TECH EU-292 Two State Traditional Communication User Manual
- June 16, 2024
- TECH
Table of Contents
USER MANUAL
EU-292 v2, v3
Safety
Before using the device for the first time the user should read the following
regulations carefully.
Not obeying the rules included in this manual may lead to personal injuries or
controller damage.
The user’s manual should be stored in a safe place for further reference. In
order to avoid accidents and errors it should be ensured that every person
using the device has familiarized themselves with the principle of operation
as well as security functions of the controller. If the device is to be sold
or put in a different place, make sure that the user’s manual is there with
the device so that any potential user has access to essential information
about the device.
The manufacturer does not accept responsibility for any injuries or damage
resulting from negligence; therefore, users are obliged to take the necessary
safety measures listed in this manual to protect their lives and property.
WARNING
- The device should be installed by a qualified electrician.
- The regulator should not be operated by children.
WARNING
- Any use other than specified by the manufacturer is forbidden.
- Before and during the heating season, the controller should be checked for condition of its cables. The user should also check if the controller is properly mounted and clean it if dusty or dirty.
Care for the natural environment is our priority. Being aware of the fact that we manufacture electronic devices obligates us to dispose of used elements and electronic equipment in a manner which is safe for nature. As a result, the company has received a registry number assigned by the Main Inspector of Environmental Protection. The symbol of a crossed out rubbish bin on a product means that the product must not be thrown out to ordinary waste bins. By segregating waste intended for recycling, we help protect the natural environment. It is the user’s responsibility to transfer waste electrical and electronic equipment to the selected collection point for recycling of waste generated from electronic and electrical equipment.
II. Description of the device
EU-292 room regulator is intended for controlling the heating or cooling
device (e.g. gas, oil or electric furnace or the CH boiler controller). Its
main task is to maintain the pre-set temperature in the flat by sending a
signal to the heating/cooling device (contact opening) when the desired
temperature is reached.
Advanced software enables the regulator to fulfil a wide range of functions:
- maintaining the pre-set room temperature
- manual mode
- day/night program
- weekly control
- control of the underfloor heating system (optional; an additional temperature sensor is necessary)
Controller equipment:
- touch buttons
- front panel made of 3mm glass
- built-in temperature sensor
- batteries
Controller versions:
- v2 – wireless, with temporary backlight. It may be optionally equipped with a wireless external sensor. This controller version cooperates with an additional signal receiver, installed near the heating device.
- v3 – wired, with temporary backlight.
Installation
The controller should be installed by a qualified person. The diagrams below show an example of connecting the regulator to the controller and heating device.
EU-292 controller may be installed as a panel mountable on the wall. You can use the stand and place the regulator anywhere.
III.a) Connection diagrams (3 versions)
The room regulator should be connected to the heating device via a two-core
cable. When connecting devices with over 1A load, it is necessary to use a
contactor. Optionally, it is possible to connect an additional sensor to the
floor sensor contact – additional functions will appear in the controller
menu.
In the case of wireless connection, use the diagram below – the two-core communication cable must be connected to appropriate sockets in the receiver.
Connection diagrams EU-292v2
In the case of wireless connection, use the diagram below – the two-core communication cable must be connected to appropriate sockets in the receiver
WARNING
If pump manufacturer requires an external main switch, power supply fuse or
additional residual current device selective for distorted currents it is
recomemnded not to connect pumps directly to pump control outputs.
To avoid damaging to the device, an additional safety circuit must be used
between the regulator and the pump. The manufacturer recommends the ZP-01 pump
adapter, which must be purchased separately.
Receiver for wireless controller
EU-292v2 regulator communicates with the heating device (or the CH boiler controller) via radio signal sent to the receiver. The receiver is connected to the heating device (or CH boiler controller) via a two-core cable whereas the communication with the room regulator is performed wirelessly via radio signal.
The receiver has the following control lights:
- green 1 (1)– indicates data reception, goes on during channel change;
- red (2)– indicates receiver operation;
- green 2 (3) – goes on when the room temperature fails to reach the pre-set value – the heating device is switched on.
NOTE
In case of communication failure (e.g. when the battery is flat), the receiver
automatically disconnects the heating device after 15 minutes.
NOTE
In case of communication failure (e.g. when the battery is flat), the receiver
automatically disconnects the heating device after 15 minutes.
How to change the communication channel
Channel “35” is the default communication channel in the room regulator.
The channel may be easily changed (if the current channel is used by other
devices). To change the channel, press and hold the channel change button (4)
for about 10 seconds until the green control light (1) goes on. Next, change
the communication channel in the room regulator following the procedure
described in part VII.c.7. Confirm with the channel change button. The green
light on the receiver should go off.
External temperature sensor
EU-292v2 room regulator may optionally be equipped with an external
temperature sensor. The ensor should be mounted in a shaded place so that it
is not affected by the weather conditions.
The current temperature value will be sent to the room regulator every few
minutes and it will be displayed on the main screen.
The external sensor communicates with the room regulator via radio signal.
Both the room regulator and the external sensor are pre-configured to operate
on channel “35”, but the user may easily change the channel (if the current
channel is used by other devices).
How to change communication channel:
In order to change the channel, press and hold the channel change button.
After the control light on the sensor flashes, the process of channel change
has been initiated. Hold the button and wait until the light starts flashing
again. The number of flashes corresponds to the first digit of the desired
channel number.
Release the button after the desired number of flashes and press it again to
set the second digit of the channel number – the control light flashes quickly
twice. Hold the button and wait until the light flashes the desired number of
times. When the button is released, the control light flashes twice – the new
communication channel has been set.
NOTE: In case of a one-digit channel number (channels 0÷9) set 0 as the
first digit.
Example 1:
28 is the desired communication channel. In order to select this channel, set
the first digit – 2, and the second digit – 8.
Press and hold the channel change button – the control light flashes quickly
once – the process of channel change has been initiated. Hold the button and
wait until the light flashes two more times (the first digit of the channel
number – 28).
Release the button and press it again – the control light flashes quickly
twice – the process of setting the second digit has been initiated. Hold the
button and wait until the light flashes 8 times.
When the button is released, the control light flashes quickly twice – the new
communication channel has been successfully set.
Example 2:
7 is the desired communication channel. In order to select this channel, set
the first digit – 0, and the second digit – 7.
Press and hold the channel change button – the control light flashes quickly
once – the process of channel change has been initiated. As the first digit is
0, release the button before the control light flashes again. Press the button
again – the control light flashes quickly twice – the process of setting the
second digit has been initiated. Hold the button and wait until the light
flashes 7 times (the second digit of the desired number). When the button is
released, the control light flashes quickly twice – the new communication
channel has been successfully set.
In case of errors in the channel change process, the control light goes on for ca. 2 seconds. In such a case the channel will not be changed.
First start-up
EU-292 v2:
In order for the controller to operate correctly, the user must follow these
steps when starting the device for the first time:
- Remove the front cover of the controller and insert the batteries.
- If the room regulator is to control the underfloor heating system, connect the additional sensor to the floor sensor contact.
- In the case of EU-292v2 connect the two-core cable to appropriate sockets in the receiver.
- Check if the current communication channel selected in the regulator is the same as in the receiver. “35” is the default communication channel in all devices. If there is a conflict with other devices using radio communication, the user needs to select a different channel.
EU-292 v3:
In order for the controller to operate correctly, the user must follow these
steps when starting the device for the first time:
- Remove the front cover of the controller and insert the batteries.
- If the room regulator is to control the underfloor heating system, connect the additional sensor to the floor sensor contact.
- Connect the controller to the heating device using a two-core cable.
NOTE
One zone may only have one room regulator assigned to it. If more room
regulators are assigned to one zone, the external controller will not work
properly.
VII. How to use the controller
VII.a) Principle of operation
The main task of EU-292 room regulator is to maintain the pre-set temperature
of the room by sending a signal to the heating/cooling device (contact
opening) when the desired temperature is reached. In such a situation, the
heating/cooling device is switched off (if the regulator is connected to the
CH boiler controller, the CH boiler enters sustain mode).
If the regulator is used in heating mode, it may cooperate with the underfloor
heating sensor.
In such a case, the contact remains closed when the floor temperature is below
the minimum threshold. After the threshold value has been reached, the contact
remains closed until the preset room temperature is reached. If the floor
sensor temperature exceeds the maximum value, the regulator opens the contact
regardless of the current room temperature.
NOTE
In order for the underfloor heating functions to be available in the
controller menu, it is necessary to connect an additional sensor to the floor
sensor contact.
VII.b) Operation modes
The user has three operation modes to choose from:
-
Day/night mode
In this mode the pre-set temperature value depends on the current time of the day. The user may set different temperature values for the daytime and nighttime (comfort temperature and economical temperature) as well as define the exact time of entering day mode and night mode.
In order to activate this mode, press EXIT button until day/night mode icon appears on the main screen.
-
Weekly control
This mode enables the user to define the time when the pre-set comfort temperature and the preset economical temperature will apply. The user may set 9 different programs divided into three groups:
– programs 1÷3 – daily temperature values are set for all days of the week;
– programs 4÷6 – daily temperature values are set separately for the weekdays (Monday-Friday) and for the weekend (Saturday-Sunday);
– programs 7÷9 – daily temperature values are set for each day of the week separately.
* The display shows the hours when the comfort temperature applies. In the remaining time period economical temperature applies.
In order to activate this mode, press and hold EXIT button until the weekly control icon appears on the main screen. -
Manual mode
In this mode the pre-set temperature is adjusted manually from the main screen view with the use of these buttons: or . Manual mode is activated when one of these buttons is pressed.
When the manual mode is activated, the previous operation mode enters ‘sleep mode’ until the next pre-programmed temperature change. Manual mode may be deactivated by pressing EXIT button.
Example 1 – manual mode activation in Day/night mode
When Day/night mode is active, the user changes the pre-set temperature by
pressing or which automatically activates manual mode.
The controller returns to Day/night mode when daytime changes into nighttime
(or the other way round) or when the user presses EXIT button.
Example 2 – manual mode activation in weekly control mode
When weekly control is active, the user changes the pre-set temperature by
pressing or , which automatically activates manual mode.
The controller returns to weekly control mode when, according to the weekly
schedule, economical temperature changes into comfort temperature (or the
other way round) or when the user presses EXIT button.
VII.b) Main screen view and description
The user operates the device using buttons. While one parameter is being
edited, the remaining icons are not displayed.
- Display
- EXIT – pressing this button in the main screen view activates weekly control mode or day/night mode. After entering the menu, this button is used to confirm the settings and return to the main screen view.
- Minus button ( ) – pressing this button in the main screen view activates manual mode and decreases the pre-set temperature. After entering the menu, this button is used to adjust parameters, enter the service code etc.
- Plus button ( ) – pressing this button in the main screen view activates manual mode and increases the pre-set temperature. After entering the menu, this button is used to adjust parameters, enter the service code etc.
- MENU button – hold this button in order to enter the controller menu. While editing parameters press this button to confirm the changes and move on to edit the next parameter.
-
Current operation mode:
a. weekly
b. manual
c. day/night -
Current temperature of the room
-
Parameters icons (see: table below)
-
Day of the week
-
Icon indicating economical temperature (according to weekly control or day/night settings)
-
Icon indicating comfort temperature (according to weekly control or day/night settings)
-
Icon which indicates displaying current external temperature (no. 9 on the display), active only with wireless controllers (EU-292v2) or with external temperature sensor.
-
Icon which indicates displaying current floor temperature (no. 9 on the display) – it is necessary to connect the floor sensor and activate it in the controller menu.
