bryant 38MHRC Outdoor Unit Single Zone Ductless System Heat Pump Instruction Manual Specifications Installation Instructions Parts List Frequently Asked Questions (FAQ)
- January 12, 2024
- bryant
Table of Contents
- 38MHRC Outdoor Unit Single Zone Ductless System Heat Pump
- Specifications
- Installation Instructions
- Safety Considerations
- Warnings
- Caution
- Parts List
- Frequently Asked Questions (FAQ)
- Q: Can untrained personnel perform any maintenance functions on
- Q: What precautions should be taken when working on the
- Q: Can air or gases containing oxygen be used for leak testing
- Q: Can the refrigerant pipe be buried in the ground?
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
38MHRC Outdoor Unit Single Zone Ductless System Heat Pump
Specifications
Product Model | 38MHRC |
---|---|
Product Type | Outdoor Unit Single Zone Ductless System Heat Pump (Sizes 09 to |
- Cooling Only (Sizes 09 to 24)
Installation Instructions
Safety Considerations
Installing, starting up, and servicing air-conditioning
equipment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated structures,
etc.). Only trained, qualified installers and service mechanics
should install, start-up, and service this equipment. Untrained
personnel can perform basic maintenance functions such as coil
cleaning. All other operations should be performed by trained
service personnel only. When working on the equipment, observe
precautions in the literature and on tags, stickers, and labels
attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves.
Keep a quenching cloth and fire extinguisher nearby when brazing.
Use care in handling, rigging, and setting bulky equipment. Read
these instructions thoroughly and follow all warnings or cautions
included in the literature and attached to the unit. Consult the
local building codes and current editions of the National
Electrical Code (NEC) NFPA 70. In Canada, refer to current editions
of the Canadian electrical code CSA 22.1.
Warnings
ELECTRICAL SHOCK HAZARD: Failure to follow this
warning could result in personal injury or death. Before
installing, modifying, or servicing the system, the main electrical
disconnect switch must be in the OFF position. There may be more
than one disconnect switch. Lock out and tag the switch with a
suitable warning label.
EXPLOSION HAZARD: Failure to follow this
warning could result in death, serious personal injury, and/or
property damage. Never use air or gases containing oxygen for leak
testing or operating refrigerant compressors. Pressurized mixtures
of air or gases containing oxygen can lead to an explosion.
Caution
EQUIPMENT DAMAGE HAZARD: Failure to follow this
caution may result in equipment damage or improper operation. Do
not bury more than 36 in. (914 mm) of refrigerant pipe in the
ground. If any section of the pipe is buried, there must be a 6 in.
(152 mm) vertical rise to the valve connections on the outdoor
units. If more than the recommended length is buried, refrigerant
may migrate to the cooler buried section during extended periods of
system shutdown. This causes refrigerant slugging and could
possibly damage the compressor at startup.
Parts List
Part No. | Part Name | Qty |
---|---|---|
1 | Outdoor Unit | 1 |
– | Literature package including installation instructions and | |
warranty | 1 | |
– | Vibration pad | 4 |
– | Drain joint | 1 |
– | Drain hose | 1 |
Frequently Asked Questions (FAQ)
Q: Can untrained personnel perform any maintenance functions on
the product?
A: Yes, untrained personnel can perform basic maintenance
functions such as coil cleaning. However, all other operations
should be performed by trained service personnel only.
Q: What precautions should be taken when working on the
equipment?
A: When working on the equipment, it is important to observe
precautions mentioned in the literature and on tags, stickers, and
labels attached to the equipment. Safety glasses and work gloves
should be worn. It is recommended to keep a quenching cloth and
fire extinguisher nearby when brazing. Care should be taken while
handling, rigging, and setting bulky equipment.
Q: Can air or gases containing oxygen be used for leak testing
or operating refrigerant compressors?
A: No, air or gases containing oxygen should never be used for
leak testing or operating refrigerant compressors. Pressurized
mixtures of air or gases containing oxygen can lead to an
explosion.
Q: Can the refrigerant pipe be buried in the ground?
A: Yes, the refrigerant pipe can be buried in the ground, but
not more than 36 in. (914 mm). If any section of the pipe is
buried, there must be a 6 in. (152 mm) vertical rise to the valve
connections on the outdoor units. Burying more than the recommended
length may cause refrigerant migration to the cooler buried section
during extended periods of system shutdown, resulting in
refrigerant slugging and possible compressor damage at startup.
38MHRC Outdoor Unit Single Zone Ductless System Heat Pump Sizes 09 to 36 Cooling Only Sizes 09 to 24
Installation Instructions
Fig. 1 — Outdoor Unit NOTES:
Read the entire instruction manual before starting the installation. Images
are for illustration purposes only. Actual models may differ slightly.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS………………………………………………..2 PARTS LIST
…………………………………………………………………………3 SYSTEM REQUIREMENTS…………………………………………………..4 PIPING
REQUIREMENTS……………………………………………………..4 WIRING ……………………………………………………………………………….5
DIMENSIONS……………………………………………………………………….6 CLEARANCES
……………………………………………………………………..13 INSTALLATION GUIDE……………………………………………………….14
OUTDOOR UNIT INSTALLATION ……………………………………….14 Step 1 – Select Installation
Location………………………………………….14 Step 2 – Install Drain Joint (Heat Pump Unit Only)
…………………….14 Step 3 – Anchor the Outdoor Unit……………………………………………..15 Step 4 –
Connect the Signal and Power Cables……………………………15 Step 5 – Refrigerant Piping
………………………………………………………16 Step 6 – Evacuate Coil and Tubing System
………………………………..18 WIRING ……………………………………………………………………………….19 Step 7 – Electrical
And Gas Leak Checks…………………………………..19 ELECTRICAL DATA…………………………………………………………….22
CONNECTION DIAGRAMS ………………………………………………….23 SYSTEM VACUUM AND
CHARGE………………………………………24 START-UP ……………………………………………………………………………25 OUTDOOR UNIT
DIAGNOSTIC GUIDES ……………………………..25 DUCTLESS START-UP CHECKLIST – SINGLE
ZONE…………..26
Specifications subject to change without notice.
38MHRC: Installation Instructions
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can be
hazardous due to system pressures, electrical components, and equipment
location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install,
start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as coil
cleaning. All other operations should be performed by trained service
personnel only.
When working on the equipment, observe precautions in the literature and on
tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep a quenching
cloth and fire extinguisher nearby when brazing. Use care in handling,
rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions
included in the literature and attached to the unit. Consult the local
building codes and current editions of the National Electrical Code (NEC) NFPA
70. In Canada, refer to current editions of the Canadian electrical code CSA
22.1.
Recognize safety information. This is the safety-alert symbol . When you see
this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury. Understand these signal words: DANGER, WARNING,
and CAUTION. These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices which may result
in minor personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation, reliability,
or operation.
WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in
personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect
switch must be in the OFF position. There may be more than 1 disconnect
switch. Lock out and tag switch with a suitable warning label.
WARNING
EXPLOSION HAZARD Failure to follow this warning could result in death, serious
personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating
refrigerant compressors. Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If
any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to
the valve connections on the outdoor units. If more than the recommended
length is buried, refrigerant may migrate to the cooler buried section during
extended periods of system shutdown. This causes refrigerant slugging and
could possibly damage the compressor at startup.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 2
38MHRC: Installation Instructions
PARTS LIST
Table 1 — Parts List
Part No.
Part Name
Qty
1
Outdoor Unit
1
–
Literature package including installation instructions and warranty
1
–
Vibration pad
4
–
Drain joint
1
–
Drain hose
1
2XWGRRU
Fig. 2 — Outdoor Unit NOTES: – If the outdoor unit is higher than the indoor
unit, prevent rain from flowing into the indoor unit along the connection pipe
by making a
downward arc in the connection pipe before it enters the wall to the indoor
unit. This ensures that rain drips from the connection pipe before it enters
the wall. – Piping and the interconnecting wiring are field supplied. – Figure
2 is only a sketch. Different models may differ slightly.
The units listed in Table 2 are covered in this manual.
System Tons 0.75 1.00 0.75 1.00 1.50 2.0 2.5 3.0
Table 2 — Heat Pump Unit Sizes
BTUh
V-Ph-Hz
9,000 12,000
115-1
9,000
12,000
18,000 24,000
208/230-1-60
30,000
36,000
Model 38MHRCQ09AA1 38MHRCQ12AA1 38MHRCQ09AA3 38MHRCQ12AA3 38MHRCQ18AA3 38MHRCQ24AA3 38MHRCQ30AA3 38MHRCQ36AA3
System Tons 1.00 0.75 1.00 1.50 2.00
Table 3 — Cooling Only Unit Sizes
BTUh 12,000
V-Ph-Hz 115-1
9,000 12,000 18,000 24,000
208/230-1-60
Model 38MHRDC12AA1 38MHRDC09AA3 38MHRDC12AA3 38MHRDC18AA3 38MHRDC24AA3
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 3
38MHRC: Installation Instructions
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and unit service. See Fig. 9 — on page 13
for the minimum required distances between the unit and walls or ceilings.
PIPING REQUIREMENTS
IMPORTANT: Both refrigerant lines must be insulated separately.
The minimum refrigerant line length between the indoor and outdoor units is 10
ft. (3 m). The following lengths are allowed. Table 4 lists the pipe sizes for
the outdoor unit. For the indoor unit pipe sizes refer to the indoor unit
installation instructions.
SYSTEM SIZE
Min. Piping Length Standard Piping Length
Max. outdoor-indoor height difference
(OU higher than IU)
ft. (m) ft. (m)
ft. (m)
Table 4 — Heat Pump System
9K (115 V)
12K
9K
12K
18K
24K
30K
36K
(115 V) (208/230 V) (208/230 V) (208/230 V) (208/230 V) (208/230 V) (208/230 V)
9.8 (3)
9.8 (3)
9.8 (3)
9.8 (3)
9.8 (3)
9.8 (3)
9.8 (3)
9.8 (3)
24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5)
32.8 (10) 32.8 (10) 32.8 (10) 32.8 (10) 65.6 (20) 82 (25)
82 (25) 98.4 (30)
Max. outdoor-indoor height difference
(IU higher than OU)
ft. (m)
32.8 (10)
32.8 (10)
32.8 (10)
32.8 (10)
65.6 (20)
82 (25)
82 (25) 98.4 (30)
PIPING
Max. Piping Length with no additional refrigerant charge per System
(Standard Piping length)
ft. (m)
24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5) 24.6 (7.5)
Total Maximum Piping Length per system
Additional refrigerant charge (between Standard
Max piping length)
Suction Pipe (size – connection type)
Liquid Pipe (size – connection type)
Refrigerant Type
ft. (m) 82 (25)
82 (25)
82 (25)
82 (25) 98.4 (30) 164 (50) 164 (50) 213 (65)
Oz/ft (g/m)
0.161(15) 0.161(15) 0.161(15) 0.161(15) 0.161(15) 0.322(30) 0.322(30) 0.322(30)
In (mm) ø3/8″ (9.52) ø1/2″ (12.7) ø3/8″ (9.52) ø1/2″ (12.7) ø1/2″ (12.7) ø5/8″ (15.9) ø5/8″ (15.9) ø5/8″ (15.9)
In (mm) ø1/4″ (6.35) ø1/4″ (6.35) ø1/4″ (6.35) ø1/4″ (6.35) ø1/4″ (6.35) ø3/8″ (9.52) ø3/8″ (9.52) ø3/8″ (9.52)
Type
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Charge Amount
lb. (kg) 1.59(0.72) 1.79(0.81) 1.59(0.72) 1.79(0.81) 2.98(1.35) 3.92(1.78) 6.17(2.8) 7.5(3.4)
REFRIGERANT
PIPING
SYSTEM SIZE
Min. Piping Length
Standard Piping Length
Max. outdoor-indoor height difference
(OU higher than IU)
Max. Piping Length with no additional refrigerant charge
per System (Standard Piping length)
Total Maximum Piping Length per system
Additional refrigerant charge (between Standard Max piping length)
Suction Pipe (size – connection type)
Liquid Pipe (size – connection type)
Refrigerant Type
ft. (m) ft. (m) ft. (m)
ft. (m)
ft. (m) Oz/ft (g/
m) In (mm) In (mm)
Type
Table 5 — Cooling Only System
12K
9K
12K
(115 V)
(208/230 V)
(208/230 V)
9.8 (3)
9.8 (3)
9.8 (3)
24.6 (7.5)
24.6 (7.5)
24.6 (7.5)
32.8 (10)
32.8 (10)
32.8 (10)
24.6 (7.5)
82 (25) 0.161(15) ø1/2″ (12.7) ø1/4″ (6.35)
R410A
24.6 (7.5)
82 (25) 0.161(15) ø3/8″ (9.52) ø1/4″ (6.35)
R410A
24.6 (7.5)
82 (25) 0.161(15) ø1/2″ (12.7) ø1/4″ (6.35)
R410A
Charge Amount
lb. (kg)
1.46(0.66)
1.26(0.57)
1.46(0.66)
18K (208/230 V)
9.8 (3) 24.6 (7.5) 65.6 (20)
24.6 (7.5)
98.4 (30) 0.161(15) ø1/2″ (12.7) ø1/4″ (6.35)
R410A
1.98 (0.9)
24K (208/230 V)
9.8 (3) 24.6 (7.5)
82 (25)
24.6 (7.5)
98.4 (30) 0.322(30) ø5/8″ (15.9) ø3/8″ (9.52)
R410A
2.36(1.07)
REFRIGERANT
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 4
38MHRC: Installation Instructions
Refrigerant Piping: Line sets to be sized based on the connection size of the
indoor unit. Each pipe should be insulated individually.
Additional Refrigerant Calculation · 9K-18K: Sum Total Liquid Pipe ft. (m) –
Additional Charge Required After ft. (m.) x Additional Charge oz./ft. (g/m)
0.16 (15) · 24K: Sum Total Liquid Pipe ft. (m) – Additional Charge Required
After ft. (m.) x Additional Charge oz./ft. (g/m) 0.322 (30)
NOTE: If the calculation results in a negative number no additional refrigerant is required. Electronic expansion valves in the outdoor unit are used as metering devices.
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian
Electrical Code) and local codes. See the rating plate and/or the installation
instructions of the compatible outdoor unit for MCA (minimum circuit amps) and
MOCP (maximum over current protection) to correctly size the wires and the
disconnect fuse or breakers respectively.
Recommended Connection Method for Power and Communication Wiring: The main
power is supplied to the outdoor unit. The field supplied 14/3 stranded wire
with ground with a 600 volt insulation rating, power/ communication wiring
from the outdoor unit to indoor unit consists of four (4) wires and provides
the power for the indoor unit. Two wires are line voltage AC power, one is
communication wiring (3) and the other is a ground wire. Wiring between indoor
and outdoor unit is polarity sensitive. The use of BX wire is NOT recommended.
If installed in a high Electromagnetic field (EMF) area and communication
issues exists, a 14/2 stranded shielded wire can be used to replace L2 and (3)
between outdoor unit and indoor unit landing the shield onto ground in the
outdoor unit only.
WARNING
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation. Be sure to comply with local codes while running wire from the
indoor unit to the outdoor unit. Every wire must be connected firmly. Loose
wiring may cause the terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Ensure all wiring is tightly connected. No wire
should touch the refrigerant tubing, compressor or any moving parts.
Disconnecting means must be provided and shall be located within sight and
readily accessible from the air conditioner. Connecting cable with conduit
shall be routed through the hole in the conduit panel.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 5
38MHRC: Installation Instructions
DIMENSIONS
SYSTEM SIZE
UNIT HEIGHT (H) in (mm) WIDTH (W) in (mm) DEPTH (D) in (mm) WEIGHT – NET lbs.
(kg)
OUTDOOR UNIT
HEIGHT
WIDTH
DEPTH
WEIGHT GROSS
CARTON DRAWING NO.
CARTON MATERIAL
MATERIAL THICKNESS
in (mm) in (mm) in (mm) lbs. (kg)
—
—
in (mm)
9K (115V)
21.85(555) 30.12(765) 11.93(303) 57.76(26.2)
24.02(610) 34.92(887) 13.27(337) 63.49(28.8)
877327590
0.197(5)
Table 6 — Dimensions Heat Pump
12K
9K
12K
18K
(115 V) (208/230 V) (208/230 V) (208/230 V)
21.85(555) 30.12(765) 11.93(303) 62.17(28.2)
24.02(610) 34.92(887) 13.27(337)
67.68(30.7)
21.85(555) 30.12(765) 11.93(303) 55.11(25.0)
24.02(610) 34.92(887) 13.27(337)
60.85(27.6)
21.85(555) 30.12(765) 11.93(303)
21.81(554) 31.69(805) 12.99(330)
59.30(26.9) 73.85(33.5)
PACKAGING 24.02(610) 24.21(615)
34.92(887) 13.27(337)
36.02(915) 14.57(370)
64.82(29.4) 79.81(36.2)
877327590 877327590 877327590 905360590
CARTON BOX
0.197(5)
0.197(5)
0.197(5)
0.197(5)
24K (208/230 V)
26.50(673) 35.04(890) 13.46(342) 97.88(44.4)
29.13(740) 39.17(995) 15.67(398) 104.50(47.4)
985388720
0.295(7.5)
30K (208/230 V)
31.89(810) 37.24(946) 16.14(410) 142.86(64.8)
34.84(885) 42.91(1090) 19.69(500) 152.56(69.2)
107548586
0.295(7.5)
36K (208/230 V)
31.89(810) 37.24(946) 16.14(410) 150.13(68.1)
34.84(885) 42.91(1090) 19.69(500) 158.95(72.1)
107548586
0.295(7.5)
SYSTEM SIZE
UNIT HEIGHT (H) WIDTH (W) DEPTH (D) WEIGHT – NET
in (mm) in (mm) in (mm) lbs.(kg)
OUTDOOR UNIT
HEIGHT
WIDTH
DEPTH
WEIGHTGROSS
CARTON DRAWING NO.
CARTON MATERIAL
MATERIAL THICKNESS
in (mm) in (mm) in (mm) lbs.(kg)
—
—
in (mm)
Table 7 — Dimensions Cooling Only
12K
9K
12K
(115 V)
(208/230 V)
(208/230 V)
19.49(495) 28.35(720) 10.63(270) 50.71(23)
21.26(540) 32.87(835) 11.81(300) 54.45(24.7)
818288520
0.197(5)
19.49(495) 28.35(720) 10.63(270) 47.38(21.49)
21.26(540) 32.87(835) 11.81(300) 51.06(23.16)
818288520
0.197(5)
19.49(495) 28.35(720) 10.63(270) 48.50(22) PACKAGING 21.26(540) 32.87(835)
11.81(300) 52.47(23.8)
818288520
CARTON BOX
0.197(5)
18K (208/230 V)
21.85(555) 30.12(765) 11.93(303) 61.51(27.9)
24.02(610) 34.92(887) 13.27(337) 66.80(30.3)
877327590
0.197(5)
24K (208/230 V)
21.81(554) 31.69(805) 12.99(330) 67.24(30.5)
24.21(615) 36.02(915) 14.57(370) 72.97(33.1)
905360590
0.295(7.5)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 6
38MHRC: Installation Instructions
DIMENSIONS (CONT)
21.90 [556] 11.38 [286.5]
10.38 [262] 10.90 [278] 30.25 [769] 33 [837.5]
11 [280.5] 11.25 [285.75] 12.38 [313.75] 2.38 [59.75] 3.63 [93.15]
17.75 [452.5]
0.75 [17.5]
3.13 [78.75]
6.90 [175]
10.38 [262]
Fig. 3 — Sizes 9K/12K (115V) and 9K/12K (208/230V) Heat Pump and 18K Cooling Only
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 7
38MHRC: Installation Instructions
DIMENSIONS (CONT)
31.5 [800.5] 30 [760.4]
19.5 [494]
0.2 [5]
11.13 [281]
28.38 [719]
10.6 [261]
1 [24.5] 1.75 [44]
15.38 [392] 17.75 [452] 1.25 [30]
3 [75]
2.38 [59.5] 3.5 [87.5] Fig. 4 — Sizes 9K/12K (115V) and 12K (208/230V) Cooling Only
11 [281]
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 8
38MHRC: Installation Instructions
DIMENSIONS (CONT)
33.38 [847.1] 34.75 [883.6]
21.75 [554.5]
0.5 [11.4]
13.5 [346.3]
1 [26] R0.2 [R5.0]
34.38 [798.8]
20 [511] 1.9 [49.4]
17.75 [449] 2 [49.5]
12.5 [317.2]
3.9 [98.2]
2.38 [60] 3.75 [95.7]
1.38 [32.7]
Fig. 5 — Size 18K Heat Pump
13.63 [346.3]
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 9
38MHRC: Installation Instructions
DIMENSIONS (CONT)
4.25 [106]
4.75 [122] 35.25 [894.72]
26.50 [672.79]
.50 [11]
13.25 [337.56] Detail A Scale 2:1
2.90 [73.50]
26 [663] 35 [890.60] A
2.90 [71.52]
13.60 [346.67] [6.0R20.6]24 14.90 [379.59] 13.25 [334]
Fig. 6 — Size 24K Heat Pump and 24K Cooling Only
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 10
38MHRC: Installation Instructions
DIMENSIONS (CONT)
31.90 [808.79]
16 [407]
37.25 [946.32] 40.60 [1033.64]
17.90 [454.80] 15.75 [400.44]
26.50 [673] 0.38 [10] 3.75 [95]
2.25 [60] 4.25 [107.50] Fig. 7 — Size 30K Heat Pump
15.90 [402.60]
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 11
38MHRC: Installation Instructions
DIMENSIONS (CONT)
31.90 [808.79]
15.9 [405]
37.25 [946.32] 40.60 [1033.64]
17.90 [454.80] 15.75 [399.03]
26.50 [673] 0.38 [10] 3.75 [95]
2.60 [59.96] 4.25 [107.51] Fig. 8 — Size 36K Heat Pump
16 [408.29]
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 12
38MHRC: Installation Instructions
CLEARANCES
A
Air-inlet
E
D
B
C
Air-outlet
Fig. 9 — Clearances
UNIT A B C D E
Table 8 — Clearance Values
MINIMUM VALUE in. (mm) 24 (609) 24 (609) 24 (609) 4 (101) 6 (152)
NOTE: The outdoor unit must be mounted at least 2in (50mm) above the maximum anticipated snow depth.
9.8in (25cm) or more for proper airflow 24in(61cm) or more is recommended for
service
9.8in (25cm) or more for proper airflow 24in (61cm) or more is recommended for
service
19in (48cm) or more on a multiple parallel unit arrangement 4in (10cm) or more
on a single parallel unit arrangement 59in (150cm) or more when facing each
other
Blowing into the air-inlet of other condenser shall be avoided.
59in (150cm) 24in (60cm) or more or more on a multiple parallel unit
arrangement 24in (61cm) or more on a single parallel unit arrangement
Fig. 10 –Clearances for multiple units
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 13
38MHRC: Installation Instructions
INSTALLATION GUIDE
INSTALLATION TIPS
Before installing the outdoor unit, choose an appropriate location. Ideal
installation locations include:
Outdoor Unit · A location which is convenient to installation and not exposed
to
strong winds. · A location which can bear the weight of the outdoor unit and
where
the outdoor unit can be mounted in a level position. · A location with
appropriate clearances as outlined (See Fig. 9 — on
page 13). · Do not install the indoor or outdoor units in a location with
special
environmental conditions. For those applications, contact your Ductless
representative.
OUTDOOR UNIT INSTALLATION
Install the unit by following local codes and regulations.
Special Considerations for Extreme Weather If the unit is exposed to heavy
wind, install the unit so the air outlet fan is at a 90° angle to the
direction of the wind. If needed, build a barrier in front of the unit to
protect it from extremely heavy winds.
Strong wind Wind Baffle ( eld supplied)
Strong wind
Strong wind
Fig. 12 — Considerations for Extreme Weather If the unit is frequently exposed
to heavy rain or snow, build a shelter above the unit to protect it from the
rain or snow. Be careful not to obstruct air flow around the unit. If the unit
is frequently exposed to salty air (seaside), use and outdoor unit which is
especially made to resist corrosion.
Step 2 – Install Drain Joint (Heat Pump Unit Only)
24in (60cm) above
12oinn(l3e0ftcm)
1fr2oinm(3b0accmk w) all
79in (i2n0f0rocnmt)
24in on
r(i6g0hctm)
Fig. 11 — Unit Clearances
Step 1 – Select Installation Location
The following are standards that will help select an appropriate location for
the unit.
· Meets all clearance requirements (see Figure 11). · Good air circulation and
ventilation · Firm and solid-the location can support the unit and will not
vibrate
· Noise from the unit will not disturb others · Protected from prolonged
periods of direct sunlight or rain
· Where snowfall is anticipated, raise the unit above the base pad to prevent
ice buildup and coil damage. Mount the unit high enough to be above the
average accumulated area snowfall. The minimum height must be 18 inches.
DO NOT install in the following locations:
· Near an obstacle that blocks air inlets and outlets · Near a public street,
crowded areas, or where noise from the unit may
disturb others · Near animals or plants that will be harmed by hot air
discharge · Near any source of combustible gas · In a location that is exposed
to large amounts of dust · In a location exposed to excessive amounts of salty
air
Before bolting the outdoor unit in place, you must install the drain joint at
the bottom of the unit. Note that there are two different types of drain
joints depending on the type of outdoor unit. If the drain joint comes with a
rubber seal (see Fig. 13), perform the following steps:
1. Fit the rubber seal on the end of the drain joint that connects to the
outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit. 3.
Rotate the drain joint 90° until it clicks in place facing the front of the
unit. 4. Connect a drain hose extension (not included) to the drain joint to
redirect water from the unit during heating mode.
If the drain joint does not come with a rubber seal (see Fig. 13), perform the
following steps:
1. Insert the drain joint into the hole in the base pan of the unit. The
drain joint clicks in place.
2. Connect a drain hose extension (field supplied) to the drain joint to
redirect water from the unit during heating mode.
Base pan hole of
Seal
outdoor unit
Seal
Drain joint
(A)
(B)
Fig. 13 — Install Drain Joint
WARNING
In cold climates, ensure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 14
38MHRC: Installation Instructions
Step 3 – Anchor the Outdoor Unit
The outdoor unit can be anchored to the ground or to a wall-mounted bracket
with bolt (M10). Table 9 provides a list of different outdoor unit sizes and
the distance between their mounting feet. Prepare the unit’s installation base
according to the dimensions in Table 9.
Table 9 — Unit Mounting Dimensions
SYSTEM SIZE 9K-12K (HP)
12K (CO)
DISTANCE A IN (MM) 17.8″ (452) 17.8″ (452)
DISTANCE B IN (MM) 11.25″ (286) 10.3″ (261)
18K (HP)
20.1″ (511)
12.5″(317)
18K (CO) 24K (HP & CO)
17.8″ (452) 26.1″ (663)
11.3″ (286) 13.9″ (354)
A
Air inlet
Air inlet
D B
Air outlet Fig. 14 — Unit Air Inlet and Outlet
If you install the unit on the ground or on a concrete mounting platform,
perform the following steps:
1. Mark the positions for four expansion bolts based on the dimensions
charts.
2. Pre-drill holes for expansion bolts. 3. Place a nut on the end of the
expansion bolt. 4. Hammer expansion bolts into the pre-drilled holes. 5.
Remove the nuts from the expansion bolts, and place the outdoor unit
on bolts. 6. Put the washer on each expansion bolt then replace the nuts. 7.
Using a wrench, tighten each nut until snug.
CAUTION
When drilling into concrete, eye protection is recommended at all times.
To install the unit on a wall-mounted bracket, perform the following steps:
CAUTION
Ensure the wall is made of a solid brick, concrete, or of similarity strong
material. The wall must be able to support at least four times the weight of
the unit.
Step 4 – Connect the Signal and Power Cables
The outside unit’s terminal block is protected by an electrical wiring cover
on the side of the unit. A comprehensive wiring diagram is printed on the
inside of the wiring cover.
WARNING
Before performing any electrical or wiring work, turn off the main power to
the system.
1. Prepare the cable for connection.
Use the Right Cable
The size of the power supply cable, signal cable, fuse, and disconnect needed
is determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit.
NOTE: Select the right cable size according to the Minimum Circuit Ampacity
indicated on the nameplate of the unit.
a. Using wire strippers, strip the outer insulation from both ends of the
cable to reveal about 1.5in (40mm) of the wires inside.
b. Strip the insulation from the ends of the wires. c. Using a wire crimper,
crimp u-lugs on the ends of the wires.
WARNING
All wiring work must be performed strictly in accordance with the wiring
diagram located inside the wire cover of the outdoor unit.
2. Unscrew the electrical wiring cover and remove it. 3. Unscrew the cable
clamp below the terminal block and place it to the
side. 4. Connect the wire according to the wiring diagram, and firmly screw
the
u-lug of each wire to its corresponding terminal. 5. After ensuring that sure
every connection is secure, loop the wires
around to prevent rain water from flowing into the terminal. 6. Using the
cable clamp, fasten the cable to the unit. 7. Screw the cable clamp down
tightly. 8. Insulate unused wires with PVC electrical tape. Arrange them so
that
they do not touch any electrical or metal parts. 9. Replace the wire cover on
the side of the unit, and screw it in place.
Cover
1. Mark the position of the bracket holes based on the dimensions chart. 2.
Pre-drill the holes for the expansion bolts. 3. Place a washer and nut on the
end of each expansion bolt. 4. Thread expansion bolts through holes in the
mounting brackets. 5. Put mounting brackets in position and hammer the
expansion bolts into
the wall. 6. Ensure the mounting brackets are level. 7. Carefully lift the
unit and place its mounting feet on the brackets. 8. Bolt the unit firmly to
the brackets. 9. If allowed, install the unit with rubber gaskets to reduce
vibrations and
noise.
Screw
Fig. 15 — Cover and Screw
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 15
38MHRC: Installation Instructions
NOTE: If the cable clamp resembles Figure 16, select the appropriate hole
according to the diameter of the wire.
Buckle
Three size hole: Small, Large, Medium
Fig. 16 — Buckle 1. Remove the wire cover from the unit by loosening the 3
screws. 2. Remove the caps on the conduit panel. 3. Mount the conduit (field
supplied) on the conduit panel. 4. Connect both the power supply and low
voltage lines to the
corresponding terminals on the terminal blocks. 5. Ground the unit in
accordance with local codes. 6. Be sure to leave several inches 4 to 6 inches
of slack in the wiring to
facilitate installation and future service work. 7. Use lock nuts to secure
the conduit.
Step 5 – Refrigerant Piping
When connecting refrigerant piping, do not allow substances or gases other
than the specified refrigerant to enter the unit. The presence of other gases
or substances will lower the unit’s capacity and can cause abnormally high
pressure in the refrigeration cycle. This can cause explosion and injury.
NOTE: The length of the refrigerant piping affects the performance and energy
efficiency of the unit. Nominal efficiency is tested on units with a pipe
length of 16.5ft (5m) (in North America, the standard pipe length is 25ft
(7.5m). A minimum pipe run of 9.8ft (3m) is required to minimize vibration and
excessive noise.
Table 10 — Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model
Capacity
Max. Length (ft/m)
Max. Lift (ft/m)
R410A Fixed-speed
Split Air Conditioner
9,000 – 12,000 18,000 24,000
82ft (25m) 98ft (30m) 164ft (50m)
33ft (10m) 66ft (20m) 82ft (25m)
Use the following steps to connect the refrigerant piping:
1. Run the interconnecting piping from the outdoor unit to the indoor unit.
2. Connect the refrigerant piping and drain line outside the indoor unit.
Complete the pipe insulation at the flare connection then fasten the piping
and wiring to the wall as required. Completely seal the hole in the wall.
3. Piping: a. Cut the pipe, with a pipe cutter, at 90 degrees (see Fig. 18).
b. Remove the service connection (if provided with the unit).
Terminal block Over 1.57in.(40mm)
Connecting cable
G
Power supply cord
Conduit panel
Wire Cover
Select the appropriate through-hole according to the diameter of the wire.
Fig. 17 — Terminal Block
90°
Oblique Rough Warped
Fig. 18 — Pipe Cutting c. Remove all the burrs from the cut cross section of
the pipe,
avoiding any burrs from inside the tubes. d. Remove the flare nuts attached to
the indoor and outdoor units. e. Install the correct size flare nut onto the
tubing and make the
flare connection. Refer to Table 11 for flare nut spacing.
Table 11 — Flare Nut Spacing
OUTER DIAM. IN (MM)
MAX.
A IN (MM)
MIN.
Ø 1/4in (6.35mm)
0.05in (1.3mm)
0.03in (0.7mm)
Ø 3/8in (9.52mm)
0.06in (1.6mm)
0.04in (1.0mm)
Ø 1/2in (12.7mm)
0.07in (1.8mm)
0.04in (1.0mm)
Ø 5/8in (15.88mm)
0.09in (2.2mm)
0.08in (2.0mm)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 16
38MHRC: Installation Instructions
Handle
“A”
Bar
Bar
Yoke
Cone
Copper pipe Clamp handle Red arrow mark
Fig. 19 — Flare Nut Spacing
f. Apply a small amount of refrigerant oil onto the flare connection on the
tubing.
g. Align the center of the pipes and/or the service valve.
Connect Piping to the Outdoor Unit
1. Unscrew the cover from the packed valve on the side of the outdoor unit.
2. Remove the protective caps from the valve ends. 3. Align the flared pipe
end with each valve, and tighten the flare nut as
tightly as possible by hand. 4. Using a spanner, grip the body of the valve.
Do not grip the nut that
seals the service valve.
Valve cover
Indoor unit tubing Flare nut Piping
Fig. 20 — Align Pipe Center
h. Connect both the liquid and gas piping to the indoor unit. i. Tighten the
flare nut with a torque wrench. j. Using the correct wrench, grip the nut on
the unit tubing. k. While firmly gripping the nut on the unit tubing, use a
torque
wrench to tighten the flare nut according to the torque values in the
Tightening Torque Requirements (Table 12). Loosen the flaring nut slightly,
then tighten again.
Fig. 21 — Valve cover 5. While firmly gripping the body of the valve, use a
torque wrench to
tighten the flare nut according to the correct torque values.
6. Loosen the flaring nut slightly, then tighten again.
7. Repeat steps 3 to 6 for the remaining pipe.
NOTE: Use a spanner to grip the main body of the valve. Torque from tightening
the flare nut can snap off other parts of the valve.
Table 12 — Tightening Torque Requirements
PIPE DIAMETER IN.(MM)
TIGHTENING TORQUE
FT-LB
N-M
Ø1/4″ (6.35) Ø3/8″ (9.52) Ø1/2″ (12.7) Ø5/8″ (15.88)
10 to 13 24 to 31 37 to 46 50 to 60
13.6 to 17.6 32.5 to 42.0 50.1 to 62.3 67.7 to 81.3
Fig. 22 — Use proper size wrenches
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 17
38MHRC: Installation Instructions
Step 6 – Evacuate Coil and Tubing System
CAUTION
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage or improper operation. Never use the system compressor as a vacuum
pump.
Refrigerant tubes and the indoor coil should be evacuated using the
recommended 500 microns deep vacuum method. The alternate triple evacuation
method may be used if the procedure outlined below is followed. NOTE: Always
break a vacuum with dry nitrogen. Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect the manifold gage charge
hose to a charge port of the low side service valve (see Fig. 23).
2. Connect the charge hose to vacuum pump. 3. Fully open the low side of
manifold gage (see Fig. 24). 4. Start the vacuum pump. 5. Evacuate using
either the deep vacuum or triple evacuation method. 6. After evacuation is
complete, fully close the low side of manifold gage
and stop the vacuum pump operation. 7. The factory charge contained in the
outdoor unit is good for up to 25 ft.
(8 m) of line length. For refrigerant lines longer than 25 ft. (8 m), add
refrigerant, up to the allowable length. 8. Disconnect the charge hose from
the charge connection of the low side service valve. 9. Fully open service
valves B and A. 10. Securely tighten the service valve caps.
Outdoor Unit
Refrigerant
A Low Side
B High Side
Service Valve
Indoor Unit
C
D
Evacuation
Evacuation of the system will remove air or nitrogen (non-condensables) as
well as moisture. A proper vacuum assures a tight, dry system before charging
with refrigerant. The two methods used to evacuate a system are the deep
vacuum method and the triple vacuum method.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of
500 microns and a vacuum gauge capable of accurately measuring this vacuum
depth. The deep vacuum method is the most positive way of assuring a system is
free of air and moisture (see Fig. 25).
MICRONS
5000 4500 4000 3500 3000 2500 2000 1500 1000 500
LEAK IN SYSTEM
VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 01234 567 MINUTES
Fig. 25 — Deep Vacuum Graph Triple Evacuation Method
The triple evacuation method should be used when vacuum pump is not capable of pumping down to 500 microns and system does not contain any liquid water. Refer to Fig. 26 and proceed as follows:
1. Attach the refrigeration gauges and evacuate system down to 28 in. of
mercury and allow the pump to continue operating for an additional 15 minutes.
2. Close the service valves and shut off the vacuum pump.
3. Connect a nitrogen cylinder and regulator to the system and flow nitrogen
until the system pressure is 2 psig.
4. Close the service valve and allow the system to stand for 1 hour. During
this time, dry nitrogen will diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 26. The system should now be
free of any contaminants and water vapor.
Fig. 23 — Service Valve
Manifold Gage
EVACUATE TO 1500 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 1000 MICRONS
500 microns Low side valve
Charge hose
High side valve Charge hose
Vacuum pump
BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 500 MICRONS MINIMUM (HOLD FOR 30 MINUTES)
CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)
Low side valve
Fig. 24 — Manifold
RELEASE CHARGE INTO SYSTEM BY OPENING VALVES COMPLETELY
Fig. 26 — Triple Evacuation Method
Final Tubing Check
IMPORTANT: Ensure the factory tubing on both the indoor and outdoor unit has
not shifted during shipment. Ensure tubes are not rubbing against each other
or any sheet metal. Pay close attention to the feeder tubes and make sure the
wire ties on the feeder tubes are secure and tight.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 18
38MHRC: Installation Instructions
WIRING
Size all wires per the NEC (National Electrical Code) or CEC (Canadian
Electrical Code) and local codes. Use the electrical data from the outdoor
unit (MCA – minimum circuit amps and MOCP – maximum over current protection),
to correctly size the wires and the disconnect fuse or breakers respectively.
SIZES 9-24 RECOMMENDED CONNECTION METHOD FOR POWER AND COMMUNICATION WIRING
Power and Communication Wiring: The main power is supplied to the outdoor
unit. The field supplied 14/3 power/communication wiring, from the outdoor
unit to the indoor unit, consists of four (4) wires and provides the power for
the indoor unit. Two wires are high voltage AC power, one is communication
wiring and the other is a ground wire.
To minimize communication interference: If installed in a high Electromagnetic
field (EMF) area and communication issues arise, a 14/2 stranded shielded
cable can be used to replace L2 and (3) between the outdoor and indoor units –
landing the shield onto the ground in the outdoor unit only.
CAUTION
EQUIPMENT DAMAGE HAZARD Be sure to comply with local codes while running wire
from the indoor unit to the outdoor unit. Every wire must be connected firmly.
Loose wiring may cause the terminal to overheat or result in a unit
malfunction. A fire hazard may also exist. Ensure all wiring is tightly
connected. No wire should touch the refrigerant tubing, compressor or any
moving parts. Disconnecting means must be provided and located within sight
and readily accessible from the system. Route the connecting cable with
conduit through the hole in the conduit panel.
NOTE: The main power is supplied to the outdoor unit. When disconnecting the
power of the outdoor unit, the indoor unit would lose power. A disconnect
switch is not required on the Indoor unit side on the wiring between the
outdoor and indoor unit. A 3 pole disconnect may be used for extra protection
between the indoor and outdoor unit (refer to local codes).
Step 7 – Electrical And Gas Leak Checks
Before Test Run
Only perform a test run after you have completed the following. · Electrical
Safety Checks Confirm that the unit’s electrical system is
safe and operating properly · Gas Leak Checks Check all flare nut
connections and confirm that
the system is not leaking · Confirm that gas and liquid (high and low
pressure) valves are fully
open
Electrical Safety Checks
After the installation, confirm that all electrical wiring is installed in
accordance with local and national regulations, and according to the
Installation Manual.
Before Test Run
Check Grounding Work Measure the grounding resistance by visual detection and
with grounding resistance tester. Grounding resistance must be less than 0.1
W. NOTE: This may not be required for some locations in North
America.
During Test Run
Check for Electrical Leakage During the Test Run, use an electroprobe and
multimeter to perform a comprehensive electrical leakage test. If electrical
leakage is detected, turn off the unit immediately and call a licensed
electrician to find and resolve the cause of the leakage. NOTE: This may not
be required for some locations in North
America. Gas Leak Checks
There are two different methods to check for gas leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe
connection points on the indoor unit and outdoor unit. The presence of bubbles
indicates a leak.
Leak Detector Method
If using a leak detector, refer to the device’s operation manual for proper
usage instructions.
After Performing Gas Leak Checks
After confirming that the all pipe connection points DO NOT leak, replace the
valve cover on the outside unit.
Check-point of indoor unit
Check-point of outdoor unit
D
B
C
A
A: Low pressure stop valve B: High pressure stop valve C & D: Indoor unit
flare nuts
Fig. 27 — Gas Leak Checks
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 19
38MHRC: Installation Instructions
MAKE REFRIGERANT PIPING CONNECTIONS (OUTDOOR UNIT)
IMPORTANT: Use refrigeration grade tubing ONLY. No other type of tubing may be
used. Use of other tubing types will void the manufacturer’s warranty.
Piping Guide:
· Do not open service valves or remove protective caps from tubing ends until
all the connections are made.
· Bend the tubing with bending tools to avoid kinks and flat spots.
· Keep the tubing free of dirt, sand, moisture, and other contaminants to
avoid damaging the refrigerant system.
· Avoid sags in the suction line to prevent the formation of oil traps.
Insulate each tube with minimum 3/8-in. (10 mm) wall thermal pipe insulation.
Inserting the tubing into the insulation before making the connections saves
time and improves installation quality.
1. Remove the service valve cover, if provided with the unit. 2. Cut the
pipe, with a pipe cutter, at 90 degrees (see Fig. 28). 3. Remove the service
connection, if provided with the unit.
Copper tube
Fig. 31 — Tighten the Flare Nut
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation. Excessive torque can break the flare nut depending on installation
conditions.
INSTALL ALL POWER AND INTERCONNECTING WIRING TO OUTDOOR UNIT
90
Oblique Roughness Burr
Fig. 28 — Cut the pipe
4. Remove all the burrs from the cut cross section of the pipe avoiding any
burrs inside the tubes.
5. Remove the flare nuts attached to the indoor and outdoor units.
6. Install the correct size flare nut onto the tubing and make a flare
connection. Refer to Table 13 for the flare nut spaces.
Table 13 — Flare Nut Spacing
OUTER DIAM. (mm) Ø1/4″ (6.35)
Max. 0.05 (1.3)
A (mm)
Min. 0.03 (0.7)
Ø3/8″ (9.52) Ø1/2″ (12.7)
0.06 (1.6) 0.07 (1.8)
0.04 (1.0) 0.04 (1.0)
Ø5/8″ (15.88)
0.09 (2.2)
0.08 (2.0)
Handle
“A”
Bar
Bar
Yoke
Cone
Copper pipe
Clamp handle Red arrow mark
Fig. 29 — Flare Nut Spacing 7. Apply a small amount of refrigerant oil to the
flare connection on the
tubing. 8. Align the center of the pipes and/or the service valve.
1. Mount the outdoor power disconnect. 2. Run the power wiring from the main
box to the disconnect per the NEC
and local codes. 3. Remove the field wiring cover (if available) from the unit
by loosening
the screws. 4. Remove the caps on the conduit panel. 5. Connect the conduit to
the conduit panel (see Fig. 32). 6. Properly connect the power supply and the
control lines to the terminal
block per the connection diagram. 7. Ground the unit in accordance with the
NEC and local electrical codes. 8. Use the lock nuts to secure the conduit. 9.
Reinstall the field wiring cover.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation. Comply with the local codes while running wire from the indoor unit
to the outdoor unit. Every wire must be connected firmly. Loose wiring may
cause the terminal to overheat or result in unit malfunction. A fire hazard
may also exist. Therefore, ensure all wiring is tightly connected. No wire
should be allowed to touch the refrigerant tubing, compressor or any moving
parts. Disconnecting means must be provided and shall be located within sight
and readily accessible from the air conditioner. Connecting cable with conduit
shall be routed through hole in the conduit panel.
Indoor unit tubing Flare nut Piping
Fig. 30 — Align Pipe Center 9. Connect both the liquid and gas piping to the
indoor unit. 10. Tighten the flare nut using a torque wrench as specified in
Table 14. 11. Complete the installation.
Table 14 — Tightening Torque
Pipe Diameter Ø1/4
Tightening Torque Ft-lb 10 to 13
N-m 13.6 to 17.6
Ø3/8 Ø1/2
24 to 31 37 to 46
35.5 to 42.0 50.1 to 62.3
Ø5/8
50 to 60
67.7 to 81.3
Terminal block Over 1.57in.(40mm)
Connecting cable
G
Power supply cord
Conduit panel
Wire Cover
Select the appropriate through-hole according to the wire diameter.
Fig. 32 — Field Wiring
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 20
38MHRC: Installation Instructions
DRAIN CONNECTIONS
Installed drains must meet local sanitation codes. Install the outdoor unit
drain joint
1. Fit the seal into the drain joint. 2. Insert the drain joint into the base
pan hole of the outdoor unit. 3. Rotate 90° to securely assemble them. 4.
Connect the drain joint with an extension drain hose to avoid
condensate from draining off the outdoor unit during the heating mode.
CAUTION
In cold climates, ensure the drain hose is as vertical as possible to ensure
swift water drainage. If water drains too slowly, it can freeze in the hose
and flood the unit.
NOTE: Basepan built-in with multiple holes for proper draining during defrost.
For applications where it is required to seal these holes, and re-direct the
condensate drain, rubber plugs are available through Replacement Components
(RC).
Table 15 — Rubber Plugs
Outdoor Unit Model Number
Basepan Rubber Plugs RC Part Number
Quantity per unit
Seal
Drain joint
Base pan hole
9K-12K
18K 24K
32 12600801A00077
26 34
Seal
Base pan
Drain joint
Fig. 33 — Drain Joint
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 21
38MHRC: Installation Instructions
ELECTRICAL DATA
OUTDOOR UNIT Minimum Circuit Ampacity (MCA)
Maximum Overcurrent Protection Ampacity (MOPA)
Voltage-Phase-Frequency Max Min Voltage Range
Running Current Power Consumption
Power Factor
Running Current Range Power Consumption Power Factor
Table 16 — Electrical Data – Heat Pump System
9K
12 K
9K
12K
18K
24K
30K
36K
(115 V) (115 V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V)
A
20
18.5
12
15
15
19
25
28
A
30
25
15
15
20
30
30
35
115-1-60 127-104
(A)
6.3
(W)
725
(%)
79.2
(A)
7.82
(W)
900
(%)
80.5
10.5
3.41
1212
782
81.8
97.6
HEATING
10.4
4.1
1172
944
81.5
98
208/230-1-60
253-187
COOLING
5.2
7
11.12
1176
1610
2570
97.5
99.1
99.3
5 1131 96.3
7.2 1650 99.17
10.25 2320 99.2
12.1 2700 96.2
12.2 2700 96.3
18.5 4235 98.7
18.3 4200 98.7
OUTDOOR UNIT
Minimum Circuit Ampacity (MCA) Maximum Overcurrent
Protection Ampacity (MOPA) Voltage-Phase-Frequency Max Min Voltage Range
Running Current Power Consumption
Power Factor
Table 17 — Electrical Data – Cooling Only
12K
9K
12K
(115 V)
(208/230V)
(208/230V)
A
18
11
11
18K (208/230V)
16
A
30
15
15
20
115-1-60 127-104
(A)
8.5
(W)
720
(%)
68.81
208/230-1-60
253-187
COOLING
3.13
4.2
6.8
960
1570
2150
82
98
99
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
24K (208/230V)
16 20
9.3 720 99.28
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 22
38MHRC: Installation Instructions
CONNECTION DIAGRAMS
Fig. 34 — Connection Diagram Size 115V
NOTES:
Fig. 35 — Connection Diagram Size 208/230V
1. Do not use the thermostat wire for any connection between indoor and outdoor units. 2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 23
38MHRC: Installation Instructions
SYSTEM VACUUM AND CHARGE
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper
operation. Never use the system compressor as a vacuum pump.
Refrigerant pipes and indoor unit coils should be evacuated using the
recommended 500 microns deep vacuum method. The alternate triple evacuation
method may be used if the following procedure is followed. NOTE: Always break
a vacuum with dry nitrogen.
Using a Vacuum Pump
1. Completely tighten flare nuts A, B, C, D and connect the manifold gage
charge hose to a charge port of the low side service valve (see Fig. 36).
2. Connect the charge hose to vacuum pump. 3. Fully open the low side of
manifold gage (see Fig. 37). 4. Start the vacuum pump. 5. Evacuate using
either the deep vacuum or triple evacuation method. 6. After evacuation is
complete, fully close the low side of manifold gage
and stop the vacuum pump operation. 7. The factory charge contained in the
outdoor unit is good for up to 25 ft.
(8 m) of line length. For refrigerant lines longer than 25 ft. (8 m), add
refrigerant, up to the allowable length, as specified in “SYSTEM REQUIREMENTS”
on page 4. 8. Disconnect the charge hose from the charge connection of the low
side service valve. 9. Fully open service valves B and A. 10. Securely tighten
the service valve caps.
Outdoor Unit
Refrigerant
Gas Side
Indoor Unit
Service Valve
Liquid Side
Fig. 36 — Service Valve
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of
500 microns and a vacuum gauge capable of accurately measuring this vacuum
depth. The deep vacuum method is the most positive way of assuring a system is
free of air and liquid water (see Fig. 38).
MICRONS
5000 4500 4000 3500 3000 2500 2000 1500 1000 500
LEAK IN SYSTEM
VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 01234 567 MINUTES
Fig. 38 — Deep Vacuum Graph
Triple Evacuation Method
The triple evacuation is the recommended method of dehydration. Refer to Fig.
39 and proceed as follows:
1. Pump the system down to 1500 microns and allow the pump to continue
operating for an additional 15 minutes.
2. Close the service valves and shut off the vacuum pump. 3. Connect a dry
nitrogen cylinder and regulator to the system and break
vacuum until the system reaches 2 psig. 4. Close the service valve and allow
the system to stand for 1 hr. During
this time, the dry nitrogen can diffuse throughout the system absorbing
moisture. 5. Pump the system down to 1000 microns. 6. Break the vacuum with
dry nitrogen (2 psig). 7. Pump the system down to 500 microns. 8. Perform the
hold test for 30 minutes.
Manifold Gage
500 microns Low side valve
Charge hose
High side valve Charge hose
Vacuum pump
EVACUATE TO 1500 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 1000 MICRONS BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG EVACUATE TO
500 MICRONS MINIMUM (HOLD FOR 30 MINUTES)
CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM BY OPENING VALVES COMPLETELY
Low side valve
Fig. 37 — Manifold Gauge
Fig. 39 — Triple Evacuation Method
Final Tubing Check
IMPORTANT: Ensure the factory tubing on both the indoor and outdoor unit has
not shifted during shipment. Ensure tubes are not rubbing against each other
or any sheet metal. Pay close attention to feeder tubes, making sure wire ties
on the feeder tubes are secure and tight.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 24
38MHRC: Installation Instructions
START-UP
CAUTION
DO NOT apply power to the outdoor unit if the Master Service Valves are not
fully open. Compressor damage will occur.
TEST OPERATION
Perform a test operation after completing a gas leak and electrical safety
check. Review the indoor unit installation instructions and owner’s manual for
additional start up information.
System Checks
1. Conceal the tubing where possible. 2. Ensure the drain tube slopes
downward along its entire length. 3. Ensure all tubing and connections are
properly insulated. 4. Fasten the tubes to the outside wall, when possible. 5.
Seal the hole through which the cables and tubing pass.
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation? Explain the
Following Items to the Customer (with the aid of the Owner’s Manual):
2. Explain care and maintenance. 3. Present the installation instructions to
the customer.
OUTDOOR UNIT DIAGNOSTIC GUIDES
For ease of service, the systems are equipped with a diagnostic code display
LED on both the indoor and outdoor units. The outdoor diagnostic is displayed
on the outdoor unit microprocessor board. There may be a few error codes
displayed on the indoor unit that might relate to the outdoor unit’s problems.
If possible, always check the diagnostic codes displayed on the indoor unit
first. In standby, the LED displays “- -“.
In the compressor operation, the LED displays the running frequency. In the
defrosting mode, the LED displays “dF” or alternative displays between the
running frequency and “dF” (each appears for 0.5s). During the compressor pre-
heating cycle, the LED displays “PH” or alternative displays between the
running frequency and “PH” (each appears for 0.5s).
During the oil return process, the LED displays “RO” or alternative displays
between the running frequency and “RO” (each appears for 0.5s). In the low
ambient cooling mode, the LED displays “LC” or alternative displays between
the running frequency and “LC” (each appears for 0.5s).
In the forced cooling mode, the LED displays “FC” or alternative displays
between the running frequency and “FC” (each appears for 0.5s). When PFC
module protection occurs three times within 15 minutes, the LED displays “E6”
or alternative displays between the running frequency and “E6” (each appears
for 0.5s). In protection or malfunction, the LED displays an error code or a
protection code. The diagnostic codes displayed on the outdoor units are
listed on Table 18.
OPERATION LAMP (TIMES) 1 2 3 4 5 5 5 5 5 6 6 12 9 8 7 2 3 5 1 6 7 1 9 11
Table 18 — Outdoor Unit Error Display
TIMER LAMP
DISPLAY
LED STATUS
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF FLASH FLASH FLASH FLASH FLASH FLASH FLASH ON OFF OFF
EH 00/EH 0A
EL 01 EH 02 EH 03 EC 51 EC 52 EC 53 EC 54 EC 56 EH 60 EH 61 EC 07 EH 0b EL 0C
PC 00 PC 01 PC 02 PC 04 PC 08 PC 40 PC 03
-EH b1 FH 0d
Indoor unit EEPROM parameter error Indoor/outdoor unit communication error Zero-crossing signal detection error Indoor fan operating outside of the normal range Outdoor unit EEPROM parameter error T3 is in open circuit or has short circuited T4 is in open circuit or has short circuited TP is in open circuit or has short circuited T2B is in open circuit or has short circuited T1 is in open circuit or has short circuited T2 is in open circuit or has short circuited Outdoor fan operating outside of the normal range Indoor PCB/Display board communication error Refrigerant leakage detection IPM malfunction or IGBT OSCP Over voltage or over low voltage protection Compressor or IPM high temp/pressure protection Inverter compressor drive error Current overload protection Communication error between outdoor chip and compressor chip Low pressure protection Indoor units mode conflict Indoor board and Multi-function communication error Ionizer malfunction
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 25
38MHRC: Installation Instructions
DUCTLESS START-UP CHECKLIST – SINGLE ZONE
Installation Data
Site
Address:____
City:____
State: Zip Code:__
Installing Contractor:__ Contractor Contact #: ( ) _-___
Job Name:___ Start-up Date:_
Distributor:___
System Details
UNITS OUTDOOR UNIT INDOOR UNIT A
MODEL NO.
SERIAL NO.
Are the outdoor unit and indoor unit compatible?
CONTROLLER
YES:__ NO:__
Wiring Electrical
Wire Size and Type Used? AWG:__ TYPE:_____
Are there any breaks, splices, wire nuts or butt connectors between the outdoor unit and the indoor unit?
YES:__ NO:__
Was the wiring from the outdoor unit port to the correct indoor unit verified?
YES:__ NO:__
REMARKS:___
Voltage Check
Wiring: Single Zone
Outdoor Unit Disconnect
1(L1):GND 2(L2):GND
1(L1):L2(2)
Indoor Unit Voltage Check @ Outdoor Unit
1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)
Outdoor Unit Terminal Block
1(L1):GND 2(L2):GND
1(L1):2(L2)
Indoor Unit Voltage Check @ Indoor Unit
1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)
NOTES:__
NOTES:__
Outdoor Unit Disconnect
1(L1):GND 2(L2):GND
1(L1):L2(2)
Indoor Unit Voltage Check @ Outdoor Unit
1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)
Outdoor Unit Terminal Block
1(L1):GND 2(L2):GND
1(L1):2(L2)
Indoor Unit Voltage Check @ Indoor Unit
1(L1):GND 2(L2):GND 1(L1):2(L2)
2(L2):3(3)
NOTES:__
NOTES:__
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 26
38MHRC: Installation Instructions
Ductless Start-Up Checklist (CONT)
Piping
Leak Check: System held 500 psig (max. 550psi) for a minimum of 30 minutes
using dry nitrogen. YES:__ NO:__
Evacuation Method: · Was the Triple Evacuation Method used as outlined in the installation manual? · Was the Deep Vacuum Method used as outlined in the installation manual? · Did the System Hold 500 microns for 1 hour? · Does the line set match the diameter of the evaporator connections? · For Conventional Fan Coils, does the line set match the outdoor unit size?
YES:__ NO:__ YES:__ NO:_ YES:__ NO:_ YES:__ NO:_ YES:__ NO:_
Single Zone Piping: Has the liquid pipe length been measured and the additional charge calculated? Size:__ Length: Charge:____
NOTES:
PORT A
LIQUID SIZE
Performance Check
SUCTION SIZE
LENGTH
CHARGE
NOTES:____
For 1:1 Single Zone Systems: Adjust the set-point to create an operational call for the desired testing operation. Allow the system to run for a minimum of 10 min. and record the following details:
(Operational data recorded on applicable heads with the wireless remote controller’s Point Check function)
UNIT SET-POINT MODE
T1
T2
T3
T4
Tb
Tp
Th
LA/Lr
A
NOTE: · T1 – Ambient Space Temperature Sensor · T2 – IDU Coil Temperature Sensor · T3 – Outdoor Coil Temperature Sensor · T4 – Outdoor Ambient Temperature · Tb – Suction Line Temperature @PMV · Tp – Discharge Temperature Sensor · Th – IPM Board Temperature · LA/Lr – PMV Temperature
Error Codes
Were there any error codes present at start-up?
YES:__ NO:__
Indoor Unit Error Code: Outdoor Unit Error Code:
Wall Controller: 24V Interface:
Notes:
Comments:
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 27
38MHRC: Installation Instructions
© 2023 Carrier. All rights reserved.
Edition Date: 04/23
Catalog No: IM-38MHRC-04
Replaces: IM-38MHRC-03
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
28