check
speed slightly and re-check the door operation. Repeat until the door opens
without slamming.
5f After the sizing cycle is completed and the door(s) are closed, apply a
maintained activation signal. Check that the door remains open while the
signal is applied.
5g If a door safety device is being used:
1. Door Open Safety:
When the door is in the closed position, activate the safety device and try to
activate the door open. The door should remain closed.
2. Door Close Safety:
When the door is in a fully open position, activate the safety device and the
door should remain open.
5h When the door is operating properly, continue with step 4j above.
Operator Adjustment
See table below and diagrams (page 16) for operator feature adjustment.
After adjusting, cycle the door several times to check for proper operation.
Then continue with step 4k on page 9.
NOTE
Adjust Operator for the SLOWEST operation practical, in accordance with the
latest revisions of the Americans with Disabilities Act (ADA); ANSI/BHMA
A156.19 Standards for Power-Assisted and Low Energy Power-Operated Doors; and
local codes.
Opening Speed: 5 seconds or more
Closing Speed: 3 seconds or more
Latch Location: 10 degrees or more
Latch Speed: 1.5 seconds or more
Features| Control| Description| Counter Clockwise|
Clockwise
---|---|---|---|---
Opening Speed| Opening Speed| Controls opening speed of door| Slower| Faster
Back Check
Speed
| Back Check Speed| Controls the speed of the door near the full
open position to prevent door slamming
| Slower| Faster
Hold Open Time Delay| Hold Open Time Delay| Controls the length of time the
door remains in the fully open position: 1 sec to
15 sec
| Less Time
Down to 1
sec
| More Time Up to 15 sec
Back Check
Position
| Back Check Position| Door position where back check speed engages| Less
Latch| More Latch
Closing Speed| Closing Speed| Controls closing speed of the door| Slower|
Faster
Delayed
Activation
| DLY (SW1)| Delays opening of door for strike applications (1-second delay)| |
Push and Go
| PNG (SW2)| ON: Pushing the door open 5° causes operator to open the door for
the remainder of open cycle| |
Power Boost
On or Off
| PB (SW3)| ON: 3-second power boost enabled: applies additional force to
close the door— used for high wind situations| |
| SW4| Not used| |
Release for Service
7a Remove all tools, installation equipment and debris from the vicinity of
the door.
7b MANDATORY: Install all Safety, Traffic Control and Instruction Labels onto
the door, as required. Failure to do this will leave the INSTALLER LIABLE for
any accidents that occur.
7c Give verbal instruction on how to properly operate the door to the owner or
person in charge.
7d Give verbal instruction to the owner or person in charge on periodic
inspection of the door for the following:
- Occasional damage
- Developing problems
- Minor preventative maintenance
7e Provide the owner or person in charge with a contact name and phone number
to call for future service and maintenance.
IMPORTANT
Be sure to install all Safety, Traffic Control, and Instruction Labels onto
the door, as required.
Benchmark III Software
8a Operation:
-
Sizing From start-up (Sizing), the door will activate via:
• 1-Way Input (Main Act and Main Act).
• 2-Way Input (3-Way OFF, 3-Way HO and 3-Way GND) with key switch in the ON position, uses either Main Act or Aux Act input
• Key switch in Hold Open position.
The first motion of the door will be towards the Door Open position. The speed during Sizing is automatic and cannot be set from a potentiometer.
The door drives to full open and the system sets the open counter to full open.
The door closes at Closing Speed. The system sets the closed counter to Full Closed when the latch goes up at the Closed position.
The system calculates all other parameters required for normal operation based on the two values of Full Open and Full Closed. -
Standard Operation
Upon a legitimate activation signal, the door accelerates to opening speed while monitoring the current load on the drive output. If the current exceeds the specified level, the door will stop and close.
The door travels at its set speed (based on the potentiometer setting) until it reaches the Back Check position, where it will decelerate to the Back Check Speed.
The door will stop at the Hold Open position and remain there until an activation or the Hold Open Timer is cleared.
The door then closes at its Closing Speed (based on the potentiometer setting) up to the latched position.
If the Closing Speed is decreased by driving the motor in the open direction (a fixed setting), power is added to allow the spring to continue closing the door to the Full Closed position.
Connection to external devices must be made using CL2, CL2P, CL2R, or CL2X Class 2 wire or equivalent.
© Allegion 2018
Printed in the U.S.A.
740158 Rev. 09/18-f
Documents / Resources
| LCN
9130 Series Complete Door
Closer
[pdf] Instruction Manual
9130 Series, Complete Door Closer, 9130 Series Complete Door Closer, 9140
Series, 9150 Series
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>