bryant 38MHRC Outdoor Unit Single Zone Ductless System Heat Pump Instruction Manual Specifications Installation Instructions Parts List Frequently Asked Questions (FAQ)

January 12, 2024
bryant

38MHRC Outdoor Unit Single Zone Ductless System Heat Pump

Specifications

Product Model 38MHRC
Product Type Outdoor Unit Single Zone Ductless System Heat Pump (Sizes 09 to
  1. Cooling Only (Sizes 09 to 24)

Installation Instructions

Safety Considerations

Installing, starting up, and servicing air-conditioning
equipment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated structures,
etc.). Only trained, qualified installers and service mechanics
should install, start-up, and service this equipment. Untrained
personnel can perform basic maintenance functions such as coil
cleaning. All other operations should be performed by trained
service personnel only. When working on the equipment, observe
precautions in the literature and on tags, stickers, and labels
attached to the equipment.

Follow all safety codes. Wear safety glasses and work gloves.
Keep a quenching cloth and fire extinguisher nearby when brazing.
Use care in handling, rigging, and setting bulky equipment. Read
these instructions thoroughly and follow all warnings or cautions
included in the literature and attached to the unit. Consult the
local building codes and current editions of the National
Electrical Code (NEC) NFPA 70. In Canada, refer to current editions
of the Canadian electrical code CSA 22.1.

Warnings

ELECTRICAL SHOCK HAZARD: Failure to follow this
warning could result in personal injury or death. Before
installing, modifying, or servicing the system, the main electrical
disconnect switch must be in the OFF position. There may be more
than one disconnect switch. Lock out and tag the switch with a
suitable warning label.

EXPLOSION HAZARD: Failure to follow this
warning could result in death, serious personal injury, and/or
property damage. Never use air or gases containing oxygen for leak
testing or operating refrigerant compressors. Pressurized mixtures
of air or gases containing oxygen can lead to an explosion.

Caution

EQUIPMENT DAMAGE HAZARD: Failure to follow this
caution may result in equipment damage or improper operation. Do
not bury more than 36 in. (914 mm) of refrigerant pipe in the
ground. If any section of the pipe is buried, there must be a 6 in.
(152 mm) vertical rise to the valve connections on the outdoor
units. If more than the recommended length is buried, refrigerant
may migrate to the cooler buried section during extended periods of
system shutdown. This causes refrigerant slugging and could
possibly damage the compressor at startup.

Parts List

Part No. Part Name Qty
1 Outdoor Unit 1
Literature package including installation instructions and
warranty 1
Vibration pad 4
Drain joint 1
Drain hose 1

Frequently Asked Questions (FAQ)

Q: Can untrained personnel perform any maintenance functions on

the product?

A: Yes, untrained personnel can perform basic maintenance
functions such as coil cleaning. However, all other operations
should be performed by trained service personnel only.

Q: What precautions should be taken when working on the

equipment?

A: When working on the equipment, it is important to observe
precautions mentioned in the literature and on tags, stickers, and
labels attached to the equipment. Safety glasses and work gloves
should be worn. It is recommended to keep a quenching cloth and
fire extinguisher nearby when brazing. Care should be taken while
handling, rigging, and setting bulky equipment.

Q: Can air or gases containing oxygen be used for leak testing

or operating refrigerant compressors?

A: No, air or gases containing oxygen should never be used for
leak testing or operating refrigerant compressors. Pressurized
mixtures of air or gases containing oxygen can lead to an
explosion.

Q: Can the refrigerant pipe be buried in the ground?

A: Yes, the refrigerant pipe can be buried in the ground, but
not more than 36 in. (914 mm). If any section of the pipe is
buried, there must be a 6 in. (152 mm) vertical rise to the valve
connections on the outdoor units. Burying more than the recommended
length may cause refrigerant migration to the cooler buried section
during extended periods of system shutdown, resulting in
refrigerant slugging and possible compressor damage at startup.

38MHRC Outdoor Unit Single Zone Ductless System Heat Pump Sizes 09 to 36 Cooling Only Sizes 09 to 24

Installation Instructions

Fig. 1 — Outdoor Unit NOTES:
Read the entire instruction manual before starting the installation. Images are for illustration purposes only. Actual models may differ slightly.

TABLE OF CONTENTS
SAFETY CONSIDERATIONS………………………………………………..2 PARTS LIST …………………………………………………………………………3 SYSTEM REQUIREMENTS…………………………………………………..4 PIPING REQUIREMENTS……………………………………………………..4 WIRING ……………………………………………………………………………….5 DIMENSIONS……………………………………………………………………….6 CLEARANCES ……………………………………………………………………..13 INSTALLATION GUIDE……………………………………………………….14 OUTDOOR UNIT INSTALLATION ……………………………………….14 Step 1 – Select Installation Location………………………………………….14 Step 2 – Install Drain Joint (Heat Pump Unit Only) …………………….14 Step 3 – Anchor the Outdoor Unit……………………………………………..15 Step 4 – Connect the Signal and Power Cables……………………………15 Step 5 – Refrigerant Piping ………………………………………………………16 Step 6 – Evacuate Coil and Tubing System ………………………………..18 WIRING ……………………………………………………………………………….19 Step 7 – Electrical And Gas Leak Checks…………………………………..19 ELECTRICAL DATA…………………………………………………………….22 CONNECTION DIAGRAMS ………………………………………………….23 SYSTEM VACUUM AND CHARGE………………………………………24 START-UP ……………………………………………………………………………25 OUTDOOR UNIT DIAGNOSTIC GUIDES ……………………………..25 DUCTLESS START-UP CHECKLIST – SINGLE ZONE…………..26

Specifications subject to change without notice.

38MHRC: Installation Instructions
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as coil cleaning. All other operations should be performed by trained service personnel only.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep a quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit. Consult the local building codes and current editions of the National Electrical Code (NEC) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
EXPLOSION HAZARD Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at startup.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 2

38MHRC: Installation Instructions

PARTS LIST

Table 1 — Parts List

Part No.

Part Name

Qty

1

Outdoor Unit

1

Literature package including installation instructions and warranty

1

Vibration pad

4

Drain joint

1

Drain hose

1

2XWGRRU

Fig. 2 — Outdoor Unit NOTES: – If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a
downward arc in the connection pipe before it enters the wall to the indoor unit. This ensures that rain drips from the connection pipe before it enters the wall. – Piping and the interconnecting wiring are field supplied. – Figure 2 is only a sketch. Different models may differ slightly.

The units listed in Table 2 are covered in this manual.

