Honeywell 69-2384ES-01 RTH111 Non Programmable Thermostat Installation Guide

June 17, 2024
Honeywell

Honeywell 69-2384ES-01 RTH111 Non Programmable Thermostat

Product Information

Specifications

  • Product Name: RTH111 Non-Programmable Thermostat
  • Model Number: 69-2384ES-01
  • Compatibility: This thermostat is compatible with certain heating/cooling systems. It cannot be used on heat pumps with auxiliary/backup heat or on multistage systems.

Product Usage Instructions

Identify System Type

  1. Check if your system is compatible with the thermostat.

Remove Old Thermostat

  1. Turn off the power at the heating/cooling system.
  2. Remove the old thermostat, but leave the wallplate with wires attached. Do not remove the wallplate yet.
  3. If your old thermostat contains mercury in a sealed tube, contact your local waste management authority for recycling and proper disposal instructions.

Identify Wires

  1. If any wires are not attached to your old thermostat or are attached to a terminal marked C or C1, they will not be connected to your new thermostat. Wrap the bare metal end of each of these wires with electrical tape to prevent shorting.
  2. Identify and label each wire using terminal screw designations.
  3. Disconnect wires and remove the old wallplate only after all wires are labelled. Wrap the wires around a pencil to prevent them from falling through the wall opening.

Mount New Wallplate

  1. Loosen the locking screw at the bottom of the thermostat.
  2. Separate the thermostat from the wallplate.
  3. Position the wallplate against the wall and mark hole positions with a pencil.
  4. Drill holes at the marked positions and insert supplied wall anchors.
  5. Pass the wires through the large opening located at the bottom center of the wallplate.
  6. Secure the wallplate to the wall with supplied mounting screws.
  7. Connect the wires to the terminals as per the wiring diagram.

Connect Wires

  1. Match each labelled wire with the terminal having the same letter.
  2. Loosen the terminal screws, insert the wires, and tighten the screws.
  3. Push any excess wire back into the wall opening.

Alternate Wiring
If a labelled wire does not match any terminal designation, follow the provided diagram:

  • Do not use C, C1, or X wire.
  • Do not use B wire if you already have an O wire.
  • Wrap the bare end of the wire with electrical tape.
  • If your old thermostat had any two of the following wires: R, RC, RH, 4, and V, this thermostat cannot be used.
  • If you have a heat pump without auxiliary/backup heat, place a jumper (piece of wire) between Y and W terminals.

Frequently Asked Questions (FAQ)

  • Q: Can this thermostat be used on heat pumps with auxiliary/backup heat or on multistage systems?
    A: No, this thermostat is not compatible with heat pumps with auxiliary/backup heat or multistage systems.

  • Q: What should I do if my old thermostat contains mercury?
    A: Contact your local waste management authority for instructions regarding recycling and proper disposal of thermostats containing mercury.

  • Q: Can I use wires that are not connected to my old thermostat?
    A: No, do not use wires that are not connected to your old thermostat.

Do you need assistance?We are here to help. Call 1-800-468-1502.

Identify System Type

This thermostat is compatible with the following systems:

  • Gas, oil or electric furnace
  • Central air conditioner
  • Hot water system with or without pump
  • Millivolt system
  • Central heating and cooling system
  • Heat pump without auxiliary/backup heat

This thermostat cannot be used on heat pumps with auxiliary/backup heat or on multistage systems.

Remove Old Thermostat

  1. Turn power off at the heating/cooling system.
  2. Remove old thermostat, but leave wallplate with wires attached.

MERCURY NOTICE: Do not put your old thermostat in the trash if it contains mercury in a sealed tube. Contact your local waste management authority for instructions regarding recycling and proper disposal.

Identify Wires

If any wires are not attached to your old thermostat or are attached to a terminal marked C or C1, they will not be connected to your new thermostat. Wrap the bare metal end of each of these wires with electrical tape, so it cannot touch and short other wires.

Disconnect wires and remove the old wallplate only after all wires are labeled. Wrap the wires around a pencil to prevent them from falling though the wall opening.

Mount New Wallplate

  1. Loosen the locking screw at the bottom of the thermostat. Note that the screw is captive and cannot be removed from the wallplate.

  2. Separate the thermostat from the wallplate as per Figure 1.

  3. Position the wallplate against the wall and mark hole positions with a pencil.
    NOTE: Levelling is for esthetics only and will not affect the performance of the thermostat.

  4. Drill holes at the marked positions and insert supplied wall anchors.

  5. Pass the wires through the large opening located at the bottom center of the wallplate as per Figure 2.

  6. Secure the wallplate to the wall with supplied mounting screws as per Figure 3.

  7. Connect the wires to the terminals.

Connect Wires

Typical Wiring

  1. Match each labeled wire with the terminal having the same letter.
  2. Loosen the terminal screws using a screwdriver, insert the wires, then tighten the screws.
  3. Push any excess wire back into the wall opening.

Labels don’t match?
If a wire does not match any terminal on the thermostat, see next page.

Alternate Wiring
If a labeled wire does not match any terminal designation, see diagram below.

  1. Do not use C, C1 or X wire. Do not use B wire if you already have O wire. Wrap bare end of wire with electrical tape.
  2. This thermostat cannot be used if your old thermostat had any two of the following wires: R, RC, RH, 4 and V.
  3. Place a jumper (piece of wire) between Y and W if you have a heat pump without auxiliary/back-up heat.

Set Heating Fan Control

Set jumper JP1, on the back of the thermostat, if you have connected a wire to the G terminal.

  • HG. Leave the jumper in this factory-set position if you have a gas or oil furnace.
  • HE. Place the jumper to this position if you have an electric furnace.

Incorrect jumper setting: An incorrect setting is noticeable in a gas or oil heating system. When heating starts, you will initially feel cold air coming out of the vents as the fan is running before the furnace has enough time to heat up the air.

Set Heat Pump Reversing Valve
Set jumper JP2, on the back of the thermostat, if you have a heat pump.

  • O. Leave the jumper in this factory-set position if you have connected O wire to the O/B terminal.
  • B. Place the jumper to this position if you have connected B wire to the O/B terminal.

Incorrect jumper setting: The heat pump operation will be reversed, i.e., it will cool in Heat mode and will heat in Cool mode.

Install Batteries and Thermostat

  1. Install 2 AAA batteries on the back of the thermostat.
  2. Align the two brackets on the top of the thermostat with the corresponding slots on the top of the wallplate.
  3. Push the thermostat against the wallplate.
  4. Tighten the screw at the bottom of the thermostat.
  5. Turn power back on at the heating/cooling system.

System Setup

Follow the procedure below to personalize and configure the thermostat according to the heating/cooling system.

  1. Press the Up and Down buttons simultaneously (for three seconds) until the display appears as shown below. See table on the next page.
  2. Press the Up or Down button to change the option.
  3. Press the Up and Down buttons simultaneously for one second to advance to the next function.
  4. When the last function is displayed, press the Up and Down buttons to save any changes and exit the menu.

NOTE: If you do not press any button for 60 seconds while you are in the setup menu, the thermostat automatically saves any changes made and exits the menu. At any time you can save the changes and exit by pressing the Run button.

  • Damage can occur if the compressor is restarted too soon after shutdown. This feature forces the compressor to wait 5 minutes before restarting. During the wait time, the message Cool On or Heat On flashes on the screen. When the safe wait time has elapsed, the message stops flashing and the compressor turns on.

Automation and Control Systems
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
http://DIYthermostats.honeywell.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals