Danfoss ENDAT SSI VACON NXP Air Cooled Installation Guide

June 16, 2024
Danfoss

danfoss-logo

Danfoss ENDAT SSI VACON NXP Air Cooled

NOTE! You can download the English and French product manuals with applicable safety, warning and caution information from https://www.danfoss.com/en/service-and-support/.

ENDAT/SSI, SIN-COS OPTION BOARD OPTBE

OPTBE layout and description

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-1

  • Description: Encoder board for VACON® NXP with input for EnDat/551 absolute encoder and Sin/Cos type encoder.
  • Allowed slots: C, D, E [Sin/Cos signals can only be used in slot Cl Type ID 16965
  • Terminals: One terminal block; Screw terminals IM2.6l: No coding.
  • Jumpers: X1 and X2 see ]
  • Board parameters: Yes

An absolute encoder is a type of encoder capable of specifying its absolute position. The position data is retained even during a power failure or breakdown. The position data carried by the absolute encoder can be used by the AC drive in motor control and position control applications. Sin/Cos encoder produces a pair of analog sinusoidal signals. There are several sine cycles (for example 1024 or 2048) per mechanical revolution.Danfoss-ENDAT-
SSI-VACON-NXP-Air-Cooled-FIG-22

EnDat is a bidirectional synchronous serial interface for encoders. For example, the absolute encoder position data can be read and encoder parameters can be set via the EnDat connection. It also forwards the messages related to the encoder functions. All EnDat connections are available in terminal X6. The board uses EnDat version 2.1. 551 [Synchronous Serial Interface) is a single directional interface for transmitting absolute position value. The absolute position value beginning with the Most Significant Bit (MSB first] is transferred on the DATA lines in synchronism with a CLOCK signal transmitted by the control. The SSI standard data word length for single turn absolute encoders is 13 bits and for multiturn absolute encoders 25 bits. More information on EnDat/SSI: http://www.heidenhain.com.

OPTBE jumpers

NOTE! It is recommended to use a 12 V or 15 V supply voltage instead of 5 V. OPTBE interface does not support the “sense” function to compensate for voltage drop with long cabling. Therefore with 5 V supply voltage the cable length limit is about 60 meters with 0.5 mm2 wire section. With 5 V supply voltage, it is recommended to use two or more wires in parallel for the supply connection. Jumper X1 selects encoder supply voltage on the OPTBE board, see jumper settings below:Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-
FIG-2

Jumper X2 selects Sin/Cos signals connection on the OPTBE board, see jumper settings below:

NOTE! Be careful with the jumper settings, wrong settings may damage the encoder.

OPTBE LEDs
There are two LEDs on the OPTBE board:

  1. Yellow LED (Board Status LED)
    • Slow blinking-> Board state is ready
    • Fast blinking-> Board state is faulted
  2. Green LED [Encoder LED]
    • ON-> Encoder serial communication is OK
    • OFF-> No serial connection to encoder

1/0 terminals on OPTBE, encoder terminal X6

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-4

Analog Sin/Cos signals deserve some more precautions for noise immunity than pulse encoders. It is recommended to use a cable that contains an individual shield for each twisted pair. Use one pair for SIN+/SIN- signals, another pair for COS+/COS- signals, another pair for DATA+/DATA- signals and another pair for CLOCK+/CLOCK- signals.

OPTBE Parameters
Notes for selecting Operating Mode: In modes “EnDat + Sin/Cos” and “SSl+Sin/Cos” Sin/Cos signals and absolute serial information are used:

  • Modes can be used in VACON® NXP option board slot C.
  • Closed loop motor control mode can be used.
  • Jumper X2 is installed into the OPTBE board because Sin/Cos signals are used.

In modes “Endat Only” and “SSI Only”, only the absolute serial information is used:

  • Modes can be used in VACON® NXP option board slots C, D and E.
  • Closed loop motor control mode cannot be used. Usage of closed-loop in these modes causes
  • Fault 43 [Encoder fault] with Subcode 10.
  • Jumper X2 is removed from the OPTBE board because Sin/Cos signals are not used.Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-5

OPTBE monitored values

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-6

SIN-COS OPTION BOARD OPTAK

PTAK layout and description

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-7

  • Description:
    Encoder board for VACON® NXP with an input for Sin/Cos type encoder. Programmable control voltage.

