WK PSU060 Pumps White Knight Fluid Handling Owner’s Manual

June 16, 2024
WK

PSU060 Pumps White Knight Fluid Handling

Product Information

Specifications & Performance

Model| Max Flow Rate| Displacement Per Cycle| Cycles per min| Air Connection| Weight| Suction Lift*| Sound Pressure| Power
---|---|---|---|---|---|---|---|---
PSU060| 62.2 lpm (16.43 gpm)| 0.178 liters (0.047 gal)| 348 max| 1/4 in| 15.2 kg (33.43 lb)| 1 m (3 ft)| 73.11 dB(a) at 100 psi 50 CPM| 64.29 dB(a) at 100 psi 50 CPM
PSUSD060| 59.5 lpm (15.72 gpm)| 0.178 liters (0.047 gal)| 348 max| 1/4 in| 15.2 kg (33.43 lb)| Flooded suction| 82.5 dB(a) at 100 psi max CPM| 74.11 dB(a) at 100 psi max CPM

  • May vary by configuration or system. Suction lift diminishes
    over time. Recommended installation level less than 3 ft above
    source. To calculate displacement, divide flow rate by CPM. **
    Sound measured in accordance with ISO9614-2:1997. *** Dry-run
    capable PSUSD060 pumps require flooded suction and may have reduced
    warranty. Contact support for details.

Product Usage Instructions

1. Installation

To install your White Knight PSU060 pump, please follow these
steps:

  1. Choose a suitable location for the pump. Ensure it is close to
    the fluid source and within the recommended installation level
    (less than 3 ft above the source).

  2. Securely mount the pump using appropriate hardware to ensure
    stability.

  3. Connect the air supply line to the 1/4 inch air connection on
    the pump.

  4. Connect the fluid inlet and outlet lines to the corresponding
    ports on the pump.

  5. Ensure all connections are tight and leak-free.

  6. Verify that the suction lift is within the specified range (1 m
    or 3 ft).

  7. Once the pump is properly installed, proceed to the next
    section for control and monitoring instructions.

2. Control & Monitoring

To control and monitor your White Knight PSU060 pump, please
follow these instructions:

  1. Ensure that the power supply is connected and turned on.

  2. Use the provided control panel or interface to adjust the
    desired flow rate and operating parameters.

  3. Monitor the pump’s performance, including the suction lift,
    sound pressure, and power consumption, using the built-in
    indicators or external monitoring devices.

  4. Regularly check for any abnormal behavior or irregularities in
    the pump’s operation.

  5. If any issues are detected, refer to the troubleshooting
    section of the manual or contact customer support for
    assistance.

3. Ordering Instructions

To order additional parts or accessories for your White Knight
PSU060 pump, please follow these steps:

  1. Identify the specific part or accessory you need based on the
    product documentation or your requirements.

  2. Contact the authorized distributor or sales representative to
    place your order.

  3. Provide the necessary details, including the model number
    (PSU060), quantity, and any specific configuration or customization
    requests.

  4. Confirm the order details, including pricing, delivery
    schedule, and payment terms.

  5. Once the order is processed, you will receive a confirmation
    with the shipment tracking information.

4. Pump Service

If you require service or maintenance for your White Knight
PSU060 pump, please follow these instructions:

4.1 Rebuild Kits & Parts

If you need to rebuild or replace certain components of your
pump, you can order rebuild kits and parts from White Knight.
Follow these steps:

  1. Identify the specific components that need to be replaced or
    rebuilt.

  2. Contact the authorized distributor or sales representative to
    inquire about available rebuild kits and parts.

  3. Provide the necessary details, including the model number
    (PSU060), required quantity, and specific components needed.

  4. Confirm the availability, pricing, and delivery schedule with
    the distributor or sales representative.

  5. Place your order and follow the instructions provided for
    payment and shipment.

4.2 Return Pump for Service

If your pump requires service or repair, you may need to return
it to White Knight. Follow these steps:

  1. Contact customer support to discuss the issue with your pump
    and determine if it can be resolved remotely or if it needs to be
    returned.

  2. If returning the pump is necessary, obtain a return
    authorization (RA) number and shipping instructions from customer
    support.

  3. Package the pump securely to prevent damage during
    transit.

  4. Include the RA number and any relevant documentation inside the
    package.

  5. Ship the package to the designated address using a reliable
    shipping method.

  6. Once the pump is received and evaluated by White Knight, they
    will perform the necessary service or repair and return the pump to
    you.

5. Warranty & Accessories

For information about the warranty coverage and available
accessories for your White Knight PSU060 pump, please refer to the
warranty documentation provided with your product or contact
customer support.

FAQ

Q: What is the maximum flow rate of the PSU060 pump?

A: The maximum flow rate of the PSU060 pump is 62.2 lpm (16.43
gpm).

Q: What is the weight of the PSU060 pump?

A: The weight of the PSU060 pump is 15.2 kg (33.43 lb).

Q: Can the PSUSD060 pump operate in a dry-run condition?

A: No, the PSUSD060 pump is not dry-run capable and requires
flooded suction. Operating it in a dry-run condition may void the
warranty. Please contact support for more information.

engineer approvedTM
PSU060 Owner’s Manual

187 E. 670 S., Kamas, UT 84036 435.783.6040 888.796.2476 https://wkfluidhandling.com

Table of Contents

1. Product Information

1

1.1 Specifications & Performance ……………………………………………………………………………….1 1.2 Temperature Limits………………………………………………………………………………………………2 1.3 Dimensions ………………………………………………………………………………………………………..2 1.4 Bill of Materials……………………………………………………………………………………………………3

2. Installation

4

2.1 Precautions ………………………………………………………………………………………………………..4 2.2 Warnings ……………………………………………………………………………………………………………5 2.3 Advantages ………………………………………………………………………………………………………..5 2.4 Environment & System…………………………………………………………………………………………5 2.5 Installation Instructions…………………………………………………………………………………………6 2.6 Shuttle Service Instructions…………………………………………………………………………………..7

3. Control & Monitoring

8

3.1 Fiber Optic Stroke Detection Installation…………………………………………………………………8 3.2 Calibrating D10 Amplifier for Stroke Detection…………………………………………………………9 3.3 Single Pressure Switch Stroke Detection Installation………………………………………………….10 3.4 Dual Pressure Switch Stroke Detection Installation ……………………………………………………10 3.5 Pressure Switch Stroke Detection Electrical Hookups……………………………………………. 11 3.6 Conductivity Leak Detection Installation…………………………………………………………………..12 3.7 Fiber Optic Leak Detection Installation ……………………………………………………………………12 3.8 Calibrating D10 Amplifier for Leak Detection …………………………………………………………13

4. Ordering Instructions

14

5. Pump Service

15

5.1 Rebuild Kits & Parts …………………………………………………………………………………………..15 5.2 Return Pump for Service…………………………………………………………………………………….16

6. Warranty & Accessories

20

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Version 2.2.1 | 5 Dec 2023 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

Dear valued customer,
Thank you for purchasing a White Knight PSU060 pump.
Our dedicated team designs products to meet your exacting specifications with a demonstrated commitment to quality that goes beyond mere words and fancy slogans.
Our patented designs offer a variety of size and material options to meet stringent requirements of high-pressure chemical delivery systems, hightemperature re-circulation processes, chemical reclaim and bulk transport applications, slurry systems, and more. Our safe, reliable products offer superior performance, optimized efficiency, and simplified maintenance.
White Knight is able to provide the highest quality fluid handling products through controlled, consistent in-house engineering and manufacturing. Through continued significant investments in engineering and manufacturing, we lead the industry with new technologies and products.
White Knight has received numerous awards for innovation and manufacturing programs. We rigorously manage our quality assurance processes to ensure consistency and reliability. Our quality controls include strict cleanliness procedures and consistent manufacturing processes. For example, high-purity product assembly, testing, and packaging is performed in a Class 100 cleanroom.
Please peruse this manual before installing your White Knight product. It details installation requirements and setup instructions, and provides additional information and accessories for enhanced functionality.
Our team has gone to great lengths to ensure our products serve your needs and meet your requirements.
Further, we provide the highest quality products at the best value, and we back them up with excellent warranties and world class support.
Thank you for your confidence and trust in White Knight products.
Sincerely,
White Knight Fluid Handling

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

1. Product Information
1.1 Specifications & Performance

Model

PSU060

PSUSD060

Max Flow Rate*

62.2 lpm (16.43 gpm)

59.5 lpm (15.72 gpm)

Displacement Per Cycle*

0.178 liters (0.047 gal)

0.178 liters (0.047 gal)

Cycles per min

348 max

348 max

Air Connection

1/4 in

1/4 in

Weight

15.2 kg (33.43 lb) 15.2 kg (33.43 lb)

Suction Lift*

1 m (3 ft)

Flooded suction

Sound

Pressure**

73.11 dB(a) at 100 psi 50 CPM 82.5 dB(a) at 100 psi max CPM

Power**

64.29 dB(a) at 100 psi 50 CPM 74.11 dB(a) at 100 psi max CPM

  • May vary by configuration or system. Suction lift diminishes over time. Recommended installation level less than 3 ft above source. To calculate displacement, divide flow rate by CPM. ** Sound measured in accordance with ISO9614-2:1997. *** Dry-run capable PSUSD060 pumps require flooded suction and may have reduced warranty. Contact support for details.

Max Fluid Temperature
Environmental Temperature
Max Supply Air Pressure
Min Startup Air Pressure
Fluid Path Materials
Non-Fluid Path Materials

210°C (412°F) min: 0°C (32°F) max: 50°C (122°F) 7 Bar (100 psi)
1.4 bar (20 psi)
PTFE, PFA
PTFE, PFA, Ceramic

Stroke Detection
Leak Detection
Electronic Control

Fiber optic with or without D10 sensor, or solid state pressure switch (NPN or PNP)
Fiber optic with or without sensor, or conductivity
CPC, CPT, or custom. Call for details.

Discharge Pressure

PSU060 Performance

100

7 100 PSI

90 6

100 CPM

80

80 PSI

160 CPM

70

5

Air Pressure Air Consumption Cycle Rate

PSUSD060 Performance

100

7 100 PSI

90

6

80

80 PSI

70

5

100 CPM
20 SCFM 160 CPM

Air Pressure Air Consumption Cycle Rate

Discharge Pressure

60 PSI 60
4 50
3 40 PSI 40

20 SCFM 15 SCFM

200 CPM 25 SCFM

30

2

20 PSI 20

1 10

5 SCFM

10 SCFM

240 CPM 280 CPM

60 PSI 60
4 50
3 40 PSI 40

15 SCFM

30

2

20 PSI

10 SCFM

20

1 10

5 SCFM

25 SCFM 200 CPM
240 CPM 280 CPM

PSI Bar

LPM

10

20

30

40

50

60

70

PSI Bar

LPM

10

20

30

40

50

60

70

m3/hr

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

m3/hr

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

GPM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Liquid Flowrate

GPM 1 2 3 4 5 6 7 8 9 10 11 1 2 13 14 15 16 17 18
Liquid Flowrate

How to Read Charts
Draw a horizontal line at your discharge pressure and vertical line at desired flow rate. At line intersect, estimate required air pressure, resultant cycle rate and air consumption.

Example At 2 Bar (30 psi) discharge pressure and 80 psi air pressure, PSU060 pumps provide 40 lpm (10.6 gpm) flow rate, cycle at ~230 CPM and exhaust 18 SCFM of air.

*Graph is for reference only. Performance was measured utilizing 1/2 in (3/8 in ID) air line and 1-1/4 in (1-1/8 in ID) liquid lines with 1 ft flooded suction. Performance may vary in your system.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 1 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

1.2 Temperature Limits

140°F 7

180°F

220°F

260°F

300°F

340°F

380°F

420°F 100

90 6
80 5
70

Air Supply Pressure

4

60

50
3 40

2

30

1 Bar 60°C

80°C

100°C

120°C

140°C

160°C

180°C

200°C

20
PSI 220°C

1.3 Dimensions
Dimensions in [mm] in
294 11.6

196 7.7

167

75

6.6

3.0

MOUNT WITH 2 EA. 3/8″ (10 mm) SOCKET HEAD CAP SCREWS

288

27

11.3

1.1

13 .5 64 2.5
54 2.1
19 .8

177 7.0

CL

95

201

3.7

7.9

10

.4

55

2.2

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 2 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

1.4 Bill of Materials

32

Shuttle Assembly

24

14450-TE-0002

27

28

35

43

35 34

1

39

22

38

20 18

37

25

13

26

41 42

23

2

16

21

19

4

17 21

20
22 15 36

7 5

23

8

14

Right Head Assembly

6

PSU060F BILL OF MATERIALS

Part

Description

Qty

1 1125-TE-0021 Pump Body

1

2 2127-TE-0031 Head, Right

1

3 2127-TE-0032 Head, Left

1

4 3133-TE-0006 Seat, Head, Shift

2

5 4100-PF-0001 PFA Check Ball, .765″

4

6 4135-MP-0014 Bottom Check Seat, Lower 2

7 4137-TE-0010 Bottom Check Cage

2

8 4137-TE-0011 Middle Check Cage

4

9 4139-TE-0005 Cage, Plug

2

10 4140-TE-0006 Top Check Plug

2

11 4142-MP-0008 Top Check Seat, Upper

2

12 4142-TE-0013 Top Check Cage

2

13 5143-MP-0004 Seal, Shaft

2

14 6020-TE-0004 Elbow, Gripper,

2

1/4″ NPT x 3/8″

15 6030-TE-0001 Elbow, Gripper,

2

1/8″ Npt X 1/4″

16 6070-TE-0001 Female Gripper Nut, 1/4″ 2

17 6070-TE-0002 Nut, Gripper, Female, 3/8″ 2

18 6070-TE-0004 Male Gripper Nut, 1/4″

2

19 6070-TE-0005 Male Gripper Nut, 3/8″

2

20 6080-KF-0001 Gripper, 1/4″

4

21 6080-KF-0002 Gripper, 3/8″

4

22 6080-TE-0001 Ferrule, 1/4″

4

23 6080-TE-0002 Ferrule, 3/8″

4

24 6140-FP-0004 Baffle

6

25 6140-PP-0002 Spacer, Baffle

6

26 6150-TE-0011 Cap, Muffler

2

27 6530-TE-0002 Shuttle End Plug

2

28 6560-CE-0002 Shuttle Spool

1

29 7400-PF-0002 Insert, S-300®

2

30 7400-PF-0006 Nut, S-300®, 3/4″

2

31 7400-TE-0004 Body, S-300®, 3/4″

2

32 10010-TE-0016 Screw, Mount, Shuttle

2

33 10010-TE-0018 Screw, Mount, Plate, Base 2

34 10020-TE-0004 Pin, Alignment, Shuttle

2

35 10040-TE-0002 Plug, NPT, 1/8″

3

36 10040-TE-0003 Plug, NPT, 1/4″

4

37 10040-TE-0015 Plug, Vent, NPT, 1/8″

2

38 10071-PF-0008 Tubing, Thick Wall, 1/4″

2

39 10071-PF-0010 Tubing, 3/8″

2

40 14200-TE-0003 Base Plate Assembly

1

41 14300-MP-0020 Bellows Assembly

2

42 14320-PF-0004 Shaft

1

43 14400-TE-0010 Shuttle Body with Sleeve 1

14100-TE-0007

9

Includes #2 and #4

33

Fittings (Type, Size, Option)

Flaretek

1/2 in. F08

Compatible 3/4 in. F12

1 in. F16

1-1/4 in. F20

Tube Out 1/2 in. T08

3/4 in. T12

1 in. T16

1-1/4 in. T20

Weldable 3/4 in. W12

1 in. W16

Pillar S-300 3/8 in. P06

1/2 in. P08

3/4 in. P12

1 in. P16

1-1/4 in. P20

FNPT

1/2 in. N08

3/4 in. N12

1 in. N16

Synchro- 1/2 in. S08 Flare 3/4 in. S12

1 in. S16

PrimeLock 1/2 in. L08

3/4 in. L12

1 in. L16

1-1/4 in. L20

Plugged

B00

Assemblies

Body Inlet Only (Nut not included)

14510-PF-0004 7200-PF-0005

14510-PF-0005 7200-PF-0006

14510-PF-0006 7200-PF-0007

14510-PF-0007 7200-PF-0008

7120-PF-0004

7120-PF-0005

7120-PF-0006

7120-PF-0011

7300-PF-0003

7300-PF-0004

14530-PF-0028 7400-TE-0036

14530-PF-0003 7400-TE-0003

14530-PF-0004 7400-TE-0004

14530-PF-0005 7400-TE-0005

14530-PF-0009 7400-TE-0012

7100-TE-0006

7100-TE-0004

7100-TE-0008

14520-TE-0003 7010-TE-0005

14520-TE-0004 7010-TE-0004

14520-TE-0006 7010-TE-0006

14570-PF-0003 7800-TE-0003

14570-PF-0004 7800-TE-0004

14570-PF-0005 7800-TE-0005 14570-PF-0012 7800-TE-0012

7130-TE-0003

10 12 5 8 11
Left Head Assembly 14100-TE-0008 Includes #3 and #4
3

31 29 30
40

Leak Detect

Part

Description

14600-XX-0009 LF0 15 ft fiber optic cable

with no amplifier

14600-XX-0010 LF1 15 ft fiber optic cable

with D10 amplifier

14600-XX-0011 LF2 25 ft fiber optic cable

with no amplifier

14600-XX-0012 LF3 25 ft fiber optic cable

with D10 amplifier

14600-XX-0031 LC0 15 ft conductivity cable

14600-XX-0040 LC1 25 ft conductivity cable

Stroke Detect with Fiber Optics

Part

Description

14700-XX-0017 SF0 15 ft fiber optic cable

with no amplifier

14700-XX-0018 SF1 15 ft fiber optic cable

with D10 amplifier

14700-XX-0019 SF2 25 ft fiber optic cable

with no amplifier

14700-XX-0020 SF3 25 ft fiber optic cable

with D10 amplifier

Stroke Detect with Pressure Switch

14900-NP-0004 SP1 Single NPN Switch 14900-NP-0003 SP2 Dual NPN Switches 14900-NP-0001 SP4 Single PNP Switch 14900-NP-0002 SP5 Dual PNP Switches

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 3 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

2. Installation
2.1 Precautions
Handling
Do NOT lift pump by shuttle valve assembly nor air tubing.
Installation Orientation
PSU060 pumps must be installed in an upright position. The check valves are actuated by gravity and/or flow, and they will not seat if the pump is not upright.
Timer Mode
PSU060 pumps require an end of stroke detection mechanism (pressure switch) to prevent over stroking in timer mode. Operating a PSU060 in timer mode without stroke detection will void the pump warranty.
Required Air Flow (Shuttle Valve)
PSU060 pumps require 1/4 in minimum orifice with unrestricted air flow.
Required Air Flow (Solenoid Valve)
PSU060 pumps require a 1.5 Cv solenoid. Using a reduced Cv will reduce flow rates. Using a valve with more than 20% greater Cv will change operating parameters, reduce pump life and void the warranty.
Under Supply of Air
PSU060 pumps operate erratically or stall when air supply is insufficient. Ensure use of air supply pressures higher than averaged air consumption lines in performance charts. Air supply lines and fittings must meet minimal inner diameter requirements shown in the installation instructions.
Air Supply Pressure
Operating PSU060 pumps ~35% below max air pressure may significantly extend pump life. PSU060 pumps require 20 psi minimum air pressure. Operation above 7 Bar (100 psi) may damage the pump and void the warranty.

Suction Lift
PSU060 pumps have an initial suction lift capacity of 3 ft. For best results minimize suction lift.
Liquid Inlet/Outlet Connections
PSU060 liquid ports are not NPT nor any other standard. Use of connectors other than those supplied by White Knight will damage the pump and void the warranty.
Liquid Line Restriction
PSU060 pumps may be controlled by closing liquid outlet lines. However, restricting liquid supply lines increases wear and should be avoided. Do NOT pump against a closed liquid inlet. It will damage the pump and void the warranty.
Running Dry
PSU060 pumps use the pumped liquid to lubricate their shafts. The pumps will cycle faster and wear more than normal when run dry, which may cause damage and loss of self-prime abilities. Standard models should not be run dry after startup and are not warrantied under dry run conditions. Dry-run capable PSUSD060 models may run dry for short periods. Warranty of dry-run models is one-year. Extended warranties are available.
Pulse Dampener with Shuttle Valve
Air supply pressure to PSU060 pumps should be at least ten psi higher than the liquid line pressure when using a pulsation dampener. Failure to do so may cause erratic operation.
Cross Contamination
PSU060 pumps use porous material that may retain chemicals. Take precautions to avoid cross contamination.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 4 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

2.2 Warnings
Pressurized Material
Pumps in use contain pressurized materials. Eliminate liquid and air pressure via shut off valves before pump is serviced or removed from the system.
High Temperature
Heat may transfer to exterior surfaces when pumps operate with high temperature fluids. Avoid direct contact with the pump when high temperature fluids are present.
Hazardous Chemical
Use appropriate personal protective equipment when handling pump. Reference Material Safety Data Sheet (MSDS) for information specific to your chemicals.
Loud Noise
Pump exhaust air contributes to work area noise levels. Only operate pumps with approved muffler media, and use ear protection in noisy conditions.
2.3 Advantages
Head Pressure / Dead-Head
PSU060 pumps can be controlled by adjusting their liquid outlet pressures and can be installed with head pressures up to dead-head (e.g. equal liquid and air pressures) with no damage to the pump.
Thermal Cycling
PSU060 pumps require no maintenance when operated within their performance range, even in thermal cycling applications.

2.4 Environment & System
Oversized Inlet Line
Pumps operate optimally with liquid inlet lines larger than the liquid outlet lines. This reduces strain on the bellows and may reduce pulsation in the pump outlet.
Clean Supply Air (CDA)
PSU060 pumps require use of Class 2 air for particles and moisture per ISO 8573-1. Use 10 micron filter; maintain -40°C dew point. A point-of-use filter is recommended during first six months of operation in new fabs/systems due to high risks of debris that can damage pumps and void warranty.
Flammable Solvents
PSU060 pumps are not constructed from conductive materials. System that pump flammable solvents should be properly grounded to avoid ignition by static charge. A River’s Edge test of isolative pumps with flammable liquids indicated that liquids must be grounded and other procedures should be followed. Copy of test available.
Pumping Liquids Near Boiling Point
Minimizing suction lift reduces pulsation and the potential for boiling or outgassing of liquid in the inlet of the pump. Although reciprocating pumps can pull suction lift, pump performance and life increase when suction lift is minimized or eliminated.
Abrasive Slurry
Pumping abrasive slurry may accelerate wear of components. PSU060 pumps are warrantied when used with slurry. However, normal wear is not covered by warranty.
Environmental Temperature
PSU060 pumps are rated for 0°C (32°F) 50°C (122°F) environmental temperatures. Do not freeze fluid in pump. Operation below 0°C may accelerate wear. Normal wear is not covered by warranty.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 5 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

2.5 Installation Instructions

  1. Move lever to up position.

  2. Slide base plate forward or pump body backward.

  3. Lift pump off of base plate.

Pull-back dismount is standard. See steps 4.1-4.3 for forward dismount.
4.
Screw base plate to surface with 3/8 in or 10 mm socket head cap screws into predrilled holes.

  1. Set pump on base knobs; slide it forward. Set lever to down position.

  2. Attach fittings to pump. Tighten to 55 inch-lbs.

  3. Attach tubes and fittings per manufacturer instructions. Use backer wrench to hold fitting in place at pump.

  4. Affix supply air via 1/4 in FNPT port on shuttle valve. Air line must be 1/4 in minimum orifice.

Push-Forward Dismount Configuration Setup Replace step 5 with steps 4.1-4.3 to re-configure the base plate to push-forward dismount configuration.

4.1
Move knobs to opposite sides.

4.2

4.3

Set pump on base

Move lever down

knobs; slide it backward. to locked position.

Install with Rigid Base Plate *Requires push-forward dismount configuration (steps 4.1-4.3)

Remove L bracket. Set lever in neutral (up) position.

Slide pump
forward; lift it off base plate.

Fix base plate to work station.
See step 4 above.

Return pump to base plate.

Move lock lever to down position. Reattach L bracket. Tighten to 12 in-lb.

Liquid Inlet/Outlet
Liquid ports are not NPT nor any other standard. Use of connectors other than those supplied by White Knight will damage the pump.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 6 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

2.6 Shuttle Service Instructions
Follow instructions below to inspect or service White Knight shuttle valves. If a pump has stopped, ensure all recommendations in this manual are followed and that there are no air supply issues (i.e. closed air valve, damaged regulator, oil in air line, etc.).
Do not lubricate or oil any of the shuttle components. White Knight shuttle valves do not require any lubrication.

1. Remove nuts on each air fitting on each pump head.

2. Unscrew both shuttle mounting bolts, and pull the shuttle from the pump.

3. Remove the airlines from both sides of the shuttle valve by unscrewing the air fittings.

4. Unscrew top shuttle end cap using the shuttle end cap tool.
Part: 12100-PV-0083

5. Carefully remove

6. Unscrew bottom

ceramic spool from

end cap using the

shuttle valve; it may

shuttle end cap tool.

break if dropped.

If the ceramic spool in your pump has a flat feature, it is critical that it is oriented towards the bottom of the pump when the shuttle valve is reassembled.

7. Unscrew
both 1/8 in NPT plugs that have an orifice in the center.

8. Remove muffler cap from left side using the
muffler cap tool. Remove muffler media and note the order of the pieces.
Repeat this step for
muffler cap and muffler media on the right side.

9. Blow out shuttle valve with CDA or N2. Ensure no residue or debris is in any areas indicated above. Debris or residue in these areas may hinder pump performance.

10. Clean the ceramic spool with IPA, and dry it using CDA or N2.

11. Reassemble shuttle and reattach it to the pump by following the above steps in reverse.
If the spool in your pump has the flat feature, ensure it is oriented towards the bottom of the pump when the shuttle valve is reassembled.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 7 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

3. Control & Monitoring

Programmable Control
White Knight CPT-1 controllers monitor and adjust run mode, flow rate, leak detection and other pump operations.

D10 Amplifier Electrical Hookups & Dimensions

White Knight recommends ExpertTM D10 amplifier for use with fiber optic stroke and leak detection assemblies.

Standard Models and Main Unit

1
3 2
Load 4
Load 5
QD hookup is functionally identical (Pink wire not used)

+ 10-30V dc Standard Models ­ 12-30V dc Bussable Power Models
150 mA max. load

Remote Teach

Wire Key 1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray

Sub-Units NPN
4 Load
5
PNP
4 Load
5

12-30V dc Connection

­ From Main

Unit Bus

Remote Teach

12-30V dc Connection

­ From Main

Unit Bus

Remote Teach

Single Sensor Design

PSU060 pumps can use only a single fiber optic sensor at a time. The probe may be installed in the “F” port on either side of the pump. White Knight offers PFA, PFH, and PFU pumps for dual fiber optic use.

Mounting Bracket (included with some models)

61.3 mm (2.42″)
68.1 mm (2.68″)

3.1 Fiber Optic Stroke Detection Installation

10.5 ± 0.2 mm (typ.) 14.5 mm

(0.41″)

(0.57″)

7.6 mm 35.9 mm 0.30″ (1.41″)
9.8 mm (0.39″)

  1. Remove stroke detect probe from fiber optic assembly.

  2. Replace NPT plug in “F” port with stroke detect probe. Hand-tighten.

  3. Insert the fiber optic cable until it seats at the bottom of the probe.

  4. Lower ferrule and gripper until snug against probe and hand tighten female gripper nut.

Fiber Optic Sensors
Fiber optic sensors melt if used at >130°C (266°F), resulting in leak or end of stroke detection failure.

  1. Open the top and slide the front face of the D10 up. Press the fiber optic ends into the holes on its front. Slide the face down to lock cables in place.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 8 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

3.2 Calibrating D10 Amplifier for Stroke Detection
When calibrating the D10 Amplifier for stroke detection, the pump should be in the same operating conditions it will be in during normal operation (i.e. supply air pressure, back pressure, etc.). The Fiber Optic must be installed as per the instructions in section 3.1.

Calibration:

Push Button Remote Line

Result

8 7 6 5 HS 4 3 DO 2 LO 1

Access Dynamic TEACH Mode

Press and hold dynamic push button >2 seconds.

Hold Remote line low (to ground) >2 Seconds.

· Power LED: OFF · Output LED: OFF · Bar graph: LO & DO Alternately Flashing

8 7 6 5 HS 4 3 DO 2 LO 1

TEACH Sensing Conditions

· Hold push button. · Operate pump normally for 15 seconds.

· Hold remote line low (to ground). · Operate pump normally for 15 seconds.

· Power LED: OFF · Output LED: OFF · Bar graph: LO & DO Alternately Flashing

Release button
Return to Run Mode

Release remote line/switch

Teach Accepted Power LED: ON Bar graph: One LED flashes to show relative contrast (successful setup requires minimum value of 4). Sensor returns to Run Mode with new settings.
Teach Unaccepted Power LED: OFF Bar graph: #1, 3, 5, 7 alternately flash to show failure to sense. Sensor returns to Run mode without changing settings. Set up again if value shows <4.

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

Upon completion of a successful learning cycle, the D10 Amplifier will continuously learn and self-teach to maintain the same cycle rate count readings.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 9 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

3.3 Single Pressure Switch Stroke Detection Installation

  1. Remove plug from “F” port.

  2. Attach NPT gripper to “F” port.

  3. Attach elbow assembly to pressure switch. Loosen female gripper nuts, and insert air tube between them. Hand tighten gripper nuts.

After your device is connected, you must set the switch point. If operating above 60 psi air supply, the set point is 43 psi (0.296 MPa), otherwise it is 18 psi (0.124 MPa). Each system is unique so values may need to be adjusted to your specific application. As the exhaust system loads, it may be necessary to adjust the set point.

3.4 Dual Pressure Switch Stroke Detection Installation
Perform all instructions to both sides of the pump.

  1. Attach T fittings to the “S” ports.

  2. Attach mufflers to the T fittings.

  3. Attach elbow assemblies to pressure switches.

  4. Loosen female gripper nuts on elbow assemblies and T fittings. Insert tubing and hand-tighten gripper nuts.

  5. Affix supply air via 1/4 in FNPT QEV ports on both sides. Air supply must be 1/4 in minimum orifice to source.

After your device is connected, you must set the switch point. If operating above 60 psi air supply, the set point is 43 psi (0.296 MPa), otherwise it is 18 psi (0.124 MPa). Each system is unique so values may need to be adjusted to your specific application. As the exhaust system loads, it may be necessary to adjust the set point.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 10 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

3.5 Pressure Switch Stroke Detection Electrical Hookups

NPN

PNP

( ) 35
1.378
( )8
0.315

( ) 50
1.969
( )8
0.315
ø3.7 ø0.146 cable

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 11 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

3.6 Conductivity Leak Detection Installation

Leaks are identified if conductive fluid contacts a sensor. Sensor provides a Sink (NPN)

or Source (PNP) signal, depending on the wire setup. See the wiring diagrams below.

Conductive leak detection does not qualify for use in explosion-proof environments. Conductive fluid required.

See below for elbow out configuration.

Source (PNP) Connection

Conductivity Leak Detect

White

+ Power

10-30

White/Blue Load – VDC

Wiring Diagrams

  1. Remove leak adapter from assembly.

  2. Replace NPT plug in “L” port with probe. Hand Tighten. Attach cable to signal translator (e.g. PLC).

Sink (NPN) Connection

White

Load

Conductivity

Leak Detect White/Blue

+ Power 10-30
– VDC

3.7 Fiber Optic Leak Detection Installation
D10 amplifier must be calibrated before attaching fiber optic probes to the pump. Fiber optic sensors can melt if used at >130°C (266°F), causing leak detect failure.
See below for elbow out configuration.

  1. Remove leak adapter and leak detect probe from fiber optic assembly.

  2. For straight out configuration replace NPT plug in “L” port with the probe. Hand-tighten.

  3. Insert the fiber optic cable until it contacts the bottom of the probe.

  4. Lower ferrule and gripper until snug against the probe. Hand tighten female gripper nut.
    For elbow out configuration:

  5. Open the top and slide the front face of the D10 up. Press the fiber optic ends into the holes on its front. Slide the face down to lock cables in place.

Fiber optic

Conductivity

1.1
Replace NPT plug in “L” port with elbow adapter.

1.2
Attach fiber optic or conductivity leak detect probe per instructions above.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 12 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

3.8 Calibrating D10 Amplifier for Leak Detection
Step 1: Power On D10 Amplifier & Set “Dark Operate” Mode:

Push Button

Remote Line

0.04 s “Click” 0.8 s 0.04 s T 0.8 s

Result

Access Setup Mode

Press and hold both buttons > 2 seconds.

Press either button until LEDs show desired settings.
Select Settings

Return to Run Mode

Press and hold both buttons >2 seconds.

8 7 6 5 HS 4 3 DO 2 LO 1

Double-pulse remote line
TT
T

· Green Power LED turns OFF.
· Output LED remains active.
2x · Icons continue to display current setup.
· Bargraph turns OFF.

Pulse the remote

line until LEDs show

desired settings.

T

T

Note: Doublepulsing remote line causes setting to “back up” one step.

Sensor toggles through these setting combinations: LO – Normal Speed – No Delay (default) DO – Normal Speed – No Delay LO – High Speed – No Delay DO – High Speed – No Delay LO – Normal Speed – Delay DO – Normal Speed – Delay LO – High Speed – Delay DO – High Speed – Delay

8 7 6 5 HS 4 3 DO 2 LO 1

Hold remote line low · Green Power LED turns ON.

T T

2 seconds.

· Sensor returns to Run

2 seconds mode with new settings.

Step 2: Access “Single-Point Dark Set” Mode

Push Button

Remote Line

0.04 s “Click” 0.8 s 0.04 s T 0.8 s

Result

Press and hold static

Single-pulse remote · Power LED: OFF.

Access button > 2

line

· Output LED: ON (push button)

Set Mode

seconds.

T 1x

OFF (remote line)

or

· Static LEDs: LO & DO

alternately flashing

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

Step 3: Set Sensing Condition

Set condition to “leak detection” sensing while probe tip is submerged in liquid. Then, remove the leak probe from liquid and reinserted into the “L” port. Amplifier will now signal when moisture if detected on the probe tip.

Push Button

Remote Line

0.04 s “Click” 0.8 s 0.04 s T 0.8 s

Result

Set Sensing Condition

· Present sensing

Present sensing

· Power LED: ON.

condition

condition

· Output LED: ON (push button)

or

· Five-click static button · Five-pulse remote lne

OFF (remote line)

· Bargraph: 4 indicators flash.

Sensor returns to Run mode with new settings

· Power LED: ON.

· Output LED: ON (push button)

OFF (remote line)

or

· Bargraph: #1, 3, 5, 7 flash for failure.

Sensor returns to Set sensing condition.

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

8 7 6 5 HS 4 3 DO 2 LO 1

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 13 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

4. Ordering Instructions

Required (Default Model)

Additional Options (Blank if not needed)

PSU060 F – F12 – LF0 – SF0 – TF12 – VX0 –

1

2

3

4

5

6

7

Rev

Options 1-3 are required. Leave Additional Options blank if not desired. Only add Outlet if different than Inlet.

Default options are highlighted

1. Pump Model

Standard

PSU060

Dry-Run

PSUSD060

2. Check Ball Material

PFA Check balls

F

PTFE Check balls

M

4. Leak Detection

No leak detection

blank

15 ft fiber optic cable with no amplifier LF0

15 ft fiber optic cable with D10 amplifier LF1

25 ft fiber optic cable with no amplifier LF2

25 ft fiber optic cable with D10 amplifier LF3

15 ft conductivity cable

LC0

25 ft conductivity cable

LC1

3. Inlet Fitting Front straight only

Flaretek

1/2 in. F08

Compatible 3/4 in. F12

1 in. F16

1-1/4 in. F20

Tube Out 1/2 in. T08

3/4 in. T12

1 in. T16

1-1/4 in. T20

Weldable 3/4 in. W12

1 in. W16

Pillar S-300 3/8 in. P06

1/2 in. P08

3/4 in. P12

1 in. P16

1-1/4 in. P20

FNPT

1/2 in. N08

3/4 in. N12

1 in. N16

Synchro- 1/2 in. S08 Flare 3/4 in. S12

1 in. S16

PrimeLock 1/2 in. L08

3/4 in. L12

1 in. L16

1-1/4 in. L20

5. Stroke Detection

No stroke detection

blank

15 ft fiber optic cable with no amplifier SF0

15 ft fiber optic cable with D10 amplifier SF1

25 ft fiber optic cable with no amplifier SF2

25 ft fiber optic cable with D10 amplifier SF3

Single NPN Pressure Switch

SP1

Dual NPN Pressure Switches * (Includes two DP2 pressure switches)

SP2

Single PNP Pressure Switch

SP4

Dual PNP Pressure Switches * (Includes two DP2 pressure switches)

SP5

7. Shuttle

Gravity reset with standard exhaust

blank

No shuttle, standard ports *

(No pressure switches included)

VX0

Sensors are required for operation.

Gravity Reset with Remote Exhaust VG1

Mag Detent with Standard Exhaust

VM0

Mag Detent with Remote Exhaust

VM1

  • White Knight shuttle valve not included.

Timer mode operation requires end-of-stroke detection. Use of timer mode without stroke detection voids the warranty.

6. Outlet Fitting Straight only. Select Top or Front.

Same as Inlet

Flaretek 1/2 in. Compatible 3/4 in.

1 in.

1-1/4 in.

Tube Out 1/2 in.

3/4 in.

1 in.

1-1/4 in.

Weldable 3/4 in.

1 in.

Pillar S-300 3/8 in.

1/2 in.

3/4 in.

1 in.

1-1/4 in.

FNPT

1/2 in.

3/4 in.

1 in.

Synchro- 1/2 in. Flare 3/4 in.

1 in.

PrimeLock 1/2 in.

3/4 in.

1 in.

1-1/4 in.

Front
blank
FF08 FF12 FF16 FF20 FF08 FF12 FF16 FF20 FW12 FW16 FP06 FP08 FP12 FP16 FP20 FN08 FN12 FN16 FS08 FS12 FS16 FL08 FL12 FL16 FL20

Top
n/a TF08 TF12 TF16 TF20 TT08 TT12 TT16 TT20 TW12 TW16 TP06 TP08 TP12 TP16 TP20 TN08 TN12 TN16 TS08 TS12 TS16 TL08 TL12 TL16 TL20

Revision

No revision

blank

Contact support for revision level
or copy exact code activation details. Configured part numbers are not Copy Exact Part Numbers. support@wkfluidhandling.com

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 14 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

5. Pump Service
Pumps fully rebuilt by White Knight, certified rebuilders, or technicians certified by White Knight receive full warranty renewal. Details below.

White Knight Rebuilds
Request factory rebuilds by web form at: https://wkfluidhandling.com/support/rma/. An RMA# will be provided after processing.
*Customers must follow decontamination instructions in Section 4.4 when returning a pump to White Knight.

Certified Rebuilders
White Knight’s global network of certified rebuilders expedite rebuild turn- around time and minimize shipping costs. Find certified rebuilders at: https://wkfluidhandling.com/rebuilders/

Rebuild Pump as Certified Technician
White Knight offers trainings to certify technicians to rebuild pumps. Technicians who pass the training are issued a two-year certification. During the two years, parts in pumps rebuilt by the technician receive a full warranty. See: https://wkfluidhandling.com/virtual-rebuilds/

5.1 Rebuild Kits & Parts

Rebuild kit for PSU060F is RBPSU060F-1. Rebuild kit for PSUSD060F is RBPSUSD060F-1 (labor not included). To request rebuilds by White Knight, use RBPSU060F-5 or RBPSUSD060F-5, respectively (labor included).

11 2 3 4 5 6

Pump rebuilds require tool kit: 12200-XX-0026 (Legacy# PSU060-170) Dry-run (SD) pumps use different shaft and shaft seals. Contact White Knight for details.

7 12 8

10

9

1

RBPSU060F-1

ITEM NO. PART NUMBER

DESCRIPTION

QTY.

1

3133-TE-0006

REPLACEABLE SEAT, SHIFT, UNIVERSAL

2

2

4100-PF-0001

PFA CHECK BALL-3/4″

4

3

4135-MP-0014

BOTTOM CHECK SEAT, LOWER

2

4

4137-TE-0010

BOTTOM CHECK CAGE, 10 GPM

2

5

4137-TE-0011

MIDDLE CHECK CAGE, 10 GPM

4

6

4142-MP-0008

TOP CHECK SEAT, UPPER

2

7

4142-TE-0013

TOP CHECK CAGE, 10 GPM

2

8

5143-MP-0004

SEAL, SHAFT, U-SERIES, 60L

2

9

6140-FP-0004

BAFFLE POROUS POLY 60L

6

10

6530-TE-0002

Shuttle End Plug 10 gpm

2

11

14300-MP-0020

BELLOWS ASSEMBLY SHIFT 60 U

2

12

14320-PF-0004 LOADED SHAFT ASSEMBLY, 60L, U-SERIES, CERAMIC

1

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 15 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

5.2 Return Pump for Service
Follow decontamination instructions when returning a pump for service.
DO NOT REMOVE PAGE FROM MANUAL. Copy page from manual or download at https://wkfluidhandling.com/support/rma/.
Decontamination Instructions
PRINT COMPLETED DECONTAMINATION CERTIFICATION. IT MUST BE INCLUDED IN YOUR RMA SHIPMENT.
White Knight products are designed for use with caustic and otherwise dangerous liquids. Handle every product as if it contains dangerous chemicals whether or not it actually does.
· Only those with adequate safety training should attempt to handle used pumps. · Wear adequate safety gear appropriate for chemicals that have been in the pump. · Review relevant Material Safety Data Sheets (MSDS) before handling the pump. · Review emergency numbers for use in event of an accident. · Prepare Ph papers, showers, antidotes, clean-up equipment, neutralizers, and other safety devices
used to detect, neutralize or minimize effects of chemicals described in appropriate MSDS documents.

Rinse with DI Water
Circulate DI water through pump for twenty minutes before disassembly and/or double bagging for shipment. If pump is nonfunctional, force DI water from inlet through outlet for 40 minutes before shipment preparations.
Remove Pump from Station:
1. Disconnect liquid tubing connectors from front of pump (opposite shuttle valve). 2. Plug NPT fittings with PTFE plug, Flare fittings with flare nose cover and cap,
or other plug or cap as recommended by connector supplier. 3. Disconnect air supply tubing from face of shuttle valve. 4. Loosen mount screw from base plate. (Note: do not remove screw from base plate). 5. Remove base plate using proper tool for the fastening devices (e.g. Allen wrench or screw driver).
Note: Base plate may stay if needed for replacement pump to be used. 6. Return all removed parts to the pump.

Return Pump to White Knight:
1. Rinse pump with DI water as described above after removing it from its station. 2. Drain remaining DI water from the pump inlet and outlet liquid tubing connectors. 3. Plug liquid outlets as described in the Remove Pump from Station section above. 4. Dry the pump, double bag it, and seal it in thick polyethylene bags. 5. Return the pump to its original packaging. 6. Include MSDS for the chemical that the pump was handling in the box with the pump. 7. Obtain RMA number from White Knight and write it on the outside of the box. 8. Ship to White Knight following all rules, regulations and laws regarding shipment of dangerous
materials. Ship freight pre-paid. No collect shipments will be accepted. Unauthorized use of White
Knight shipping accounts will result in the adding of freight to the bill in addition to a service charge.

Include All Pump Components:
Pumps returned to White Knight for evaluation, service or repair must be complete with all components, including but not limited to base plate, mount screws, tubing connectors, tubing connector caps, flare noses, shuttle valves, mufflers, and tubing. Missing parts will be added to the pump and charged to the customer.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 16 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

DO NOT REMOVE PAGE FROM MANUAL. Copy page from manual or download at https://wkfluidhandling.com/support/rma/.

Decontamination Certification

COMPLETE AND PRINT THIS FORM. IT MUST BE INCLUDED IN YOUR RMA SHIPMENT.

I, the undersigned employee of

, certify that all

decontamination and safety procedures described in Decontamination Instructions section have

been followed for return of product below.

RMA#: (We cannot process returns without an RMA number.)

Serial#: (We cannot process returns without a product serial number.)

Metal Exposure:
(Check all that apply. Write in other metals if necessary.)

Product was used in a Metal Process.

Yes

No

Product was used in a Copper Metal Process.

Yes

No

Product was used with:

Aluminum

Cobalt

Gold

Lead

Nickel

Platinum

Silver

Tin

Titanium

Tungsten

Zinc

Other:

Chemical Exposure:
(Check all that apply. Write in other chemicals if necessary.)

Product was NOT used in chemicals (DI Water only).

Product was used in chemicals.

Ammonia Nitric Acid

Ammonium Hydroxide Phosphoric Acid

Hydrochloric Acid Sulfuric Acid

Hydrofluoric Acid Other:

Hydrogen Peroxide IPA

Shipping Information:
Please indicate metal processes to which the product has been exposed by clearly and conspicuously labeling the outside of the return package with the metal.

Products exposed to Metal Processes must be sent to the following address:

Products NOT exposed to Metal Processes must be sent to the following address:

White Knight Fluid Handling 187 East 670 South, Suite B Kamas, UT 84036

White Knight Fluid Handling 187 East 670 South, Suite C Kamas, UT 84036

Print Name: Signature:

Date:

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 17 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

6. Warranty
White Knight follows strict manufacturing, assembly and testing procedures to ensure consistency and reliability.
White Knight warrants PSU060 pumps and components are free from defects in materials and workmanship for two years from our shipment date or your installation date if provided within 90 days of shipment from our facility.
Failures due to normal wear, misuse, abuse or unauthorized disassembly nullify this warranty.
White Knight does not guarantee the suitability of products for specific applications. White Knight is not liable for any damage or expense resulting from use or misuse of its products in any application. Responsibility is limited solely to repair or replacement of defective products or components.
Prior written, faxed or emailed approval must be obtained from White Knight before returning any product or component for warranty consideration. All determinations regarding cause of failure are made by White Knight, and all decisions regarding warranty fulfillment or nullification are made by White Knight.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, INCLUDING ANY GUARANTEE OF SUITABILITY FOR ANY PURPOSE. NO VARIATIONS OF THIS WARRANTY SHALL BE HONORED NOR CONSIDERED LEGALLY BINDING, EXCEPT WRITTEN AGREEMENTS SIGNED BY THE CEO OF WHITE KNIGHT FLUID HANDLING.

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 18 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 19 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

Pump Solutions and Accessories

Ultra-Pure Closed-Loop Systems
Automatically maintain laminar flow or steady pressure with metal-free closed- loop pump systems offering stable temperatures, deadhead and suction lift. Control your high purity chemical processes and delivery systems. Simplify process automation to save time, resources and reduce costs.
https://wkfluidhandling.com/closed-loop/

· 140 lpm (36 gpm) flow rates · 7 Bar (100 psi) pressures · 210°C (410°F) temperatures · Maintain stable temperatures
· No metals, no corrosion · No elastomer O-rings, no leaks · No electric motors, no heat rise

Pulse Dampeners
In-line and pump-mounted pulse dampeners reduce pulsation in fluid systems to improve flow control, increase batch yields, protect components, and minimize maintenance and downtime for repairs. DBU030 dampeners fit 30 and 60 lpm pumps. DBU060 dampeners fit 30, 60 and 140 lpm pumps. DBU140 dampeners fit 60 and 140 lpm pumps.
https://wkfluidhandling.com/dampeners/

In-line pulse dampener
Pump-mounted pulse dampener

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 20 Subject to change without notice

engineer approvedTM

PSU060 Owner’s Manual

Pressure Regulators
White Knight pressure regulators offer remote piloting capability to maintain system pressure for high-purity chemical circulation loops and systems with multiple tool drops or dispense points. They feature fully-swept PTFE/PFA flow paths. A single back-pressure regulator equalizes upstream fluid pressure across multiple discharge outlets. Forward-pressure regulators control downstream pressure.

Pressure Regulators

Back-pressure regulator
40 PSI 40 PSI 40 PSI 40 PSI

Liquid Air
40 PSI

Fluid Tank

Forward-pressure regulator

Air

20 PSI

Liquid

25 PSI

20 PSI

25 PSI 10 PSI

10 PSI

15 PSI

A single back-pressure regulator equalizes upstream 10 PSI

15 PSI

fluid pressure for discharge outlets. Each forward-pressure regulator controls fluid pressure for a single discharge outlet.

Fluid Tank

Filter Housings
Two-chamber and four-chamber filter housings provide parallel or series (in- line) operation. Their compact, non-metallic PTFE/PFA designs offer superior containment and high-flow performance within a smaller footprint than traditional housings. They fit many filter types, and enable filters to be changed without disconnecting liquid lines. https://wkfluidhandling.com /filter-housings/

Cycle-Rate Translator
The CPT enables pump replacements in existing tools. It operates a White Knight pump at its optimal cycle rate and scales the operational cycle rate to that expected by the tool. https://wkfluidhandling.com/cpt/

CatcherTM Pre-Filters
White Knight CatcherTM pre-filters protect pumps from wafer shards and other harmful solids. They can be cleaned without disconnecting liquid lines. https://wkfluidhandling.com/catchers/

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Ver. 2.2.1 | 5 Dec 2023 | P. 21 Subject to change without notice

engineer approvedTM
White Knight Support
187 E. 670 S. Kamas, UT 84036 Phone: 435.783.6040 Toll Free: 888.796.2476 Fax: 435.783.6128 support@wkfluidhandling.com https://wkfluidhandling.com/support/

Part No. 18200-LM-0021

Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com

Version 2.2.1 | 5 Dec 2023 Subject to change without notice

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

WK User Manuals

Related Manuals