WK PSU060 Pumps White Knight Fluid Handling Owner’s Manual
- June 16, 2024
- WK
Table of Contents
- PSU060 Pumps White Knight Fluid Handling
- Product Information
- Specifications & Performance
- Product Usage Instructions
- 1. Installation
- 2. Control & Monitoring
- 3. Ordering Instructions
- 4. Pump Service
- 4.1 Rebuild Kits & Parts
- 4.2 Return Pump for Service
- Q: What is the maximum flow rate of the PSU060 pump?
- Q: What is the weight of the PSU060 pump?
- Q: Can the PSUSD060 pump operate in a dry-run condition?
PSU060 Pumps White Knight Fluid Handling
Product Information
Specifications & Performance
Model| Max Flow Rate| Displacement Per Cycle| Cycles per min| Air
Connection| Weight| Suction Lift*| Sound Pressure| Power
---|---|---|---|---|---|---|---|---
PSU060| 62.2 lpm (16.43 gpm)| 0.178 liters (0.047 gal)| 348 max| 1/4 in| 15.2
kg (33.43 lb)| 1 m (3 ft)| 73.11 dB(a) at 100 psi 50 CPM| 64.29 dB(a) at 100
psi 50 CPM
PSUSD060| 59.5 lpm (15.72 gpm)| 0.178 liters (0.047 gal)| 348 max| 1/4 in|
15.2 kg (33.43 lb)| Flooded suction| 82.5 dB(a) at 100 psi max CPM| 74.11
dB(a) at 100 psi max CPM
- May vary by configuration or system. Suction lift diminishes
over time. Recommended installation level less than 3 ft above
source. To calculate displacement, divide flow rate by CPM. **
Sound measured in accordance with ISO9614-2:1997. *** Dry-run
capable PSUSD060 pumps require flooded suction and may have reduced
warranty. Contact support for details.
Product Usage Instructions
1. Installation
To install your White Knight PSU060 pump, please follow these
steps:
-
Choose a suitable location for the pump. Ensure it is close to
the fluid source and within the recommended installation level
(less than 3 ft above the source). -
Securely mount the pump using appropriate hardware to ensure
stability. -
Connect the air supply line to the 1/4 inch air connection on
the pump. -
Connect the fluid inlet and outlet lines to the corresponding
ports on the pump. -
Ensure all connections are tight and leak-free.
-
Verify that the suction lift is within the specified range (1 m
or 3 ft). -
Once the pump is properly installed, proceed to the next
section for control and monitoring instructions.
2. Control & Monitoring
To control and monitor your White Knight PSU060 pump, please
follow these instructions:
-
Ensure that the power supply is connected and turned on.
-
Use the provided control panel or interface to adjust the
desired flow rate and operating parameters. -
Monitor the pump’s performance, including the suction lift,
sound pressure, and power consumption, using the built-in
indicators or external monitoring devices. -
Regularly check for any abnormal behavior or irregularities in
the pump’s operation. -
If any issues are detected, refer to the troubleshooting
section of the manual or contact customer support for
assistance.
3. Ordering Instructions
To order additional parts or accessories for your White Knight
PSU060 pump, please follow these steps:
-
Identify the specific part or accessory you need based on the
product documentation or your requirements. -
Contact the authorized distributor or sales representative to
place your order. -
Provide the necessary details, including the model number
(PSU060), quantity, and any specific configuration or customization
requests. -
Confirm the order details, including pricing, delivery
schedule, and payment terms. -
Once the order is processed, you will receive a confirmation
with the shipment tracking information.
4. Pump Service
If you require service or maintenance for your White Knight
PSU060 pump, please follow these instructions:
4.1 Rebuild Kits & Parts
If you need to rebuild or replace certain components of your
pump, you can order rebuild kits and parts from White Knight.
Follow these steps:
-
Identify the specific components that need to be replaced or
rebuilt. -
Contact the authorized distributor or sales representative to
inquire about available rebuild kits and parts. -
Provide the necessary details, including the model number
(PSU060), required quantity, and specific components needed. -
Confirm the availability, pricing, and delivery schedule with
the distributor or sales representative. -
Place your order and follow the instructions provided for
payment and shipment.
4.2 Return Pump for Service
If your pump requires service or repair, you may need to return
it to White Knight. Follow these steps:
-
Contact customer support to discuss the issue with your pump
and determine if it can be resolved remotely or if it needs to be
returned. -
If returning the pump is necessary, obtain a return
authorization (RA) number and shipping instructions from customer
support. -
Package the pump securely to prevent damage during
transit. -
Include the RA number and any relevant documentation inside the
package. -
Ship the package to the designated address using a reliable
shipping method. -
Once the pump is received and evaluated by White Knight, they
will perform the necessary service or repair and return the pump to
you.
5. Warranty & Accessories
For information about the warranty coverage and available
accessories for your White Knight PSU060 pump, please refer to the
warranty documentation provided with your product or contact
customer support.
FAQ
Q: What is the maximum flow rate of the PSU060 pump?
A: The maximum flow rate of the PSU060 pump is 62.2 lpm (16.43
gpm).
Q: What is the weight of the PSU060 pump?
A: The weight of the PSU060 pump is 15.2 kg (33.43 lb).
Q: Can the PSUSD060 pump operate in a dry-run condition?
A: No, the PSUSD060 pump is not dry-run capable and requires
flooded suction. Operating it in a dry-run condition may void the
warranty. Please contact support for more information.
engineer approvedTM
PSU060 Owner’s Manual
187 E. 670 S., Kamas, UT 84036 435.783.6040 888.796.2476 https://wkfluidhandling.com
Table of Contents
1. Product Information
1
1.1 Specifications & Performance ……………………………………………………………………………….1 1.2 Temperature Limits………………………………………………………………………………………………2 1.3 Dimensions ………………………………………………………………………………………………………..2 1.4 Bill of Materials……………………………………………………………………………………………………3
2. Installation
4
2.1 Precautions ………………………………………………………………………………………………………..4 2.2 Warnings ……………………………………………………………………………………………………………5 2.3 Advantages ………………………………………………………………………………………………………..5 2.4 Environment & System…………………………………………………………………………………………5 2.5 Installation Instructions…………………………………………………………………………………………6 2.6 Shuttle Service Instructions…………………………………………………………………………………..7
3. Control & Monitoring
8
3.1 Fiber Optic Stroke Detection Installation…………………………………………………………………8 3.2 Calibrating D10 Amplifier for Stroke Detection…………………………………………………………9 3.3 Single Pressure Switch Stroke Detection Installation………………………………………………….10 3.4 Dual Pressure Switch Stroke Detection Installation ……………………………………………………10 3.5 Pressure Switch Stroke Detection Electrical Hookups……………………………………………. 11 3.6 Conductivity Leak Detection Installation…………………………………………………………………..12 3.7 Fiber Optic Leak Detection Installation ……………………………………………………………………12 3.8 Calibrating D10 Amplifier for Leak Detection …………………………………………………………13
4. Ordering Instructions
14
5. Pump Service
15
5.1 Rebuild Kits & Parts …………………………………………………………………………………………..15 5.2 Return Pump for Service…………………………………………………………………………………….16
6. Warranty & Accessories
20
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Version 2.2.1 | 5 Dec 2023 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
Dear valued customer,
Thank you for purchasing a White Knight PSU060 pump.
Our dedicated team designs products to meet your exacting specifications with
a demonstrated commitment to quality that goes beyond mere words and fancy
slogans.
Our patented designs offer a variety of size and material options to meet
stringent requirements of high-pressure chemical delivery systems,
hightemperature re-circulation processes, chemical reclaim and bulk transport
applications, slurry systems, and more. Our safe, reliable products offer
superior performance, optimized efficiency, and simplified maintenance.
White Knight is able to provide the highest quality fluid handling products
through controlled, consistent in-house engineering and manufacturing. Through
continued significant investments in engineering and manufacturing, we lead
the industry with new technologies and products.
White Knight has received numerous awards for innovation and manufacturing
programs. We rigorously manage our quality assurance processes to ensure
consistency and reliability. Our quality controls include strict cleanliness
procedures and consistent manufacturing processes. For example, high-purity
product assembly, testing, and packaging is performed in a Class 100
cleanroom.
Please peruse this manual before installing your White Knight product. It
details installation requirements and setup instructions, and provides
additional information and accessories for enhanced functionality.
Our team has gone to great lengths to ensure our products serve your needs and
meet your requirements.
Further, we provide the highest quality products at the best value, and we
back them up with excellent warranties and world class support.
Thank you for your confidence and trust in White Knight products.
Sincerely,
White Knight Fluid Handling
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
1. Product Information
1.1 Specifications & Performance
Model
PSU060
PSUSD060
Max Flow Rate*
62.2 lpm (16.43 gpm)
59.5 lpm (15.72 gpm)
Displacement Per Cycle*
0.178 liters (0.047 gal)
0.178 liters (0.047 gal)
Cycles per min
348 max
348 max
Air Connection
1/4 in
1/4 in
Weight
15.2 kg (33.43 lb) 15.2 kg (33.43 lb)
Suction Lift*
1 m (3 ft)
Flooded suction
Sound
Pressure**
73.11 dB(a) at 100 psi 50 CPM 82.5 dB(a) at 100 psi max CPM
Power**
64.29 dB(a) at 100 psi 50 CPM 74.11 dB(a) at 100 psi max CPM
- May vary by configuration or system. Suction lift diminishes over time. Recommended installation level less than 3 ft above source. To calculate displacement, divide flow rate by CPM. ** Sound measured in accordance with ISO9614-2:1997. *** Dry-run capable PSUSD060 pumps require flooded suction and may have reduced warranty. Contact support for details.
Max Fluid Temperature
Environmental Temperature
Max Supply Air Pressure
Min Startup Air Pressure
Fluid Path Materials
Non-Fluid Path Materials
210°C (412°F) min: 0°C (32°F) max: 50°C (122°F) 7 Bar (100 psi)
1.4 bar (20 psi)
PTFE, PFA
PTFE, PFA, Ceramic
Stroke Detection
Leak Detection
Electronic Control
Fiber optic with or without D10 sensor, or solid state pressure switch (NPN or
PNP)
Fiber optic with or without sensor, or conductivity
CPC, CPT, or custom. Call for details.
Discharge Pressure
PSU060 Performance
100
7 100 PSI
90 6
100 CPM
80
80 PSI
160 CPM
70
5
Air Pressure Air Consumption Cycle Rate
PSUSD060 Performance
100
7 100 PSI
90
6
80
80 PSI
70
5
100 CPM
20 SCFM 160 CPM
Air Pressure Air Consumption Cycle Rate
Discharge Pressure
60 PSI 60
4 50
3 40 PSI 40
20 SCFM 15 SCFM
200 CPM 25 SCFM
30
2
20 PSI 20
1 10
5 SCFM
10 SCFM
240 CPM 280 CPM
60 PSI 60
4 50
3 40 PSI 40
15 SCFM
30
2
20 PSI
10 SCFM
20
1 10
5 SCFM
25 SCFM 200 CPM
240 CPM 280 CPM
PSI Bar
LPM
10
20
30
40
50
60
70
PSI Bar
LPM
10
20
30
40
50
60
70
m3/hr
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
m3/hr
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
GPM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Liquid Flowrate
GPM 1 2 3 4 5 6 7 8 9 10 11 1 2 13 14 15 16 17 18
Liquid Flowrate
How to Read Charts
Draw a horizontal line at your discharge pressure and vertical line at desired
flow rate. At line intersect, estimate required air pressure, resultant cycle
rate and air consumption.
Example At 2 Bar (30 psi) discharge pressure and 80 psi air pressure, PSU060 pumps provide 40 lpm (10.6 gpm) flow rate, cycle at ~230 CPM and exhaust 18 SCFM of air.
