EMERSON Max-Flo Series Spence Max-Flo Series High Capacity Steam Traps Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
Max-Flo Series Spence Max-Flo Series High Capacity Steam Traps
Instruction Manual
WARNING
Failure to follow these instructions or to properly install and maintain this
equipment could result in an explosion, fire, and/or chemical contamination
causing property damage and personal injury or death.
Max-Flo Series steam trap must be installed, operated, and maintained in
accordance with federal, state, and local codes, rules and regulations, and
Emerson instructions.
If a leak develops in the system, service to the unit may be required. Failure
to correct trouble could result in a hazardous condition.
Installation, operation, and maintenance procedures performed by unqualified
personnel may result in improper adjustment and unsafe operation. Either
condition may result in equipment damage or personal injury. Only a qualified
person shall install or service the Max-Flo Series steam trap.
Introduction
Scope of the Manual
This manual provides instructions for installation, maintenance, and parts
ordering for the Max-Flo Series.
Product Description
Max-Flo Series are float and thermostatic steam traps. Float actuates the
valve via a hinged lever and linkage. The air vent is a balanced-pressure
design with stainless steel welded encapsulated bellows capable of discharging
air and non-condensable gases continuously for heavy load process. The trap is
cast iron bodied suitable for pressures of 175 psi / 12.1 bar with an NPT
connection.
Principle of Operation
On startup, air and non-condensible gases enter the trap and are automatically
vented through an accurate balanced-pressure internal thermostatic air vent.
As condensate enters the trap, the float and lever mechanism is raised,
lifting the valve off the seat, and discharging the condensate. Condensate
will continue to be discharged at the same rate at which it is entering. Any
air or non-condensible gas that may accumulate will be continually and
efficiently passed by the thermostatic air vent.
Installation
WARNING
Personal injury, property damage, equipment damage, or leakage due to escape
steam or burst of pressure-containing parts may result if this equipment is
over-pressured or is installed where service conditions could exceed the
limits given in the
Specifications
The specifications section on this page provides the ratings and other specifications for the Max-Flo Series.
Available Configurations
Type HC-15: Steam pressures to 15 PSIG / 1.03 barg
Type HC-30: Steam pressures to 30 PSIG / 2.07 barg
Type HC-75: Steam pressures to 75 PSIG / 5.17 barg
Type HC-125: Steam pressures to 125 PSIG / 8.62 barg
Type HC-175: Steam pressures to 175 PSIG / 12.1 barg
Maximum Operating Pressure (1)
175 psig / 12.1 barg
Maximum Allowable Pressure (1)
175 psig / 12.1 barg
Maximum Operating Temperature (1)
Saturated at pressure| Maximum Allowable Temperature (1)
377°F / 192°C
Materials of Construction
Body and Cover: Cast iron
V alve, Pin, and Seat: Hardened Stainless steel
Float: Stainless steel
Lever Assembly: Stainless steel
Thermostatic Air Vent: Stainless steel cage and Thermal element
Cover Bolts: Grade 5
Baffle: Stainless steel (NPS 2-1/2 / DN 65 units only)
---|---
1. The pressure/temperature limits in this Instruction Manual and any
applicable standard or code limitation should not be exceeded.
Specifications or where conditions exceed any ratings of the adjacent
piping or piping connections.
To avoid such injury or damage, provide a pressure-relieving or pressure-
limiting device.
Max-Flo Series should be installed in an accessible position and location for
easy servicing. The trap seat rating stamped on the nameplate must be equal to
or greater than the maximum pressure differential across the trap. Install the
trap straight and in a level position to ensure proper installation.
-
Determine where to install the trap, based on the following requirements:
a. The trap must be located as closely as possible, and below the equipment to be drained.
b. The trap must be in a straight run of horizontal pipe as shown in Figure 2, and pitched to allow condensate to flow into the trap inlet, and away from the trap outlet.
c. Allow for enough space around the trap for servicing which may include removal of the body or cover, depending on the model you are installing. -
Install a Y-strainer with a Blowdown valve in a pipe, ahead of the steam trap. This prevents dirt from entering the trap.
-
Install union fittings and a shutoff valve in the inlet pipe and outlet pipe. This allows the trap to be isolated when servicing.
-
Install a test valve in the outlet pipe, and cap it. This allows the trap to be tested. Cap is used as a safety precaution when the unit is not being tested.
-
Blowdown piping using full steam pressure for five minutes. This cleaning process will remove debris from pipes and oil from the system.
Maintenance
WARNING
To avoid personal injury, property damage, or equipment damage caused by
the sudden release of pressure or the explosion of accumulated gas, do not
attempt any maintenance or disassembly without first isolating the equipment
from system pressure and relieving all internal pressure from the equipment.
When checked regularly and properly maintained, the Max-Flo Series Float and
Thermostatic Traps will provide optimum performance.
Recommended schedule:
- Initially, every 2 to 3 days after startup until system is clean.
- Due to normal wear that may occur, recommended to inspect the parts periodically and replace them if necessary.
Note
The frequency of inspection depends on the severity of service
conditions or the requirements of state and federal laws.
- Inspect the joints for any leaks. Ensure to follow the “Removal from Service” and “Repair” procedures before addressing any joint leaks.
- Clean strainers by opening the blow-down valve and allowing full steam pressure to flow out for a couple of minutes. Then, close the valve.
Removal from Service
- Close the inlet and outlet supply valves and allow the unit to cool. If a test valve is installed, open this valve to relieve any pressure.
- Remove the drain plug to drain condensate from the trap body.
- Remove bolts that attach the cover to the body and remove the trap body.
Repair
- With the body assembly removed from the trap cover, remove the pin that holds the lever assembly to the yoke. Inspect seat and pin for wear, replace if worn.
- Inspect the thermostatic element by placing it in boiling water to see if it closes. If it doesn’t close, replace it.
- Check the alignment of the pin and seat, and adjust or replace parts as necessary. See Table 1.
- Check the float ball for damaged shake float to make sure there is no fluid inside the float. Replace if necessary.
- Clean gasket surfaces and installs the new cover gasket.
Table 1. HC Series – “Max-Flo” Super High Capacity F&T Steam Trap Parts
PART | MODEL | P/N |
---|---|---|
Thermostat | All Models | WAL5891200 |
Lever and Valve Kit
(Includes float lever, mounting pin and yoke, valve pin, and seat)| NPS 2 / DN
50, HC-15 L&V| WAL5818101
NPS 2-1/2 / DN 65, HC-15 L&V| WAL5819101
NPS 2 / DN 50, HC-30 L&V| WAL5818102
NPS 2-1/2 / DN 65, HC-30 L&V| WAL5819102
NPS 2 / DN 50, HC-75 L&V| WAL5818103
NPS 2-1/2 / DN 65, HC-75 L&V| WAL5819103
NPS 2 / DN 50, HC-125 L&V| WAL5818104
NPS 2-1/2 / DN 65, HC-125 L&V| WAL5819104
NPS 1-1/4 / DN 32, HC-175 L&V| WAL5817105
NPS 1-1/2 / DN 40, HC-175 L&V| WAL5817105
NPS 2 / DN 50, HC-175 L&V| WAL5818105
NPS 2-1/2 / DN 65, HC-15 L&V| WAL5819105
PART| MODEL| P/N
Float Ball Kit
(Includes float ball, mounting screw, and washer)| NPS 1-1/4 / DN 32, HC-FLO|
WAL5817201
NPS 1-1/2 / DN 40, HC-FLO| WAL5817201
NPS 2 / DN 50, HC-FLO| WAL5818201
NPS 2-1/2 / DN 65, HC-FLO| WAL5819201
Cover Gasket| NPS 1-1/4 / DN 32, HC-CG| WAL5817301
NPS 1-1/2 / DN 40, HC-CG| WAL5817301
NPS 2 / DN 50, HC-CGF| WAL5818301
NPS 2-1/2 / DN 65, HC-CG| WAL5819301
Cover Casting| NPS 2 / DN 50, HC-CC| WAL5818401
NPS 2-1/2 / DN 65, HC-CC| WAL5819401
Service Kito)| NPS 1-1/4 / DN 32, HC-KIT| WAL5816501
NPS 1-1/2 / DN 40, HC-KIT| WAL5817501
1. Includes thermostatic element, lever and valve kit, float ball kit, cover,
and cover gasket.
Return to Service
- Reinstall the trap body assembly on the cover.
- Insert and securely tighten the drain plug.
- Open the supply valve on the trap outlet side, and slowly open the supply valve to the trap inlet.
- Check for leaks and normal operation.
Emerson Automation Solutions
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574| Asia Pacific
Singapore 128461, Singapore
T +65 6777 8211
---|---
Europe
Bologna 40013, Italy
T +39 051 419 0611| The Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
Parts Ordering
When corresponding with your local Sales Office about Max-Flo Series, always reference the assembly number, see Table 1.
VCIMD-14919 © 2021 Emerson Electric Co. All rights reserved. 11/21
Spence is a mark owned by one of the companies in the Emerson Automation
Solutions business unit of Emerson Electric Co. The Emerson logo is a
trademark and service mark of Emerson Electric Co. All other marks are the
property of their prospective owners.
The contents of this publication are presented for informational purposes
only, and while every effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied, regarding
the products or services described herein or their use or applicability. All
sales are governed by our terms and conditions, which are available upon
request. We reserve the right to modify or improve the designs or
specifications of such products at any time without notice.
Emerson Electric Co. does not assume responsibility for the selection, use, or
maintenance of any product. Responsibility for the proper selection, use, and
maintenance of any Emerson Electric Co. product remains solely with the
purchaser.
www.SpenceValve.com
VCIMD-14919
November 2021
0011533
Documents / Resources
|
EMERSON Max-Flo Series Spence Max-Flo Series High Capacity Steam
Traps
[pdf] Instruction Manual
Max-Flo Series Spence Max-Flo Series High Capacity Steam Traps, Max-Flo
Series, Spence Max-Flo Series High Capacity Steam Traps, High Capacity Steam
Traps, Capacity Steam Traps, Steam Traps, Traps
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>