System Tons 0.75 1.00 0.75 1.00 1.50 2.0 2.5 3.0

Table 2 — Heat Pump Unit Sizes

BTUh

V-Ph-Hz

9,000 12,000

115-1

9,000

12,000

18,000 24,000

208/230-1-60

30,000

36,000

Model 38MHRCQ09AA1 38MHRCQ12AA1 38MHRCQ09AA3 38MHRCQ12AA3 38MHRCQ18AA3 38MHRCQ24AA3 38MHRCQ30AA3 38MHRCQ36AA3

System Tons 1.00 0.75 1.00 1.50 2.00

Table 3 — Cooling Only Unit Sizes

BTUh 12,000

V-Ph-Hz 115-1

9,000 12,000 18,000 24,000

208/230-1-60

Model 38MHRDC12AA1 38MHRDC09AA3 38MHRDC12AA3 38MHRDC18AA3 38MHRDC24AA3

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 3

38MHRC: Installation Instructions

SYSTEM REQUIREMENTS
Allow sufficient space for airflow and unit service. See Fig. 9 — on page 13 for the minimum required distances between the unit and walls or ceilings.

PIPING REQUIREMENTS

IMPORTANT: Both refrigerant lines must be insulated separately.
The minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m). The following lengths are allowed. Table 4 lists the pipe sizes for the outdoor unit. For the indoor unit pipe sizes refer to the indoor unit installation instructions.

SYSTEM SIZE

Min. Piping Length Standard Piping Length

Max. outdoor-indoor height difference
(OU higher than IU)

ft. (m) ft. (m)
ft. (m)

Table 4 — Heat Pump System

9K (115 V)

12K

9K

12K

18K

24K

30K

36K

(115 V) (208/230 V) (208/230 V) (208/230 V) (208/230 V) (208/230 V) (208/230 V)

9.8 (3)

9.8 (3)

9.8 (3)

9.8 (3)

9.8 (3)

9.8 (3)

9.8 (3)

9.8 (3)

24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5)

32.8 (10) 32.8 (10) 32.8 (10) 32.8 (10) 65.6 (20) 82 (25)

82 (25) 98.4 (30)

Max. outdoor-indoor height difference
(IU higher than OU)

ft. (m)

32.8 (10)

32.8 (10)

32.8 (10)

32.8 (10)

65.6 (20)

82 (25)

82 (25) 98.4 (30)

PIPING

Max. Piping Length with no additional refrigerant charge per System
(Standard Piping length)

ft. (m)

24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5)

Total Maximum Piping Length per system
Additional refrigerant charge (between Standard
­ Max piping length)
Suction Pipe (size – connection type)
Liquid Pipe (size – connection type)
Refrigerant Type

ft. (m) 82 (25)

82 (25)

82 (25)

82 (25) 98.4 (30) 164 (50) 164 (50) 213 (65)

Oz/ft (g/m)

0.161(15) 0.161(15) 0.161(15) 0.161(15) 0.161(15) 0.322(30) 0.322(30) 0.322(30)

In (mm) ø3/8″ (9.52) ø1/2″ (12.7) ø3/8″ (9.52) ø1/2″ (12.7) ø1/2″ (12.7) ø5/8″ (15.9) ø5/8″ (15.9) ø5/8″ (15.9)

In (mm) ø1/4″ (6.35) ø1/4″ (6.35) ø1/4″ (6.35) ø1/4″ (6.35) ø1/4″ (6.35) ø3/8″ (9.52) ø3/8″ (9.52) ø3/8″ (9.52)

Type

R410A

R410A

R410A

R410A

R410A

R410A

R410A

R410A

Charge Amount

lb. (kg) 1.59(0.72) 1.79(0.81) 1.59(0.72) 1.79(0.81) 2.98(1.35) 3.92(1.78) 6.17(2.8) 7.5(3.4)

REFRIGERANT

PIPING

SYSTEM SIZE

Min. Piping Length
Standard Piping Length
Max. outdoor-indoor height difference
(OU higher than IU)
Max. Piping Length with no additional refrigerant charge
per System (Standard Piping length)
Total Maximum Piping Length per system
Additional refrigerant charge (between Standard ­ Max piping length)
Suction Pipe (size – connection type)
Liquid Pipe (size – connection type)
Refrigerant Type

ft. (m) ft. (m) ft. (m)
ft. (m)
ft. (m) Oz/ft (g/
m) In (mm) In (mm)
Type

Table 5 — Cooling Only System

12K

9K

12K

(115 V)

(208/230 V)

(208/230 V)

9.8 (3)

9.8 (3)

9.8 (3)

24.6 (7.5)

24.6 (7.5)

24.6 (7.5)

32.8 (10)

32.8 (10)

32.8 (10)

24.6 (7.5)
82 (25) 0.161(15) ø1/2″ (12.7) ø1/4″ (6.35)
R410A

24.6 (7.5)
82 (25) 0.161(15) ø3/8″ (9.52) ø1/4″ (6.35)
R410A

24.6 (7.5)
82 (25) 0.161(15) ø1/2″ (12.7) ø1/4″ (6.35)
R410A

Charge Amount

lb. (kg)

1.46(0.66)

1.26(0.57)

1.46(0.66)

18K (208/230 V)
9.8 (3) 24.6 (7.5) 65.6 (20)
24.6 (7.5)
98.4 (30) 0.161(15) ø1/2″ (12.7) ø1/4″ (6.35)
R410A
1.98 (0.9)

24K (208/230 V)
9.8 (3) 24.6 (7.5)
82 (25)
24.6 (7.5)
98.4 (30) 0.322(30) ø5/8″ (15.9) ø3/8″ (9.52)
R410A
2.36(1.07)

REFRIGERANT

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 4

38MHRC: Installation Instructions
Refrigerant Piping: Line sets to be sized based on the connection size of the indoor unit. Each pipe should be insulated individually.
Additional Refrigerant Calculation · 9K-18K: Sum Total Liquid Pipe ft. (m) – Additional Charge Required After ft. (m.) x Additional Charge oz./ft. (g/m) 0.16 (15) · 24K: Sum Total Liquid Pipe ft. (m) – Additional Charge Required After ft. (m.) x Additional Charge oz./ft. (g/m) 0.322 (30)

NOTE: If the calculation results in a negative number no additional refrigerant is required. Electronic expansion valves in the outdoor unit are used as metering devices.

WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. See the rating plate and/or the installation instructions of the compatible outdoor unit for MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Recommended Connection Method for Power and Communication Wiring: The main power is supplied to the outdoor unit. The field supplied 14/3 stranded wire with ground with a 600 volt insulation rating, power/ communication wiring from the outdoor unit to indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are line voltage AC power, one is communication wiring (3) and the other is a ground wire. Wiring between indoor and outdoor unit is polarity sensitive. The use of BX wire is NOT recommended.
If installed in a high Electromagnetic field (EMF) area and communication issues exists, a 14/2 stranded shielded wire can be used to replace L2 and (3) between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only.

WARNING
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Be sure to comply with local codes while running wire from the indoor unit to the outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected. No wire should touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with conduit shall be routed through the hole in the conduit panel.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 5

38MHRC: Installation Instructions
DIMENSIONS

SYSTEM SIZE
UNIT HEIGHT (H) in (mm) WIDTH (W) in (mm) DEPTH (D) in (mm) WEIGHT – NET lbs. (kg)

OUTDOOR UNIT

HEIGHT
WIDTH
DEPTH
WEIGHT GROSS
CARTON DRAWING NO.
CARTON MATERIAL
MATERIAL THICKNESS

in (mm) in (mm) in (mm) lbs. (kg)


in (mm)

9K (115V)
21.85(555) 30.12(765) 11.93(303) 57.76(26.2)
24.02(610) 34.92(887) 13.27(337) 63.49(28.8)
877327590
0.197(5)

Table 6 — Dimensions Heat Pump

12K

9K

12K

18K

(115 V) (208/230 V) (208/230 V) (208/230 V)

21.85(555) 30.12(765) 11.93(303) 62.17(28.2)
24.02(610) 34.92(887) 13.27(337)
67.68(30.7)

21.85(555) 30.12(765) 11.93(303) 55.11(25.0)
24.02(610) 34.92(887) 13.27(337)
60.85(27.6)

21.85(555) 30.12(765) 11.93(303)

21.81(554) 31.69(805) 12.99(330)

59.30(26.9) 73.85(33.5)

PACKAGING 24.02(610) 24.21(615)

34.92(887) 13.27(337)

36.02(915) 14.57(370)

64.82(29.4) 79.81(36.2)

877327590 877327590 877327590 905360590

CARTON BOX

0.197(5)

0.197(5)

0.197(5)

0.197(5)

24K (208/230 V)
26.50(673) 35.04(890) 13.46(342) 97.88(44.4)
29.13(740) 39.17(995) 15.67(398) 104.50(47.4)
985388720
0.295(7.5)

30K (208/230 V)
31.89(810) 37.24(946) 16.14(410) 142.86(64.8)
34.84(885) 42.91(1090) 19.69(500) 152.56(69.2)
107548586
0.295(7.5)

36K (208/230 V)
31.89(810) 37.24(946) 16.14(410) 150.13(68.1)
34.84(885) 42.91(1090) 19.69(500) 158.95(72.1)
107548586
0.295(7.5)

SYSTEM SIZE

UNIT HEIGHT (H) WIDTH (W) DEPTH (D) WEIGHT – NET

in (mm) in (mm) in (mm) lbs.(kg)

OUTDOOR UNIT

HEIGHT
WIDTH
DEPTH
WEIGHTGROSS
CARTON DRAWING NO.
CARTON MATERIAL
MATERIAL THICKNESS

in (mm) in (mm) in (mm) lbs.(kg)


in (mm)

Table 7 — Dimensions Cooling Only

12K

9K

12K

(115 V)

(208/230 V)

(208/230 V)

19.49(495) 28.35(720) 10.63(270) 50.71(23)
21.26(540) 32.87(835) 11.81(300) 54.45(24.7)
818288520
0.197(5)

19.49(495) 28.35(720) 10.63(270) 47.38(21.49)
21.26(540) 32.87(835) 11.81(300) 51.06(23.16)
818288520
0.197(5)

19.49(495) 28.35(720) 10.63(270) 48.50(22) PACKAGING 21.26(540) 32.87(835) 11.81(300) 52.47(23.8)
818288520
CARTON BOX
0.197(5)

18K (208/230 V)
21.85(555) 30.12(765) 11.93(303) 61.51(27.9)
24.02(610) 34.92(887) 13.27(337) 66.80(30.3)
877327590
0.197(5)

24K (208/230 V)
21.81(554) 31.69(805) 12.99(330) 67.24(30.5)
24.21(615) 36.02(915) 14.57(370) 72.97(33.1)
905360590
0.295(7.5)

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 6

38MHRC: Installation Instructions
DIMENSIONS (CONT)

21.90 [556] 11.38 [286.5]

10.38 [262] 10.90 [278] 30.25 [769] 33 [837.5]

11 [280.5] 11.25 [285.75] 12.38 [313.75] 2.38 [59.75] 3.63 [93.15]

17.75 [452.5]

0.75 [17.5]

3.13 [78.75]

6.90 [175]

10.38 [262]

Fig. 3 — Sizes 9K/12K (115V) and 9K/12K (208/230V) Heat Pump and 18K Cooling Only

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 7

38MHRC: Installation Instructions
DIMENSIONS (CONT)

31.5 [800.5] 30 [760.4]

19.5 [494]

0.2 [5]

11.13 [281]

28.38 [719]

10.6 [261]

1 [24.5] 1.75 [44]

15.38 [392] 17.75 [452] 1.25 [30]

3 [75]

2.38 [59.5] 3.5 [87.5] Fig. 4 — Sizes 9K/12K (115V) and 12K (208/230V) Cooling Only

11 [281]

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 8

38MHRC: Installation Instructions
DIMENSIONS (CONT)

33.38 [847.1] 34.75 [883.6]

21.75 [554.5]

0.5 [11.4]

13.5 [346.3]

1 [26] R0.2 [R5.0]

34.38 [798.8]

20 [511] 1.9 [49.4]

17.75 [449] 2 [49.5]

12.5 [317.2]

3.9 [98.2]

2.38 [60] 3.75 [95.7]

1.38 [32.7]

Fig. 5 — Size 18K Heat Pump

13.63 [346.3]

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 9

38MHRC: Installation Instructions
DIMENSIONS (CONT)

4.25 [106]

4.75 [122] 35.25 [894.72]

26.50 [672.79]

.50 [11]

13.25 [337.56] Detail A Scale 2:1
2.90 [73.50]

26 [663] 35 [890.60] A

2.90 [71.52]

13.60 [346.67] [6.0R20.6]24 14.90 [379.59] 13.25 [334]

Fig. 6 — Size 24K Heat Pump and 24K Cooling Only
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 10

38MHRC: Installation Instructions
DIMENSIONS (CONT)

31.90 [808.79]

16 [407]

37.25 [946.32] 40.60 [1033.64]

17.90 [454.80] 15.75 [400.44]

26.50 [673] 0.38 [10] 3.75 [95]

2.25 [60] 4.25 [107.50] Fig. 7 — Size 30K Heat Pump

15.90 [402.60]

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 11

38MHRC: Installation Instructions
DIMENSIONS (CONT)

31.90 [808.79]

15.9 [405]

37.25 [946.32] 40.60 [1033.64]

17.90 [454.80] 15.75 [399.03]

26.50 [673] 0.38 [10] 3.75 [95]

2.60 [59.96] 4.25 [107.51] Fig. 8 — Size 36K Heat Pump

16 [408.29]

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 12

38MHRC: Installation Instructions
CLEARANCES

A

Air-inlet

E

D

B

C

Air-outlet

Fig. 9 — Clearances

UNIT A B C D E

Table 8 — Clearance Values

MINIMUM VALUE in. (mm) 24 (609) 24 (609) 24 (609) 4 (101) 6 (152)

NOTE: The outdoor unit must be mounted at least 2in (50mm) above the maximum anticipated snow depth.

9.8in (25cm) or more for proper airflow 24in(61cm) or more is recommended for service
9.8in (25cm) or more for proper airflow 24in (61cm) or more is recommended for service

19in (48cm) or more on a multiple parallel unit arrangement 4in (10cm) or more on a single parallel unit arrangement 59in (150cm) or more when facing each other
Blowing into the air-inlet of other condenser shall be avoided.
59in (150cm) 24in (60cm) or more or more on a multiple parallel unit arrangement 24in (61cm) or more on a single parallel unit arrangement

Fig. 10 –Clearances for multiple units

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 13

38MHRC: Installation Instructions

INSTALLATION GUIDE
INSTALLATION TIPS
Before installing the outdoor unit, choose an appropriate location. Ideal installation locations include:
Outdoor Unit · A location which is convenient to installation and not exposed to
strong winds. · A location which can bear the weight of the outdoor unit and where
the outdoor unit can be mounted in a level position. · A location with appropriate clearances as outlined (See Fig. 9 — on
page 13). · Do not install the indoor or outdoor units in a location with special
environmental conditions. For those applications, contact your Ductless representative.
OUTDOOR UNIT INSTALLATION
Install the unit by following local codes and regulations.

Special Considerations for Extreme Weather If the unit is exposed to heavy wind, install the unit so the air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds.
Strong wind Wind Baffle ( eld supplied)
Strong wind
Strong wind
Fig. 12 — Considerations for Extreme Weather If the unit is frequently exposed to heavy rain or snow, build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow around the unit. If the unit is frequently exposed to salty air (seaside), use and outdoor unit which is especially made to resist corrosion.
Step 2 – Install Drain Joint (Heat Pump Unit Only)

24in (60cm) above

12oinn(l3e0ftcm)

1fr2oinm(3b0accmk w) all

79in (i2n0f0rocnmt)

24in on

r(i6g0hctm)

Fig. 11 — Unit Clearances

Step 1 – Select Installation Location
The following are standards that will help select an appropriate location for the unit.
· Meets all clearance requirements (see Figure 11). · Good air circulation and ventilation · Firm and solid-the location can support the unit and will not vibrate
· Noise from the unit will not disturb others · Protected from prolonged periods of direct sunlight or rain
· Where snowfall is anticipated, raise the unit above the base pad to prevent ice buildup and coil damage. Mount the unit high enough to be above the average accumulated area snowfall. The minimum height must be 18 inches.
DO NOT install in the following locations:
· Near an obstacle that blocks air inlets and outlets · Near a public street, crowded areas, or where noise from the unit may
disturb others · Near animals or plants that will be harmed by hot air discharge · Near any source of combustible gas · In a location that is exposed to large amounts of dust · In a location exposed to excessive amounts of salty air

Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Note that there are two different types of drain joints depending on the type of outdoor unit. If the drain joint comes with a rubber seal (see Fig. 13), perform the following steps:
1. Fit the rubber seal on the end of the drain joint that connects to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit. 3. Rotate the drain joint 90° until it clicks in place facing the front of the
unit. 4. Connect a drain hose extension (not included) to the drain joint to
redirect water from the unit during heating mode.
If the drain joint does not come with a rubber seal (see Fig. 13), perform the following steps:
1. Insert the drain joint into the hole in the base pan of the unit. The drain joint clicks in place.
2. Connect a drain hose extension (field supplied) to the drain joint to redirect water from the unit during heating mode.

Base pan hole of

Seal

outdoor unit

Seal

Drain joint

(A)

(B)

Fig. 13 — Install Drain Joint

WARNING
In cold climates, ensure that the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 14

38MHRC: Installation Instructions

Step 3 – Anchor the Outdoor Unit
The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt (M10). Table 9 provides a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the unit’s installation base according to the dimensions in Table 9.

Table 9 — Unit Mounting Dimensions

SYSTEM SIZE 9K-12K (HP)
12K (CO)

DISTANCE A IN (MM) 17.8″ (452) 17.8″ (452)

DISTANCE B IN (MM) 11.25″ (286) 10.3″ (261)

18K (HP)

20.1″ (511)

12.5″(317)

18K (CO) 24K (HP & CO)

17.8″ (452) 26.1″ (663)

11.3″ (286) 13.9″ (354)

A
Air inlet

Air inlet

D B

Air outlet Fig. 14 — Unit Air Inlet and Outlet
If you install the unit on the ground or on a concrete mounting platform, perform the following steps:
1. Mark the positions for four expansion bolts based on the dimensions charts.
2. Pre-drill holes for expansion bolts. 3. Place a nut on the end of the expansion bolt. 4. Hammer expansion bolts into the pre-drilled holes. 5. Remove the nuts from the expansion bolts, and place the outdoor unit
on bolts. 6. Put the washer on each expansion bolt then replace the nuts. 7. Using a wrench, tighten each nut until snug.
CAUTION
When drilling into concrete, eye protection is recommended at all times.
To install the unit on a wall-mounted bracket, perform the following steps:
CAUTION
Ensure the wall is made of a solid brick, concrete, or of similarity strong material. The wall must be able to support at least four times the weight of the unit.

Step 4 – Connect the Signal and Power Cables
The outside unit’s terminal block is protected by an electrical wiring cover on the side of the unit. A comprehensive wiring diagram is printed on the inside of the wiring cover.
WARNING
Before performing any electrical or wiring work, turn off the main power to the system.
1. Prepare the cable for connection.
Use the Right Cable
The size of the power supply cable, signal cable, fuse, and disconnect needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit.
NOTE: Select the right cable size according to the Minimum Circuit Ampacity indicated on the nameplate of the unit.
a. Using wire strippers, strip the outer insulation from both ends of the cable to reveal about 1.5in (40mm) of the wires inside.
b. Strip the insulation from the ends of the wires. c. Using a wire crimper, crimp u-lugs on the ends of the wires.
WARNING
All wiring work must be performed strictly in accordance with the wiring diagram located inside the wire cover of the outdoor unit.
2. Unscrew the electrical wiring cover and remove it. 3. Unscrew the cable clamp below the terminal block and place it to the
side. 4. Connect the wire according to the wiring diagram, and firmly screw the
u-lug of each wire to its corresponding terminal. 5. After ensuring that sure every connection is secure, loop the wires
around to prevent rain water from flowing into the terminal. 6. Using the cable clamp, fasten the cable to the unit. 7. Screw the cable clamp down tightly. 8. Insulate unused wires with PVC electrical tape. Arrange them so that
they do not touch any electrical or metal parts. 9. Replace the wire cover on the side of the unit, and screw it in place.
Cover

1. Mark the position of the bracket holes based on the dimensions chart. 2. Pre-drill the holes for the expansion bolts. 3. Place a washer and nut on the end of each expansion bolt. 4. Thread expansion bolts through holes in the mounting brackets. 5. Put mounting brackets in position and hammer the expansion bolts into
the wall. 6. Ensure the mounting brackets are level. 7. Carefully lift the unit and place its mounting feet on the brackets. 8. Bolt the unit firmly to the brackets. 9. If allowed, install the unit with rubber gaskets to reduce vibrations and
noise.

Screw
Fig. 15 — Cover and Screw

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 15

38MHRC: Installation Instructions
NOTE: If the cable clamp resembles Figure 16, select the appropriate hole according to the diameter of the wire.
Buckle
Three size hole: Small, Large, Medium
Fig. 16 — Buckle 1. Remove the wire cover from the unit by loosening the 3 screws. 2. Remove the caps on the conduit panel. 3. Mount the conduit (field supplied) on the conduit panel. 4. Connect both the power supply and low voltage lines to the
corresponding terminals on the terminal blocks. 5. Ground the unit in accordance with local codes. 6. Be sure to leave several inches 4 to 6 inches of slack in the wiring to
facilitate installation and future service work. 7. Use lock nuts to secure the conduit.

Step 5 – Refrigerant Piping
When connecting refrigerant piping, do not allow substances or gases other than the specified refrigerant to enter the unit. The presence of other gases or substances will lower the unit’s capacity and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
NOTE: The length of the refrigerant piping affects the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 16.5ft (5m) (in North America, the standard pipe length is 25ft (7.5m). A minimum pipe run of 9.8ft (3m) is required to minimize vibration and excessive noise.

Table 10 — Maximum Length and Drop Height of Refrigerant Piping per Unit Model

Model

Capacity

Max. Length (ft/m)

Max. Lift (ft/m)

R410A Fixed-speed
Split Air Conditioner

9,000 – 12,000 18,000 24,000

82ft (25m) 98ft (30m) 164ft (50m)

33ft (10m) 66ft (20m) 82ft (25m)

Use the following steps to connect the refrigerant piping:
1. Run the interconnecting piping from the outdoor unit to the indoor unit.
2. Connect the refrigerant piping and drain line outside the indoor unit. Complete the pipe insulation at the flare connection then fasten the piping and wiring to the wall as required. Completely seal the hole in the wall.
3. Piping: a. Cut the pipe, with a pipe cutter, at 90 degrees (see Fig. 18). b. Remove the service connection (if provided with the unit).

Terminal block Over 1.57in.(40mm)

Connecting cable
G
Power supply cord

Conduit panel

Wire Cover
Select the appropriate through-hole according to the diameter of the wire.
Fig. 17 — Terminal Block

90°

Oblique Rough Warped

Fig. 18 — Pipe Cutting c. Remove all the burrs from the cut cross section of the pipe,
avoiding any burrs from inside the tubes. d. Remove the flare nuts attached to the indoor and outdoor units. e. Install the correct size flare nut onto the tubing and make the
flare connection. Refer to Table 11 for flare nut spacing.

Table 11 — Flare Nut Spacing

OUTER DIAM. IN (MM)

MAX.

A IN (MM)

MIN.

Ø 1/4in (6.35mm)

0.05in (1.3mm)

0.03in (0.7mm)

Ø 3/8in (9.52mm)

0.06in (1.6mm)

0.04in (1.0mm)

Ø 1/2in (12.7mm)

0.07in (1.8mm)

0.04in (1.0mm)

Ø 5/8in (15.88mm)

0.09in (2.2mm)

0.08in (2.0mm)

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 16

38MHRC: Installation Instructions

Handle

“A”

Bar

Bar

Yoke

Cone

Copper pipe Clamp handle Red arrow mark
Fig. 19 — Flare Nut Spacing
f. Apply a small amount of refrigerant oil onto the flare connection on the tubing.
g. Align the center of the pipes and/or the service valve.

Connect Piping to the Outdoor Unit
1. Unscrew the cover from the packed valve on the side of the outdoor unit.
2. Remove the protective caps from the valve ends. 3. Align the flared pipe end with each valve, and tighten the flare nut as
tightly as possible by hand. 4. Using a spanner, grip the body of the valve. Do not grip the nut that
seals the service valve.
Valve cover

Indoor unit tubing Flare nut Piping
Fig. 20 — Align Pipe Center
h. Connect both the liquid and gas piping to the indoor unit. i. Tighten the flare nut with a torque wrench. j. Using the correct wrench, grip the nut on the unit tubing. k. While firmly gripping the nut on the unit tubing, use a torque
wrench to tighten the flare nut according to the torque values in the Tightening Torque Requirements (Table 12). Loosen the flaring nut slightly, then tighten again.

Fig. 21 — Valve cover 5. While firmly gripping the body of the valve, use a torque wrench to
tighten the flare nut according to the correct torque values.
6. Loosen the flaring nut slightly, then tighten again.
7. Repeat steps 3 to 6 for the remaining pipe.
NOTE: Use a spanner to grip the main body of the valve. Torque from tightening the flare nut can snap off other parts of the valve.

Table 12 — Tightening Torque Requirements

PIPE DIAMETER IN.(MM)

TIGHTENING TORQUE

FT-LB

N-M

Ø1/4″ (6.35) Ø3/8″ (9.52) Ø1/2″ (12.7) Ø5/8″ (15.88)

10 to 13 24 to 31 37 to 46 50 to 60

13.6 to 17.6 32.5 to 42.0 50.1 to 62.3 67.7 to 81.3

Fig. 22 — Use proper size wrenches

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 17

38MHRC: Installation Instructions

Step 6 – Evacuate Coil and Tubing System

CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum pump.
Refrigerant tubes and the indoor coil should be evacuated using the recommended 500 microns deep vacuum method. The alternate triple evacuation method may be used if the procedure outlined below is followed. NOTE: Always break a vacuum with dry nitrogen. Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect the manifold gage charge hose to a charge port of the low side service valve (see Fig. 23).
2. Connect the charge hose to vacuum pump. 3. Fully open the low side of manifold gage (see Fig. 24). 4. Start the vacuum pump. 5. Evacuate using either the deep vacuum or triple evacuation method. 6. After evacuation is complete, fully close the low side of manifold gage
and stop the vacuum pump operation. 7. The factory charge contained in the outdoor unit is good for up to 25 ft.
(8 m) of line length. For refrigerant lines longer than 25 ft. (8 m), add refrigerant, up to the allowable length. 8. Disconnect the charge hose from the charge connection of the low side service valve. 9. Fully open service valves B and A. 10. Securely tighten the service valve caps.

Outdoor Unit

Refrigerant
A Low Side

B High Side
Service Valve

Indoor Unit
C
D

Evacuation
Evacuation of the system will remove air or nitrogen (non-condensables) as well as moisture. A proper vacuum assures a tight, dry system before charging with refrigerant. The two methods used to evacuate a system are the deep vacuum method and the triple vacuum method.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gauge capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and moisture (see Fig. 25).