  • Allowed slots:

    • C (Sin/Cos signals can only be used in slot C)
  • Type ID:

    • 16715
  • Terminals:

    • One terminal block; Screw terminals (M2.6); No coding.
  • Jumpers: X1 (see page 9)

  • Board parameters: Yes (see page 10)

The sin/Cos encoder produces a pair of analog sinusoidal signals. There are several sine cycles (for example 1024 or 2048) per mechanical revolution.

OPTAK jumper settings
NOTE! It is recommended to use a 12 V or 15 V supply voltage instead of 5 V. OPT AK interface does not support the “sense” function to compensate for voltage drop with long cabling. Therefore with 5 V supply voltage the cable length limit is about 60 meters with 0.5 mm2 wire section. With 5 V supply voltage, it is recommended to use two or more wires in parallel for the supply connection. Jumper X1 selects encoder supply voltage on the OPT AK board, see jumper settings below:Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-
FIG-8

NOTE! Be careful with the jumper setting, wrong voltage may damage the encoder.

I/0 terminals on OPTAK, encoder terminal X6

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-9

NOTE! Analog Sin/Cos signals deserve some more precautions for noise immunity than pulse encoders. It is recommended to use a cable that contains an individual shield for each twisted pair. Use one pair for SIN+/SIN- signals, another pair for COS+/COS- signals and another pair for R+/Rsignals.

OPTAK parameters

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-10

OPTAK monitored values

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-11

OPTAR layout and description

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-12

  • Description:
    Encoder board for VACON® NXP with an input for Sin/Cos type encoder. Programmable control voltage for the encoder. Differential two-channel pulse output.

  • Allowed slots: C (Sin/Cos signals can only be used in slot C)

  • Type ID :

    • 16722
  • Terminals:

    • X6 D-sub 15-pin male connector with female screw lock for Sin/Cos input
    • X3 4-pin screw terminal for pulse output
  • Jumpers: X1 and X4 (see)

  • Board parameters: Yes (see)

A Sin/Cos encoder produces a pair of analog sinusoidal signals. There are several sine cycles (for example 1024 or 2048] per mechanical revolution.

OPTAR jumper settings
NOTE! It is recommended to use a 12 V or 15 V supply voltage instead of 5 V. OPT AR interface does not support the “sense” function to compensate for voltage drop with long cabling. Therefore with 5 V supply voltage the cable length limit is about 60 meters with 0.5 mm2 wire section. With 5 V supply voltage, it is recommended to use two or more wires in parallel for the supply connection. Jumper Xl selects encoder supply voltage on the OPT AR board, see jumper settings below:Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-
FIG-13

NOTE! Be careful with the jumper setting, the wrong voltage may damage the encoder. Jumper X4 selects grounding mode for the cable shield of the encoder on the OPT AR board, see jumper settings below:Danfoss-ENDAT-SSI-
VACON-NXP-Air-Cooled-FIG-14

I/0 terminals on OPTAR, encoder terminal X6

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-15

NOTE! It is recommended to use a cable that contains an individual shield for each twisted pair. Use one pair for SIN+/SIN- signals, another pair for COS+/COS- signals and another pair for R+/ Rsignals.

I /0 terminals on OPTAR, pulse output X3

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-16

OPTAR parameters

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-17

OPTAR monitored values

Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-FIG-18

INSTALLATION

WARNING
Internal components and circuit boards are at high potential when the AC drive is connected to the power source. This voltage is extremely dangerous and may cause death or severe injury if you come into contact with it.

Installing option boards
Option boards OPTBE, OPTAK and OPTAR can only be used with VACON® NXP drives. OPTAK and OPTAR can be connected to slot C. OPTBE board can be connected to slots C, and Dor E, but Sin/Cos signals can only be used in slot C. If OPTBE board is connected to slots Dor E, the Sin/Cos signals have to be disconnected using the jumpers (see chapter 1.21. Disconnect the drive from the mains before starting the installation.Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-
FIG-19 Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-
FIG-20 Danfoss-ENDAT-SSI-VACON-NXP-Air-Cooled-
FIG-21

Vacon Ltd
Member of the Danfoss Group Runsorintie 7 65380 Vaasa Finland

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals