MOXA MB3170 1 Port Advanced Modbus TCP Installation Guide
- June 16, 2024
- MOXA
Table of Contents
MOXA MB3170 1 Port Advanced Modbus TCP
Overview
The M Gate MB3170 and MB3270 are 1 and 2-port advanced Modbus gateways that convert between Modbus TCP and Modbus ASCII/RTU protocols. They allow Ethernet masters to control serial slaves, or they allow serial masters to control Ethernet slaves. Up to 32 TCP masters and slaves can be connected simultaneously. The M Gate MB3170 and MB3270 can connect up to 31 or 62 Modbus RTU/ASCII slaves, respectively.
Package Checklist
Before installing the M Gate MB3170 or MB3270, verify that the package contains the following items:
- M Gate MB3170 or MB3270 Modbus gateway
- Quick installation guide (printed)
- Warranty card
Optional Accessories:
- DK-35A: DIN-rail mounting kit (35 mm)
- Mini DB9F-to-TB Adaptor: DB9 female to terminal block adapter
- DR-4524: 45W/2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
- DR-75-24: 75W/3.2A DIN-rail 24 VDC power supply with universal 85 to 264 VAC input
- DR-120-24: 120W/5A DIN-rail 24 VDC power supply with 88 to 132 VAC/176 to 264 VAC input by switch.
NOTE Please notify your sales representative if any of the above items are missing or damaged.
Hardware Introduction
LED Indicators
Name | Color | Function |
---|---|---|
PWR1 | Red | Power is being supplied to the power input |
PWR2 | Red | Power is being supplied to the power input |
RDY | Red | Steady: Power is on and the unit is booting up |
Blinking: IP conflict, DHCP or BOOTP server did not respond properly, or a
relay output occurred
Green| Steady: Power is on and the unit is functioning
normally
Blinking: Unit is responding to locate function
Off| Power is off or power error condition exists
Ethernet| Amber| 10 Mbps Ethernet connection
Green| 100 Mbps Ethernet connection
Off| Ethernet cable is disconnected or has a short
P1, P2| Amber| Serial port is receiving data
Green| Serial port is transmitting data
Off| Serial port is not transmitting or receiving data
FX| Amber| Steady on: Ethernet fiber connection, but port is idle.
Blinking: Fiber port is transmitting or receiving
data.
Off| Fiber port is not transmitting or receiving data.
Reset Button
Press the Reset button continuously for 5 sec to load factory defaults:
The reset button is used to load factory defaults. Use a pointed object such
as a straightened paper clip to hold the reset button down for five seconds.
Release the reset button when the Ready LED stops blinking.
Panel Layouts
The M Gate MB3170 has a male DB9 port and a terminal block for connecting to serial devices. The M Gate MB3270 has two DB9 connectors for connecting to serial devices.
Hardware Installation Procedure
STEP 1: After removing the M Gate MB3170/3270 from the box, connect the M
Gate MB3170/3270 to a network. Use a standard straight-through Ethernet
(fiber) cable to connect the unit to a hub or switch. When setting up or
testing the M Gate MB3170/3270, you might find it convenient to connect
directly to your computer’s Ethernet port. Here, use a crossover Ethernet
cable.
STEP 2: Connect the serial port(s) of the M Gate MB3170/3270 to a serial
device.
STEP 3: The MGate MB3170/3270 is designed to be attached to a DIN rail or
mounted on a wall. The two sliders on the M Gate MB3170/3270 rear panel serve
a dual purpose. For wall mounting, both sliders should be extended. For DIN-
rail mounting, start with one slider pushed in, and the other slider extended.
After attaching the M Gate MB3170/3270 on the DIN rail, push the extended
slider in to lock the device server to the rail. We illustrate the two
placement options in the accompanying figures.
STEP 4: Connect the 12 to 48 VDC power source to terminal block power
input.
Wall or Cabinet Mounting
Mounting the M Gate MB3170/3270 Series on to a wall requires two screws. The heads of the screws should be 5 to 7 mm in diameter, the shafts should be 3 to 4 mm in diameter, and the length of the screws should be more than 10.5 mm.
NOTE Wall mounting is certified for maritime applications.
Wall mount
DIN-rail
Termination Resistor and Adjustable Pull-high/low Resistors
For some RS-485 environments, you may need to add termination resistors to
prevent the reflection of serial signals. When using termination resistors, it
is important to set the pull-high/low resistors correctly so that the
electrical signal is not corrupted.
The DIP switches are beneath the DIP switch panel on the side of the unit.
To add a 120 Ω termination resistor, set switch 3 to ON; set switch 3 to
OFF (the default setting) to disable the termination resistor.
To set the pull-high/low resistors to 150 KΩ, set switches 1 and 2 to
OFF. This is the default setting.
To set the pull-high/low resistors to 1 KΩ, set switches 1 and 2 to ON.
Switch 4 on the port’s assigned DIP switch is reserved.
ATTENTION
Do not use the 1 KΩ pull-high/low setting on the M Gate MB3000 when using an RS-232 interface. Doing so will degrade the RS-232 signals and reduce the effective communication distance.
Software Installation Information
You can download the M Gate Manager, User’s Manual, and Device Search Utility (DSU) from Moxa’s website: www.moxa.com Please refer to the User’s Manual for additional details on using the M Gate Manager and DSU.
The MGate MB3170/3270 also supports login via a web browser.
Default IP address: 192.168.127.254
Default account: admin
Default password: moxa
Pin Assignments
Ethernet Port (RJ45)
Pin | Signal |
---|---|
1 | Tx+ |
2 | Tx- |
3 | Rx+ |
6 | Rx- |
6 Rx Serial Port (DB9 Male)
Pin | RS-232 | RS-422/ RS-485 (4W) | RS-485 (2W) |
---|---|---|---|
1 | DCD | TxD- | – |
2 | RxD | TxD+ | – |
3 | TxD | RxD+ | Data+ |
4 | DTR | RxD- | Data- |
5 | GND | GND | GND |
6 | DSR | – | – |
7 | RTS | – | – |
8 | CTS | – | – |
9 | – | – | – |
NOTE For the MB3170 Series, the DB9 male port can only be used for RS-232.
Terminal Block Female Connector on the M Gate (RS-422, RS485)
Pin | RS-422/ RS-485 (4W) | RS-485 (2W) |
---|---|---|
1 | TxD+ | – |
2 | TxD- | – |
3 | RxD + | Data+ |
4 | RxD – | Data- |
5 | GND | GND |
Power Input and Relay Output Pinouts
**** | V2+ | V2- | **** | V1+ | V1- |
---|---|---|---|---|---|
Shielded Ground | DC Power Input 1 | DC |
Power Input 1
| Relay Output| Relay Output| DC
Power Input 2
| DC
Power Input 2
Optical Fiber Interface
| 100BaseFX
---|---
Multi-mode| Single-mode
Fiber Cable Type| OM1| 50/125 μm| G.652
*800 MHzkm
Typical Distance| 4 km| 5 km| 40 km
Wave- length| Typical (nm)| 1300| 1310
TX Range (nm)| 1260 to 1360| 1280 to 1340
RX Range (nm)| 1100 to 1600| 1100 to 1600
** Optical Power| TX Range (dBm)| -10 to -20| 0 to -5
RX Range (dBm)| -3 to -32| -3 to -34
Link Budget (dB)| 12| 29
Dispersion Penalty (dB)| 3| 1
Note: When connecting a single-mode fiber transceiver, we recommend using
an attenuator to prevent damage caused by excessive optical power.
Note: Compute the “typical distance” of a specific fiber transceiver as follows: Link budget (dB) > dispersion penalty (dB) + total link loss (dB).
Specifications
Power Requirements
Power Input| 12 to 48 VDC
Power Consumption (Input Rating)|
- M Gate MB3170, M Gate MB3170-T, M Gate MB3270, M Gate MB3270-T: 12 to 48 VDC, 435 mA (max.)
- M Gate MB3270I, M Gate MB3270I-T, M Gate MB3170-M-ST, M Gate MB3170-M-ST-T, M Gate MB3170-M-SC, M Gate MB3170-M- SC-T: 12 to 48 VDC, 510 mA (max.)
- M Gate MB3170I, M Gate MB3170I-T, M Gate MB3170-S-SC, M Gate MB3170-S-SC-T, M Gate MB3170I-S-SC, M Gate MB3170I-S- SC-T, M Gate MB3170I-M-SC, M Gate MB3170I-M-SC-T: 12 to 48 VDC, 555 mA (max.)
Operating Temperature| 0 to 60°C (32 to 140°F),
-40 to 75°C (-40 to 167°F) for –T model
Storage Temperature| -40 to 85°C (-40 to 185°F)
Operating Humidity| 5 to 95% RH
Magnetic Isolation
Protection (serial)
| 2 kV (for “I” models)
Dimensions
Without ears: With ears extended:
| **** 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.9 in)
Relay Output| 1 digital relay output to alarm (normally open): current
carrying capacity 1 A @ 30 VDC
Hazardous Location| UL/cUL Class 1 Division 2 Group A/B/C/D, ATEX Zone 2,
IECEx
This device complies with Part 15 of the FCC rules.
Operation is subject to the following conditions:
- This device may not cause harmful interference.
- This device must accept any interference received, including interference that may cause undesired operation.
ATEX and IECEx Information
MB3170/3270 Series
-
Certificate number: DEMKO 18 ATEX 2168X
-
IECEx number: IECEx UL 18.0149X
-
Certification string: Ex nA IIC T4 Gc
Ambient Range : 0°C ≤ Tamb ≤ 60°C (For suffix without -T)
Ambient Range : -40°C ≤ Tamb ≤ 75°C (For suffix with -T) -
Standards covered:
ATEX: EN 60079-0:2012+A11:2013, EN 60079-15:2010
IECEx: IEC 60079-0 Ed.6; IEC 60079-15 Ed.4 -
The conditions of safe usage:
-
The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC/EN 60664-1.
- The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP4 in accordance with IEC/EN 60079-0.
- Conductors suitable for Rated Cable Temperature ≥ 100°C
- Input conductor with 28-12 AWG (max. 3.3 mm2) to be used with the devices.
MB3170I/3270I Series
-
ATEX Certificate number: DEMKO 19 ATEX 2232X
-
IECEx number: IECEx UL 19.0058X
-
Certification string: Ex nA IIC T4 Gc
Ambient Range : 0°C ≤ Tamb ≤ 60°C (For suffix without -T)
Ambient Range : -40°C ≤ Tamb ≤ 75°C (For suffix with -T) -
Standards covered:
ATEX: EN 60079-0:2012+A11:2013, EN 60079-15:2010
IECEx: IEC 60079-0 Ed.6; IEC 60079-15 Ed.4 -
The conditions of safe usage:
- The equipment shall only be used in an area of at least pollution degree 2, as defined in IEC/EN 60664-1.
- The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP 54 in accordance with IEC/EN 60079-0.
- Conductors suitable for Rated Cable Temperature ≥ 100°C
- Input conductor with 28-12 AWG (max. 3.3 mm2) to be used with the devices.
Address of manufacturer: No. 1111, Hoping Rd., Bade Dist., Taoyuan City 334004, Taiwan
Documents / Resources
| MOXA
MB3170 1 Port Advanced Modbus
TCP
[pdf] Installation Guide
MB3170 1 Port Advanced Modbus TCP, MB3170 1, Port Advanced Modbus TCP,
Advanced Modbus TCP, Modbus TCP
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>