*Graph is for reference only. Performance was measured utilizing 1/2 in (3/8 in ID) air line and 1-1/4 in (1-1/8 in ID) liquid lines with 1 ft flooded suction. Performance may vary in your system.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 1 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
1.2 Temperature Limits
140°F 7
180°F
220°F
260°F
300°F
340°F
380°F
420°F 100
90 6
80 5
70
Air Supply Pressure
4
60
50
3 40
2
30
1 Bar 60°C
80°C
100°C
120°C
140°C
160°C
180°C
200°C
20
PSI 220°C
1.3 Dimensions
Dimensions in [mm] in
294 11.6
196 7.7
167
75
6.6
3.0
MOUNT WITH 2 EA. 3/8″ (10 mm) SOCKET HEAD CAP SCREWS
288
27
11.3
1.1
13 .5 64 2.5
54 2.1
19 .8
177 7.0
CL
95
201
3.7
7.9
10
.4
55
2.2
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 2 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
1.4 Bill of Materials
32
Shuttle Assembly
24
14450-TE-0002
27
28
35
43
35 34
1
39
22
38
20 18
37
25
13
26
41 42
23
2
16
21
19
4
17 21
20
22 15 36
7 5
23
8
14
Right Head Assembly
6
PSU060F BILL OF MATERIALS
Part
Description
Qty
1 1125-TE-0021 Pump Body
1
2 2127-TE-0031 Head, Right
1
3 2127-TE-0032 Head, Left
1
4 3133-TE-0006 Seat, Head, Shift
2
5 4100-PF-0001 PFA Check Ball, .765″
4
6 4135-MP-0014 Bottom Check Seat, Lower 2
7 4137-TE-0010 Bottom Check Cage
2
8 4137-TE-0011 Middle Check Cage
4
9 4139-TE-0005 Cage, Plug
2
10 4140-TE-0006 Top Check Plug
2
11 4142-MP-0008 Top Check Seat, Upper
2
12 4142-TE-0013 Top Check Cage
2
13 5143-MP-0004 Seal, Shaft
2
14 6020-TE-0004 Elbow, Gripper,
2
1/4″ NPT x 3/8″
15 6030-TE-0001 Elbow, Gripper,
2
1/8″ Npt X 1/4″
16 6070-TE-0001 Female Gripper Nut, 1/4″ 2
17 6070-TE-0002 Nut, Gripper, Female, 3/8″ 2
18 6070-TE-0004 Male Gripper Nut, 1/4″
2
19 6070-TE-0005 Male Gripper Nut, 3/8″
2
20 6080-KF-0001 Gripper, 1/4″
4
21 6080-KF-0002 Gripper, 3/8″
4
22 6080-TE-0001 Ferrule, 1/4″
4
23 6080-TE-0002 Ferrule, 3/8″
4
24 6140-FP-0004 Baffle
6
25 6140-PP-0002 Spacer, Baffle
6
26 6150-TE-0011 Cap, Muffler
2
27 6530-TE-0002 Shuttle End Plug
2
28 6560-CE-0002 Shuttle Spool
1
29 7400-PF-0002 Insert, S-300®
2
30 7400-PF-0006 Nut, S-300®, 3/4″
2
31 7400-TE-0004 Body, S-300®, 3/4″
2
32 10010-TE-0016 Screw, Mount, Shuttle
2
33 10010-TE-0018 Screw, Mount, Plate, Base 2
34 10020-TE-0004 Pin, Alignment, Shuttle
2
35 10040-TE-0002 Plug, NPT, 1/8″
3
36 10040-TE-0003 Plug, NPT, 1/4″
4
37 10040-TE-0015 Plug, Vent, NPT, 1/8″
2
38 10071-PF-0008 Tubing, Thick Wall, 1/4″
2
39 10071-PF-0010 Tubing, 3/8″
2
40 14200-TE-0003 Base Plate Assembly
1
41 14300-MP-0020 Bellows Assembly
2
42 14320-PF-0004 Shaft
1
43 14400-TE-0010 Shuttle Body with Sleeve 1
14100-TE-0007
9
Includes #2 and #4
33
Fittings (Type, Size, Option)
Flaretek
1/2 in. F08
Compatible 3/4 in. F12
1 in. F16
1-1/4 in. F20
Tube Out 1/2 in. T08
3/4 in. T12
1 in. T16
1-1/4 in. T20
Weldable 3/4 in. W12
1 in. W16
Pillar S-300 3/8 in. P06
1/2 in. P08
3/4 in. P12
1 in. P16
1-1/4 in. P20
FNPT
1/2 in. N08
3/4 in. N12
1 in. N16
Synchro- 1/2 in. S08 Flare 3/4 in. S12
1 in. S16
PrimeLock 1/2 in. L08
3/4 in. L12
1 in. L16
1-1/4 in. L20
Plugged
B00
Assemblies
Body Inlet Only (Nut not included)
14510-PF-0004 7200-PF-0005
14510-PF-0005 7200-PF-0006
14510-PF-0006 7200-PF-0007
14510-PF-0007 7200-PF-0008
7120-PF-0004
7120-PF-0005
7120-PF-0006
7120-PF-0011
7300-PF-0003
7300-PF-0004
14530-PF-0028 7400-TE-0036
14530-PF-0003 7400-TE-0003
14530-PF-0004 7400-TE-0004
14530-PF-0005 7400-TE-0005
14530-PF-0009 7400-TE-0012
7100-TE-0006
7100-TE-0004
7100-TE-0008
14520-TE-0003 7010-TE-0005
14520-TE-0004 7010-TE-0004
14520-TE-0006 7010-TE-0006
14570-PF-0003 7800-TE-0003
14570-PF-0004 7800-TE-0004
14570-PF-0005 7800-TE-0005 14570-PF-0012 7800-TE-0012
7130-TE-0003
10 12 5 8 11
Left Head Assembly 14100-TE-0008 Includes #3 and #4
3
31 29 30
40
Leak Detect
Part
Description
14600-XX-0009 LF0 15 ft fiber optic cable
with no amplifier
14600-XX-0010 LF1 15 ft fiber optic cable
with D10 amplifier
14600-XX-0011 LF2 25 ft fiber optic cable
with no amplifier
14600-XX-0012 LF3 25 ft fiber optic cable
with D10 amplifier
14600-XX-0031 LC0 15 ft conductivity cable
14600-XX-0040 LC1 25 ft conductivity cable
Stroke Detect with Fiber Optics
Part
Description
14700-XX-0017 SF0 15 ft fiber optic cable
with no amplifier
14700-XX-0018 SF1 15 ft fiber optic cable
with D10 amplifier
14700-XX-0019 SF2 25 ft fiber optic cable
with no amplifier
14700-XX-0020 SF3 25 ft fiber optic cable
with D10 amplifier
Stroke Detect with Pressure Switch
14900-NP-0004 SP1 Single NPN Switch 14900-NP-0003 SP2 Dual NPN Switches 14900-NP-0001 SP4 Single PNP Switch 14900-NP-0002 SP5 Dual PNP Switches
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 3 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
2. Installation
2.1 Precautions
Handling
Do NOT lift pump by shuttle valve assembly nor air tubing.
Installation Orientation
PSU060 pumps must be installed in an upright position. The check valves are
actuated by gravity and/or flow, and they will not seat if the pump is not
upright.
Timer Mode
PSU060 pumps require an end of stroke detection mechanism (pressure switch) to
prevent over stroking in timer mode. Operating a PSU060 in timer mode without
stroke detection will void the pump warranty.
Required Air Flow (Shuttle Valve)
PSU060 pumps require 1/4 in minimum orifice with unrestricted air flow.
Required Air Flow (Solenoid Valve)
PSU060 pumps require a 1.5 Cv solenoid. Using a reduced Cv will reduce flow
rates. Using a valve with more than 20% greater Cv will change operating
parameters, reduce pump life and void the warranty.
Under Supply of Air
PSU060 pumps operate erratically or stall when air supply is insufficient.
Ensure use of air supply pressures higher than averaged air consumption lines
in performance charts. Air supply lines and fittings must meet minimal inner
diameter requirements shown in the installation instructions.
Air Supply Pressure
Operating PSU060 pumps ~35% below max air pressure may significantly extend
pump life. PSU060 pumps require 20 psi minimum air pressure. Operation above 7
Bar (100 psi) may damage the pump and void the warranty.
Suction Lift
PSU060 pumps have an initial suction lift capacity of 3 ft. For best results
minimize suction lift.
Liquid Inlet/Outlet Connections
PSU060 liquid ports are not NPT nor any other standard. Use of connectors
other than those supplied by White Knight will damage the pump and void the
warranty.
Liquid Line Restriction
PSU060 pumps may be controlled by closing liquid outlet lines. However,
restricting liquid supply lines increases wear and should be avoided. Do NOT
pump against a closed liquid inlet. It will damage the pump and void the
warranty.
Running Dry
PSU060 pumps use the pumped liquid to lubricate their shafts. The pumps will
cycle faster and wear more than normal when run dry, which may cause damage
and loss of self-prime abilities. Standard models should not be run dry after
startup and are not warrantied under dry run conditions. Dry-run capable
PSUSD060 models may run dry for short periods. Warranty of dry-run models is
one-year. Extended warranties are available.
Pulse Dampener with Shuttle Valve
Air supply pressure to PSU060 pumps should be at least ten psi higher than the
liquid line pressure when using a pulsation dampener. Failure to do so may
cause erratic operation.
Cross Contamination
PSU060 pumps use porous material that may retain chemicals. Take precautions
to avoid cross contamination.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 4 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
2.2 Warnings
Pressurized Material
Pumps in use contain pressurized materials. Eliminate liquid and air pressure
via shut off valves before pump is serviced or removed from the system.
High Temperature
Heat may transfer to exterior surfaces when pumps operate with high
temperature fluids. Avoid direct contact with the pump when high temperature
fluids are present.
Hazardous Chemical
Use appropriate personal protective equipment when handling pump. Reference
Material Safety Data Sheet (MSDS) for information specific to your chemicals.
Loud Noise
Pump exhaust air contributes to work area noise levels. Only operate pumps
with approved muffler media, and use ear protection in noisy conditions.
2.3 Advantages
Head Pressure / Dead-Head
PSU060 pumps can be controlled by adjusting their liquid outlet pressures and
can be installed with head pressures up to dead-head (e.g. equal liquid and
air pressures) with no damage to the pump.
Thermal Cycling
PSU060 pumps require no maintenance when operated within their performance
range, even in thermal cycling applications.
2.4 Environment & System
Oversized Inlet Line
Pumps operate optimally with liquid inlet lines larger than the liquid outlet
lines. This reduces strain on the bellows and may reduce pulsation in the pump
outlet.
Clean Supply Air (CDA)
PSU060 pumps require use of Class 2 air for particles and moisture per ISO
8573-1. Use 10 micron filter; maintain -40°C dew point. A point-of-use filter
is recommended during first six months of operation in new fabs/systems due to
high risks of debris that can damage pumps and void warranty.
Flammable Solvents
PSU060 pumps are not constructed from conductive materials. System that pump
flammable solvents should be properly grounded to avoid ignition by static
charge. A River’s Edge test of isolative pumps with flammable liquids
indicated that liquids must be grounded and other procedures should be
followed. Copy of test available.
Pumping Liquids Near Boiling Point
Minimizing suction lift reduces pulsation and the potential for boiling or
outgassing of liquid in the inlet of the pump. Although reciprocating pumps
can pull suction lift, pump performance and life increase when suction lift is
minimized or eliminated.
Abrasive Slurry
Pumping abrasive slurry may accelerate wear of components. PSU060 pumps are
warrantied when used with slurry. However, normal wear is not covered by
warranty.
Environmental Temperature
PSU060 pumps are rated for 0°C (32°F) 50°C (122°F) environmental temperatures.
Do not freeze fluid in pump. Operation below 0°C may accelerate wear. Normal
wear is not covered by warranty.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 5 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
2.5 Installation Instructions
-
Move lever to up position.
-
Slide base plate forward or pump body backward.
-
Lift pump off of base plate.
Pull-back dismount is standard. See steps 4.1-4.3 for forward dismount.
4.
Screw base plate to surface with 3/8 in or 10 mm socket head cap screws into
predrilled holes.
-
Set pump on base knobs; slide it forward. Set lever to down position.
-
Attach fittings to pump. Tighten to 55 inch-lbs.
-
Attach tubes and fittings per manufacturer instructions. Use backer wrench to hold fitting in place at pump.
-
Affix supply air via 1/4 in FNPT port on shuttle valve. Air line must be 1/4 in minimum orifice.
Push-Forward Dismount Configuration Setup Replace step 5 with steps 4.1-4.3 to re-configure the base plate to push-forward dismount configuration.
4.1
Move knobs to opposite sides.
4.2
4.3
Set pump on base
Move lever down
knobs; slide it backward. to locked position.
Install with Rigid Base Plate *Requires push-forward dismount configuration (steps 4.1-4.3)
Remove L bracket. Set lever in neutral (up) position.
Slide pump
forward; lift it off base plate.
Fix base plate to work station.
See step 4 above.
Return pump to base plate.
Move lock lever to down position. Reattach L bracket. Tighten to 12 in-lb.
Liquid Inlet/Outlet
Liquid ports are not NPT nor any other standard. Use of connectors other than
those supplied by White Knight will damage the pump.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 6 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
2.6 Shuttle Service Instructions
Follow instructions below to inspect or service White Knight shuttle valves.
If a pump has stopped, ensure all recommendations in this manual are followed
and that there are no air supply issues (i.e. closed air valve, damaged
regulator, oil in air line, etc.).
Do not lubricate or oil any of the shuttle components. White Knight shuttle
valves do not require any lubrication.
1. Remove nuts on each air fitting on each pump head.
2. Unscrew both shuttle mounting bolts, and pull the shuttle from the pump.
3. Remove the airlines from both sides of the shuttle valve by unscrewing the air fittings.
4. Unscrew top shuttle end cap using the shuttle end cap tool.
Part: 12100-PV-0083
5. Carefully remove
6. Unscrew bottom
ceramic spool from
end cap using the
shuttle valve; it may
shuttle end cap tool.
break if dropped.
If the ceramic spool in your pump has a flat feature, it is critical that it is oriented towards the bottom of the pump when the shuttle valve is reassembled.
7. Unscrew
both 1/8 in NPT plugs that have an orifice in the center.
8. Remove muffler cap from left side using the
muffler cap tool. Remove muffler media and note the order of the pieces.
Repeat this step for
muffler cap and muffler media on the right side.
9. Blow out shuttle valve with CDA or N2. Ensure no residue or debris is in any areas indicated above. Debris or residue in these areas may hinder pump performance.
10. Clean the ceramic spool with IPA, and dry it using CDA or N2.
11. Reassemble shuttle and reattach it to the pump by following the above
steps in reverse.
If the spool in your pump has the flat feature, ensure it is oriented towards
the bottom of the pump when the shuttle valve is reassembled.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 7 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
3. Control & Monitoring
Programmable Control
White Knight CPT-1 controllers monitor and adjust run mode, flow rate, leak
detection and other pump operations.
D10 Amplifier Electrical Hookups & Dimensions
White Knight recommends ExpertTM D10 amplifier for use with fiber optic stroke and leak detection assemblies.
Standard Models and Main Unit
1
3 2
Load 4
Load 5
QD hookup is functionally identical (Pink wire not used)
+ 10-30V dc Standard Models 12-30V dc Bussable Power Models
150 mA max. load
Remote Teach
Wire Key 1 = Brown 2 = White 3 = Blue 4 = Black 5 = Gray
Sub-Units NPN
4 Load
5
PNP
4 Load
5
12-30V dc Connection
From Main
Unit Bus
Remote Teach
12-30V dc Connection
From Main
Unit Bus
Remote Teach
Single Sensor Design
PSU060 pumps can use only a single fiber optic sensor at a time. The probe may be installed in the “F” port on either side of the pump. White Knight offers PFA, PFH, and PFU pumps for dual fiber optic use.
Mounting Bracket (included with some models)
61.3 mm (2.42″)
68.1 mm (2.68″)
3.1 Fiber Optic Stroke Detection Installation
10.5 ± 0.2 mm (typ.) 14.5 mm
(0.41″)
(0.57″)
7.6 mm 35.9 mm 0.30″ (1.41″)
9.8 mm (0.39″)
-
Remove stroke detect probe from fiber optic assembly.
-
Replace NPT plug in “F” port with stroke detect probe. Hand-tighten.
-
Insert the fiber optic cable until it seats at the bottom of the probe.
-
Lower ferrule and gripper until snug against probe and hand tighten female gripper nut.
Fiber Optic Sensors
Fiber optic sensors melt if used at >130°C (266°F), resulting in leak or end
of stroke detection failure.
- Open the top and slide the front face of the D10 up. Press the fiber optic ends into the holes on its front. Slide the face down to lock cables in place.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 8 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
3.2 Calibrating D10 Amplifier for Stroke Detection
When calibrating the D10 Amplifier for stroke detection, the pump should be in
the same operating conditions it will be in during normal operation (i.e.
supply air pressure, back pressure, etc.). The Fiber Optic must be installed
as per the instructions in section 3.1.
Calibration:
Push Button Remote Line
Result
8 7 6 5 HS 4 3 DO 2 LO 1
Access Dynamic TEACH Mode
Press and hold dynamic push button >2 seconds.
Hold Remote line low (to ground) >2 Seconds.
· Power LED: OFF · Output LED: OFF · Bar graph: LO & DO Alternately Flashing
8 7 6 5 HS 4 3 DO 2 LO 1
TEACH Sensing Conditions
· Hold push button. · Operate pump normally for 15 seconds.
· Hold remote line low (to ground). · Operate pump normally for 15 seconds.
· Power LED: OFF · Output LED: OFF · Bar graph: LO & DO Alternately Flashing
Release button
Return to Run Mode
Release remote line/switch
Teach Accepted Power LED: ON Bar graph: One LED flashes to show relative
contrast (successful setup requires minimum value of 4). Sensor returns to Run
Mode with new settings.
Teach Unaccepted Power LED: OFF Bar graph: #1, 3, 5, 7 alternately flash to
show failure to sense. Sensor returns to Run mode without changing settings.
Set up again if value shows <4.
8 7 6 5 HS 4 3 DO 2 LO 1
8 7 6 5 HS 4 3 DO 2 LO 1
Upon completion of a successful learning cycle, the D10 Amplifier will continuously learn and self-teach to maintain the same cycle rate count readings.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 9 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
3.3 Single Pressure Switch Stroke Detection Installation
-
Remove plug from “F” port.
-
Attach NPT gripper to “F” port.
-
Attach elbow assembly to pressure switch. Loosen female gripper nuts, and insert air tube between them. Hand tighten gripper nuts.
After your device is connected, you must set the switch point. If operating above 60 psi air supply, the set point is 43 psi (0.296 MPa), otherwise it is 18 psi (0.124 MPa). Each system is unique so values may need to be adjusted to your specific application. As the exhaust system loads, it may be necessary to adjust the set point.
3.4 Dual Pressure Switch Stroke Detection Installation
Perform all instructions to both sides of the pump.
-
Attach T fittings to the “S” ports.
-
Attach mufflers to the T fittings.
-
Attach elbow assemblies to pressure switches.
-
Loosen female gripper nuts on elbow assemblies and T fittings. Insert tubing and hand-tighten gripper nuts.
-
Affix supply air via 1/4 in FNPT QEV ports on both sides. Air supply must be 1/4 in minimum orifice to source.
After your device is connected, you must set the switch point. If operating above 60 psi air supply, the set point is 43 psi (0.296 MPa), otherwise it is 18 psi (0.124 MPa). Each system is unique so values may need to be adjusted to your specific application. As the exhaust system loads, it may be necessary to adjust the set point.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 10 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
3.5 Pressure Switch Stroke Detection Electrical Hookups
NPN
PNP
( ) 35
1.378
( )8
0.315
( ) 50
1.969
( )8
0.315
ø3.7 ø0.146 cable
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 11 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
3.6 Conductivity Leak Detection Installation
Leaks are identified if conductive fluid contacts a sensor. Sensor provides a Sink (NPN)
or Source (PNP) signal, depending on the wire setup. See the wiring diagrams below.
Conductive leak detection does not qualify for use in explosion-proof environments. Conductive fluid required.
See below for elbow out configuration.
Source (PNP) Connection
Conductivity Leak Detect
White
+ Power
10-30
White/Blue Load – VDC
Wiring Diagrams
-
Remove leak adapter from assembly.
-
Replace NPT plug in “L” port with probe. Hand Tighten. Attach cable to signal translator (e.g. PLC).
Sink (NPN) Connection
White
Load
Conductivity
Leak Detect White/Blue
+ Power 10-30
– VDC
3.7 Fiber Optic Leak Detection Installation
D10 amplifier must be calibrated before attaching fiber optic probes to the
pump. Fiber optic sensors can melt if used at >130°C (266°F), causing leak
detect failure.
See below for elbow out configuration.
-
Remove leak adapter and leak detect probe from fiber optic assembly.
-
For straight out configuration replace NPT plug in “L” port with the probe. Hand-tighten.
-
Insert the fiber optic cable until it contacts the bottom of the probe.
-
Lower ferrule and gripper until snug against the probe. Hand tighten female gripper nut.
For elbow out configuration: -
Open the top and slide the front face of the D10 up. Press the fiber optic ends into the holes on its front. Slide the face down to lock cables in place.
Fiber optic
Conductivity
1.1
Replace NPT plug in “L” port with elbow adapter.
1.2
Attach fiber optic or conductivity leak detect probe per instructions above.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 12 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
3.8 Calibrating D10 Amplifier for Leak Detection
Step 1: Power On D10 Amplifier & Set “Dark Operate” Mode:
Push Button
Remote Line
0.04 s “Click” 0.8 s 0.04 s T 0.8 s
Result
Access Setup Mode
Press and hold both buttons > 2 seconds.
Press either button until LEDs show desired settings.
Select Settings
Return to Run Mode
Press and hold both buttons >2 seconds.
8 7 6 5 HS 4 3 DO 2 LO 1
Double-pulse remote line
TT
T
· Green Power LED turns OFF.
· Output LED remains active.
2x · Icons continue to display current setup.
· Bargraph turns OFF.
Pulse the remote
line until LEDs show
desired settings.
T
T
Note: Doublepulsing remote line causes setting to “back up” one step.
Sensor toggles through these setting combinations: LO – Normal Speed – No Delay (default) DO – Normal Speed – No Delay LO – High Speed – No Delay DO – High Speed – No Delay LO – Normal Speed – Delay DO – Normal Speed – Delay LO – High Speed – Delay DO – High Speed – Delay
8 7 6 5 HS 4 3 DO 2 LO 1
Hold remote line low · Green Power LED turns ON.
T T
2 seconds.
· Sensor returns to Run
2 seconds mode with new settings.
Step 2: Access “Single-Point Dark Set” Mode
Push Button
Remote Line
0.04 s “Click” 0.8 s 0.04 s T 0.8 s
Result
Press and hold static
Single-pulse remote · Power LED: OFF.
Access button > 2
line
· Output LED: ON (push button)
Set Mode
seconds.
T 1x
OFF (remote line)
or
· Static LEDs: LO & DO
alternately flashing
8 7 6 5 HS 4 3 DO 2 LO 1
8 7 6 5 HS 4 3 DO 2 LO 1
8 7 6 5 HS 4 3 DO 2 LO 1
Step 3: Set Sensing Condition
Set condition to “leak detection” sensing while probe tip is submerged in liquid. Then, remove the leak probe from liquid and reinserted into the “L” port. Amplifier will now signal when moisture if detected on the probe tip.
Push Button
Remote Line
0.04 s “Click” 0.8 s 0.04 s T 0.8 s
Result
Set Sensing Condition
· Present sensing
Present sensing
· Power LED: ON.
condition
condition
· Output LED: ON (push button)
or
· Five-click static button · Five-pulse remote lne
OFF (remote line)
· Bargraph: 4 indicators flash.
Sensor returns to Run mode with new settings
· Power LED: ON.
· Output LED: ON (push button)
OFF (remote line)
or
· Bargraph: #1, 3, 5, 7 flash for failure.
Sensor returns to Set sensing condition.
8 7 6 5 HS 4 3 DO 2 LO 1
8 7 6 5 HS 4 3 DO 2 LO 1
8 7 6 5 HS 4 3 DO 2 LO 1
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 13 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
4. Ordering Instructions
Required (Default Model)
Additional Options (Blank if not needed)
PSU060 F – F12 – LF0 – SF0 – TF12 – VX0 –
1
2
3
4
5
6
7
Rev
Options 1-3 are required. Leave Additional Options blank if not desired. Only add Outlet if different than Inlet.
Default options are highlighted
1. Pump Model
Standard
PSU060
Dry-Run
PSUSD060
2. Check Ball Material
PFA Check balls
F
PTFE Check balls
M
4. Leak Detection
No leak detection
blank
15 ft fiber optic cable with no amplifier LF0
15 ft fiber optic cable with D10 amplifier LF1
25 ft fiber optic cable with no amplifier LF2
25 ft fiber optic cable with D10 amplifier LF3
15 ft conductivity cable
LC0
25 ft conductivity cable
LC1
3. Inlet Fitting Front straight only
Flaretek
1/2 in. F08
Compatible 3/4 in. F12
1 in. F16
1-1/4 in. F20
Tube Out 1/2 in. T08
3/4 in. T12
1 in. T16
1-1/4 in. T20
Weldable 3/4 in. W12
1 in. W16
Pillar S-300 3/8 in. P06
1/2 in. P08
3/4 in. P12
1 in. P16
1-1/4 in. P20
FNPT
1/2 in. N08
3/4 in. N12
1 in. N16
Synchro- 1/2 in. S08 Flare 3/4 in. S12
1 in. S16
PrimeLock 1/2 in. L08
3/4 in. L12
1 in. L16
1-1/4 in. L20
5. Stroke Detection
No stroke detection
blank
15 ft fiber optic cable with no amplifier SF0
15 ft fiber optic cable with D10 amplifier SF1
25 ft fiber optic cable with no amplifier SF2
25 ft fiber optic cable with D10 amplifier SF3
Single NPN Pressure Switch
SP1
Dual NPN Pressure Switches * (Includes two DP2 pressure switches)
SP2
Single PNP Pressure Switch
SP4
Dual PNP Pressure Switches * (Includes two DP2 pressure switches)
SP5
7. Shuttle
Gravity reset with standard exhaust
blank
No shuttle, standard ports *
(No pressure switches included)
VX0
Sensors are required for operation.
Gravity Reset with Remote Exhaust VG1
Mag Detent with Standard Exhaust
VM0
Mag Detent with Remote Exhaust
VM1
- White Knight shuttle valve not included.
Timer mode operation requires end-of-stroke detection. Use of timer mode without stroke detection voids the warranty.
6. Outlet Fitting Straight only. Select Top or Front.
Same as Inlet
Flaretek 1/2 in. Compatible 3/4 in.
1 in.
1-1/4 in.
Tube Out 1/2 in.
3/4 in.
1 in.
1-1/4 in.
Weldable 3/4 in.
1 in.
Pillar S-300 3/8 in.
1/2 in.
3/4 in.
1 in.
1-1/4 in.
FNPT
1/2 in.
3/4 in.
1 in.
Synchro- 1/2 in. Flare 3/4 in.
1 in.
PrimeLock 1/2 in.
3/4 in.
1 in.
1-1/4 in.
Front
blank
FF08 FF12 FF16 FF20 FF08 FF12 FF16 FF20 FW12 FW16 FP06 FP08 FP12 FP16 FP20
FN08 FN12 FN16 FS08 FS12 FS16 FL08 FL12 FL16 FL20
Top
n/a TF08 TF12 TF16 TF20 TT08 TT12 TT16 TT20 TW12 TW16 TP06 TP08 TP12 TP16 TP20
TN08 TN12 TN16 TS08 TS12 TS16 TL08 TL12 TL16 TL20
Revision
No revision
blank
Contact support for revision level
or copy exact code activation details. Configured part numbers are not Copy
Exact Part Numbers. support@wkfluidhandling.com
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 14 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
5. Pump Service
Pumps fully rebuilt by White Knight, certified rebuilders, or technicians
certified by White Knight receive full warranty renewal. Details below.
White Knight Rebuilds
Request factory rebuilds by web form at:
https://wkfluidhandling.com/support/rma/. An RMA# will be provided after
processing.
*Customers must follow decontamination instructions in Section 4.4 when returning a pump to White Knight.
Certified Rebuilders
White Knight’s global network of certified rebuilders expedite rebuild turn-
around time and minimize shipping costs. Find certified rebuilders at:
https://wkfluidhandling.com/rebuilders/
Rebuild Pump as Certified Technician
White Knight offers trainings to certify technicians to rebuild pumps.
Technicians who pass the training are issued a two-year certification. During
the two years, parts in pumps rebuilt by the technician receive a full
warranty. See: https://wkfluidhandling.com/virtual-rebuilds/
5.1 Rebuild Kits & Parts
Rebuild kit for PSU060F is RBPSU060F-1. Rebuild kit for PSUSD060F is RBPSUSD060F-1 (labor not included). To request rebuilds by White Knight, use RBPSU060F-5 or RBPSUSD060F-5, respectively (labor included).
11 2 3 4 5 6
Pump rebuilds require tool kit: 12200-XX-0026 (Legacy# PSU060-170) Dry-run (SD) pumps use different shaft and shaft seals. Contact White Knight for details.
7 12 8
10
9
1
RBPSU060F-1
ITEM NO. PART NUMBER
DESCRIPTION
QTY.
1
3133-TE-0006
REPLACEABLE SEAT, SHIFT, UNIVERSAL
2
2
4100-PF-0001
PFA CHECK BALL-3/4″
4
3
4135-MP-0014
BOTTOM CHECK SEAT, LOWER
2
4
4137-TE-0010
BOTTOM CHECK CAGE, 10 GPM
2
5
4137-TE-0011
MIDDLE CHECK CAGE, 10 GPM
4
6
4142-MP-0008
TOP CHECK SEAT, UPPER
2
7
4142-TE-0013
TOP CHECK CAGE, 10 GPM
2
8
5143-MP-0004
SEAL, SHAFT, U-SERIES, 60L
2
9
6140-FP-0004
BAFFLE POROUS POLY 60L
6
10
6530-TE-0002
Shuttle End Plug 10 gpm
2
11
14300-MP-0020
BELLOWS ASSEMBLY SHIFT 60 U
2
12
14320-PF-0004 LOADED SHAFT ASSEMBLY, 60L, U-SERIES, CERAMIC
1
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 15 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
5.2 Return Pump for Service
Follow decontamination instructions when returning a pump for service.
DO NOT REMOVE PAGE FROM MANUAL. Copy page from manual or download at
https://wkfluidhandling.com/support/rma/.
Decontamination Instructions
PRINT COMPLETED DECONTAMINATION CERTIFICATION. IT MUST BE INCLUDED IN YOUR RMA
SHIPMENT.
White Knight products are designed for use with caustic and otherwise
dangerous liquids. Handle every product as if it contains dangerous chemicals
whether or not it actually does.
· Only those with adequate safety training should attempt to handle used
pumps. · Wear adequate safety gear appropriate for chemicals that have been in
the pump. · Review relevant Material Safety Data Sheets (MSDS) before handling
the pump. · Review emergency numbers for use in event of an accident. ·
Prepare Ph papers, showers, antidotes, clean-up equipment, neutralizers, and
other safety devices
used to detect, neutralize or minimize effects of chemicals described in
appropriate MSDS documents.
Rinse with DI Water
Circulate DI water through pump for twenty minutes before disassembly and/or
double bagging for shipment. If pump is nonfunctional, force DI water from
inlet through outlet for 40 minutes before shipment preparations.
Remove Pump from Station:
1. Disconnect liquid tubing connectors from front of pump (opposite shuttle
valve). 2. Plug NPT fittings with PTFE plug, Flare fittings with flare nose
cover and cap,
or other plug or cap as recommended by connector supplier. 3. Disconnect air
supply tubing from face of shuttle valve. 4. Loosen mount screw from base
plate. (Note: do not remove screw from base plate). 5. Remove base plate using
proper tool for the fastening devices (e.g. Allen wrench or screw driver).
Note: Base plate may stay if needed for replacement pump to be used. 6. Return
all removed parts to the pump.
Return Pump to White Knight:
1. Rinse pump with DI water as described above after removing it from its
station. 2. Drain remaining DI water from the pump inlet and outlet liquid
tubing connectors. 3. Plug liquid outlets as described in the Remove Pump from
Station section above. 4. Dry the pump, double bag it, and seal it in thick
polyethylene bags. 5. Return the pump to its original packaging. 6. Include
MSDS for the chemical that the pump was handling in the box with the pump. 7.
Obtain RMA number from White Knight and write it on the outside of the box. 8.
Ship to White Knight following all rules, regulations and laws regarding
shipment of dangerous
materials. Ship freight pre-paid. No collect shipments will be accepted.
Unauthorized use of White
Knight shipping accounts will result in the adding of freight to the bill in
addition to a service charge.
Include All Pump Components:
Pumps returned to White Knight for evaluation, service or repair must be
complete with all components, including but not limited to base plate, mount
screws, tubing connectors, tubing connector caps, flare noses, shuttle valves,
mufflers, and tubing. Missing parts will be added to the pump and charged to
the customer.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 16 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
DO NOT REMOVE PAGE FROM MANUAL. Copy page from manual or download at https://wkfluidhandling.com/support/rma/.
Decontamination Certification
COMPLETE AND PRINT THIS FORM. IT MUST BE INCLUDED IN YOUR RMA SHIPMENT.
I, the undersigned employee of
, certify that all
decontamination and safety procedures described in Decontamination Instructions section have
been followed for return of product below.
RMA#: (We cannot process returns without an RMA number.)
Serial#: (We cannot process returns without a product serial number.)
Metal Exposure:
(Check all that apply. Write in other metals if necessary.)
Product was used in a Metal Process.
Yes
No
Product was used in a Copper Metal Process.
Yes
No
Product was used with:
Aluminum
Cobalt
Gold
Lead
Nickel
Platinum
Silver
Tin
Titanium
Tungsten
Zinc
Other:
Chemical Exposure:
(Check all that apply. Write in other chemicals if necessary.)
Product was NOT used in chemicals (DI Water only).
Product was used in chemicals.
Ammonia Nitric Acid
Ammonium Hydroxide Phosphoric Acid
Hydrochloric Acid Sulfuric Acid
Hydrofluoric Acid Other:
Hydrogen Peroxide IPA
Shipping Information:
Please indicate metal processes to which the product has been exposed by
clearly and conspicuously labeling the outside of the return package with the
metal.
Products exposed to Metal Processes must be sent to the following address:
Products NOT exposed to Metal Processes must be sent to the following address:
White Knight Fluid Handling 187 East 670 South, Suite B Kamas, UT 84036
White Knight Fluid Handling 187 East 670 South, Suite C Kamas, UT 84036
Print Name: Signature:
Date:
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 17 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
6. Warranty
White Knight follows strict manufacturing, assembly and testing procedures to
ensure consistency and reliability.
White Knight warrants PSU060 pumps and components are free from defects in
materials and workmanship for two years from our shipment date or your
installation date if provided within 90 days of shipment from our facility.
Failures due to normal wear, misuse, abuse or unauthorized disassembly nullify
this warranty.
White Knight does not guarantee the suitability of products for specific
applications. White Knight is not liable for any damage or expense resulting
from use or misuse of its products in any application. Responsibility is
limited solely to repair or replacement of defective products or components.
Prior written, faxed or emailed approval must be obtained from White Knight
before returning any product or component for warranty consideration. All
determinations regarding cause of failure are made by White Knight, and all
decisions regarding warranty fulfillment or nullification are made by White
Knight.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES
EXPRESSED OR IMPLIED, INCLUDING ANY GUARANTEE OF SUITABILITY FOR ANY PURPOSE.
NO VARIATIONS OF THIS WARRANTY SHALL BE HONORED NOR CONSIDERED LEGALLY
BINDING, EXCEPT WRITTEN AGREEMENTS SIGNED BY THE CEO OF WHITE KNIGHT FLUID
HANDLING.
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 18 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 19 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
Pump Solutions and Accessories
Ultra-Pure Closed-Loop Systems
Automatically maintain laminar flow or steady pressure with metal-free closed-
loop pump systems offering stable temperatures, deadhead and suction lift.
Control your high purity chemical processes and delivery systems. Simplify
process automation to save time, resources and reduce costs.
https://wkfluidhandling.com/closed-loop/
· 140 lpm (36 gpm) flow rates · 7 Bar (100 psi) pressures · 210°C (410°F)
temperatures · Maintain stable temperatures
· No metals, no corrosion · No elastomer O-rings, no leaks · No electric
motors, no heat rise
Pulse Dampeners
In-line and pump-mounted pulse dampeners reduce pulsation in fluid systems to
improve flow control, increase batch yields, protect components, and minimize
maintenance and downtime for repairs. DBU030 dampeners fit 30 and 60 lpm
pumps. DBU060 dampeners fit 30, 60 and 140 lpm pumps. DBU140 dampeners fit 60
and 140 lpm pumps.
https://wkfluidhandling.com/dampeners/
In-line pulse dampener
Pump-mounted pulse dampener
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 20 Subject to change without notice
engineer approvedTM
PSU060 Owner’s Manual
Pressure Regulators
White Knight pressure regulators offer remote piloting capability to maintain
system pressure for high-purity chemical circulation loops and systems with
multiple tool drops or dispense points. They feature fully-swept PTFE/PFA flow
paths. A single back-pressure regulator equalizes upstream fluid pressure
across multiple discharge outlets. Forward-pressure regulators control
downstream pressure.
Back-pressure regulator
40 PSI 40 PSI 40 PSI 40 PSI
Liquid Air
40 PSI
Fluid Tank
Forward-pressure regulator
Air
20 PSI
Liquid
25 PSI
20 PSI
25 PSI 10 PSI
10 PSI
15 PSI
A single back-pressure regulator equalizes upstream 10 PSI
15 PSI
fluid pressure for discharge outlets. Each forward-pressure regulator controls fluid pressure for a single discharge outlet.
Fluid Tank
Filter Housings
Two-chamber and four-chamber filter housings provide parallel or series (in-
line) operation. Their compact, non-metallic PTFE/PFA designs offer superior
containment and high-flow performance within a smaller footprint than
traditional housings. They fit many filter types, and enable filters to be
changed without disconnecting liquid lines. https://wkfluidhandling.com
/filter-housings/
Cycle-Rate Translator
The CPT enables pump replacements in existing tools. It operates a White
Knight pump at its optimal cycle rate and scales the operational cycle rate to
that expected by the tool. https://wkfluidhandling.com/cpt/
CatcherTM Pre-Filters
White Knight CatcherTM pre-filters protect pumps from wafer shards and other
harmful solids. They can be cleaned without disconnecting liquid lines.
https://wkfluidhandling.com/catchers/
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Ver. 2.2.1 | 5 Dec 2023 | P. 21 Subject to change without notice
engineer approvedTM
White Knight Support
187 E. 670 S. Kamas, UT 84036 Phone: 435.783.6040 Toll Free: 888.796.2476 Fax:
435.783.6128 support@wkfluidhandling.com https://wkfluidhandling.com/support/
Part No. 18200-LM-0021
Copyright © 2023 White Knight Fluid Handling | A Graco company P: 435.783.6040 | support@wkfluidhandling.com | https://wkfluidhandling.com
Version 2.2.1 | 5 Dec 2023 Subject to change without notice
References
- White Knight Fluid Handling | High Purity Chemical Solutions
- Closed-Loop Systems - White Knight Fluid Handling
- Cycle Rate Translators - White Knight Fluid Handling
- Filter Housings - White Knight Fluid Handling
- Pressure Regulators - White Knight Fluid Handling
- Certified Service Providers - White Knight Fluid Handling
- Support RMA - White Knight Fluid Handling
- Virtual Rebuilds - White Knight Fluid Handling
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>