-
External temperature alternately with floor temperature
-
Pre-set temperature of the room
-
Time
-
Battery level
-
Temperature information (depending on the current operation mode):
o heating mode – the icon is flashing when the pre-set temperature of the room has not been reached and it is steady when the pre-set temperature has been reached.
o cooling mode – the icon is moving when the room temperature is above the preset value and it is steady when the pre-set temperature has been reached.
Parameters icons:
| Time settings| | Weekly control settings
---|---|---|---
| Day from…| | Floor sensor
| Night from…| | Comfort temperature
| Optimum start / heatingcooling mode selection (in service menu)| |
Economical temperature
| Channel selection| | Hysteresis
| | | Temperature sensor calibration
VII.c) Controller functions
The user navigates the menu structure using , , EXIT and MENU. In order to
edit particular parameters, press MENU. Next, press MENU to view the
controller functions – the edited parameter is flashing whereas the remaining
parameters are not displayed. Use or to change the parameter settings. Press
MENU to confirm the changes and move on to edit the next parameter or press
EXIT to confirm the changes and return to the main screen view.
V.c.1) Block diagram – main menu
*Functions available in the menu after the floor sensor has been activated by connecting the additional sensor to the floor sensor contact and selecting ON in Floor sensor submenu.
VII.c.2) Day of the week
After entering the main menu, all icons which are not connected with the
parameter which is being edited are not displayed. The first parameter is day
of the week.
Press or until the current day of the week is displayed. Press MENU to confirm
and move on to the next parameter or press EXIT to confirm and return to the
main screen view.
VII.c.3) Time settings
In order to set current time, press MENU until time setting panel is displayed
on the screen.
By pressing or set the hour and minutes.
Press MENU to confirm and move on to the next parameter or press EXIT to
confirm and return to the main screen view.
VII.c.4) Day from…
This function enables the user to define the exact time of entering the day
mode. When Day/nightmode is active, comfort temperature applies atdaytime.
To configure this parameter press MENU until Day from… setting appears on the
screen.
By pressing or set the hour and minute ofday mode activation.
Press MENU to confirm and move on to the next parameter or EXIT to confirm and
return to themain screen view
VII.c.5) Night from…
This function enables the user to define the exact time of entering the night
mode. When Day/night mode is active, economical temperature applies at
nighttime.
To configure this parameter press MENU until Night from… setting appears on
the screen.
By pressing or set the hour and minute of night mode activation.
Press MENU to confirm and move on to the next parameter or press EXIT to
confirm and return to the main screen view.
VII.c.6) Optimum start
Optimum start is an intelligent system controlling the heating/cooling
process. It involves constant monitoring of the heating/cooling system
efficiency and using the information to activate the heating/cooling process
in advance in order to reach the pre-set temperatures.
The system requires no user intervention. It precisely reacts to any changes
that affect the efficiency of the heating system. If, for example, some
changes have been introduced to the heating system and the house heats up
faster than before, the Optimum start system will recognize the changes at
the next pre-programmed temperature change (from comfort to economical) and in
the next cycle the heating system activation will be adequately
delayed,reducing the time needed to reach the desired temperature.
A – pre-programmed change
from economical temperature to comfort temperature
Activating this function means that at the time of pre-programmed change of
the pre-set temperature from comfort to economical or the other way round, the
current room temperature is close to the desired value.
In order to configure this parameter, press MENU until Optimum start setting
panel appears on the screen.
Use or to activate or deactivate Optimum start function. Press MENU to confirm
and move on to edit the next parameter or press EXIT to confirm and return to
the main screen view.
VII.c.7) Service menu
Certain functions in the controller service menu are secured with a code. In
order to adjust their parameters, press MENU until Service menu settings
appear on the screen.
To view the service menu it is necessary to enter the code – 215. Use or to
select the first digit (2) and confirm by pressing and holding MENU until the
next digit starts flasihing. Follow the same steps selecting the remaining two
digits.
Heating/cooling mode
This function enables the user to select the room regulator operation mode:
– controlling the cooling system
– controlling the heating system
Press or to select desired type of system.
Press MENU to confirm and move on to edit another parameter in the service
menu or press EXIT to confirm to return to the main screen view.
WARNING
DO NOT select cooling system control if a floor sensor is used as it may
damage the underfloor heating system.
Channel selection (option available only in EU-292v2)
EU-292v2 communicates with the heating device or the CH boiler controller via
a receiver using a radio signal. For the communication to take place it is
necessary to select the same channel in both the controller and the receiver
(and also in the external sensor if it is used). Channel “35” is the default
communication channel in all devices.
The channel should be changed only if the current channel is used by other
devices.
In order to change, go to service menu and press MENU until the channel change
panel appears on the screen. Use or to select the channel. Press MENU to
confirm and move on to the next parameter or EXIT to confirm and return to
the main screen view.
VII.c.8) Weekly control
This function is used to change the current weekly control program and edit
the weekly programs.
-
How to change the current weekly program number
When weekly control is enabled (see: V.b Operation modes) the current program is activated. In order to choose the program number, press MENU until weekly program setting appears on the screen.
By pressing and holding MENU button the user opens the program selection panel. Each time the user holds the MENU button, the program number changes. When the desired number appears on the screen, press EXIT – the controller returns to the main screen view and the selected program number is set.
-
How to configure particular weekly programs
Weekly program allows the user to define the time when comfort temperature and economical temperature will apply. Depending on the program number, the user may set daily temperature values for all days of the week (programs 1÷3), for weekdays and the weekend separately (programs 4÷6) and for each day of the week separately (programs 7÷9).
In order to edit weekly program, press MENU until weekly program setting panel appears on the screen.
STEP 1 – choose the program to be edited:
By pressing and holding MENU button the user opens the program editing panel.
Each time the user holds the MENU button, the program number changes. When the
desired number appears on the screen, the user may start editing its
parameters.
Step 2 – select days of the week
If the user wants to edit programs 1÷3, there is no possibility of selecting
particular days of the week as the setting applies to each day.
If the user wants to edit programs 4÷6 , it is possible to edit the settings
for weekdays and the weekend separately. Press MENU in order to select.
If the user wants to edit programs 7÷9, it is possible to edit the settings
for each day separately.
Press MENU in order to select a day.
Step 3 – assign comfort temperature or economical temperature to particular
hours
An hour which is being edited is displayed on the controller screen. In order
to assign comfort temperature, press . In order to select economical
temperature, press . The controller automatically moves on to editing the next
hour.
The parameters of the weekly program are displayed at the bottom of the
screen: hours to which comfort temperature has been assigned are displayed
whereas hours to which economical temperature has been assigned are not
displayed.
Example:
The following screenshot presents daily settings of program no. 7 for Monday
24⁰⁰-01⁵⁹- economical temperature
02⁰⁰-06⁵⁹- comfort temperature
07⁰⁰-14⁵⁹- economical temperature
15⁰⁰-21⁵⁹- comfort temperature
22⁰⁰-00⁵⁹- economical temperature
NOTE
When the user finishes the editing process by pressing EXIT button, the
controller returns to the main screen view and this program is selected as the
current program.
VII.c.9) Floor sensor
NOTE
This parameter is not available in the menu if the additional sensor has not
been connected to the floor sensor contact or when the cooling mode is
selected.
This function enables the user to activate the floor sensor. When the floor sensor is enabled, the contact status depends also on the floor temperature. The contact remains closed (the device is on) when the floor temperature is lower than the minimum value (regardless of the room temperature). When the minimum temperature of the floor sensor has been exceeded, the contact remains closed until the pre-set room temperature is reached. If the floor sensor temperature exceeds the maximum value, the contact is opened (the device is disabled) regardless of the current room temperature.
Use or to activate/deactivate the floor sensor by selecting ON or OFF.
Press MENU to confirm and move on to edit the next parameter or press MENU to confirm and eturn to the main screen view.
NOTE
Selecting ON is necessary for the following functions to appear in the menu:
maximum floor temperature, floor sensor hysteresis and minimum floor
temperature.
VII.c.10) Maximum floor temperature
It is the floor temperature threshold. When this threshold is exceeded, the
contact opens (the device is switched off) regardless of the current room
temperature.
Press MENU until the maximum floor temperature panel appears on the screen (it
is necessary to activate the floor sensor beforehand by selecting ON)
Use or to select desired temperature value.
Press MENU to confirm and move on to edit the next parameter or press MENU to
confirm and return to the main screen view.
VII.c.11) Floor temperature hysteresis
Floor temperature hysteresis defines the floor temperature tolerance in order
to prevent undesired oscillation in case of small temperature fluctuation
within the range of 0,4 ÷ 5°C. This parameter concerns both the maximum and
the minimum floor temperature.
Example:
Maximum floor temperature = 45°C
Hysteresis = 2°C
Minimum floor temperature = 30⁰C
The room regulator disables the contact when the temperature of 45⁰C on the
floor sensor is exceeded. When the temperature starts falling, the contact is
activated again at the temperature of 43⁰C on the floor sensor (unless the
pre-set room temperature has been reached).
With the minimum floor temperature the hysteresis function works the other way
round. After the value of 30⁰C has been reached on the floor sensor, contact
opening/closing depends only on the current room temperature (reaching this
value opens the contact). When the floor sensor temperature drops to 28⁰C the
contact closes regardless of the current room temperature.
In order to set the floor temperature hysteresis, press menu until hysteresis
panel appears on the screen (floor sensor must be activated beforehand by
selecting ON)
Use or to select desired hysteresis value.
Press MENU to confirm and move on to edit the next parameter or press MENU to
confirm and return to the main screen view.
VII.c.12) Minimum floor temperature
Minimum floor temperature concerns the underfloor heating system operation.
After this value has been reached by the floor sensor, contact opening and
closing depends only on the current room temperature. Below this value the
contact remains closed regardless of other factors.
Press MENU until the minimum floor temperature panel appears on the screen (it
is necessary to activate the floor sensor beforehand by selecting ON)
Use or to select desired temperature value.
Press MENU to confirm and move on to edit the next parameter or press MENU to
confirm and return to the main screen view.
VII.c.13) Pre-set comfort temperature
Pre-set comfort temperature is used in weekly control mode and day/night mode.
Press MENU button until the comfort temperature change panel appears on the
screen.
Press or to set the desired temperature.
Press MENU to confirm and move on to the next parameter or press EXIT to
confirm and return to the main screen view.
VII.c.14) Pre-set economical temperature
Pre-set economical temperature is used in weekly control mode and day/night
mode. Press MENU button until the economical temperature change panel appears
on the screen.
Press or to set the desired temperature.
Press MENU to confirm and move on to the next parameter or press EXIT to
confirm and return to the main screen view.
VII.c.15) Pre-set temperature hysteresis
Room temperature hysteresis defines the pre-set temperature tolerance in order
to prevent undesired oscillation in case of small temperature fluctuation
(within the range of 0,2 ÷ 4°C).
Example:
Pre-set temperature: 23°C
Hysteresis: 1°C
The room regulator reports that the temperature is too low only when the room
temperature drops to 22 °C.
In order to set the hysteresis, press MENU until the hysteresis setting
appears on the screen.
Use or to set the desired hysteresis value. Press MENU to confirm and move on
to the next parameter or press EXIT to confirm and return to the main screen
view.
VII.c.16) Temperature sensor calibration
It is performed when mounting the regulator or after it has been used for a
long time, if the room temperature measured by the internal sensor differs
from the actual temperature. Calibration setting range is from -10°C to +10°C
with the accuracy of 0,1°C.
Press MENU until the sensor calibration panel appears on the screen. Use or to
define correction. Press MENU to confirm and move on to edit the next
parameter or press MENU to confirm and return to the main screen view.
Technical data
Range of room temperature settings | 5 o C ÷ 35 o C |
---|---|
Supply voltage | Batteries 2xAA, 1,5V |
Potential-free cont. nom. out. Load (EU-292 v3) | 230V AC / 0,5A (AC1) * |
24V DC / 0,5A (DC1) **
Measurement error| -/+0,5°C
Frequency (EU-292 v2)| 868MHz
Room regulator power supply EU-292v2
Supply voltage | 230V+/-10%/50Hz |
---|---|
Ambient temperature | 5 |
o
C ÷ 50
o
C
Frequency| 868MHz
Potential-free cont. nom. out. Load| 230V AC / 0,5A (AC1) *
24V DC / 0,5A (DC1) **
- AC1 load category: single-phase, resistive or slightly inductive AC load.
** DC1 load category: direct current, resistive or slightly inductive load.
EU Declaration of conformity
Hereby, we declare under our sole responsibility that EU-292v3 manufactured by TECH STEROWNIKI II Sp. z o.o., head-quartered in Wieprz Biała Droga 31, 34-122 Wieprz, is compliant with Directive 2014/35/EU of the European Parliament and of the Council of 26 February 2014 on the harmonisation of the laws of Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits (EU OJ L 96, of 29.03.2014, p. 357), Directive 2014/30/EUof the European Parliament and of the Council of 26 February 2014 on the harmonisation of the laws of Member States relating to electromagnetic compatibility (EU OJ L 96 of 29.03.2014, p.79), Directive2009/125/EC establishing a framework for the setting of ecodesign requirements for energy-relatedproducts as well as the regulation by the MINISTRY OF ENTREPRENEURSHIP AND TECHNOLOGY of 24June 2019 amending the regulation concerning the essential requirements as regards the restriction ofthe use of certain hazardous substances in electrical and electronic equipment, implementing provisionsof Directive (EU) 2017/2102 of the European Parliament and of the Council of 15 November 2017amending Directive 2011/65/EU on the restriction of the use of certain hazardous substances in electricaland electronic equipment (OJ L 305, 21.11.2017, p. 8).
For compliance assessment, harmonized standards were used:
PN-EN IEC 60730-2-9:2019-06, PN-EN 60730-1:2016-10, PN EN IEC 63000:2019-01
RoHS.
Wieprz, 22.07.2020
EU Declaration of conformity
Hereby, we declare under our sole responsibility that EU-292v2 manufactured by TECH STEROWNIKI II Sp. z o.o., head-quartered in Wieprz Biała Droga 31, 34-122 Wieprz, is compliant with Directive 2014/53/EU of the European parliament and of the Council of 16 April 2014 on the harmonisation of the laws of the Member States relating to the making available on the market of radio equipment, Directive 2009/125/EC establishing a framework for the setting of ecodesign requirements for energy-related products as well as the regulation by the MINISTRY OF ENTREPRENEURSHIP AND TECHNOLOGY of 24 June 2019 amending the regulation concerning the essential requirements as regards the restriction of the use of certain hazardous substances in electrical and electronic equipment, implementing provisions of Directive (EU) 2017/2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment (OJ L 305, 21.11.2017, p. 8).
For compliance assessment, harmonized standards were used:
PN-EN IEC 60730-2-9 :2019-06 art. 3.1a Safety of use
ETSI EN 301 489-1 V2.2.3 (2019-11) art.3.1b Electromagnetic compatibility
ETSI EN 301 489-3 V2.1.1:2019-03 art.3.1 b Electromagnetic compatibility
ETSI EN 300 220-2 V3.2.1 (2018-06) art.3.2 Effective and coherent use of radio
spectrum
ETSI EN 300 220-1 V3.1.1 (2017-02) art.3.2 Effective and coherent use of radio
spectrum
PN EN IEC 63000:2019-01 RoHS
Wieprz, 22.07.2020
EU-292 User’s manual
Central headquarters:
ul. Biata Droga 31, 34-122 Wieprz
Service:
ul. Skotnica 120, 32-652 Bulowice
phone: +48 33 875 93 80
e-mail: serwis@techsterowniki.pl
www.tech-controllers.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>