MICRONS

5000 4500 4000 3500 3000 2500 2000 1500 1000 500

LEAK IN SYSTEM
VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 01234 567 MINUTES

Fig. 25 — Deep Vacuum Graph Triple Evacuation Method

The triple evacuation method should be used when vacuum pump is not capable of pumping down to 500 microns and system does not contain any liquid water. Refer to Fig. 26 and proceed as follows:

1. Attach the refrigeration gauges and evacuate system down to 28 in. of mercury and allow the pump to continue operating for an additional 15 minutes.
2. Close the service valves and shut off the vacuum pump.
3. Connect a nitrogen cylinder and regulator to the system and flow nitrogen until the system pressure is 2 psig.
4. Close the service valve and allow the system to stand for 1 hour. During this time, dry nitrogen will diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 26. The system should now be free of any contaminants and water vapor.

Fig. 23 — Service Valve
Manifold Gage

EVACUATE TO 1500 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 1000 MICRONS

500 microns Low side valve
Charge hose

High side valve Charge hose
Vacuum pump

BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 500 MICRONS MINIMUM (HOLD FOR 30 MINUTES)
CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)

Low side valve
Fig. 24 — Manifold

RELEASE CHARGE INTO SYSTEM BY OPENING VALVES COMPLETELY
Fig. 26 — Triple Evacuation Method
Final Tubing Check
IMPORTANT: Ensure the factory tubing on both the indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to the feeder tubes and make sure the wire ties on the feeder tubes are secure and tight.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 18

38MHRC: Installation Instructions

WIRING
Size all wires per the NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use the electrical data from the outdoor unit (MCA – minimum circuit amps and MOCP – maximum over current protection), to correctly size the wires and the disconnect fuse or breakers respectively.
SIZES 9-24 RECOMMENDED CONNECTION METHOD FOR POWER AND COMMUNICATION WIRING Power and Communication Wiring: The main power is supplied to the outdoor unit. The field supplied 14/3 power/communication wiring, from the outdoor unit to the indoor unit, consists of four (4) wires and provides the power for the indoor unit. Two wires are high voltage AC power, one is communication wiring and the other is a ground wire.
To minimize communication interference: If installed in a high Electromagnetic field (EMF) area and communication issues arise, a 14/2 stranded shielded cable can be used to replace L2 and (3) between the outdoor and indoor units – landing the shield onto the ground in the outdoor unit only.
CAUTION
EQUIPMENT DAMAGE HAZARD Be sure to comply with local codes while running wire from the indoor unit to the outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in a unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected. No wire should touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and located within sight and readily accessible from the system. Route the connecting cable with conduit through the hole in the conduit panel.
NOTE: The main power is supplied to the outdoor unit. When disconnecting the power of the outdoor unit, the indoor unit would lose power. A disconnect switch is not required on the Indoor unit side on the wiring between the outdoor and indoor unit. A 3 pole disconnect may be used for extra protection between the indoor and outdoor unit (refer to local codes).

Step 7 – Electrical And Gas Leak Checks
Before Test Run
Only perform a test run after you have completed the following. · Electrical Safety Checks ­ Confirm that the unit’s electrical system is
safe and operating properly · Gas Leak Checks ­ Check all flare nut connections and confirm that
the system is not leaking · Confirm that gas and liquid (high and low pressure) valves are fully
open
Electrical Safety Checks
After the installation, confirm that all electrical wiring is installed in accordance with local and national regulations, and according to the Installation Manual.
Before Test Run
Check Grounding Work Measure the grounding resistance by visual detection and with grounding resistance tester. Grounding resistance must be less than 0.1 W. NOTE: This may not be required for some locations in North
America.
During Test Run
Check for Electrical Leakage During the Test Run, use an electroprobe and multimeter to perform a comprehensive electrical leakage test. If electrical leakage is detected, turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage. NOTE: This may not be required for some locations in North
America. Gas Leak Checks
There are two different methods to check for gas leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit. The presence of bubbles indicates a leak.
Leak Detector Method
If using a leak detector, refer to the device’s operation manual for proper usage instructions.
After Performing Gas Leak Checks
After confirming that the all pipe connection points DO NOT leak, replace the valve cover on the outside unit.

Check-point of indoor unit

Check-point of outdoor unit
D

B

C

A

A: Low pressure stop valve B: High pressure stop valve C & D: Indoor unit flare nuts
Fig. 27 — Gas Leak Checks
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 19

38MHRC: Installation Instructions

MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR UNIT)
IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be used. Use of other tubing types will void the manufacturer’s warranty.
Piping Guide:
· Do not open service valves or remove protective caps from tubing ends until all the connections are made.
· Bend the tubing with bending tools to avoid kinks and flat spots.
· Keep the tubing free of dirt, sand, moisture, and other contaminants to avoid damaging the refrigerant system.
· Avoid sags in the suction line to prevent the formation of oil traps. Insulate each tube with minimum 3/8-in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections saves time and improves installation quality.
1. Remove the service valve cover, if provided with the unit. 2. Cut the pipe, with a pipe cutter, at 90 degrees (see Fig. 28). 3. Remove the service connection, if provided with the unit.

Copper tube
Fig. 31 — Tighten the Flare Nut
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Excessive torque can break the flare nut depending on installation conditions.
INSTALL ALL POWER AND INTERCONNECTING WIRING TO OUTDOOR UNIT

90

Oblique Roughness Burr

Fig. 28 — Cut the pipe
4. Remove all the burrs from the cut cross section of the pipe avoiding any burrs inside the tubes.
5. Remove the flare nuts attached to the indoor and outdoor units.
6. Install the correct size flare nut onto the tubing and make a flare connection. Refer to Table 13 for the flare nut spaces.

Table 13 — Flare Nut Spacing

OUTER DIAM. (mm) Ø1/4″ (6.35)

Max. 0.05 (1.3)

A (mm)

Min. 0.03 (0.7)

Ø3/8″ (9.52) Ø1/2″ (12.7)

0.06 (1.6) 0.07 (1.8)

0.04 (1.0) 0.04 (1.0)

Ø5/8″ (15.88)

0.09 (2.2)

0.08 (2.0)

Handle

“A”

Bar

Bar

Yoke

Cone

Copper pipe
Clamp handle Red arrow mark
Fig. 29 — Flare Nut Spacing 7. Apply a small amount of refrigerant oil to the flare connection on the
tubing. 8. Align the center of the pipes and/or the service valve.

1. Mount the outdoor power disconnect. 2. Run the power wiring from the main box to the disconnect per the NEC
and local codes. 3. Remove the field wiring cover (if available) from the unit by loosening
the screws. 4. Remove the caps on the conduit panel. 5. Connect the conduit to the conduit panel (see Fig. 32). 6. Properly connect the power supply and the control lines to the terminal
block per the connection diagram. 7. Ground the unit in accordance with the NEC and local electrical codes. 8. Use the lock nuts to secure the conduit. 9. Reinstall the field wiring cover.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Comply with the local codes while running wire from the indoor unit to the outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure all wiring is tightly connected. No wire should be allowed to touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with conduit shall be routed through hole in the conduit panel.

Indoor unit tubing Flare nut Piping
Fig. 30 — Align Pipe Center 9. Connect both the liquid and gas piping to the indoor unit. 10. Tighten the flare nut using a torque wrench as specified in Table 14. 11. Complete the installation.

Table 14 — Tightening Torque

Pipe Diameter Ø1/4

Tightening Torque Ft-lb 10 to 13

N-m 13.6 to 17.6

Ø3/8 Ø1/2

24 to 31 37 to 46

35.5 to 42.0 50.1 to 62.3

Ø5/8

50 to 60

67.7 to 81.3

Terminal block Over 1.57in.(40mm)

Connecting cable
G
Power supply cord

Conduit panel

Wire Cover
Select the appropriate through-hole according to the wire diameter.
Fig. 32 — Field Wiring

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 20

38MHRC: Installation Instructions

DRAIN CONNECTIONS
Installed drains must meet local sanitation codes. Install the outdoor unit drain joint
1. Fit the seal into the drain joint. 2. Insert the drain joint into the base pan hole of the outdoor unit. 3. Rotate 90° to securely assemble them. 4. Connect the drain joint with an extension drain hose to avoid
condensate from draining off the outdoor unit during the heating mode.

CAUTION
In cold climates, ensure the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.
NOTE: Basepan built-in with multiple holes for proper draining during defrost. For applications where it is required to seal these holes, and re-direct the condensate drain, rubber plugs are available through Replacement Components (RC).

Table 15 — Rubber Plugs

Outdoor Unit Model Number

Basepan Rubber Plugs RC Part Number

Quantity per unit

Seal

Drain joint

Base pan hole

9K-12K
18K 24K

32 12600801A00077
26 34

Seal

Base pan

Drain joint

Fig. 33 — Drain Joint

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 21

38MHRC: Installation Instructions
ELECTRICAL DATA
OUTDOOR UNIT Minimum Circuit Ampacity (MCA)
Maximum Overcurrent Protection Ampacity (MOPA)
Voltage-Phase-Frequency Max ­ Min Voltage Range
Running Current Power Consumption
Power Factor
Running Current Range Power Consumption Power Factor

Table 16 — Electrical Data – Heat Pump System

9K

12 K

9K

12K

18K

24K

30K

36K

(115 V) (115 V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V)

A

20

18.5

12

15

15

19

25

28

A

30

25

15

15

20

30

30

35

115-1-60 127-104

(A)

6.3

(W)

725

(%)

79.2

(A)

7.82

(W)

900

(%)

80.5

10.5

3.41

1212

782

81.8

97.6

HEATING

10.4

4.1

1172

944

81.5

98

208/230-1-60

253-187

COOLING

5.2

7

11.12

1176

1610

2570

97.5

99.1

99.3

5 1131 96.3

7.2 1650 99.17

10.25 2320 99.2

12.1 2700 96.2
12.2 2700 96.3

18.5 4235 98.7
18.3 4200 98.7

OUTDOOR UNIT
Minimum Circuit Ampacity (MCA) Maximum Overcurrent
Protection Ampacity (MOPA) Voltage-Phase-Frequency Max ­ Min Voltage Range
Running Current Power Consumption
Power Factor

Table 17 — Electrical Data – Cooling Only

12K

9K

12K

(115 V)

(208/230V)

(208/230V)

A

18

11

11

18K (208/230V)
16

A

30

15

15

20

115-1-60 127-104

(A)

8.5

(W)

720

(%)

68.81

208/230-1-60

253-187

COOLING

3.13

4.2

6.8

960

1570

2150

82

98

99

*Permissible limits of the voltage range at which the unit will operate satisfactorily.

24K (208/230V)
16 20
9.3 720 99.28

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 22

38MHRC: Installation Instructions
CONNECTION DIAGRAMS

Fig. 34 — Connection Diagram Size 115V

NOTES:

Fig. 35 — Connection Diagram Size 208/230V

1. Do not use the thermostat wire for any connection between indoor and outdoor units. 2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 23

38MHRC: Installation Instructions

SYSTEM VACUUM AND CHARGE
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum pump.
Refrigerant pipes and indoor unit coils should be evacuated using the recommended 500 microns deep vacuum method. The alternate triple evacuation method may be used if the following procedure is followed. NOTE: Always break a vacuum with dry nitrogen.
Using a Vacuum Pump
1. Completely tighten flare nuts A, B, C, D and connect the manifold gage charge hose to a charge port of the low side service valve (see Fig. 36).
2. Connect the charge hose to vacuum pump. 3. Fully open the low side of manifold gage (see Fig. 37). 4. Start the vacuum pump. 5. Evacuate using either the deep vacuum or triple evacuation method. 6. After evacuation is complete, fully close the low side of manifold gage
and stop the vacuum pump operation. 7. The factory charge contained in the outdoor unit is good for up to 25 ft.
(8 m) of line length. For refrigerant lines longer than 25 ft. (8 m), add refrigerant, up to the allowable length, as specified in “SYSTEM REQUIREMENTS” on page 4. 8. Disconnect the charge hose from the charge connection of the low side service valve. 9. Fully open service valves B and A. 10. Securely tighten the service valve caps.

Outdoor Unit

Refrigerant
Gas Side

Indoor Unit

Service Valve

Liquid Side

Fig. 36 — Service Valve

Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gauge capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water (see Fig. 38).

MICRONS

5000 4500 4000 3500 3000 2500 2000 1500 1000 500

LEAK IN SYSTEM
VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 01234 567 MINUTES

Fig. 38 — Deep Vacuum Graph

Triple Evacuation Method
The triple evacuation is the recommended method of dehydration. Refer to Fig. 39 and proceed as follows:
1. Pump the system down to 1500 microns and allow the pump to continue operating for an additional 15 minutes.
2. Close the service valves and shut off the vacuum pump. 3. Connect a dry nitrogen cylinder and regulator to the system and break
vacuum until the system reaches 2 psig. 4. Close the service valve and allow the system to stand for 1 hr. During
this time, the dry nitrogen can diffuse throughout the system absorbing moisture. 5. Pump the system down to 1000 microns. 6. Break the vacuum with dry nitrogen (2 psig). 7. Pump the system down to 500 microns. 8. Perform the hold test for 30 minutes.

Manifold Gage

500 microns Low side valve
Charge hose

High side valve Charge hose
Vacuum pump

EVACUATE TO 1500 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 1000 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG EVACUATE TO 500 MICRONS MINIMUM (HOLD FOR 30 MINUTES)
CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM BY OPENING VALVES COMPLETELY

Low side valve
Fig. 37 — Manifold Gauge

Fig. 39 — Triple Evacuation Method
Final Tubing Check
IMPORTANT: Ensure the factory tubing on both the indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on the feeder tubes are secure and tight.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 24

38MHRC: Installation Instructions
START-UP
CAUTION
DO NOT apply power to the outdoor unit if the Master Service Valves are not fully open. Compressor damage will occur.
TEST OPERATION
Perform a test operation after completing a gas leak and electrical safety check. Review the indoor unit installation instructions and owner’s manual for additional start up information.
System Checks
1. Conceal the tubing where possible. 2. Ensure the drain tube slopes downward along its entire length. 3. Ensure all tubing and connections are properly insulated. 4. Fasten the tubes to the outside wall, when possible. 5. Seal the hole through which the cables and tubing pass.
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation? Explain the Following Items to the Customer (with the aid of the Owner’s Manual):
2. Explain care and maintenance. 3. Present the installation instructions to the customer.

OUTDOOR UNIT DIAGNOSTIC GUIDES
For ease of service, the systems are equipped with a diagnostic code display LED on both the indoor and outdoor units. The outdoor diagnostic is displayed on the outdoor unit microprocessor board. There may be a few error codes displayed on the indoor unit that might relate to the outdoor unit’s problems. If possible, always check the diagnostic codes displayed on the indoor unit first. In standby, the LED displays “- -“.
In the compressor operation, the LED displays the running frequency. In the defrosting mode, the LED displays “dF” or alternative displays between the running frequency and “dF” (each appears for 0.5s). During the compressor pre- heating cycle, the LED displays “PH” or alternative displays between the running frequency and “PH” (each appears for 0.5s).
During the oil return process, the LED displays “RO” or alternative displays between the running frequency and “RO” (each appears for 0.5s). In the low ambient cooling mode, the LED displays “LC” or alternative displays between the running frequency and “LC” (each appears for 0.5s).
In the forced cooling mode, the LED displays “FC” or alternative displays between the running frequency and “FC” (each appears for 0.5s). When PFC module protection occurs three times within 15 minutes, the LED displays “E6” or alternative displays between the running frequency and “E6” (each appears for 0.5s). In protection or malfunction, the LED displays an error code or a protection code. The diagnostic codes displayed on the outdoor units are listed on Table 18.

OPERATION LAMP (TIMES) 1 2 3 4 5 5 5 5 5 6 6 12 9 8 7 2 3 5 1 6 7 1 9 11

Table 18 — Outdoor Unit Error Display

TIMER LAMP

DISPLAY

LED STATUS

OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF FLASH FLASH FLASH FLASH FLASH FLASH FLASH ON OFF OFF

EH 00/EH 0A
EL 01 EH 02 EH 03 EC 51 EC 52 EC 53 EC 54 EC 56 EH 60 EH 61 EC 07 EH 0b EL 0C PC 00 PC 01 PC 02 PC 04 PC 08 PC 40 PC 03
-EH b1 FH 0d

Indoor unit EEPROM parameter error Indoor/outdoor unit communication error Zero-crossing signal detection error Indoor fan operating outside of the normal range Outdoor unit EEPROM parameter error T3 is in open circuit or has short circuited T4 is in open circuit or has short circuited TP is in open circuit or has short circuited T2B is in open circuit or has short circuited T1 is in open circuit or has short circuited T2 is in open circuit or has short circuited Outdoor fan operating outside of the normal range Indoor PCB/Display board communication error Refrigerant leakage detection IPM malfunction or IGBT OSCP Over voltage or over low voltage protection Compressor or IPM high temp/pressure protection Inverter compressor drive error Current overload protection Communication error between outdoor chip and compressor chip Low pressure protection Indoor units mode conflict Indoor board and Multi-function communication error Ionizer malfunction

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 25

38MHRC: Installation Instructions

DUCTLESS START-UP CHECKLIST – SINGLE ZONE

Installation Data
Site Address:____ City:____ State: Zip Code:__

Installing Contractor:__ Contractor Contact #: ( ) _-___

Job Name:___ Start-up Date:_

Distributor:___

System Details

UNITS OUTDOOR UNIT INDOOR UNIT A

MODEL NO.

SERIAL NO.

Are the outdoor unit and indoor unit compatible?

CONTROLLER
YES:__ NO:__

Wiring Electrical

Wire Size and Type Used? AWG:__ TYPE:_____

Are there any breaks, splices, wire nuts or butt connectors between the outdoor unit and the indoor unit?

YES:__ NO:__

Was the wiring from the outdoor unit port to the correct indoor unit verified?

YES:__ NO:__

REMARKS:___


Voltage Check

Wiring: Single Zone

Outdoor Unit Disconnect

1(L1):GND 2(L2):GND
1(L1):L2(2)

Indoor Unit Voltage Check @ Outdoor Unit

1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)

Outdoor Unit Terminal Block

1(L1):GND 2(L2):GND
1(L1):2(L2)

Indoor Unit Voltage Check @ Indoor Unit

1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)

NOTES:__





NOTES:__





Outdoor Unit Disconnect

1(L1):GND 2(L2):GND
1(L1):L2(2)

Indoor Unit Voltage Check @ Outdoor Unit

1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)

Outdoor Unit Terminal Block

1(L1):GND 2(L2):GND
1(L1):2(L2)

Indoor Unit Voltage Check @ Indoor Unit

1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)

NOTES:__





NOTES:__





Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 26

38MHRC: Installation Instructions

Ductless Start-Up Checklist (CONT)

Piping
Leak Check: System held 500 psig (max. 550psi) for a minimum of 30 minutes using dry nitrogen. YES:__ NO:__

Evacuation Method: · Was the Triple Evacuation Method used as outlined in the installation manual? · Was the Deep Vacuum Method used as outlined in the installation manual? · Did the System Hold 500 microns for 1 hour? · Does the line set match the diameter of the evaporator connections? · For Conventional Fan Coils, does the line set match the outdoor unit size?

YES:__ NO:__ YES:__ NO:_ YES:__ NO:_ YES:__ NO:_ YES:__ NO:_

Single Zone Piping: Has the liquid pipe length been measured and the additional charge calculated? Size:__ Length: Charge:____

NOTES:

PORT A

LIQUID SIZE

Performance Check

SUCTION SIZE

LENGTH

CHARGE

NOTES:____



For 1:1 Single Zone Systems: Adjust the set-point to create an operational call for the desired testing operation. Allow the system to run for a minimum of 10 min. and record the following details:

(Operational data recorded on applicable heads with the wireless remote controller’s Point Check function)

UNIT SET-POINT MODE

T1

T2

T3

T4

Tb

Tp

Th

LA/Lr

A

NOTE: · T1 – Ambient Space Temperature Sensor · T2 – IDU Coil Temperature Sensor · T3 – Outdoor Coil Temperature Sensor · T4 – Outdoor Ambient Temperature · Tb – Suction Line Temperature @PMV · Tp – Discharge Temperature Sensor · Th – IPM Board Temperature · LA/Lr – PMV Temperature

Error Codes
Were there any error codes present at start-up?

YES:__ NO:__

Indoor Unit Error Code: Outdoor Unit Error Code:
Wall Controller: 24V Interface:

Notes:

Comments:





Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 27

38MHRC: Installation Instructions

© 2023 Carrier. All rights reserved.

Edition Date: 04/23

Catalog No: IM-38MHRC-04

Replaces: IM-38MHRC-03

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

28

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals