WK PXU140 White Knight Fluid Handling Owner’s Manual

June 16, 2024
WK

PXU140 White Knight Fluid Handling

Product Information

Specifications & Performance

  • Model: PXU140

  • Max Flow Rate: 139.9 lpm (36.96 gpm)

  • Displacement Per Cycle: 0.5 liters (0.132 gal)

  • Cycles per min: 247 max

  • Air Connection: 3/8 in

  • Weight: 20.4 kg (45 lb)

  • Suction Lift: 1 m (3 ft)

  • Sound Pressure: 76.9 dB(a) at 100 psi 50 CPM, 80.19 dB(a) at
    100 psi max CPM

  • Power: 74.22 dB(a) at 100 psi 50 CPM, 76.42 dB(a) at 100 psi
    max CPM

Product Usage Instructions

1. Installation

Before installing the PXU140 pump, please ensure that you have
read and understood the installation requirements and setup
instructions provided in the manual. Follow the steps below for
proper installation:

  1. Select a suitable location for the pump, ensuring it is placed
    on a stable and level surface.

  2. Connect the air supply hose to the air connection port on the
    pump.

  3. Connect the pump’s inlet and outlet hoses to the desired fluid
    system.

  4. Securely tighten all hose connections to prevent leaks.

  5. Verify that the suction lift is within the recommended range
    (less than 3 ft above the fluid source).

  6. Double-check all connections and ensure that the pump is
    properly aligned.

  7. Once the installation is complete, refer to the control and
    monitoring section for operating instructions.

2. Control & Monitoring

The PXU140 pump features intuitive controls and monitoring
capabilities. Follow the steps below to operate and monitor the
pump:

  1. Ensure that the air supply is connected and the pump is
    properly installed.

  2. Turn on the air supply to the pump.

  3. Adjust the air pressure to the desired level using the control
    knob on the air supply.

  4. The pump will start automatically and begin pumping fluid.

  5. Monitor the flow rate and pressure using the built-in gauges on
    the pump.

  6. If adjustments are required, use the control knob on the air
    supply to regulate the air pressure.

  7. To stop the pump, turn off the air supply.

FAQ

Q: Can the suction lift be increased beyond 3 ft?

A: It is not recommended to exceed the maximum suction lift of 3
ft for optimal performance and longevity of the pump. Exceeding
this limit may result in decreased efficiency and potential damage
to the pump.

Q: How often should I perform maintenance on the PXU140

pump?

A: Regular maintenance is recommended to ensure the pump
operates at its best. It is advised to follow the maintenance
schedule provided in the manual. Additionally, any signs of
abnormal operation or decrease in performance should prompt
immediate inspection and maintenance.

Q: Can the PXU140 pump handle high-pressure chemical

delivery?

A: Yes, the PXU140 pump is designed to meet the requirements of
high-pressure chemical delivery systems. However, it is important
to ensure that the pump is properly configured and compatible with
the specific chemicals being used.

engineer approvedTM
PXU140 Owner’s Manual

187 E. 670 S., Kamas, UT 84036 435.783.6040 888.796.2476 https://wkfluidhandling.com

Table of Contents

1. Product Information

1

1.1 Specifications & Performance ……………………………………………………………………………….1 1.2 Temperature Limits………………………………………………………………………………………………2 1.3 Dimensions ………………………………………………………………………………………………………..2 1.4 Bill of Materials……………………………………………………………………………………………………3

2. Installation

4

2.1 Precautions ………………………………………………………………………………………………………..4 2.2 Warnings ……………………………………………………………………………………………………………5 2.3 Advantages ………………………………………………………………………………………………………..5 2.4 Environment & System…………………………………………………………………………………………5 2.5 Proximity Sensor Installation…………………………………………………………………………………6 2.6 Installation Instructions…………………………………………………………………………………………7

3. Control & Monitoring

8

3.1 Proximity Detection Wiring Information …………………………………………………………………..9 3.2 Shift Logic for Proximity Pumps …………………………………………………………………………….9 3.3 Conductivity Leak Detection Installation…………………………………………………………………..10 3.4 Fiber Optic Leak Detection Installation ……………………………………………………………………10 3.5 Calibrating D10 Amplifier for Fiber Optic Leak Detection………………………………………… 11

4. Ordering Instructions

12

5. Pump Service

13

5.1 Rebuild Kits & Parts …………………………………………………………………………………………..13 5.2 Return Pump for Service…………………………………………………………………………………….14

6. Warranty & Accessories

16

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Version 2.2.2 | 5 Dec 2023 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

Dear valued customer,
Thank you for purchasing a White Knight PXU140 pump.
Our dedicated team designs products to meet your exacting specifications with a demonstrated commitment to quality that goes beyond mere words and fancy slogans.
Our patented designs offer a variety of size and material options to meet stringent requirements of high-pressure chemical delivery systems, hightemperature re-circulation processes, chemical reclaim and bulk transport applications, slurry systems, and more. Our safe, reliable products offer superior performance, optimized efficiency, and simplified maintenance.
White Knight is able to provide the highest quality fluid handling products through controlled, consistent in-house engineering and manufacturing. Through continued significant investments in engineering and manufacturing, we lead the industry with new technologies and products.
White Knight has received numerous awards for innovation and manufacturing programs. We rigorously manage our quality assurance processes to ensure consistency and reliability. Our quality controls include strict cleanliness procedures and consistent manufacturing processes. For example, high-purity product assembly, testing, and packaging is performed in a Class 100 cleanroom.
Please peruse this manual before installing your White Knight product. It details installation requirements and setup instructions, and provides additional information and accessories for enhanced functionality.
Our team has gone to great lengths to ensure our products serve your needs and meet your requirements.
Further, we provide the highest quality products at the best value, and we back them up with excellent warranties and world class support.
Thank you for your confidence and trust in White Knight products.
Sincerely,
White Knight Fluid Handling

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

1. Product Information
1.1 Specifications & Performance

Model

PXU140

Max Flow Rate*

139.9 lpm (36.96 gpm)

Displacement Per Cycle*

0.5 liters (0.132 gal)

Cycles per min

247 max

Air Connection

3/8 in

Weight

20.4 kg (45 lb)

Suction Lift*

1 m (3 ft)

Sound

Pressure**

76.9 dB(a) at 100 psi 50 CPM 80.19 dB(a) at 100 psi max CPM

Power**

74.22 dB(a) at 100 psi 50 CPM 76.42 dB(a) at 100 psi max CPM

  • May vary by configuration or system. Suction lift diminishes over time. Recommended installation level less than 3 ft above source. To calculate displacement, divide flow rate by CPM. ** Sound measured in accordance with ISO9614-2:1997.

Max Fluid Temperature
Environmental Temperature
Max Supply Air Pressure
Min Startup Air Pressure
Fluid Path Materials
Non-Fluid Path Materials

210°C (412°F) min: 0°C (32°F) max: 50°C (122°F) 7 Bar (100 psi)
1.4 Bar (20 psi)
PTFE, PFA
PTFE, PFA, SS

Stroke Detection
Leak Detection
Electronic Control

Proximity stroke detection
Fiber optic with or without sensor, or conductivity CPC, CPT, or custom. Call for details.

Discharge Pressure

PXU140 Performance

100

7 100 PSI

Air Pressure

How to Read Charts Draw a horizontal line at

90
6

100 CPM 130 CPM

Air Consumption Cycle Rate

your discharge pressure and vertical line at desired

80

80 PSI

40 SCFM

flow rate. At line intersect,

70

5

160 CPM

estimate required air pressure, resultant cycle

60 PSI 60
4

30 SCFM

180 CPM

rate and air consumption. Example

50

200 CPM

At 2 Bar (30 psi) discharge

3 40 PSI
40

pressure and 80 psi supply pressure, PXU140 pumps

220 CPM

provide 95 lpm (25 gpm) flow

30

2

20 SCFM

230 CPM

rates. They would cycle at 210 CPM and exhaust 38

20 PSI 20

SCFM of air.

1
10

10 SCFM

240 CPM

*Graph is for reference only. Performance was measured

PSI Bar

utilizing 1/2 in (3/8 in ID) air

LPM

20

40

60

80

100

120

140 line and 1-1/4 in (1-1/8 in ID)

liquid lines with 1 ft flooded

m3/hr

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

suction. Performance may

GPM 2 4 6 8 10 12 1 4 16 1 8 20 22 24 26 28 3 0 32 34 3 6

vary in your system.

Liquid Flowrate

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 1 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

1.2 Temperature Limits

140°F 7

180°F

220°F

260°F

300°F

340°F

380°F

420°F 100

90 6
80 5
70

Air Supply Pressure

4

60

50
3 40

2

30

1 Bar 60°C

80°C

100°C

120°C

140°C

160°C

180°C

200°C

20
PSI 220°C

1.3 Dimensions
Dimensions in [mm] in
298 11.7

MOUNT WITH 2 EA. 3/8″ (10 mm) SOCKET HEAD CAP SCREWS

13

30

.5

1.2

76

3.0

60 2.4

384 15.1

103 4.1

234

9.2

249 9.8

224

CL

8.8

138 5.4

256

201

10.1

7.9

10

62

.4

2.4

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 2 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

1.4 Bill of Materials

PXU140 BILL OF MATERIALS

Item Part Number Description

Qty.

1 1125-TE-0022 Body, Pump

1

2 2127-TE-0039 Head, Right

1

3 2127-TE-0040 Head, Left

1

4 14300-MP-0023 Bellows Assembly

2

5 14320-PF-0003 Shaft

1

6 5143-MP-0005 Seal, Shaft

2

7 14200-TE-0004 Base Plate Assembly

1

8 4142-MP-0007 Top Check Seat

2

9 4100-MP-0003 1-1/8″ Check Ball

4

10 4140-TE-0007 Check Plug

2

11 4137-TE-0003 Check Cage

2

12 4135-MP-0009 Check Seat

2

13 4139-TE-0006 Check Plug

2

14 10040-TE-0003 1/4″ NPT Plug

2

15 10010-TE-0018 Base Plate Mount Screw

2

16 10040-TE-0006 Plug, 5/8″, .300″

4

17 3200-VI-0002 Diaphragm, 1.190

2

18 6150-UH-0002 QEV Exhaust Seat

2

19 6140-FP-0001 QEV Baffle Porous Poly

4

20 10080-VI-023-75 O-ring, 023 x .070

2

21 6140-PP-0005 QEV Mesh

6

22 10080-VI-019-75 O-ring, .019 x .070

2

23 8200-TE-0001 Adapter, Cap, Proximity

2

24 8110-TE-0006 Sensor Housing

2

25 8600-XX-0057 Proximity Sensor

2

26 10010-TE-0019 Nut, Jam

2

27 7400-TE-0007 1″ Fitting S-300® Body

2

28 7400-PF-0003 1″ Fitting S-300® Insert

2

29 7400-PF-0007 1″ Fitting S-300® Nut

2

30 6090-UH-0004 QEV Body, 07

2

31 6150-NP-0008 QEV Muffler Cap

2

Leak Detect
Part 14600-XX-0009 14600-XX-0010 14600-XX-0011 14600-XX-0012 14600-XX-0031 14600-XX-0040

Description LF0 15 ft fiber optic cable with no amplifier LF1 15 ft fiber optic cable with D10 amplifier LF2 25 ft fiber optic cable with no amplifier LF3 25 ft fiber optic cable with D10 amplifier LC0 15 ft conductivity cable LC1 25 ft conductivity cable

Stroke Detect

Part

Description

14700-XX-0039 SX1 15 ft PNP normally

open proximity switch

14

Fittings (Type, Size, Option)

Flaretek

1/2 in. F08

Compatible 3/4 in. F12

1 in. F16

1-1/4 in. F20

Pillar S-300 1/2 in. P08

3/4 in. P12

1 in. P16

1-1/4 in. P20

1-1/2 in. P24

SynchroFlare 3/4 in. S12

1 in. S16 3/4 in. L12 PrimeLock 1 in. L16 1-1/4 in. L20

Assemblies
14510-PF-0011 14510-PF-0008 14510-PF-0009 14510-PF-0010 14530-PF-0011 14530-PF-0006 14530-PF-0007 14530-PF-0008 14530-PF-0026

Body Inlet Only (Nut not included) 7200-PF-0015 7200-PF-0009 7200-PF-0010 7200-PF-0011 7400-TE-0019 7400-TE-0006 7400-TE-0007 7400-TE-0008 7400-TE-0035

14520-TE-0008 7010-TE-0007

14520-TE-0007 14570-PF-0006 14570-PF-0007 14570-PF-0008

7010-TE-0009 7800-TE-0006 7800-TE-0007 7800-TE-0008

Fittings (Type, Size, Option) Assemblies

Tube Out
Weldable FNPT Plugged

3/4 in. T12 7120-PF-0007 1 in. T16 7120-PF-0008 1-1/4 in. T20 7120-PF-0009 1-1/2 in. T24 7120-PF-0010 3/4 in. W12 7300-PF-0005 1 in. W16 7300-PF-0006 3/4 in. N12 7100-TE-0009 1 in. N16 7100-TE-0005 1-1/4 in. N20 7100-TE-0010
B00 7130-TE-0005

10 9

8

1

4

65

11 9 12 13 15

3
27 28 29

16 7

30

19

2

22 23

17
20 18

21

24

31

25 26

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 3 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

2. Installation
2.1 Precautions
Handling
Do NOT lift pump by proximity cables, quick exhaust valves nor air tubing.
Installation Orientation
PXU140 pumps must be installed in an upright position. Check valves are actuated by gravity and/or flow and will not seat if the pump is not upright. Do not install pumps within 3 ft of each other or it may interfere with proximity sensors.
Timer Mode
PXU140 pumps require an end of stroke detection mechanism (pressure switch) to prevent over stroking in timer mode. Operating a PXU140 in timer mode without stroke detection will void the pump warranty.
Required Air Flow (Shuttle Valve)
PXU140 pumps require 3/8 in minimum orifice with unrestricted air flow.
Required Air Flow (Solenoid Valve)
PXU140 pumps require a 3 Cv solenoid. Using a reduced Cv will reduce flow rates. Using a valve with more than 20% greater Cv will change operating parameters, reduce pump life and void the warranty.
Under Supply of Air
PXU140 pumps operate erratically or stall when air supply is insufficient. Ensure use of air supply pressures higher than averaged air consumption lines in performance charts. Air supply lines and fittings must meet minimal inner diameter requirements shown in the installation instructions.
Air Supply Pressure
Operating PXU140 pumps ~35% below max air pressure may significantly extend pump life. PXU140 pumps require 20 psi minimum air pressure. Operation above 7 Bar (100 psi) may damage the pump and void the warranty.

Using Proximity Sensors
Pumps using a proximity sensor are not intrinsically safe and do not qualify for use in explosion-proof environments.
Suction Lift
PXU140 pumps have initial suction lift of 3 ft. For best results minimize suction lift.
Liquid Inlet/Outlet Connections
PXU140 liquid ports are not NPT nor any other standard. Use of connectors other than those supplied by White Knight will damage the pump and void the warranty.
Liquid Line Restriction
PXU140 pumps may be controlled by closing liquid outlet lines. However, restricting liquid supply lines increases wear and should be avoided. Do NOT pump against a closed liquid inlet. It will damage the pump and void the warranty.
Running Dry
PXU140 pumps use the pumped liquid to lubricate their shafts. The pumps will cycle faster and wear more than normal when run dry, which may cause damage and loss of self-prime abilities. PXU140 pumps should not be run dry after startup and are not warrantied under dry run conditions.
Pulse Dampener with Shuttle Valve
Air supply pressure to PXU140 pumps should be at least ten psi higher than the liquid line pressure when using a pulsation dampener. Failure to do so may cause erratic operation.
Cross Contamination
PXU140 pumps use porous material that may retain chemicals. Take precautions to avoid cross contamination.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 4 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

2.2 Warnings
Pressurized Material
Pumps in use contain pressurized materials. Eliminate liquid and air pressure via shut off valves before pump is serviced or removed from the system.
High Temperature
Heat may transfer to exterior surfaces when pumps operate with high temperature fluids. Avoid direct contact with the pump when high temperature fluids are present.
Hazardous Chemical
Use appropriate personal protective equipment when handling pump. Reference Material Safety Data Sheet (MSDS) for information specific to your chemicals.
Loud Noise
Pump exhaust air contributes to work area noise levels. Only operate pumps with approved muffler media, and use ear protection in noisy conditions.
2.3 Advantages
Head Pressure / Dead-Head
PXU140 pumps can be controlled by adjusting their liquid outlet pressures and can be installed with head pressures up to dead-head (e.g. equal liquid and air pressures) with no damage to the pump.
Thermal Cycling
PXU140 pumps require no maintenance when operated within their performance range, even in thermal cycling applications.

2.4 Environment & System
Oversized Inlet Line
Pumps operate optimally with liquid inlet lines larger than the liquid outlet lines. This reduces strain on the bellows and may reduce pulsation in the pump outlet.
Clean Supply Air (CDA)
PXU140 pumps require use of Class 2 air for particles and moisture per ISO 8573-1. Use 10 micron filter; maintain -40°C dew point. A point-of-use filter is recommended during first six months of operation in new fabs/systems due to high risks of debris that can damage pumps and void warranty.
Flammable Solvents
PXU140 pumps are not constructed from conductive materials. System that pump flammable solvents should be properly grounded to avoid ignition by static charge. A River’s Edge test of isolative pumps with flammable liquids indicated that liquids must be grounded and other procedures should be followed. Copy of test available.
Pumping Liquids Near Boiling Point
Minimizing suction lift reduces pulsation and the potential for boiling or outgassing of liquid in the inlet of the pump. Although reciprocating pumps can pull suction lift, pump performance and life increase when suction lift is minimized or eliminated.
Abrasive Slurry
Pumping abrasive slurry may accelerate wear of components. PXU140 pumps are warrantied when used with slurry. However, normal wear is not covered by warranty.
Environmental Temperature
PXU140 pumps are rated for 0°C (32°F) 50°C (122°F) environmental temperatures. Do not freeze fluid in pump. Operation below 0°C may accelerate wear. Normal wear is not covered by warranty.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 5 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

2.5 Proximity Sensor Installation

  1. Remove QEV plug.

  2. Attach QEV. Thread in NPT. Do not overtighten.

Proximity sensors ship already installed in their housings. Follow steps 2.1-2.3 if sensors are removed from their housings.

  1. Ensure proximity sensor is properly installed in housing. Tighten to light contact. Tighten lock nut to housing.

Note: No gap

Attach sensor assembly to pump head.

Use a crescent wrench to tighten cap.

Tighten to bottom out. Do not overtighten.

  1. Repeat steps for both pump heads.

Sensor Installation

2.1
Ensure O-ring is set on the cap.

2.2
Place cap into housing.

2.3
Ensure proximity sensor is properly installed in housing. Tighten to light contact. Tighten lock nut to housing.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 6 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

D10 amplifier must be calibrated before attaching fiber optic probes to the pump.

2.6 Installation Instructions

Pull-back dismount is standard. See steps 3.1-3.3 for forward dismount.

  1. Set lever to up position. Slide base plate forward or pump body backward.

  2. Lift pump off of base plate.

  3. Screw base plate to surface with 3/8 in or 10 mm socket head cap screws into pre-drilled holes.

  4. Set pump on base knobs; slide it forward. Set lever to down position.

  5. Attach fittings to pump. Tighten to 80 inch-lbs.

  6. Attach tubes and fittings per manufacturer instructions. Use backer wrench to hold fitting in place at pump.

  7. Set air line via 3/8 in FNPT ports on quick exhaust valves. Line must be 3/8 in minimum orifice.

Push-Forward Dismount

Configuration Setup Replace step 4 with steps 3.1-3.3 to re-configure the base plate to pushforward dismount.

3.1
Move knobs to

opposite sides.

3.2
Set pump on base knobs; slide it backward.

3.3
Move lever down to locked position.

Install with Rigid Base Plate *Requires push-forward dismount configuration (steps 3.1-3.3)

Remove L bracket. Set lever in neutral (up) position.

Slide pump
forward; lift it off base plate.

Fix base plate to work station.
See step 4 above.

Return pump to base plate.

Move lock lever to down position. Reattach L bracket. Tighten to 12 in-lb.

Liquid Inlet/Outlet
Liquid ports are not NPT nor any other standard. Use of connectors other than those supplied by White Knight will damage the pump.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 7 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

3. Control & Monitoring
Programmable Control
White Knight CPT-1 controllers monitor and adjust run mode, flow rate, leak detection and other pump operations.

D10 Amplifier Electrical Hookups & Dimensions
White Knight recommends ExpertTM D10 amplifier for use with fiber optic stroke and leak detection assemblies.

Standard Models and Main Unit

1
3 2
Load 4
Load 5
QD hookup is functionally identical (Pink wire not used)

+ 10-30V dc Standard Models ­ 12-30V dc Bussable Power Models
150 mA max. load

Remote Teach

Wire Key 1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

Sub-Units NPN
4 Load
5
PNP
4 Load
5

12-30V dc Connection

­ From Main

Unit Bus

Remote Teach

12-30V dc Connection

­ From Main

Unit Bus

Remote Teach

10.5 ± 0.2 mm (typ.) 14.5 mm

(0.41″)

(0.57″)

7.6 mm 35.9 mm 0.30″ (1.41″)

Mounting Bracket (included with some models)

61.3 mm (2.42″)
68.1 mm (2.68″)

9.8 mm (0.39″)

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 8 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

3.1 Proximity Detection Wiring Information
· 10-30 V DC · 200 mA · NPN-normally open · Listed IND.CONT.EQ 81u2 · For use in the secondary of
a Class 2 source of supply
· Use of Proximity Sensors does not qualify for intrinsically safe environments.

3.2 Shift Logic for Proximity Pumps

Air must be sent to either side at startup to initiate movement.

Pump Startup

During pump operation, the timing of the solenoid valve should be dependent on sensors with no time delays. There should be no delay between reading the sensor signal and actuating the solenoid valve.

Send air to left side
of pump

Check Sensors

Send air to right side
of pump

Logic

Only left sensor is true

Only right sensor is true

Air remains on either side if both sensors are true or false

Proximity End Stroke Operation

  • The proximity sensors on the pump can both be seen in the middle of the stroke; thus it is required that the solenoid not be switched until just one sensor is seen. * Vertical line denotes when the solenoid was switched.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 9 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

3.3 Conductivity Leak Detection Installation

Leaks are identified if conductive fluid contacts a sensor. Sensor provides a Sink (NPN)

or Source (PNP) signal, depending on the wire setup. See the wiring diagrams below.

Conductive leak detection does not qualify for use in explosion-proof environments. Conductive fluid required.

See below for elbow out configuration.

Source (PNP) Connection

Conductivity Leak Detect

White

+ Power

10-30

White/Blue Load – VDC

Wiring Diagrams

  1. Remove leak adapter from assembly.

  2. Replace NPT plug in “L” port with probe. Hand Tighten. Attach cable to signal translator (e.g. PLC).

Sink (NPN) Connection

White

Load

Conductivity

Leak Detect White/Blue

+ Power 10-30
– VDC

3.4 Fiber Optic Leak Detection Installation
D10 amplifier must be calibrated before attaching fiber optic probes to the pump. Fiber optic sensors can melt if used at >130°C (266°F), causing leak detect failure.
See below for elbow out configuration.

  1. Remove leak adapter and leak detect probe from fiber optic assembly.

  2. For straight out configuration replace NPT plug in “L” port with the probe. Hand-tighten.

  3. Insert the fiber optic cable until it contacts the bottom of the probe.

  4. Lower ferrule and gripper until snug against the probe. Hand tighten female gripper nut.
    For elbow out configuration:

  5. Open the top and slide the front face of the D10 up. Press the fiber optic ends into the holes on its front. Slide the face down to lock cables in place.

Fiber optic

Conductivity

1.1
Replace NPT plug in “L” port with elbow adapter.

1.2
Attach fiber optic or conductivity leak detect probe per instructions above.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 10 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

3.5 Calibrating D10 Amplifier for Fiber Optic Leak Detection
Step 1: Power On D10 Amplifier & Set “Dark Operate” Mode:

Push Button

Remote Line

0.04 s “Click” 0.8 s 0.04 s T 0.8 s

Result

Access Setup Mode

Press and hold both buttons > 2 seconds.

Press either button until LEDs show desired settings.
Select Settings

Return to Run Mode

Press and hold both buttons >2 seconds.

8 7 6 5 HS 4 3 DO 2 LO 1

Double-pulse remote line
TT
T

· Green Power LED turns OFF.
· Output LED remains active.
2x · Icons continue to display current setup.
· Bargraph turns OFF.

Pulse the remote

line until LEDs show

desired settings.

T

T

Note: Doublepulsing remote line causes setting to “back up” one step.

Sensor toggles through these setting combinations: LO – Normal Speed – No Delay (default) DO – Normal Speed – No Delay LO – High Speed – No Delay DO – High Speed – No Delay LO – Normal Speed – Delay DO – Normal Speed – Delay LO – High Speed – Delay DO – High Speed – Delay

8 7 6 5 HS 4 3 DO 2 LO 1

Hold remote line low · Green Power LED turns ON.

T T

2 seconds.

· Sensor returns to Run

2 seconds mode with new settings.

Step 2: Access “Single-Point Dark Set” Mode

Push Button

Remote Line

0.04 s “Click” 0.8 s 0.04 s T 0.8 s

Result

Press and hold static

Single-pulse remote · Power LED: OFF.

Access button > 2

line

· Output LED: ON (push button)

Set Mode

seconds.

T 1x

OFF (remote line)

or

· Static LEDs: LO & DO

alternately flashing

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

Step 3: Set Sensing Condition

Set condition to “leak detection” sensing while probe tip is submerged in liquid. Then, remove the leak probe from liquid and reinserted into the “L” port. Amplifier will now signal when moisture if detected on the probe tip.

Push Button

Remote Line

0.04 s “Click” 0.8 s 0.04 s T 0.8 s

Result

Set Sensing Condition

· Present sensing

Present sensing

· Power LED: ON.

condition

condition

· Output LED: ON (push button)

or

· Five-click static button · Five-pulse remote lne

OFF (remote line)

· Bargraph: 4 indicators flash.

Sensor returns to Run mode with new settings

· Power LED: ON.

· Output LED: ON (push button)

OFF (remote line)

or

· Bargraph: #1, 3, 5, 7 flash for failure.

Sensor returns to Set sensing condition.

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 11 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

4. Ordering Instructions

Required (Default Model)

Additional Options (Blank if not needed)

PXU140 – F16 – LF0 – SX1 – TF16 –

1

2

3

4

5

6

Rev

Options 1-3 are required. Leave Additional Options blank if not desired. Only add Outlet if different than Inlet.

Default options are highlighted

1. Pump Model

Standard

PXU140

2. Check Ball Material

PTFE Check balls

blank

PFA Check balls

F

3. Inlet Fitting Front straight only

Flaretek

1/2 in. F08

Compatible 3/4 in. F12

1 in. F16

1-1/4 in. F20

Tube Out 3/4 in. T12

1 in. T16

1-1/4 in. T20

1-1/2 in. T24

Weldable 3/4 in. W12

1 in. W16

Pillar S-300 1/2 in. P08

3/4 in. P12

1 in. P16

1-1/4 in. P20

1-1/2 in. P24

FNPT

3/4 in. N12

1 in. N16

1-1/4 in. N20

Synchro- 1/2 in. S08 Flare 3/4 in. S12

1 in. S16

PrimeLock 3/4 in. L12

1 in. L16

1-1/4 in. L20

4. Leak Detection

No leak detection

blank

15 ft fiber optic cable with no amplifier LF0

15 ft fiber optic cable with D10 amplifier LF1

25 ft fiber optic cable with no amplifier LF2

25 ft fiber optic cable with D10 amplifier LF3

15 ft conductivity cable

LC0

25 ft conductivity cable

LC1

5. Stroke Detection

No stroke detection

blank

15 ft PNP normally open proximity switch

SX1

  • Proximity switch ordered separately. Proximity switch is required for operation. Standard configuration does NOT include proximity switch. For applications requiring the NPN signal, White Knight recommends the use of a signal converter similar to Balluf part number BAE002H.
    Timer mode operation requires end-of-stroke detection. Use of timer mode without stroke detection voids the warranty. Operating the pump without the included quick exhaust valves (QEVs) voids pump warranty. Customers may use their own QEVs with the optional NPT adapter.

6. Outlet Fitting

Straight only.

Front Top

Select Top or Front.

Same as Inlet

blank n/a

Flaretek

1/2 in. FF08 TF08

Compatible 3/4 in. FF12 TF12

1 in. FF16 TF16

1-1/4 in. FF20 TF20

Tube Out 3/4 in. FT12 TT12

1 in. FT16 TT16

1-1/4 in. FT20 TT20

1-1/2 in. FT24 TT24

Weldable 3/4 in. FW12 TW12

1 in. FW16 TW16

Pillar S-300 1/2 in. FP08 TP08

3/4 in. FP12 TP12

1 in. FP16 TP16

1-1/4 in. FP20 TP20

1-1/2 in. FP24 TP24

FNPT

3/4 in. FN12 TN12

1 in. FN16 TN16

1-1/4 in. FN20 TN20

Synchro- 1/2 in. FS08 TS08 Flare 3/4 in. FS12 TS12

1 in. FS16 TS16

PrimeLock 3/4 in. FL12 TL12

1 in. FL16 TL16

1-1/4 in. FL20 TL20

Revision

No revision

blank

Contact support for revision level
or copy exact code activation details. Configured part numbers are not Copy Exact Part Numbers. support@wkfluidhandling.com

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 12 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

5. Pump Service
Pumps fully rebuilt by White Knight, certified rebuilders, or technicians certified by White Knight receive full warranty renewal. Details below.

White Knight Rebuilds
Request factory rebuilds by web form at: https://wkfluidhandling.com/support/rma/. An RMA# will be provided after processing.
*Customers must follow decontamination instructions in Section 4.4 when returning a pump to White Knight.

Certified Rebuilders
White Knight’s global network of certified rebuilders expedite rebuild turn- around time and minimize shipping costs. Find certified rebuilders at: https://wkfluidhandling.com/rebuilders/

Rebuild Pump as Certified Technician
White Knight offers trainings to certify technicians to rebuild pumps. Technicians who pass the training are issued a two-year certification. During the two years, parts in pumps rebuilt by the technician receive a full warranty. See: https://wkfluidhandling.com/virtual-rebuilds/

5.1 Rebuild Kits & Parts
Rebuild kit for PXU140 is RBPXU140-1. To request rebuilds by White Knight, use RBPXU140-5 (labor included). Pump rebuilds require tool kit: 12200-XX-0027 (Legacy# PXU140-170).
1

2 3 4 5 6

7 8

9

RBPXU140-1

ITEM NO. PART NUMBER

DESCRIPTION

QTY.

1

14300-MP-0023

BELLOWS ASSEMBLY, 140L, PROXIMITY

2

2

4100-MP-0003

CHECK BALL- 1-1/8″

4

3

4135-MP-0009

SEAT, CHECK, BOTTOM, U,140L (HI-FLOW)

2

4

4142-MP-0007

SEAT, CHECK, TOP, U, 140L (HI-FLOW)

2

5

14320-PF-0003 LOADED SHAFT ASSEMBLY, 140L, (with Ceramic Insert)

1

6

5143-MP-0005

SEAL, SHAFT, 140L, U-SERIES

2

7

6140-FP-0001

BAFFLE, 1.100″

4

8

6150-UH-0002

SEAT, QEA

2

9

3200-VI-0002

DIAPHRAGM, 1.190

2

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 13 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

5.2 Return Pump for Service
Follow decontamination instructions when returning a pump for service.
DO NOT REMOVE PAGE FROM MANUAL. Copy page from manual or download at https://wkfluidhandling.com/support/rma/.
Decontamination Instructions
PRINT COMPLETED DECONTAMINATION CERTIFICATION. IT MUST BE INCLUDED IN YOUR RMA SHIPMENT.
White Knight products are designed for use with caustic and otherwise dangerous liquids. Handle every product as if it contains dangerous chemicals whether or not it actually does.
· Only those with adequate safety training should attempt to handle used pumps. · Wear adequate safety gear appropriate for chemicals that have been in the pump. · Review relevant Material Safety Data Sheets (MSDS) before handling the pump. · Review emergency numbers for use in event of an accident. · Prepare Ph papers, showers, antidotes, clean-up equipment, neutralizers, and other safety devices
used to detect, neutralize or minimize effects of chemicals described in appropriate MSDS documents.

Rinse with DI Water
Circulate DI water through pump for twenty minutes before disassembly and/or double bagging for shipment. If pump is nonfunctional, force DI water from inlet through outlet for 40 minutes before shipment preparations.
Remove Pump from Station:
1. Disconnect liquid tubing connectors from front of pump (opposite shuttle valve). 2. Plug NPT fittings with PTFE plug, Flare fittings with flare nose cover and cap,
or other plug or cap as recommended by connector supplier. 3. Disconnect air supply tubing from face of shuttle valve. 4. Loosen mount screw from base plate. (Note: do not remove screw from base plate). 5. Remove base plate using proper tool for the fastening devices (e.g. Allen wrench or screw driver).
Note: Base plate may stay if needed for replacement pump to be used. 6. Return all removed parts to the pump.

Return Pump to White Knight:
1. Rinse pump with DI water as described above after removing it from its station. 2. Drain remaining DI water from the pump inlet and outlet liquid tubing connectors. 3. Plug liquid outlets as described in the Remove Pump from Station section above. 4. Dry the pump, double bag it, and seal it in thick polyethylene bags. 5. Return the pump to its original packaging. 6. Include MSDS for the chemical that the pump was handling in the box with the pump. 7. Obtain RMA number from White Knight and write it on the outside of the box. 8. Ship to White Knight following all rules, regulations and laws regarding shipment of dangerous
materials. Ship freight pre-paid. No collect shipments will be accepted. Unauthorized use of White
Knight shipping accounts will result in the adding of freight to the bill in addition to a service charge.

Include All Pump Components:
Pumps returned to White Knight for evaluation, service or repair must be complete with all components, including but not limited to base plate, mount screws, tubing connectors, tubing connector caps, flare noses, shuttle valves, mufflers, and tubing. Missing parts will be added to the pump and charged to the customer.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 14 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

DO NOT REMOVE PAGE FROM MANUAL. Copy page from manual or download at https://wkfluidhandling.com/support/rma/.

Decontamination Certification

COMPLETE AND PRINT THIS FORM. IT MUST BE INCLUDED IN YOUR RMA SHIPMENT.

I, the undersigned employee of

, certify that all

decontamination and safety procedures described in Decontamination Instructions section have

been followed for return of product below.

RMA#: (We cannot process returns without an RMA number.)

Serial#: (We cannot process returns without a product serial number.)

Metal Exposure:
(Check all that apply. Write in other metals if necessary.)

Product was used in a Metal Process.

Yes

No

Product was used in a Copper Metal Process.

Yes

No

Product was used with:

Aluminum

Cobalt

Gold

Lead

Nickel

Platinum

Silver

Tin

Titanium

Tungsten

Zinc

Other:

Chemical Exposure:
(Check all that apply. Write in other chemicals if necessary.)

Product was NOT used in chemicals (DI Water only).

Product was used in chemicals.

Ammonia Nitric Acid

Ammonium Hydroxide Phosphoric Acid

Hydrochloric Acid Sulfuric Acid

Hydrofluoric Acid Other:

Hydrogen Peroxide IPA

Shipping Information:
Please indicate metal processes to which the product has been exposed by clearly and conspicuously labeling the outside of the return package with the metal.

Products exposed to Metal Processes must be sent to the following address:

Products NOT exposed to Metal Processes must be sent to the following address:

White Knight Fluid Handling 187 East 670 South, Suite B Kamas, UT 84036

White Knight Fluid Handling 187 East 670 South, Suite C Kamas, UT 84036

Print Name: Signature:

Date:

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 15 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

6. Warranty
White Knight follows strict manufacturing, assembly and testing procedures to ensure consistency and reliability.
White Knight warrants PXU140 pumps and components are free from defects in materials and workmanship for two years from our shipment date or your installation date if provided within 90 days of shipment from our facility.
Failures due to normal wear, misuse, abuse or unauthorized disassembly nullify this warranty.
White Knight does not guarantee the suitability of products for specific applications. White Knight is not liable for any damage or expense resulting from use or misuse of its products in any application. Responsibility is limited solely to repair or replacement of defective products or components.
Prior written, faxed or emailed approval must be obtained from White Knight before returning any product or component for warranty consideration. All determinations regarding cause of failure are made by White Knight, and all decisions regarding warranty fulfillment or nullification are made by White Knight.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, INCLUDING ANY GUARANTEE OF SUITABILITY FOR ANY PURPOSE. NO VARIATIONS OF THIS WARRANTY SHALL BE HONORED NOR CONSIDERED LEGALLY BINDING, EXCEPT WRITTEN AGREEMENTS SIGNED BY THE CEO OF WHITE KNIGHT FLUID HANDLING.

Accessories
See ordering instructions or contact us for details.
Stroke Detection · Fiber Optic stroke detection with or without sensor · Solid state pressure switch · Solid state dual pressure switch
Leak Detection · Fiber Optic leak detection with or without sensor · Conductivity leak detection
CPT-1 · Control/monitor run mode and flow rate.
CatcherTM Pre-Filters · In-line and pump-mounted options · Large through holes to avoid loading · Filter may be removed without removing the CatcherTM from the pump or the line. · Pumps damaged by passing solids that use a CatcherTM are repaired as in warranty.
Filter Housing · 100% non-metallic · Allows for filter changing without disconnecting the inlet/outlet lines · Rated for temperatures up to 210°C · Install with industry standard connections · Designed to allow for thermal cycling · Upright and inverted installation options
Quick Exhaust Valves · Allows for immediate escape of exhaust air reducing pulsation and exposure of solenoid valve to corrosive fumes · In-line and pump-mounted options · UHMW-PE design · Comes standard with a one-year warranty
Pulse Dampeners · Uses same CDA as supplied to pump · In-line and pump-mounted options · Sizes available for all PXU Series pumps · Self-adjusting, Auto- Level Valve is regulated by liquid line pressure

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 16 Subject to change without notice

engineer approvedTM

PXU140 Owner’s Manual

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.2 | 5 Dec 2023 | P. 17 Subject to change without notice

engineer approvedTM
White Knight Support
187 E. 670 S. Kamas, UT 84036 Phone: 435.783.6040 Toll Free: 888.796.2476 Fax: 435.783.6128 support@wkfluidhandling.com https://wkfluidhandling.com/support/

Part No. 18200-LM-0028

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Version 2.2.2 | 5 Dec 2023 Subject to change without notice

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals