Danfoss VACON 100 X Heater Instruction Manual
- June 16, 2024
- Danfoss
Table of Contents
Danfoss VACON 100 X Heater
Specifications
Document code | DPD01097C |
---|---|
Supply voltage input terminals | 1AC 230V 50Hz 60 Hz 900 mA |
Tolerance | 208V -15%… 250V +10% |
Switching capacity | X1 Feedback relay output 24VDC / 3A, 250VAC /3A |
Product Usage Instructions
Safety
This manual contains important safety information to ensure your personal
safety and prevent any unintentional damage to the product or connected
appliances. Please read the following information carefully:
Dangers
Table 1. Dangers
The components of the optional heater are live when the element
is connected to mains potential. Coming into contact with this
voltage is extremely dangerous and may cause death or severe
injury.
Mounting Instructions: MM4 Example
Follow the steps below to mount the optional heater:
- Step 1: Remove the cable entry plate (right side example).
- Step 2: Remove the powerhead from the terminal box.
- Step 3: Connect the supply voltage (black cable) and the output relay (red cable) to the optional heater through the bottom cable entry plate. Colors of the cables are only examples.
- Step 4: Mount the optional heater on the terminal box and then close the powerhead.
FAQ
-
Q: What is the supply voltage for the heater?
A: The supply voltage for the heater is 1AC 230V 50Hz 60 Hz. -
Q: What is the recommended fuse rating for the heater supply voltage?
A: The recommended fuse types for the heater supply voltage are as follows:
Fuses for heater supply voltage input – 230VAC | Rating |
---|---|
gG/gL (IEC 60269-1) 500V | 1A |
class T (UL & CSA) 600V | 1A |
class J (UL & CSA) 600V | 1A |
VACON® 100 X – HEATER (ARCTIC OPTION)
Document code : DPD01097C
Safety
This manual contains clearly marked cautions and warnings which are intended
for your personal safety and to avoid any unintentional damage to the product
or connected appliances.
Please read the information included in dangers carefully.
The optional heater allows the drive to operate in low-temperature conditions
down to -40°C. This option is intended to be installed inside the drive.
Only VACON® authorized, trained and qualified personnel are allowed to install
and maintain this component.
Dangers
Table 1. Dangers
The components of the optional heater are live when the element is connected
to mains potential. Coming into contact with this voltage is extremely
dangerous and may cause death or severe injury.
The heater can be used only inside the drive and in combination with only the
VACON® 100 X. Before connecting the heater to mains, make sure that the VACON®
100 X drive is closed firmly.
Technical data
The optional heater has to be supplied with single-phase 230V. The thermal
element is always supplied and if the drive is connected at -40°C the drive
will be heated up until the temperature of -10°C is exceeded. The heating is
temperature-controlled and an internal fan ensures that the air is equally
distributed inside the enclosure.
The integrated relay output (switching capacity: 24VDC / 3A, 277VAC / 3A) can
be used to control the power-up of the drive. The contact is closed when the
internal temperature is higher than the minimum allowed value for the power-up
(~ -10°C). This can be included and managed in the logic of the entire system.
A bi-color LED (on the enclosure of this option), shows the status of the
drive, ready or not-ready.
Table 2. Technical information on input and relay terminals.
Fuses
The recommended fuse types for the heater supply voltage are shown in the
table below.
Table 3. Fuses ratings.
Mounting instructions: MM4 Example
Figure 4. Connect the supply voltage (black cable) and the output relay (red cable) to the optional heater through the bottom cable entry plate. Colors of the cables are only examples.
Figure 5. Mount the optional heater on the terminal box and then close the powerhead.
Local contacts: http://drives.danfoss.com/danfoss-drives/local- contacts/