xmart by integra SUPRA 500 Interactive Ups 230v
Important information
- Technical information on this manual is property of XMART by INTEGRA® . This manual Information cannot be copied or distributed totally or partially without written approval of XMART.
- XMART can introduce modifications in their products or manuals without further notice.
- XMART is not responsible of mistakes or missing information in this manual.
- XMART is not responsible for wrong use a third part can do of this information.
- Trademarks and logos in this manual are property of their owners.
SAFETY INSTRUCTIONS
SYMBOLS
| WARNING
---|---
| ELECTRICAL SHOCK RISK
WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for future consults.
WARNING: This product operates with dangerous voltages. It must be installed, operated, and maintained ONLY by qualified technicians trained for this kind of products. Service personnel MUST know and understand very well all electric risks related to this product. UPS manufacturer or distributor will never be responsible for any accident produced by lack of knowledge or negligent practices at the moment of install, starting up, or maintain this product. UPS manufacturer or distributor is not liable for any damage that might rise from misusing this unit or defective installation.
WARNING: If you are not qualified technician do not try to repair this product.
WARNING: Internal area of this product is locked by screws. Do not try to access inside the UPS unless you are a qualified technician. UPS must be checked, repaired, and maintained by qualified personnel only.
ELECTRICAL SHOCK RISK
CAUTION: There are dangerous voltages in the UPS power outlets although
the equipment is not plugged into power line.
CAUTION: Inside this equipment, due to internal batteries, there are ALWAYS dangerous voltages, even UPS is OFF and unplugged of power line.
WARNING: EQUIPMENT DISPOSAL
OUT OF SERVICE UNITS : It is strongly recommended to dispose this piece
of equipment according to valid directives in your country. At the moment of
disposing all pieces need to be managed appropriately to avoid possible
environmental damage or for some materials to be recycled.
BATTERIES: Do not throw it to fire (risk of explosion). Do not open the batteries, there are dangerous liquids inside.
SAFETY & QUALITY STANDARDS
SAFETY – LOW VOLTAGE DIRECTIVE (2014/35/EU)|
---|---
UPS Part 1-1: General & Safety UPS in accessible areas| IEC/EN 62040-1
ELECTROMAGNETIC COMPATIBILITY – EMC DIRECTIVE (2014/30/EU)|
UPS, Part 2, Electromagnetic Compatibility:| IEC/EN 62040-2
Low Freq. Conducted Disturbances & Signals:| IEC/EN 61000-2-2
Electrostatic discharge immunity Test:| IEC/EN 61000-4-2 (Air: Level 3,
Contact: Level 2)
Radiated radio Frequency immunity:| IEC/EN 61000-4-3 (Level 3)
Electrical Fast Transient / burst immunity:| EC/EN 61000-4-4 (Level 3)
Surge immunity:| IEC/EN 61000-4-5 (L-L: Level 2, L-G: Level 3)
UPS Part 3: Methods of operation, specifications, and test requirement| IEC/EN
62040-3
IT Equipment’s. SAFETY. Part 1: General Requirements| IEC/EN 60950-1
IP PROTECTION| IP20 (static)
QUALITY MANAGEMENT: ISO 9001 : 2000| Manufactured under: ISO 9001
ENVIRONMENTAL MANAGEMENT: ISO 14001 : 2004| Manufactured under: ISO 14001
Any modification made by user or operator may affect compliance of the safety
and performance certifications listed above.
UPS manufacturer is not responsible of any modification made on the product or
its accessories after it is manufactured.
This product is designed to operate in domestic and commercial environment. CE
standards apply for 230V models.
This is a C2 category product. In residential environment, this product may
cause radio interference, in this case the user may require taking additional
measures.
BATTERY MAINTENANCE
- Batteries capacity, in general (of all kinds), decreases with time and use.
- Our products contain high quality batteries only.
- Batteries useful life in our UPS is between 3 and 5 years, considering environment temperature under 25ºC and optimal operational conditions. This time can be dramatically reduced by high temperature and other adverse operation condition.
- Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipment connected to UPS.
- Batteries should be periodically tested to check capacity and assure and appropriate back up
*** To enlarge batteries life expectancy, it is recommendable to fully discharge UPS once every 3 months
- During long UPS storage recharge batteries according to following table:**
STORAGE TEMPERATURE | FREQUENCY | RECHARGING TIME |
---|---|---|
-25°C a +30°C | Every 4 months | 4 h |
+30°C a +45°C | Every 2 months | 4 h |
UPS DESCRIPTION
This kind of equipment is known as UPS (Uninterruptible Power Supply). It has
2 main functions: give electrical protection against surges, spikes and some
other dangerous failures of electrical main system and also provides
electrical backup based on internal batteries. In that way products you
connect to your UPS will be protected and will receive electrical energy even
during failures of main electrical AC system.
This UPS is designed to satisfy all requirements of Personal Computers (PCs).
It includes internal voltage regulator to stabilize input AC variations
without using internal batteries. Only in presence of important input failures
UPS will use internal batteries to provide energy in outlet sockets. In this
way batteries life expectancy is longer.
SUPRA 500/700/900 Series : It is an interactive UPS with step-wave
output. It includes surge protection in all AC outlets. RJ45 & RJ11 sockets
also include surge protection for the phone line of the router.
Parts Identification
- Output sockets
- Input AC
- Input breaker
- Input Fuse
- USB
- RJ45/RJ11 surge protected sockets
UPS will provide backup energy in its outlets when main AC input fails. Runtime will depend on some different factors:
- Battery charging level.
- Battery capacity according to the use given and lifetime.
- Load consumption connected to UPS outlets. Higher the output load shorter the runtime.
Under normal condition, when UPS is ON and connected to AC source, UPS will keep batteries fully charged.
NOTE: For Self-protection, all models of this family have a Max. backup time of 120 Minutes, limited by UPS electronic.
- This UPS must be installed indoor, in controlled environment free of excessive dust, corrosive air, or conductive dust.
- Do not install it outdoor. Keep UPS working under operational conditions listed in specifications table of this manual. Keep out of direct sun light, water, and heat sources.
- Do not install UPS close to PC screen to avoid interference. UPS must be at least at 20cm from screen.
- Connect TEL or LAN line to RJ45/RJ11 port identified as IN. Connect OUT to your Router (TEL input) or to your PC LAN port.
- Plug power cord of this UPS to AC source socket. Plug your equipment to UPS outlets.
- This unit MUST NOT be installed in closed boxes/cabinets that avoid fresh air access. During normal operation, this unit needs fresh air to flow through ventilation system (Vents) to cool power circuits.
Installing this unit in a closed box/cabinet makes inner air to be recycled without refreshing, increasing inside temperature, exceeding operation max. temperature, and causing permanent damage to the UPS.
MPORTANT WARNINGS:
- Make sure UPS is plugged to AC source compatible with UPS electrical specifications. Check UPS specs in UPS label.
- Make sure your products input voltage is compatible with UPS voltage output.
- Check total load in Watts to be connected to UPS is not higher to maximum UPS capacity.
- Do NOT plug neither laser printers nor copiers to this UPS. This equipment are high load products will overload your UPS.
OPERATION
- Once UPS is installed and connected according to section 4 of this manual, please turn UPS on by ON/OFF button in front panel. Front panel green LED must turn ON.
- Turn your products ON one by one.
- After finishing your products will be fully protected by the UPS.
This UPS has COLD-START function that allows to turn UPS on even during a
failure in the main AC source.
Front panel LED will let you know UPS status: OFF / ON / BATTERY MODE.
CONTROL SOFTWARE
Most models of this UPS family come with USB port to communicate with your PC.
Thus, UPS can be monitored and configured. Your PC can be automatically shut
down when AC input failure is detected saving your info and providing a
controlled shutdown. Event log and alarms can also be monitored from your PC.
Control software can be downloaded from our website: www.XMART-
ups.com. User and installation manual is also
available in our web.
Our software is available in different versions for: Windows, Mac OSX, Linux,
and Unix.
TROUBLESHOOTING
# | PROBLEM | CAUSE | SOLUTION |
---|---|---|---|
1 | UPS does not turn ON LED OFF | ON button not properly activated. | Push ON |
button for 2-3 seconds
Very low battery level| Keep UPS plugged to main service to recharge batteries
Battery failure| Contact service center to replace batteries
2| UPS in battery mode even main source is OK. Front LED Green flashing.
Intermittent BEEP alarm| Input cable or plug not connected to AC source| Check
and plug properly
Input breaker activated (open)| Check and reset input breaker
3| Input breaker frequently activated| Equipment connected to UPS outlets
overload UPS.| Check and unplug equipment until overload condition is solved
4| Continuous BEEP alarm.| UPS overloaded| Check and unplug equipment until
overload condition is solved
5| UPS power off when AC main source fails. (runtime = 0s)| Low battery level
because recent discharge| Keep UPS plugged to main service to recharge
batteries
Battery failure| Contact service center to replace batteries
AFTER SALES SUPPORT & WARRANTY
Support: If a failure or problem is detected please check troubleshooting
section in user manual. If problem cannot be solved, please contact authorized
service center or authorized dealer.
Batteries: Rechargeable batteries can be charged and discharged hundreds
of times. However, they will eventually wear out.
This is not a defect or failure so that batteries wear out is not covered by
this warranty.
Battery lifetime will depend on operative conditions like working temperature,
type and frequency of discharging cycles. Higher the temperature shorter will
be the lifetime. Frequent and deep discharging cycles also will short
lifetime. For critical applications batteries should be revised and replaced
periodically. Long storage (longer than 6 months) without required recharging
will wear out batteries. This situation is not covered by this limited
warranty since this is not considered as a defect. Check recharging
instructions on user manual.
Conditions Limited Warranty “PLUS”
-
Subject to the conditions of this limited warranty, this product is warranted to be free from defects in materials and
workmanship at the time of XMART supplies the product.- In Europe, warranty time is 2 years on electronic parts and 2 years on internal batteries from XMART invoice date.
- In America, standard warranty times could vary depending on country/region or can be extended by purchasing
warranty options. Please check warranty plans and extensions with your local distributor.
-
If during the warranty period, this product fails to operate under normal use and service, due to defects in materials or workmanship, authorized distributor or service center will, at their option, either repair or replace the product in accordance with terms and conditions stipulated herein. Transportation expenses are not covered by this limited warranty.
-
Warranty is valid only if the original invoice issued by XMART, specifying date of purchase, serial number, and name of the dealer, is presented with the product to be revised. XMART and authorized partners reserve the right to refuse warranty service if any of this information has been removed, changed, or missing in original invoice document.
-
If product is repaired or replaced, repaired, or replaced product will be warranted for the remaining time of the original
warranty or for 90 days on repaired part from date of repair, whichever is longer. -
XMART or their distribution/service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty.
-
If product is out of warranty a reparation proposal will be sent to the user for his approval. If proposal is not accepted, service center will keep product available for the user during 60 continuous days. After this period product would be disposed and user will not be able to rise any claim.
-
Rechargeable batteries, like included in this product, will definitively wear out even under normal operation. This is not a defect or failure, so it is not covered by this warranty.
-
This warranty does not cover batteries wear out caused by improper or long storage (over 6 months without required
recharging indicated in product manual). Even performing recharging procedure this product cannot be storage longer than 18 months. Problems on batteries caused by this kind of long storage are not covered by this warranty. -
This warranty does not cover product failures caused by installations, modifications or repair performed by non-authorized person. If product is open by not authorized technician warranty will be considered void. This warranty does not cover failure caused by inadequate installation or maintenance, misuse, accidents, fire or floods.
-
This product can include protection devices like input fuse or input breaker. Activation of this kind of devices is not a failure it is caused by an improper product installation. Input fuse or breaker reset, or replacement is not covered by this warranty.
-
This warranty does not cover damages produced during transportation from user to technical service caused by improper packing of the product by user.
-
Warranty terms and conditions cannot be modified or extended by third parties without written approval of XMART.
Limited Warranty “PLUS”
- XMART does not warrant that the operation of this product will be uninterrupted or error-free during its lifetime. If product fails to work, the maximum liability of XMART under this limited warranty is expressly limited to the lesser of the price you have paid for the product or the cost of repairing or replacement of any hardware components that malfunction in conditions of normal use.
- In no event will XMART be liable for any damages caused by the product or the failure of the product to perform, including any lost profits or savings or special, incidental, or consequential damages. XMART is not liable for any claim made by a third party to XMART or to final user.
- XMART is not responsible for damage that occurs because of your failure to follow the instructions intended for this hardware product.
TECHNICAL SPECIFICATIONS
INTERACTIVE UPS | 500 VA | 700 VA | 900 VA |
---|---|---|---|
Capacity | 500VA / 250W | 700VA / 360W | 900VA / 480W |
Input
Voltage| 120V Model: (89-145 Vac) – 220VModel: (162-290V) – 230V Model:
(170-299Vac)
Frequency| 60Hz / 50 Hz: Auto Sensing / Autodetection
Generator Compatible| Yes / is
Output
Voltage| +/- 10% (1 Phase / 1Fase)
Frequency| 60Hz (+/- 1Hz) – 50Hz (+/- 1Hz)
Transfer Time:| 2 – 6 ms typical / típico
Waveform (Normal Mode)| Sinewave
Waveform Battery Mode)| Simulated Sinewave
Batteries
Type| Sealed Lead Acid – Maintenance Free (VRLA AGM)
Capacity| 5AH| 7AH| 9AH
Quantity| 1| 1| 1
Back-up Time Typical / Autonomy Typical (N1*)| 10-12 min.| 17-20 min| 22-25
min
Recharge Time| 4-6 hours to 90% capacity
Protections| Deep discharge and overcharge
Alarms-Indications
Models: 501-901 & 503-903: LED| Battery Mode / Low Battery / Overload /
Battery Replacement / UPS Fault
AC Mode| Green Lighting
Battery Mode| Green Flashing
Acoustic Alarm (all models)| Battery Mode / Low Battery / Overload / Battery
Replacement / UPS Fault
Protections
Input Circuit Breaker| With Manual Reset / Rearm able
Surge/Spikes Protection (Line H-N) Protection contra Pico’s / Rayo’s (Linnea
L-N)| Power Outlet Sockets with surge & spikes protection: L-N Tomas de Salida
Protelids contra Pico’s/Rayo’s: L-N
Surge/Spikes Protection (RJ45) Protección contra Picos / Rayos (RJ45)|
Tel/Internet/Ethernet: RJ45
Total Suge Suppression| 120V Model: (> 758J) – 220V & 230 Models: (>175J)
Features
Power Outlets per model
Models: 501 / 701 / 901 – NEMA 120V & NEMA 220V| 6 x NEMA5-15R
Models: 501 / 701 / 901 – SCHUKO 230V| 2 x Schuko
Models: 503 / 703 / 903 – IEC+SCHUKO 230V| 1 x IEC + 2 x Schuko
Communication| USB Port / Puerto USB (optional for 120V models / opcional para
modelos 120V)
Dimensions| 300 x 101 x 142 mm
Net Weight| 3.6 Kg| 4.3 Kg| 4.9 Kg
Operating| < 95% RH / 0-40ºC / ≤ 40 dB @ 1mt
Packing
Carton Information| 4 units per carton| (350x600x260 mm)
Half Pallet Information| 96pcs / 364Kg 120x100x113cm| 96pcs / 432Kg
120x100x113cm| 96pcs / 489Kg 120x100x113cm
Full Pallet Information| 192pcs / 729Kg 120x100x213cm| 192pcs / 864Kg
120x100x213cm| 192pcs / 979Kg 120x100x213cm
Safety & Standards
For 220V & 230V| CE (Low Voltage Directive 2006/95/EC & EMC Directive
2004/108/EC)
Conduction & Radiation (Models 220V/230V)| IEC / EN 62040-2 (Class 2 EMC)
Quality & Environment| RoHS / ISO9001 & ISO14001
Technical specifications may change without further notice. Las specifications
peened cambia sin aviso previa.
N1*: Times for 1PC + TFT load / Tempos para 1PC + Patella TFT
CUSTOMER SUPPORT
USA Headquarters:
Miami, FL33196
Florida, USA
xmartmiami@xmart-ups.com
EUROPE Headquarters:
Sabadell, 08202
Barcelona, SPAIN
sales@xmart-ups.com
Latin America Headquarters:
Santiago de Chile, 8330662
Chile, CHILE
sales@xmart-ups.com
www.xmart-ups.com
VER. 2311.23-AP_ENG